A B C D F G ADJACENT PLOT
J L N O Q R
(JVC15BMRA700)
3 B
A-302
N=2772630.973 A-203 N=2772658.702
E=486891.211 E=486859.399
P
0.60 OPENING AT
RC WALL REINF. BOTTOM OF TRENCH
GRADE SLAB
FFL -2150 SSL -2300
AS PER DETAIL
LVL = -2850
AS PER PLAN
REFER SECTION P-P
BOTTOM OF TRENCH
PCC
LVL = -2950
L.V. ROOM
2 LAYER MEMBRANE
UP TO LVDB
WITH PROTECTION BOARD
DRIVE WAY
2 LAYER MEMBRANE
SIDE BARS
WITH PROTECTION BOARD
AS PER SCHEDULE FFL - 2150
REINF.
AS PER PILES DETAILS L.V. ROOM
D7
SECTION P-P
1:25
2 2
FRESH AIR
1400X1000
PLAN
2 TRANSFORMER
D13 GAS SYSTEM LEGEND
65 SQ.MTR F/A FROM ABOVE
P
FFL - 2150 HOLDING AREA
SYMBOL DESCRIPTION
F/B FROM BELOW
G PANEL DETECTOR
300MM FROM FFL T/A TO ABOVE
600MM CABLE TRAY RUNNING @ GAS DETECTOR
AT TRENCH LVL
T/B TO BELOW
150MM ØPVC
TRANSFORMER BASE
G
BASEMENT FLOOR H/L KITCHEN - TYPE
300MM FROM FFL
H/L HIGH LEVEL
- 2.05 SSFFL.
SUBSTATION D13 GAS SWITCH
- 2.20 FFL.
L/L LOW LEVEL
D1
1200MM FROM FFL
GAS CONTROL UNIT GS GAS SWITCH
FFL - 2300 INSIDE KITCHEN KGD KITCHEN GAS
05 HIGHER CABINET DETECTOR
BY CABLE TRAY
R.M.U ROOM
SENSOR ACCESS DOOR OGD OTS/DUCT GAS
X
DETECTOR
Z
D13 D13
1700X800
D7
DELIVERY AREA
3 FFL - 2300 3
D7
8% SLOPE
ETS ROOM
RAMP
BULK STORE
FFL - 3000
FFL - 2300
FFL - 2300
Z SERVICE CORRIDOR
SERVICE RAMP
(JVC15BMRM002)
ADJACENT PLOT
(JVC15BMRM001)
FFL - 3000
10% SLOPE
ADJACENT PLOT
D7
45000
45000
D1
STAIRCASE 2 SERVICE
SERVICE
4 LIFT PIT LIFT PIT LIFT
LOBBY LIFT STAIRCASE 1 A 4
UP UP A-301
FFL - 3000 02 27-11-2024
Issued For Approval
4 5
A-204 2
LIFT LIFT A-202
OGD 32
FOR RETAIL H/L
Ø1" CS PIPE SCH40 F/A
6 6
G
CONSULTANT :
X
WATER TANK
500 cu. m.
FFL - 3000 B.O.H.
FFL - 3000
MEP CONTRACTOR :
HV CABLE PASSAGE
PLOT NO:
7 7
600MM CABLE TRAY RUNNING
PROJECT TITLE :
FROM RMU ROOM TO
PUMP ROOM
TRANSFORMER ROOM ON
FFL - 3000
Y COMMON HV PASSAGE @
BASEMENT FLOOR H/L
8 PLOT PLOT
LIMIT
8
LIMIT
PLOT NO. : LOCALITY : ALBARSHA SOUTH FOURTH
N=2772664.895 N=2772692.623
E=486920.779 E=486888.968 SCALE : DATE :
S NORTH
SE DRAWN :
W
A E H K M R CHECKED :
SW
NW
42200
N APPROVED :
R O A D W I D T H 3 . 6 5 m
DWG NAME :
NE
E
B
1 A-302
A-201
3 B
N=2772630.973 A-302 N=2772658.702
A-203
E=486891.211 E=486859.399
PLOT
1 LIMIT
PLOT
LIMIT
1
14 13 12 11 10 9 8 7 6 5 4 3 2 1 G
GAS DETECTOR
KITCHEN - TYPE
T/B TO BELOW
300MM FROM FFL
H/L
2 2 GAS SWITCH
L/L
HIGH LEVEL
15 16 17 18 19 20
SEE STAIRCASE21
DETAIL 1
PODIUM LEVEL 1
PODIUM LEVEL 1
RAMP UP TO
10% SLOPE
10% SLOPE
FFL + 2600
D8
D8
D3B
TELEPHONE STORE
RAMP DOWN
ROOM
10% SLOPE
10% SLOPE
RAMP UP
(JVC15BMRM002)
ADJACENT PLOT
(JVC15BMRM001)
ADJACENT PLOT
FFL + 2600
CCTV ROOM
45000
45000
DOWN DN
D1 02 Issued For Approval 27-11-2024
STAIRCASE 2 SERVICE SERVICE STAIRCASE 1
4 LIFT 1 LIFT 2
LIFT LOBBY LIFT FFL + 300 4 01 Issued For Approval 22-11-2024
UP UP D1 A 12-11-2024
00 Issued For Approval
A-301
Rev. No. Discription Date Drawn Checked
D1 D1 SERVICE
D2 OGD 31
SERVICE RAMP
FEMALE
FEMALE
MALE
MALE
RETAIL LINE
4
GARBAGE
toilet
Ø1" CS PIPE SCH40 F/A FFL + 300
2
5
A-204 LIFT 3 D6
LIFT 4
ROOM A-202
NOTES:-
1. Final tie in connection shall be carried out after authority approval by the GAS in building contractor
W14A CONSULTANT :
CAFE
DUMBWAITER
W14 RETAIL LINE
Ø1" CS PIPE SCH40 T/B
1
9
3 10 11 7
1 1
5 8
1
4
6
9
MEP CONTRACTOR :
RECEPTION
3 7
1 8
1 1
CONTROL PANEL TO BE PLACE 4
D7
NEAR FIRE ALARM PANEL
TRAFFIC SIGNAGE FOR RAMP
DOWN TO BASEMENT AT H/L
12
HOLDING CAFE RESTAURANT
AREA WASTE
LOBBY
TRAFFIC SIGNAGE FOR SERVICE SEGREGATION
RAMP UP TO PODIUM 1 AT H/L AREA PLOT NO:
MAIN LINE AREA
Ø3" CS PIPE SCH40 T/A
7 7
2HR FIRE RATED SHAFT
20X20
OGD 30 AUTOMATIC SLIDING
300mm FROM FFL DOOR WITH AIR CERTAIN
± 0.00 ± 0.00 STD1 SCOPE OF SERVICE
SOLENOID VALVE
ASSEMBLY
G
PC15B/9 R.M.U. FFL + 300 PROVIDER
GAS IN BUILDING
CONTRACTOR SCOPE
PROJECT TITLE :
BARRIER
(EXISTING) BARRIER
roll-up shutter FFL + 150 AUTOMATIC SLIDING
I.L. = 6.652 TRAFFIC SIGNAGE FOR DOOR WITH AIR CERTAIN
PRMS ASSEMBLY & ENCLOSURE`
G
SLOPE = -2.0% TRAFFIC SIGNAGE FOR SERVICES ENTRY
ENTRANCE (AT H/L) ED1 ED2 ED2A
N 2772666.344 ONLY(AT H/L) ED3 W1
OGD 29 E 486916.073
300mm FROM FFL
