D185-00-001-IS Issue 5 L101X
D185-00-001-IS Issue 5 L101X
86.4mm [3.40"]
86.4mm [3.40"]
86.4mm [3.40"]
CE, UKCA & UL Approved
VdS/CPR Approval for EN54-23 (24/48Vdc Application Only)
General Signalling for US & Canada - UL1638A & CSA22.2-205-17
Private Mode Fire for US & Canada - UL1638, CAN/ULC-S526
L101XDC012[Z]…[X]/[Y] 12V dc/ac 11.5-14V dc/ac 500mA/380mA 531mA @14Vdc / 341mA @14Vac
L101XDC024[Z]…[X]/[Y] 24V dc/ac 20-28V dc/ac 250mA/300mA 271mA @20Vdc / 426mA @28Vac
L101XDC048[Z]…[X]/[Y] 48V dc 42-54V dc 170mA 170mA @42Vdc M20 Stopping Plug M20 Stopping Plug
92.7mm [3.65"]
92.7mm [3.65"]
82.2mm [3.24"]
L101XAC048[Z]…[X]/[Y] 48V ac 42-54V ac 250mA 360mA @52.8Vac
L101XAC115[Z]…[X]/[Y] 115V ac 115V ac +-10% 50/60Hz 70mA 101mA @126.5Vac
L101XAC230[Z]…[X]/[Y] 230V ac 230V ac +-10% 50/60Hz 35mA 58mA @253Vac
[Z] Denotes Backbox Type: B = Standard L101; S = Sonora; M = Multi-purpose (with Lugs)
[X] Denotes Housing Colour: R = Red; G = Grey; W = White
[Y] Denotes Lens Colour*: R = Red; G = Green; A = Amber; B = Blue; C = Clear; M = Magenta 85.1mm [3.35"] 114.2mm [4.50"] 84.8mm [3.34"]
*Only Red & Clear Lens VdS/CPR Approved.
†Nominal Voltage, 1Hz Flash Pattern & Tone 12; #Worst-case input voltage and worst case flash pattern
Access to Enclosure
Attention: Installation must be carried out by an electrician in compliance with the latest codes and regulations.
Attention: L'installation doit être effectuée par un électricien conformément aux derniers codes et réglementations.
Achtung: Die Installation muss von einem Elektriker gemäß den neuesten Vorschriften und Bestimmungen durchgeführt werden.
Attenzione: L'installazione deve essere eseguita da un elettricista in conformità con i codici e le normative più recenti.
Atención: La instalación debe ser realizada por un electricista de acuerdo con los últimos códigos y regulaciones.
Atenção: A instalação deve ser realizada por um eletricista de acordo com os códigos e regulamentos mais recentes.
1
Внимание: установка должна выполняться электриком в соответствии с последними нормами и правилами. 5
Attention: Disconnect from power source before installation or service to prevent electric shock
Attention: Débranchez-le de la source d'alimentation avant l'installation ou l'entretien pour éviter tout choc électrique.
Achtung: Vor Installation oder Wartung von der Stromquelle trennen, um einen Stromschlag zu vermeiden.
Attenzione: scollegare dall'alimentazione prima dell'installazione o dell'assistenza per evitare scosse elettriche.
Atención: desconéctelo de la fuente de alimentación antes de la instalación o el servicio para evitar descargas eléctricas.
Atenção: Desconecte da fonte de alimentação antes da instalação ou serviço para evitar choque elétrico
4
Внимание: отключите от источника питания перед установкой или обслуживанием, чтобы предотвратить поражение
2
электрическим током.
E2S Warning Signals Impress House, Mansell Road, Acton, London W3 7QH [email protected] e2s.com Page 1 of 3 D185-00-001-IS_Issue_5 - 10/11/2022
INSTRUCTION & SERVICE MANUAL
L101X Range - Xenon Strobe Beacon
B
A C 1Hz Flash (60FPM) 3
B
A C
B
A C Double Strike Flash Pattern*
TORQUE 5Nm
(4lb.in) Rear Ø20mm Knockout
for M20 Cable Entry
if required
2
*Flashing 1.5Hz and Double Strike modes are not available on the following units: L101XDC012[b][x]/[y]
when used with an AC supply; L101XAC048[b][x]/[y]; L101XAC115[b][x]/[y] & L101XAC230[b][x]/[y].
+(pos) N~ L~ N~
y x
L~
100.0
x
x
y
C
B
y y
A
-+ LNE
Category C-x-y (Ceiling Category W-x-y (Wall mounted): Category O-x-y (Open class):
mounted): Ceiling mounted, Wall mounted, where x is the maximum Centrally wall mounted, where x is the max
where x is the maximum ceiling mounting height from the floor and y is the height and width of the wall area covered
height and y the diameter of the maximum length of the sides of the square by the device and y is the max depth of the
10-14 VDC/AC 115 VAC cylindrical volume covered by the floor area covered by the VAD. volume covered by the VAD or ceiling
20-28 VDC/AC 230 VAC VAD. mounted where x is the max width and
E2S Warning Signals Impress House, Mansell Road, Acton, London W3 7QH [email protected] e2s.com Page 2 of 3 D185-00-001-IS_Issue_5 - 10/11/2022
INSTRUCTION & SERVICE MANUAL
L101X Range - Xenon Strobe Beacon
Attention: Installation must be carried out by an electrician in compliance with the National Electrical Code, NFPA 70, and the National Fire Alarm
Signaling Code, NFPA 72 or CSA 22.1 Canadian Electrical Code, Part I, Safety Standard for Electrical Installations, Section 32. / L'installation doit
exclusivement être réalisée par du personnel qualifié, conformément au code national d'électricité américain, NFPA 70, et le code national d’alarrme
incendie et de signalisation NFPA 72 ou CSA 22.1 Code canadien de l'électricité, première partie, norme de sécurité relative aux installations électriques,
Section 32
Attention: Disconnect from power source before installation or service to prevent electric shock / Débranchez-le de la source d'alimentation avant l'instal-
lation ou l'entretien pour éviter tout choc électrique.
Blue 11.75 -
Magenta 11.75 -
Red 8.62 -
E2S Warning Signals Impress House, Mansell Road, Acton, London W3 7QH [email protected] e2s.com Page 3 of 3 D185-00-001-IS_Issue_5 - 10/11/2022