Maintenance of Transformers
Maintenance of Transformers
Some other types of maintenance for a transformer we perform only as they are
required – known as emergency or breakdown transformer maintenance. But
if one performs regular maintenance properly, this significantly reduces the
chances of needing to perform such emergency maintenance. The regular
checking and maintenance of transformer is also known as condition
maintenance.
1. The oil level in oil cap under silica gel breather must be checked in a one-
month interval. If it is found the transformer oil inside the cup comes
below the specified level, oil to be top up as per specified level.
2. Breathing holes in silica gel breather should also be checked monthly and
properly cleaned if required, for proper breathing action.
3. If the transformer has oil filled bushing the oil level of transformer oil
inside the bushing must be vidually checked in the oil gage attached to
those bushing. This action also to be done monthly basis.
If it is required, the oil to be filled in the bushing upto correct level. Oil filling
to be done under shutdown condition.
In case of unsatisfactory oil level in the MOG, oil to be filled in transformer and
also the transformer tank to be checked for oil leakage. If oil leakage is found
take required action to plug the leakage. If silica gel becomes pinkish, it should
be replaced.
Yearly Basis Transformer Maintenance Schedule
1. The auto, remote, manual function of cooling system that means, oil
pumps, air fans, and other items engaged in cooling system of
transformer, along with their control circuit to be checked in the interval
of one year. In the case of trouble, investigate control circuit and physical
condition of pumps and fans.
3. Oil condition of OLTC to be examined in every year. For that, oil sample
to be taken from drain valve of divertor tank, and this collected oil sample
to be tested for dielectric strength (BDV) and moisture content (PPM). If
BDV is low and PPM for moisture is found high compared to
recommended values, the oil inside the OLTC to be replaced or filtered.
6. All the relays, alarms and control switches along with their circuit, in
R&C panel (Relay and Control Panel) and RTCC (Remote Tap Changer
Control Panel) to be cleaned by appropriate cleaning agent.
7. The pockets for OTI, WTI (Oil Temperature Indicator & Winding
Temperature Indicator) on the transformer top cover to be checked and
if required oil to be replenished.
8. The proper function of Pressure Release Device and Buchholz relay must
be checked annually. For that, trip contacts and alarm contacts of the said
devices are shorted by a small piece of wire, and observe whether the
concerned relays in remote panel are properly working or not.
10. Resistive value of earth connection and rizer must be measured annually
with clamp on earth resistance meter.
1. The calibration of OTI and WTI must be carried once in two years.
1. Oil leakage from any joint should be visually inspected if leakage found,
it must be plugged by taking shutdown.
2. The secondary terminals are also checked for oil leakage, if leakage
found, immediate action to be taken to plug the leakage.
In addition to these, tans or loss factor measurement to be performed on a
current transformer, preferably above 66 KV class, once in two years.
Dissolve Gas Analysis of oil also to be done preferably once in 4 years. If the
results are found unsatisfactory as per standard, the insulating oil must be
replaced.