ENTRANCE FFL + 150
TRAFFIC SIGNAGE FOR EXIT ENTRY SERVICES RAMP UP FFL + 150
NO ENTRY (AT H/L) FFL + 300 8% SLOPE PRESSURE REDUCTION & METERING UNIT ARRANGEMENT
ENTRY/EXIT ± 0.00 ± 0.00
8 PLOT G.L. = 8.50+0.17 = 8.67
PLOT
LIMIT
8 Pin=Max4bar Pout=350mbar Commercial & 75mbar Residential
LIMIT = ±0.00 G.L. = 8.50+0.17 = 8.67
= ±0.00
N=2772664.895 PROPOSED N=2772692.623 PLOT NO. : LOCALITY : ALBARSHA SOUTH FOURTH
FEEDING F.I.C. PROPOSED INTERLOCKS FOR
E=486920.779 CAR ACCESS @ OWNER COST E=486888.968
LINE C.L. = 8.67 B 21 SCALE : DATE :
I.L. = 6.692 1 A-302 S
SLOPE = -2.0% SE 77
A-201 NORTH
N 2772667.865
W
DRAWN :
A E 486917.372 E PROPOSED KERBH K M R 7-1
SW
@ OWNER COST
NW
42200 CHECKED :
R O A D W I D T H 3 . 6 5 m
N APPROVED :
NE
E
DWG NAME :
PROPOSED KERB
@ OWNER COST
3 B
N=2772630.973 A-203
A-302 N=2772658.702
E=486891.211 E=486859.399
2061 EB LP=250 2061 EB LP=250 2061 EB LP=250 2061 EB LP=250 2061 EB LP=250 2061 EB LP=250 2061 EB LP=250 2061 EB LP=250 2061 EB LP=250 2061 EB LP=250 2061 EB LP=250 2061 EB LP=250 2061 EB LP=250 2061 EB LP=250
PLOT
1 LIMIT
PLOT
LIMIT
1
28 27 26 25 24 23 22 21 20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
2 2 GAS SYSTEM LEGEND
F/A FROM ABOVE
SYMBOL DESCRIPTION
F/B FROM BELOW
ROAD MARKINGS G PANEL DETECTOR
AS PER STANDARDS 300MM FROM FFL T/A TO ABOVE
TRAFFIC SIGNAGE FOR
TURNING LEFT AND GAS DETECTOR T/B TO BELOW
RAMP DOWN AT H/L TRAFFIC SIGNAGE FOR G KITCHEN - TYPE
300MM FROM FFL
TURNING LEFT TO AT H/L H/L HIGH LEVEL
GAS SWITCH
1200MM FROM FFL L/L LOW LEVEL
FFL + 5900
FFL + 5900 GAS CONTROL UNIT GS GAS SWITCH
TRAFFIC SIGNAGE FOR INSIDE KITCHEN KGD KITCHEN GAS
HIGHER CABINET DETECTOR
TURNING RIGHT AT H/L TRAFFIC SIGNAGE FOR
TURNING RIGHT AND SENSOR ACCESS DOOR OGD OTS/DUCT GAS
RAMP UP AT H/L DETECTOR
3 3
46 45 44 43 42 41 40 39 38 37 36 35 34 33 32 31 30 29
PODIUM LEVEL 2
PODIUM LEVEL 2
3% SLOPE
3% SLOPE
RAMP UP
RAMP UP TO
12% SLOPE
12% SLOPE
2061 EB LP=250 2061 EB LP=250 2061 EB LP=250 2061 EB LP=250 2061 EB LP=250 2061 EB LP=250 2061 EB LP=250 2061 EB LP=250 2061 EB LP=250
FFL + 5900
(JVC15BMRM002)
ADJACENT PLOT
(JVC15BMRM001)
ADJACENT PLOT
45000
45000
DOWN
DOWN DOWN
STAIRCASE 2 FFL + 4950
SERVICE
4 LIFT 1 LIFT 2
LIFT STAIRCASE 1 A
4
UP
D1 UP
A-301 02 Issued For Approval 27-11-2024
D15
ELECTRICAL
"NO SMOKING" RETAIL LINE 00 Issued For Approval 12-11-2024
SIGNAGE Ø1" CS PIPE SCH40 T/B
RAMP DOWN TO
RAMP UP FROM
A
GROUND LEVEL
LIFT LOBBY
GROUND LEVEL
FFL + 4950
Rev. No. Discription Date Drawn Checked
12% SLOPE
12% SLOPE
A-301
CLIENT :
FFL + 4950
D14
4
OGD 28
PIPE IN PIPE
2 5
A-204 LIFT 4 LIFT 3 A-202
G
47 48 49 50
6 6
64 63 62 61 60 59 58 57 56 55 54 53 52 51
MAIN LINE
Ø3" CS PIPE SCH40 F/B T/A
PLOT NO:
7 7
2HR FIRE RATED SHAFT
20X20
OGD 26 OGD 27
PIPE IN PIPE PIPE IN PIPE
BACKLIT GLASS
8 PLOT PLOT
LIMIT
8
LIMIT
E=486920.779 E=486888.968
SCALE : DATE :
S NORTH
SE DRAWN :
W
A E H K M R CHECKED :
SW
NW
42200
N APPROVED :
R O A D W I D T H 3 . 6 5 m
B NE DWG NAME :
E
1 A-302
A-201
3 B
N=2772630.973 A-203
A-302 N=2772658.702
E=486891.211 E=486859.399
2061 EB LP=250 2061 EB LP=250 2061 EB LP=250 2061 EB LP=250 2061 EB LP=250 2061 EB LP=250 2061 EB LP=250 2061 EB LP=250 2061 EB LP=250 2061 EB LP=250 2061 EB LP=250 2061 EB LP=250 2061 EB LP=250 2061 EB LP=250
PLOT
1 LIMIT
PLOT
LIMIT
1
28 27 26 25 24 23 22 21 20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
2 2 GAS SYSTEM LEGEND
F/A FROM ABOVE
SYMBOL DESCRIPTION
ROAD MARKINGS F/B FROM BELOW
TRAFFIC SIGNAGE FOR AS PER STANDARDS G PANEL DETECTOR
300MM FROM FFL T/A TO ABOVE
TURNING LEFT AND
RAMP DOWN AT H/L TRAFFIC SIGNAGE FOR GAS DETECTOR T/B TO BELOW
TURNING LEFT TO AT H/L G KITCHEN - TYPE
300MM FROM FFL
H/L HIGH LEVEL
GAS SWITCH
1200MM FROM FFL L/L LOW LEVEL
FFL + 10600
GAS CONTROL UNIT GS GAS SWITCH
FFL + 10600 TRAFFIC SIGNAGE FOR
INSIDE KITCHEN KGD KITCHEN GAS
TURNING RIGHT AT H/L TRAFFIC SIGNAGE FOR HIGHER CABINET DETECTOR
TURNING RIGHT AND
RAMP UP AT H/L SENSOR ACCESS DOOR OGD OTS/DUCT GAS
DETECTOR
3 3
46 45 44 43 42 41 40 39 38 37 36 35 34 33 32 31 30 29
PODIUM LEVEL 3
PODIUM LEVEL 3
12% SLOPE
