SISTEMA 1000
SISTEMA 1000
SI60i
2 www.erico.com
Testing and Working Principles
www.erico.com 3
Testing and Working Principles
Working Principles
During thunderstorm conditions when the
lightning down leader is approaching ground
level, an upward leader may be created by any
surface. In the case of a passive lightning rod,
the upward leader propagates only after a long
period of charge reorganization. In the case
of the ERICO® INTERCEPTOR ESE i-Series, the
initiation time of an upward leader is greatly
reduced. The ERICO INTERCEPTOR ESE i-Series
generates controlled magnitude and frequency
pulses at the tip of the terminal during high
static fields prior to a lightning discharge.
This enables the creation of an upward leader
from the terminal that propagates toward
the downward leader coming from the
thundercloud.
According to
the NF C 17-102
and similar
ESE standards
Features
• Designed and tested to NF C 17-102 and
SI60i
similar standards
4 www.erico.com
Protecting Areas
According to NF C 17-102:2011, the standard protection radius (Rp) of the ERICO® INTERCEPTOR ESE i-Series is linked to
ΔT (below), the protection levels I, II, III or IV (as calculated in EN 62305-2) and the height (h) of the ERICO INTERCEPTOR
ESE i-Series above the structure or feature to be protected (defined by NF C 17-102 as a minimum 2 m).
Rp
Protection Protection Level I Protection Level II Protection Level III Protection Level IV
Level (99%, D = 20 m) (97%, D = 30 m) (91%, D = 45 m) (84%, D = 60 m)
Model SI25i SI40i SI60i SI25i SI40i SI60i SI25i SI40i SI60i SI25i SI40i SI60i
ΔT (μs) 25 40 60 25 40 60 25 40 60 25 40 60
h (m) Rp (m) Protection Radius
2 17 23 32 19 26 34 23 30 40 26 34 44
3 25 35 48 26 39 52 34 45 59 39 50 65
4 34 46 64 39 52 68 46 60 78 52 67 87
5 42 58 79 49 65 86 57 75 97 65 83 107
6 43 59 79 49 66 86 58 76 97 66 84 107
7 44 59 79 50 66 87 59 76 98 67 85 108
8 44 59 79 51 67 87 60 77 99 68 86 108
www.erico.com 5
Design
LPSD Design
Software
System Requirements:
The design and installation of the terminals should be Each downconductor requires a test clamp and dedicated
completed in compliance with the requirements of the earth system of 10 ohms or less. The lightning protection
French Standard NF C 17-102. In addition to terminal ground should be connected to the main building ground
placement requirements, the standard requires a minimum and any nearby buried metallic items. The NF C 17-102
of two paths to ground per terminal for non-isolated and similar ESE standards requirements for inspection
conductor systems. A downconductor cross-sectional and testing range from each year to every four years
area of ≥50 mm2 is specified. The downconductors are to dependent upon location and protection level selected.
be secured at three points per meter with equipotential Refer to your ERICO representative or the ERICO® SYSTEM
bonding made to nearby metallic items. 1000 installation manual for additional information.
6 www.erico.com
Importance of Grounding
The transient nature of lightning with its associated fast
rise times and large magnitude currents mean that special
consideration needs to be given to grounding for lightning
protection to be effective. A poorly grounded system
increases the likelihood of the strike flashing over to the
structure and/or finding a non-preferred path within the
structure. Many factors, such as soil resistivity variations,
installation accessibility, layout and existing physical
features are all site-specific and tend to affect decisions on
grounding methods employed. The primary requirements
of a direct strike grounding system are to:
Test Clamp
www.erico.com 7
Ordering Information
Air Terminals
ERICO® INTERCEPTOR SI
SI25i 25 μs 1.53 kg
SI40i 40 μs 1.53 kg
SI60i 60 μs 1.53 kg
Masts Accessories
Guy Kit
GUYKIT4MGRIP (701305) 4m 0.4 kg
GUYKIT7MGRIP (701315) 7m 0.7 kg
Cable Tie
CABTIESS (701420) 0.05 kg
Mast Bracket
ALOF1GS (702175) 1.5 kg
8 www.erico.com
Ordering Information for Europe and Asia
Mast Adapter
INTCPTSIIERICOR 0.1 kg
Cantilevered
Guyed Masts:
Masts:
Mast Height (m) 2 4 5 6 7 8 Mast Height (m) 4 5 7
SIM40C2 X X SIM33B2 X
SIM33B3 X X
SIM40C3 X
SIM40C2 X
SIMBASE2840 X X X X X X
CABTIESS 8 10 14
GUYKIT4M/GRIP X X X X X ALOF1GS 2 2 3
GUYKIT7M/GRIP X X
CABTIESS 4 8 10 12 14 16
BASEADAPTER40 X X
www.erico.com 9
Ordering Information for North America and South America
Masts and Bases Accessories
Masts and Bases Mast Clamp
ER1-1000-SS (702255) Upper section, 1 m 3.5 kg LPC570 0.2 kg
ER1-2000-SS (702260) Upper section, 2 m 6.2 kg
ER2-2000-SS (702265) Mid section, 2 m 4.9 kg Clamp for connecting stranded conductor to
ER2-3000-SS (702270) Mid section, 3 m 7.3 kg ER mast.