12% SLOPE
RAMP UP
RAMP UP TO
12% SLOPE
12% SLOPE
2061 EB LP=250 2061 EB LP=250 2061 EB LP=250 2061 EB LP=250 2061 EB LP=250 2061 EB LP=250 2061 EB LP=250 2061 EB LP=250 2061 EB LP=250
FFL + 10600
FFL + 10600
(JVC15BMRM002)
ADJACENT PLOT
(JVC15BMRM001)
ADJACENT PLOT
DOWN
FFL + 9928.58
45000
45000
DOWN
FFL + 8250
DOWN DOWN
STAIRCASE 2
SERVICE
4 LIFT 1 LIFT 2
LIFT STAIRCASE 1 A
4
D1 UP
UP
FFL + 8250 A-301 27-11-2024
D15 02 Issued For Approval
RAMP DOWN TO
PODIUM LEVEL 1
PODIUM LEVEL 1
12-11-2024
RAMP UP FROM
SIGNAGE 00 Issued For Approval
A LIFT LOBBY
12% SLOPE
12% SLOPE
Rev. No. Discription Date Drawn Checked
A-301
CLIENT :
D14
4 2 5
A-204 LIFT 4 LIFT 3 A-202
47 48 49 50 51 52 53 54
6 6
76 75 74 73 72 71 70 69 68 67 66 65 64 63 62 61 60 59 58 57 56 55
MAIN LINE
Ø3" CS PIPE SCH40 F/B T/A
PLOT NO:
7 7
2HR FIRE RATED SHAFT
20X20
PROJECT TITLE :
PARKING SAFEGUARD PARKING SAFEGUARD PARKING SAFEGUARD PARKING SAFEGUARD
2061 EB LP=250 2061 EB LP=250 2061 EB LP=250 2061 EB LP=250 2061 EB LP=250 2061 EB LP=250 2061 EB LP=250 2061 EB LP=250 2061 EB LP=250 2061 EB LP=250 2061 EB LP=250
8 PLOT PLOT
LIMIT
8
LIMIT
W
DRAWN :
A E H K M R
SW
NW
42200 CHECKED :
R O A D W I D T H 3 . 6 5 m N APPROVED :
B NE
E
1 A-302 DWG NAME :
A-201
- PODIUM LEVEL 2
A 104 SCALE 1: 100
PROJECT NO. : DWG NO. : REV NO. :
42200
A B C D F G ADJACENT PLOT
J L N O Q R
(JVC15BMRA700)
3 B
N=2772630.973 A-203
A-302 N=2772658.702
E=486891.211 E=486859.399
2061 EB LP=250 2061 EB LP=250 2061 EB LP=250 2061 EB LP=250 2061 EB LP=250 2061 EB LP=250 2061 EB LP=250
PLOT
1 LIMIT
PLOT
LIMIT
1
2 2 SYMBOL DESCRIPTION
F/A
F/B
FROM ABOVE
FROM BELOW
G PANEL DETECTOR
ROAD MARKINGS 300MM FROM FFL T/A TO ABOVE
25 24 23 22
3 3
43 42 41 40 39 38 37 36 35 34 33 32 31 30 29 28 27 26
OGD 24
RAMP DOWN
PIPE IN PIPE
12% SLOPE
12% SLOPE
RAMP UP
G
2061 EB LP=250 2061 EB LP=250 2061 EB LP=250 2061 EB LP=250 2061 EB LP=250 2061 EB LP=250 2061 EB LP=250 2061 EB LP=250 2061 EB LP=250
Ø1" SCH 40 CS PIPE
Ø2" SLEEVE PIPE
DROPPER 11 FFL + 15300
Ø1" CS PIPE SCH40 F/A FFL + 15300
(JVC15BMRM002)
DROPPER 10
ADJACENT PLOT
(JVC15BMRM001)
45000
45000
DOWN
DOWN DOWN
RAMP DOWN TO
PODIUM LEVEL 2
PODIUM LEVEL 2
RAMP UP FROM
STAIRCASE 2
SERVICE
4 4
12% SLOPE
12% SLOPE
LIFT 1 LIFT 2
LIFT
FFL + 12950 D1 UP
FFL + 12950
UP
A 02 Issued For Approval 27-11-2024
STAIRCASE 1 A-301
D15
01 Issued For Approval 22-11-2024
D14
4 2 5
A-204 DROPPER 9 LIFT 4 LIFT 3 A-202
Ø1" CS PIPE SCH40 T/A OGD 18
DROPPER 4
PIPE IN PIPE
44 45 46 47 Ø1" CS PIPE SCH40 F/A
48 49 50 51
6 OGD 23
DROPPER 7
Ø1" CS PIPE SCH40 F/A
OGD 22
OGD 21
PIPE IN PIPE
6
PIPE IN PIPE PIPE IN PIPE G
DROPPER 8
Ø1" CS PIPE SCH40 T/A
DROPPER 3
TRAFFIC SIGNAGE FOR Ø1" CS PIPE SCH40 T/A
TURNING RIGHT AND TRAFFIC SIGNAGE FOR
RAMP UP AT H/L TURNING RIGHT AT H/L
FFL + 12950
73 72 71 70 69 68 67 66 65 64 63 62 61 60 59 58 57 56 55 54 53 52 PLOT NO:
MAIN LINE
Ø3" CS PIPE SCH40 F/B T/A
7 7
2HR FIRE RATED SHAFT
20X20
2061 EB LP=250 2061 EB LP=250 2061 EB LP=250 2061 EB LP=250 2061 EB LP=250 2061 EB LP=250 2061 EB LP=250 2061 EB LP=250 2061 EB LP=250 2061 EB LP=250 2061 EB LP=250
8 PLOT PLOT
LIMIT
8
LIMIT
PLOT NO. : LOCALITY : ALBARSHA SOUTH FOURTH
N=2772664.895 N=2772692.623
E=486920.779 E=486888.968 SCALE : DATE :
B
1 A-302 NORTH
A-201
S DRAWN :
SE
W
A E H K M R CHECKED :
SW
NW
42200 N APPROVED :
R O A D W I D T H 3 . 6 5 m
DWG NAME :
NE
E
- PODIUM LEVEL 3 PROJECT NO. : DWG NO. : REV NO. :
A 105 SCALE 1: 100
POOL WATER LEVEL
FFL+20275 FFL+20275
FFL+20075
SSL+19925
200
350
950
FFL+19325
1550
SLOPE 10%
FFL+18725
4620
4340
4340
2680
PODIUM LVL 3 (H/L)
FFL +15300mm
SECTION N-N
42200
A B C D F G ADJACENT PLOT
J L N O Q R GAS SYSTEM LEGEND
F/A FROM ABOVE
(JVC15BMRA700) SYMBOL DESCRIPTION
F/B FROM BELOW
G PANEL DETECTOR
N=2772630.973 N=2772658.702 300MM FROM FFL T/A TO ABOVE
E=486891.211 E=486859.399 GAS DETECTOR T/B TO BELOW
G KITCHEN - TYPE
300MM FROM FFL
H/L HIGH LEVEL
PLOT
1 LIMIT
PLOT
LIMIT
1 GAS SWITCH
1200MM FROM FFL L/L LOW LEVEL
2 2
N N
FFL + 20275
POOL
s
FFL + 20275
LOCKABLE ENCLOSURE
01 02 03 04
05 06 07 08
W7SS
CHANGE W7A
ROOM
12U
SAUNA SHO.
TOI. TOI.
3 BEDROOM 1 LIVING/DINING 3
LOCKERS
MALE WELLNESS AREA
BENCH
LOCKERS
BENCH
ED9
D10 UNIT 9 GYM
FFL + 20275 2BHK TYPE 1 STEAM
G
OGD 15
D4 ED10
300mm FROM SHAFT END PRAYER ROOM
2HR FIRE RATED
D5 HORIZONTAL SHAFT
2HR FIRE RATED BATH 10X10
UNIT 10
HORIZONTAL SHAFT (BY MAIN CONTRACTOR) OGD 14
STUDIO TYPE 13 SERVICE 300mm FROM SHAFT END
10X10 SAUNA
(BY MAIN CONTRACTOR) CHANGE TOI. SHO. ROOM
ROOM TOI.
HALLWAY
SENSOR ACCESS G
FFL + 20000
SENSOR ACCESS
@ H/L G @ H/L
FEMALE WELLNESS AREA
SENSOR ACCESS
@ H/L
02 Issued For Approval 27-11-2024
LOCKERS
& BENCH
SENSOR ACCESS
BENCH
DROPPER 11 D5@ H/L F.H.R.
Ø1" CS PIPE SCH40 F/A T/B SENSOR ACCESS LOCKERS
DB
G G G
OGD 10 BEDROOM 2
D4 @ H/L
OGD 13 D4B 01 Issued For Approval 22-11-2024
300mm FROM SHAFT 300mm FROM SHAFT END
(JVC15BMRM002)
DROPPER 10 C.BATH D5
END BATH SENSOR ACCESS
ADJACENT PLOT
(JVC15BMRM001)
Ø1" CS PIPE SCH40 F/B T/A ENT 2HR FIRE RATED SHAFT 00 Issued For Approval 12-11-2024
ADJACENT PLOT
45000
12U DB
MAIN LINE
G
CLIENT :
W11 OGD 12
Ø3" CS PIPE SCH40 F/B T/A
JACUZZI DOWN 300mm DROM SHAFT END UP
STAIRCASE 2
SERVICE
OGD 16
4 4
LIFT
LIFT 1 LIFT 2 300mm ABOVE FFL
STAIRCASE 1
HALLWAY
a
In
fu
n
si o AUDIO
MENU TUNE/TRK
SEEK
ELV
OPEN TERRACE CABINET
ED7A
IN LOCKABLE CABINET
ELECTRICAL METER CABINET
FFL + 20000
LIVING / DINING WATER
LIFT LOBBY METER RM. ED7B
D11A SENSORD10
ACCESS
LIVING/DINING
GAS EMERGENCY SWITCHES OPEN TERRACE
@ H/L
IN LOCKABLE CABINET CONSULTANT :
FFL + 20000 DROPPER 9 GAR. F.H.R. FFL + 20000
Ø1" CS PIPE SCH40 F/B T/A ELECTRICAL
RM. TELEPHONE
ROOM
OGD 9 ROOM
D10
300mm FROM FFL
5
HALLWAY
DB
SENSOR ACCESS
DROPPER 4
D10
@ L/L
UNIT 8 OGD 7 Ø1" CS PIPE SCH40 F/A T/B
ED7B DROPPER 5 LIFT 4 OGD 4 ED7B
12U
W11 G 3-BHK TYPE 2 LIFT 3 W10
300MM FROM SHAFT Ø1" CS PIPE SCH40 300mm FROM SHAFT END
SHAFTF/A SENSOR ACCESS
END @ H/L
DB
SENSOR ACCESS SENSOR ACCESS SENSOR ACCESS
G @ H/L G
2HR FIRE RATED SHAFT @ H/L @ H/L UNIT 1
6 KITCHEN
D5B ENT.LOBBY
DROPPER 7
Ø1" CS PIPE SCH40 F/A T/B HALLWAY
20X20
DROPPER 6
DB 12U
G G
2HR FIRE RATED SHAFT
DROPPER 3
OGD 2
300mm FROM SHAFT END
HALLWAY
3-BHK TYPESENSOR
1
ENT.LOBBY
ACCESS
@ H/LD5B KITCHEN 6
Ø1" CS PIPE SCH40 F/A Ø1" CS PIPE SCH40 F/B T/A DROPPER 2 ENT
D4 ENT
SENSOR ACCESS D4 20X20 D4 D4
VOID
SENSOR ACCESS SENSOR ACCESS
ENT ENT Ø1" CS PIPE ENT
SCH40 F/A T/B
@ H/L @ H/L ENT @ENT
H/L ENT
VOID
BEDROOM 1 G G
DROPPER 1 MEP CONTRACTOR :
G
D4 G
D4 Ø1" CS PIPE SCH40 F/B T/A
G
DB
D4
DB
G
D4
DB
OGD 8 BATH
PASSAGE
DB
DB
PASSAGE
Ø1" CS PIPE SCH40 F/B T/A BATH OGD 6 300MM FROM SHAFT END BATH
D5 OGD 3 D5 BEDROOM 1
300mm FROM SHAFT
D5 D5 BATH
END 300mm FROM SHAFT END
OGD 1 C.BATH
C.BATH BATH D5 D5 BATH
G
G G 300mm FROM SHAFT END
D5 D10
2HR FIRE RATED
SHAFT G G
D10 D5 DRESS
UNIT 5
12U
PASSAGE PASSAGE
1-BHK TYPE 1
D10
UNIT 7 UNIT 4 UNIT 2
2HR FIRE RATED
D10 STUDIO TYPE 3 HORIZONTAL SHAFT D10
STUDIO TYPE 5 STUDIO TYPE 3 D10 D10 PLOT NO:
BEDROOM 1
12U
10X10 UNIT 6 2HR FIRE RATED SHAFT 2HR FIRE RATED SHAFT
(BY MAIN CONTRACTOR)
STUDIO TYPE 4 20X20 UNIT 3 20X20
STUDIO TYPE 4 BATH
LIVING/DINING BEDROOM 2
BATH
BEDROOM 2 D16 D16
BEDROOM 3
PROJECT TITLE :
12U
VOID
VOID
BEDROOM 3
12U
7 7
12U
12U
ED4C W6 W6
ED4D ED4D ED4B
BALCONY BALCONY
SCALE : DATE :
8 PLOT PLOT
LIMIT
8
LIMIT NORTH
DRAWN :
N=2772664.895 N=2772692.623
E=486920.779 E=486888.968 CHECKED :
S N APPROVED :
SE
W
A E H K M R DWG NAME :
SW
NW
42200
R O A D W I D T H 3 . 6 5 m
NE
E
PROJECT NO. : DWG NO. : REV NO. :
42200
A B C D F G ADJACENT PLOT
J L N O Q R
(JVC15BMRA700)
3 B
N=2772630.973 A-203
A-302 N=2772658.702
E=486891.211 E=486859.399
PLOT
1 LIMIT
PLOT
LIMIT
1
01 02 03 04
05 06 07 08
12U
12U
G
3 BEDROOM 1 LIVING/DINING 3
12U
12U
2HR FIRE RATEDSTUDIO TYPE 7 STUDIO TYPE 9 STUDIO TYPE 10
G HORIZONTAL SHAFT
10X10