ER3-2000-SS (702275) Lower section, 2 m 5.3 kg
ER3-3000-SS (702280) Lower section, 3 m 7.9 kg
ER2-BASE-SS (702290) Base for ER2 mast 5.2 kg
ER3-BASE-SS (702295) Base for ER3 mast 5.6 kg
ER1-xxxx-SS mast diameter 25 mm
ER2-xxxx-SS mast diameter 32 mm
ER3-xxxx-SS mast diameter 38 mm
Adapters
Adapter
INTCPTSIIER1 0.1 kg
Adapter
INTCPTSIIER2 0.1 kg
Cantilevered
Guyed Masts
Masts:
Mast Height (m) 2 3 4 5 6 7 8 Mast Height (m) 3 4 6 7
ER11000SS X Height above roof
2 3 4 5
plane (m)
ER12000SS X
ER11000SS X
ER22000SS X X X ER22000SS X
ER23000SS X X X X ER23000SS X X X
ER32000SS X ER32000SS X
ER33000SS X X X X ER33000SS X X
CABTIESS 6 8 10 14
ER2BASESS X X
ALOF1GS 2 2 3 3
ER3BASESS X X X X X
INTCPTSIIER1 X
GUYKIT4M/GRIP X X X X
INTCPTSIIER2 X X X
GUYKIT7M/GRIP X X X X
CABTIESS 4 6 8 10 12 14 16
INTCPTSIIER1 X X
INTCPTSIIER2 X X X X X
10 www.erico.com
Other Lightning Protection and Grounding Accessories
PDCUC 711352
WPC 702230
STCS253
Guy Kit 701305
DCCS253
SDH-3-GI 107500
WARNING
ERICO products shall be installed and used only as indicated in ERICO’s product instruction sheets and training materials. Instruction sheets are available at www.erico.com and from your ERICO customer service representative.
Improper installation, misuse, misapplication or other failure to completely follow ERICO’s instructions and warnings may cause product malfunction, property damage, serious bodily injury and death.
WARRANTY
ERICO products are warranted to be free from defects in material and workmanship at the time of shipment. NO OTHER WARRANTY, WHETHER EXPRESS OR IMPLIED (INCLUDING ANY WARRANTY OF MERCHANTABILITY OR FITNESS FOR
A PARTICULAR PURPOSE), SHALL EXIST IN CONNECTION WITH THE SALE OR USE OF ANY ERICO PRODUCTS. Claims for errors, shortages, defects or nonconformities ascertainable upon inspection must be made in writing within 5 days
after Buyer’s receipt of products. All other claims must be made in writing to ERICO within 6 months from the date of shipment or transport. Products claimed to be nonconforming or defective must, upon ERICO’s prior written approval
in accordance with its standard terms and procedures governing returns, promptly be returned to ERICO for inspection. Claims not made as provided above and within the applicable time period will be barred. ERICO shall in no event be
responsible if the products have not been stored or used in accordance with its specifications and recommended procedures. ERICO will, at its option, either repair or replace nonconforming or defective products for which it is responsible
or return the purchase price to the Buyer. THE FOREGOING STATES BUYER’S EXCLUSIVE REMEDY FOR ANY BREACH OF ERICO WARRANTY AND FOR ANY CLAIM, WHETHER SOUNDING IN CONTRACT, TORT OR NEGLIGENCE, FOR LOSS OR
INJURY CAUSED BY THE SALE OR USE OF ANY PRODUCT.
LIMITATION OF LIABILITY
ERICO excludes all liability except such liability that is directly attributable to the willful or gross negligence of ERICO’s employees. Should ERICO be held liable its liability shall in no event exceed the total purchase price under the contract.
ERICO SHALL IN NO EVENT BE RESPONSIBLE FOR ANY LOSS OF BUSINESS OR PROFITS, DOWNTIME OR DELAY, LABOR, REPAIR OR MATERIAL COSTS OR ANY SIMILAR OR DISSIMILAR CONSEQUENTIAL LOSS OR DAMAGE INCURRED BY BUYER.
www.erico.com 11
www.erico.com