(BY MAIN CONTRACTOR)
12U
2HR FIRE RATED
HORIZONTAL SHAFT
UNIT 18
2HR FIRE RATED BATH 10X10
(BY MAIN CONTRACTOR)
G STUDIO TYPE 11
HORIZONTAL SHAFT 2HR FIRE RATED UNIT 14
BATH
10X10 HORIZONTAL STUDIO
SHAFT TYPE 8
(BY MAIN CONTRACTOR) 10X10 BEDROOM
(BY MAIN CONTRACTOR) G BATH
UNIT 12
12U
2-BHK G UNIT 15
1-BHK
DB
DROPPER 11
DB
DB
Ø1" CS PIPE SCH40 F/A T/B BATH
DB
DB
BEDROOM 2 STUDIO 215 216 217 G
C.BATH
(JVC15BMRM002)
DROPPER 10 213 G
BATH
ADJACENT PLOT
(JVC15BMRM001)
G HALLWAY DROPPER 15
DROPPER 14
ENTRANCE Ø1" CS PIPE SCH40 F/A
214 Ø1" CS PIPE SCH40 F/A
LOBBY 212
45000
45000
DB
12U DB
RECYCLE BINS
MAIN LINE
Ø3" CS PIPE SCH40 F/B T/A
4
DROPPER 12
3
Ø1" CS PIPE SCH40 F/A
02 22-11-2024
STAIRCASE 2 A Issued For Approval
SERVICE
2
DROPPER 16
12U
4 4
LIFT
VOID DROPPER 13
1
VOID Ø1" CS PIPE SCH40 F/A T/B
Ø1" CS PIPE SCH40 F/A A-301 01 Issued For Approval 22-11-2024
STAIRCASE 1
HALLWAY
BALCONY 00 Issued For Approval 12-11-2024
UNIT 11
"NO SMOKING"
STUDIO TYPE 6 SIGNAGE
Rev. No. Discription Date Drawn Checked
GAS EMERGENCY SWITCHES
A IN LOCKABLE CABINET GAS EMERGENCY SWITCHES CLIENT :
ELECTRICAL ROOM
A-301 FFL + 20000 IN LOCKABLE CABINET
LIFT LOBBY BATH
WATER METER
ROOM
UNIT 19
G BATH STUDIO TYPE 12
4 DROPPER 9
GAR.
RM.
F.H.R G
2
A-204 Ø1" CS PIPE SCH40 F/B T/A TELEPHONE
ELECTRICAL
5
HALLWAY
RM.
RM. A-202
DROPPER 5 DROPPER 4
Ø1" CS PIPE SCH40 F/A T/B LIFT 4 Ø1" CS PIPE
LIFTSCH40
3 F/A T/B
DB
DB
SHAFT G 12U
211 DROPPER 17
OGD 17 219 2HR FIRE RATED
Ø1" CS PIPE SCH40 F/A
HALLWAY
10X10
(BY MAIN CONTRACTOR)
6 CONSULTANT :
210 DROPPER 2 201 UNIT 1
HORIZONTAL SHAFT DROPPER 3
VOID
206 205 Ø1" CS PIPE SCH40 F/A T/B STUDIO TYPE 1
10X10 Ø1" CS PIPE SCH40 F/B T/A BATH
BATH G 209 208 203 202 G
VOID
G
DB
DB
BATH
DB
G
DB
DROPPER 8
Ø1" CS PIPE SCH40 F/B T/A BATH BATH DROPPER 1
Ø1" CS PIPE SCH40 F/B T/A
BATH
BATH 2HR FIRE RATED BATH
G
BATH HORIZONTAL SHAFT G BATH
10X10 MEP CONTRACTOR :
UNIT 10 G (BY MAIN CONTRACTOR) DRESS G
STUDIO TYPE 1 UNIT 6
G
1-BHK TYPE 1
G
UNIT 3
UNIT 8 UNIT 5 STUDIO TYPE 3
STUDIO TYPE 3 STUDIO TYPE 5
BEDROOM 1 UNIT 4
UNIT 9
12U
UNIT 7
12U
STUDIO TYPE 4
12U
VOID
PROJECT TITLE :
12U
7 7
12U
12U
BALCONY BALCONY
BALCONY
BALCONY
8 PLOT PLOT
LIMIT
8 SCALE : DATE :
LIMIT NORTH
DRAWN :
N=2772664.895 N=2772692.623
CHECKED :
E=486920.779 WS3 WS4 WS1 B E=486888.968
A-307 A-307
1 A-306 A-302 S N APPROVED :
A-201 SE
W
DWG NAME :
A E H K M R
SW
NW
42200
R O A D W I D T H 3 . 6 5 m
NE
E
PROJECT NO. : DWG NO. : REV NO. :
42200
A B C D F G ADJACENT PLOT
J L N O Q R
(JVC15BMRA700)
3 B
N=2772630.973 A-203
A-302 N=2772658.702
E=486891.211 E=486859.399
PLOT
1 LIMIT
PLOT
LIMIT
1
01 02 03 04
SENSOR ACCESS DOOR OGD OTS/DUCT GAS
DETECTOR
05 06 07 08
W7
ED6B
12U
12U
3 BEDROOM 1 LIVING/DINING
ED6A
BALCONY
W8A ED6C BALCONY
3
12U
12U
STUDIO TYPE 9
2HR FIRE RATEDSTUDIO TYPE 7 STUDIO TYPE 10
G
HORIZONTAL SHAFT
10X10
(BY MAIN CONTRACTOR)
12U
2HR FIRE RATED
D5 HORIZONTAL SHAFT
UNIT 18
2HR FIRE RATED BATH UNIT 14 10X10 G STUDIO TYPE 11
HORIZONTAL SHAFT STUDIO TYPE 8
2HR FIRE RATED (BY MAIN CONTRACTOR)
BATH
10X10 HORIZONTAL SHAFT D5
(BY MAIN CONTRACTOR) 10X10 BEDROOM
D5 (BY MAIN CONTRACTOR) D10 G D5 BATH
UNIT 12
12U
2-BHK G UNIT 15
1-BHK
DB
DROPPER 11 D5
DB
DB
D4
Ø1" CS PIPE SCH40 F/A T/B D4 BATH
D4
DB
D4 BATH
D5 G D5
C.BATH
(JVC15BMRM002)
DROPPER 10 D5 G
ADJACENT PLOT
(JVC15BMRM001)
DROPPER 14
DROPPER 15
ENTRANCE
G Ø1" CS PIPE SCH40HALLWAY
F/A T/B
Ø1" CS PIPE SCH40 F/A T/B
D4
D10
LOBBY D4
D1
SEE STAIRCASE DETAIL 1
W11
45000
45000
DB
12U DB
RECYCLE BINS
MAIN LINE
Ø3" CS PIPE SCH40 F/B T/A
4
DROPPER 12
3
Ø1" CS PIPE SCH40 F/A T/B
STAIRCASE 2 A
SERVICE
2
DROPPER 16
12U
4 4
LIFT
1
VOID VOID Ø1" CS PIPE SCH40 F/A T/B
A-301
DROPPER 13 STAIRCASE 1
HALLWAY
HALLWAY
RM D11 TELEPHONE A-202
W11 RM.
LIFT 4 LIFT 3 W11
D4
DB
DB
SHAFT
DROPPER 5
D4 DROPPER 4
Ø1" CS PIPE SCH40 F/A T/B
Ø1" CS PIPE SCH40 F/A T/B 2HR FIRE RATED
DROPPER 17
HORIZONTAL SHAFT
6 D4
2HR FIRE RATED
DROPPER 7
Ø1" CS PIPE SCH40 F/A T/B
DB 12U
DROPPER 3 HALLWAY
Ø1" CS PIPE SCH40 F/A T/B
10X10
(BY MAIN CONTRACTOR)
6
DROPPER 6 Ø1" CS PIPE SCH40 F/B T/A DROPPER 2 D4 UNIT 1
HORIZONTAL SHAFT
VOID
D5 D4
Ø1" CS PIPE SCH40 F/A T/B D4
Ø1" CS PIPE SCH40 F/A T/B STUDIO TYPE 1 D5 BATH
10X10
BATH G D4 G
VOID
D4 D4 D4
CONSULTANT :
G D4
D4
DB
DB
BATH
DB
G
DB
DROPPER 8
Ø1" CS PIPE SCH40 F/B BATH BATH DROPPER 1
D5 D5 D5 Ø1" CS PIPE SCH40 F/B
BATH
D5 G BATH D5 D5 BATH D5
BATH 2HR FIRE RATED D5 G BATH
HORIZONTAL SHAFT
UNIT 10 G 10X10 DRESS G
STUDIO TYPE 1 UNIT 6
(BY MAIN CONTRACTOR)
G
1-BHK TYPE 1
G
UNIT 3
UNIT 8 UNIT 5 STUDIO TYPE 3 MEP CONTRACTOR :
STUDIO TYPE 3 STUDIO TYPE 5
D10 BEDROOM 1 UNIT 4
UNIT 9
12U
UNIT 7
12U
STUDIO TYPE 4
12U
VOID
PLOT NO:
12U
7 7
12U
ED4D W6 W6 ED4D
12U
ED5B
BALCONY ED5B
BALCONY ED5B
BALCONY BALCONY ED5B ED5B
BALCONY ED5B
BALCONY
8 PLOT PLOT
LIMIT
8
LIMIT
PLOT NO. : LOCALITY : ALBARSHA SOUTH FOURTH
N=2772664.895 N=2772692.623
SCALE : DATE :
E=486920.779 WS3 WS4 WS1 B E=486888.968
A-307 A-307
1 A-306 A-302 S NORTH
DRAWN :
A-201 SE
W
CHECKED :
A E H K M R
SW
NW
42200 N APPROVED :
R O A D W I D T H 3 . 6 5 m DWG NAME :
E NE
- TYPICAL FLOOR PLAN (3RD TO 6TH) PROJECT NO. : DWG NO. : REV NO. :
PLOT
1 LIMIT
PLOT
LIMIT
1
LOCKABLE ENCLOSURE
ED6CM
BAL. ED6C BAL ED6CM
BAL. ED6C BAL.
01 02 03 04
05 06 07 08
W7 BAL
ED6B
12U
12U
G
3 BAL ED6A
W8A ED6C BAL. 3
12U
BED
D10 LIVING/DINING
12U
2HR FIRE RATED UNIT 12
HORIZONTAL SHAFT UNIT 11
G 10X10 STUDIO TYPE 9 STUDIO TYPE 10
UNIT
(BY MAIN CONTRACTOR) 8
STUDIO TYPE 7
LIVING/DINING
12U
2HR FIRE RATED
D5 HORIZONTAL SHAFT
2HR FIRE RATED 10X10 G UNIT 13
HORIZONTAL SHAFT 2HR FIRE RATED (BY MAIN CONTRACTOR)
STUDIO TYPE 11
10X10 UNIT 7 HORIZONTAL SHAFT D5
(BY MAIN CONTRACTOR) 2-BHK TYPE 1 10X10
D5 (BY MAIN CONTRACTOR) D10 D5
UNIT 9 UNIT 10 G
STUDIO TYPE8 1-BHK TYPE 2
12U
G
D5
DB
DROPPER 11
DB
DB
Ø1" CS PIPE SCH40 F/A T/B DB
F.H.R.
D5A D4 DB
D4 G D5
D5 D4
(JVC15BMRM002)
DROPPER 10 D5 D4 G
ADJACENT PLOT
(JVC15BMRM001)
DROPPER 14
G DROPPER 15
HALLWAY
Ø1" CS PIPE SCH40 F/A T/B
Ø1" CS PIPE SCH40 F/A T/B
D4
D4
D10 D1
W11
45000
45000
DB
12U DB
MAIN LINE
Ø3" CS PIPE SCH40 F/B T/A
DROPPER 12
DOWN Ø1" CS PIPE SCH40 F/A T/B UP
STAIRCASE 2 DROPPER 13 DROPPER 16 A
HALLWAY
SERVICE
4 LIFT 1 LIFT 2 Ø1" CS PIPE SCH40 F/A T/B
LIFT
STAIRCASE 1
Ø1" CS PIPE SCH40 F/A T/B
A-301 4
ROOF DECK UP DOWN 02 Issued For Approval 22-11-2024
D1
01 Issued For Approval 22-11-2024
ED7B
HALLWAY
ELE. RM. D11
TELEPHONE
W12B W9 W10 SHAFT SHAFT ROOM D4C W9 W12B
D10 SHAFT 5
DROPPER
12U DB
Ø1" CS PIPE SCH40 F/A T/B DROPPER 4 DB 12U
VOID
HORIZONTAL SHAFT
(BY MAIN CONTRACTOR) D4 D4 10X10
(BY MAIN CONTRACTOR) CONSULTANT :
G
DB
DB
DB
G D5 G
D5 G
D5
G D5
D10 D10
D5A D5A
VOID
12U
VOID
PLOT NO:
7 W6 W6
7
ED4D ED4D D10
ED4C D10 ED4B
OPEN
BELOW
BALCONY BALCONY
BALCONY BALCONY
PROJECT TITLE :
ED5B W8B ED5B ED5B W8B ED5B
BALCONY BALCONY BALCONY BALCONY
8 PLOT PLOT
LIMIT
8
LIMIT
PLOT NO. : LOCALITY : ALBARSHA SOUTH FOURTH
N=2772664.895 N=2772692.623
E=486920.779 WS3 WS4 WS1 B E=486888.968 SCALE : DATE :
A-307 A-307
1 A-306 A-302 S
A-201 NORTH
SE DRAWN :
W
A E H K M R CHECKED :
SW
NW
42200
N APPROVED :
R O A D W I D T H 3 . 6 5 m
NE DWG NAME :
E
PLOT
1 LIMIT
PLOT
LIMIT
1
01 02 03 04
05 06 07 08
ED6CM
BAL. ED6C BAL ED6CM
BAL. ED6C BAL.
G
W7 BAL
ED6B
12U
12U
3 BAL ED6A
W8A ED6C BAL. 3
12U
DROPPER 14
BED Ø1" CS PIPE SCH40 T/B
D10 LIVING/DINING
12U
DROPPER 15
UNIT 12
2HR FIRE RATED UNIT 11
G STUDIO TYPE 9 STUDIO
Ø1" CS PIPE SCH40 F/A TYPE
T/B 10
HORIZONTAL SHAFT UNIT 8
10X10
STUDIO TYPE
(BY MAIN CONTRACTOR)
7
LIVING/DINING
12U
2HR FIRE RATED
D5 HORIZONTAL SHAFT G
2HR FIRE RATED 10X10 G UNIT 13
HORIZONTAL SHAFT 2HR FIRE RATED (BY MAIN CONTRACTOR)
STUDIO TYPE 11
10X10 UNIT 7 HORIZONTAL SHAFT D5
(BY MAIN CONTRACTOR) 2-BHK TYPE 1 10X10
D5 (BY MAIN CONTRACTOR) D10 D5
UNIT 9 UNIT 10
STUDIO TYPE8 1-BHK TYPE 2
12U
G
D5
DB
DB
DB
DROPPER 11
Ø1" CS PIPE SCH40 F/A T/B F.H.R.
DB
D5A D4 DB
D4 G D5
D5 D4 G
(JVC15BMRM002)
DROPPER 10 D5 D4 G
ADJACENT PLOT
(JVC15BMRM001)
OGD 23
G PIPE IN PIPE HALLWAY
D4 15TH FLR ONLY
D4
D10 D1
W11
45000
45000
DB
12U DB
MAIN LINE
Ø3" CS PIPE SCH40 F/B T/A
DROPPER 12
DOWN Ø1" CS PIPE SCH40 F/A T/B UP
STAIRCASE 2 DROPPER 13 DROPPER 16 A
HALLWAY
SERVICE
4 LIFT 1 LIFT 2 Ø1" CS PIPE SCH40 F/A T/B
LIFT
STAIRCASE 1
Ø1" CS PIPE SCH40 F/A T/B
A-301 4
UP DOWN
02 Issued For Approval 27-11-2024
D1
GAS EMERGENCY SWITCHES
IN LOCKABLE CABINET ED7B 01 Issued For Approval 22-11-2024
WATER
METER RM. Rev. No. Discription Date Drawn Checked
D11 D11
GAR. ED7B CLIENT :
4 D7 RM.
F.H.R.
2
A-204
A-202 5
HALLWAY
ELE. ROOM D11
TELEPHONE
W12B W9 W10 SHAFT SHAFT ROOM D4C W9 W12B
D10 SHAFT
12U DB DROPPER 4 DB 12U
DROPPER 5
Ø1" CS PIPE SCH40 F/A T/B
Ø1" CS PIPE SCH40 F/A T/B DROPPER 17 D10
6 D5
2HR FIRE RATED
DROPPER D47
Ø1" CS PIPE SCH40 F/A T/B
DB 12U
Ø1" CS PIPE SCH40
D4 F/A T/B
DROPPER 2
Ø1" CS PIPE SCH40 F/A T/B
D5 6
HORIZONTAL SHAFT DROPPER 6
10X10 D4
Ø1" CS PIPE SCH40 F/A T/B D4
VOID
2HR FIRE RATED
(BY MAIN CONTRACTOR) D4 D4 HORIZONTAL SHAFT
10X10
G (BY MAIN CONTRACTOR) CONSULTANT :
DB
DB
DB
G D5 G
D5 D5
G D5 G
D10 D10
D5A D5A
VOID
12U
VOID
PLOT NO:
7 W6 W6
7
ED4D ED4D D10
ED4C D10 ED4B
OPEN
BELOW
BALCONY BALCONY
BALCONY BALCONY
PROJECT TITLE :
ED5B W8B ED5B ED5B W8B ED5B
BALCONY BALCONY BALCONY BALCONY
8 PLOT PLOT
LIMIT
8
LIMIT
W
A E H K M R
SW
CHECKED :
NW
42200
R O A D W I D T H 3 . 6 5 m N APPROVED :
NE
E
DWG NAME :
3 B
N=2772630.973 A-203
A-302 N=2772658.702
E=486891.211 E=486859.399
PLOT
1 LIMIT
PLOT
LIMIT
1
LOCKABLE ENCLOSURE
01 02 03 04
05 06 07 08
G
DECK DECK
3 3
ED4A ED4A ED4A W13 W13 ED4A W6B
BEDROOM 1
ED7B
D5 BEDROOM 1
ED4B
ED7B D10
LIVING/DINING D10 UNIT 5
12U
12U
BEDROOM 2 LIVING/DINING 2-BHK - TYPE 6 LOBBY
UNIT 4 DROPPER 11 ROOF DECK
2-BHK - TYPE 5 Ø1" CS PIPE SCH40 F/A T/B D5
D10 550
D10
DB
1100
D4 BEDROOM 2
D5 G BATH
DROPPER 13 DROPPER 16 DECK
Ø1" CS PIPE SCH40 F/A T/B F.H.R. Ø1" CS PIPE SCH40 F/A T/B
ED7B
(JVC15BMRM002)
ENT
ADJACENT PLOT
(JVC15BMRM001)
G
D5
ADJACENT PLOT
450
45000
45000
D4
RECYCLE BINS
MAIN LINE
D1 Ø3" CS PIPE SCH40 F/B T/A
4
DROPPER 12
ENT
Ø1" CS PIPE SCH40 F/A T/B
3
DOWN
STAIRCASE 2 A
2
HALLWAY
SERVICE
4 4
1
LIFT 1 LIFT 2
LIFT A-301
UP DOWN
STAIRCASE 1 02 Issued For Approval 27-11-2024
ELV
D1
600
"NO SMOKING"
CABINET
SIGNAGE
550
01 Issued For Approval 22-11-2024
450
ROOF DECK
IN LOCKABLE CABINET
DROPPER 4
ROOM ROOF DECK
5
400 300
GAR. CLIENT :
4 D10 RM.
F.H.R. Ø1" CS PIPE SCH40 F/A T/B
2
A-204
ELE. ROOM A-202
800
D10 TELEPHONE
ROOM
400 100
D4 FRIDGE
DB
6 DB 12U
DROPPER 2 6
500
12U
300 1300
DROPPER 6 UNIT 1
Ø1" CS PIPE SCH40 D4
ENT F/A T/B 2-BHK - TYPE 2
VOID
ENT G
VOID
D10
700 1100 300 1900
G
700
500
DROPPER 5
500
500
D4 BEDROOM 2 CONSULTANT :
DB
1900 1602
BEDROOM 2 Ø1" CS PIPE SCH40 F/A T/B
12U UNIT 2
D6A 2-BHK - TYPE 3 D6A
PANTRY
BATH DROPPER 7
OPEN SHELVES
TIMBER FINISH
VOID
DECK
VOID
PROJECT TITLE :
8 PLOT PLOT
LIMIT
8
LIMIT
N=2772664.895 N=2772692.623
E=486920.779 WS3 WS4 WS1 B E=486888.968
PLOT NO. : LOCALITY : ALBARSHA SOUTH FOURTH
A-307 A-307
1 A-306 A-302 S
A-201 SE SCALE : DATE :
W
A E H K M R NORTH
SW
DRAWN :
NW
42200
R O A D W I D T H 3 . 6 5 m CHECKED :
NE
E
N APPROVED :
DWG NAME :
250mm THK AAC BLOCKS EXTERNAL WALL PROJECT NO. : DWG NO. : REV NO. :
(FOR PODIUM LEVELS USE 200mm THK AAC
BLOCKS EXTERNAL WALL)
200mm THK INTERNAL WALL PARTITIONS
100mm THK INTERNAL WALL PARTITIONS
42200
A B C D F G ADJACENT PLOT
J L N O Q R
(JVC15BMRA700)
3 B
N=2772630.973 A-203
A-302 N=2772658.702
E=486891.211 E=486859.399
PLOT
1 LIMIT
PLOT
LIMIT
1
2 2 SYMBOL DESCRIPTION
F/A
F/B
FROM ABOVE
FROM BELOW
G PANEL DETECTOR
300MM FROM FFL T/A TO ABOVE
WS2 GAS DETECTOR T/B TO BELOW
A-306 G KITCHEN - TYPE
300MM FROM FFL
H/L HIGH LEVEL
GAS SWITCH
1200MM FROM FFL L/L LOW LEVEL
3 3
ROOF DECK
AREA
DECK SSL + 77600 DECK
BELOW FFL + 74000 BELOW
WATER TANK NOTE:
ROOF FINISHING MATERIALS SHALL
DECK HAVE A SOLAR REFLECTIVE INDEX
DROPPER 11
VALUE OF 78 OR ABOVE
Ø1" CS PIPE SCH40 T/B ROOF DECK
RISER -10 AREA
1100
SSL + 77600
RISER -08
DROPPER 14 DROPPER 15 2nd STAGE PRDP
700
NOTE: Ø1" CS PIPE SCH40 T/B Ø1" CS PIPE SCH40 T/B 75mBar
(JVC15BMRM002)
3350 Ø2" SCH 40 CS PIPE
RISER -11
ADJACENT PLOT
(JVC15BMRM001)
950
D8
450
950
45000
45000
600
DROPPER 12 800
Ø1" CS PIPE SCH40 T/B MAIN LINE
D1 DOWN Ø3" CS PIPE SCH40 F/B
LIFT
STAIRCASE 2 A
2100
DROPPER 16
SHAFTDROPPER 13 SHAFT
4 MACHINE
4
2850
Ø1" CS PIPE SCH40 T/B
Ø1" CS PIPE SCH40 T/B A-301
ROOM
02 Issued For Approval 27-11-2024
RISER -PR-01
RISER -PR-02
01 Issued For Approval 22-11-2024
410
450
120
A 150
LIFT
Ø2" SCH 40 CS PIPE
2330
ROOF DECK D8
D8 ROOF DECK
DROPPER PIPE 17
5 CLIENT :
BELOW BELOW
4 Ø1" CS PIPE SCH40 T/B
400 2
A-204
RISER -12
600
SHAFT SHAFT A-202
900
1050
200
400
200 DROPPER 4
DROPPER 5
400 Ø1" CS PIPE SCH40 T/B
Ø1" CS PIPE SCH40 T/B
6 DROPPER 2 6
500
2900 Ø1" CS PIPE SCH40 T/B
VOID
VOID
DECK RISER -00 DECK
3250
3300
500
700
500
500
ROOF DECK
2000 SSL + 77600 RISER -04 1900
1900 AREA
RISER -01 DROPPER 7
RISER -02 RISER -05
Ø1" CS PIPE SCH40 T/B 400
400 DROPPER 6
Ø1" CS PIPE SCH40 T/B
A.H.U. A.H.U.
MEP CONTRACTOR :
VOID
VALUE OF 78 OR ABOVE
1950
VOID
PLOT NO:
DECK
7 7
PROJECT TITLE :
8 PLOT PLOT
LIMIT
8
LIMIT
PLOT NO. : LOCALITY : ALBARSHA SOUTH FOURTH
N=2772664.895 N=2772692.623
E=486920.779 E=486888.968 SCALE : DATE :
WS3 WS4 WS1 B
A-307 A-307
1 A-306 A-302 NORTH
A-201
S DRAWN :
SE
W
A E H K M R CHECKED :
SW
NW
42200 N APPROVED :
R O A D W I D T H 3 . 6 5 m
DWG NAME :
NE
E
- ROOF DECK PLAN
A 118 SCALE 1: 100
PROJECT NO. : DWG NO. : REV NO. :
Ø2" SCH.40 C.S. PIPE Ø2" SCH.40 C.S. PIPE Ø2" SCH.40 C.S. PIPE Ø2" SCH.40 C.S. PIPE Ø2" SCH.40 C.S. PIPE
ROOF PRDP ROOF
FLOOR FLOOR
K K K
K K
16TH OGD 25 16TH
FLOOR H/L P/P FLOOR
OGD
K K K K K K K K K
K K K K
15TH 15TH
FLOOR FLOOR
K K K K K K K K K
K K K K
14TH 14TH
FLOOR FLOOR
K K K K K K K K K
K K K K
13TH 13TH
FLOOR FLOOR
K K K K K K K K K
K K K K
8TH 8TH
FLOOR FLOOR
DROPPER 16 Ø1" SCH.40 C.S. PIPE
K K K K
K K K K K K K K K K K K
K K K K K K K
C.S. PIPE
6TH 6TH
FLOOR FLOOR
K K K K K K K K K K K K
DROPPER 01 Ø1" SCH.40
K K K K K K K
FLOOR FLOOR
K K K K K K K K K K K K
K K K K K K K
3RD 3RD
FLOOR FLOOR
K OGD
K K K K K K K K OGD
K OGD
K OGD OGD
K
K K OGD 17
30CM FROM K K K K OGD 12
30CM FROM
OGD 13
30CM FROM
OGD 14
30CM FROM K OGD 15
30CM FROM
2ND SHAFT END SHAFT END SHAFT END SHAFT END SHAFT END 2ND
FLOOR FLOOR
K OGD
OGD
K OGD
K K OGD
K OGD OGD
K OGD
K OGD 09 OGD
K OGD
OGD 16
OGD 01
30CM FROM OGD 18
30CM
OGD 02
30CM FROM
OGD 03
30CM FROM
OGD 04
30CM FROM
OGD 05
30CM FROM
OGD 06
30CM FROM
K OGD 07
30CM FROM
OGD 08
30CM FROM
30CM
FROM FFL
OGD 10
30CM FROM
OGD 11
30CM FROM
K
FIRST FROM FFL FIRST
SHAFT END H/L P/P
OGD
SHAFT END SHAFT END OGD
SHAFT END SHAFT END SHAFT END SHAFT END SHAFT END OGD
SHAFT END SHAFT END
FLOOR FLOOR
Ø1" SCH.40 C.S. PIPE Ø1" SCH.40 C.S. PIPE
OGD OGD OGD OGD
OGD
GROUND
FEEDING LINE GROUND
OGD
Ø1" SCH.40 C.S. PIPE
FLOOR OGD 30 OGD
FLOOR
30CM FROM FFL OGD 32
FP200 4 CORE+E H/L
1.5mm EACH CONSULTANT :
FP200 4 CORE+E
1.5mm EACH
BASEMENT BASEMENT
NOTES:-
1. Final tie in connection shall be carried out after authority approval by the GAS in building contractor
with the witness of project consultant and service provider.
MEP CONTRACTOR :
1
9
3 10 11 7
1 1
5 8
PLOT NO:
1
4
6
9
3 7
1 8
4
1 1 PROJECT TITLE :
12
SCALE : DATE :
CHECKED :
N APPROVED :
DWG NAME :