BOQ and Price Break up details (1)

The document outlines a new Bill of Quantities (BOQ) for HVAC equipment, including detailed specifications and costs for items such as a chilled room DX refrigeration unit, PUF panels, insulated doors, and electrical works. It includes quantities, rates, and total amounts for each item, with a grand total of 26,916,750 Rs. GST and freight are additional costs, with some responsibilities assigned to the customer.

Uploaded by

cuprnn
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
22 views3 pages

BOQ and Price Break up details (1)

The document outlines a new Bill of Quantities (BOQ) for HVAC equipment, including detailed specifications and costs for items such as a chilled room DX refrigeration unit, PUF panels, insulated doors, and electrical works. It includes quantities, rates, and total amounts for each item, with a grand total of 26,916,750 Rs. GST and freight are additional costs, with some responsibilities assigned to the customer.

Uploaded by

cuprnn
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 3

NEW BOQ

Rate Amount Comments


S. No. Item Description Unit QTY
(Rs.) (Rs.)

SUB HEAD 'A' - HVAC EQUIPMENTS

1.0 CHILLED ROOM DX REFRIGERATION UNIT


Supply, Installation, Testing and commissioning of chilled room Refrigeration unit suitable to operate from 415+10%
volt, 50 Hz, 3 phase power supply, with air-cooled evaporator with coil, fan, and fan motor, air-cooled condenser
with hermetic/semi hermetic compressor/Scroll with R-404A Refrigerant including first charges of gas, condenser
coil, propeller fans controls, inter connection ,filter , Digital Controller + Electrical Panel, Suction Accumulator, Oil
Separator, Check vale , Receiver Tank, Filter Drier, Sight Glass, Solenoid Valve, LP/HP Switch, MCB , Compressor
Contactor, Compressor overload relay, Compressor Discharge gas Thermostat, Electrical Scanner (U.V, OV, SPPR,
Voltage Unbalance, Single phase protection) with LED Panel on CDU , Defrost Heater Safety Switch. Unit constructed
with SS sheet panels and should be assembled to form a rigid structure. Cooler surface should be assembled to form
copper tubes and Aluminum fins mechanically bound in place complete with refrigerant piping with 19mm thick
nitrile insulation ,condensate drip tray at the base with drain line connection complete as per specification
It shall include weather proof lighting and strip curtains.
Coils shall be applied with anti-rust coating.

The unit shall be capable of operating at maximum ambient 45deg c.


Inside design condition for room is 0±5
Considered Refrigeration systems Capacity
each is 13 kw @ room temperature of -8
1.1 Cooling Caapcity - 13 KW(3.7 TR) Nos. 40 444,800 17,792,000
Deg. C. Casing of CDU & IDU Shall be powder
coated GI

2 PUF PANEL FOR WALL AND ROOF


Pre-fabricated panels with 0.5 MM interior and exterior 0.5 MM (100 MM) thick pre-painted GI sheets precisely
formed with steel dies and rollform equipment, confirming to I.S.12346. The panels “foamed-in-place” with CFC free
RPUF with a 97% closed cell structure should not have internal wood, metal or high-density urethane structural
members. All joints should be airtight and vapor proof, with all panel edges having a tongue and groove edge of the
2.1 same density as the rest of the panels, coving and corner coves. Panels to lock together with cam lock mechanism SQM 3510
and joints finished using good quality silicon sealant . No timber should be incorporated with the construction.
Flexible vinyl gasket,resistant to damage from oil, grease, water, detergents and sunlight which is also “foamed-in-
place”, should be provided around the interior and exterior perimeter of each male edge complete as per
specification
Wall & Ceiling Panels - 100 mm - PP/PPGI - 0.5 MM / 0.5 MM Sheet (TPC) Quantity considered as per the room
dimensions shared - Each room external
SQM 1800 3,250 5,850,000
dimention - 6.75 m x 5 m x 3.5 m - With
common partition wall for each room
PUF slab with Polythene on both sides Quantity considered as per the room
SQM 650 1,585 1,030,250 dimensions shared - Each room external
dimention - 6.75 m x 5 m x 3.5 m

2.2 Supply & installation of flashing (0.5mm) for Bottom & Top of Puff Panel plus door. RM 900 150 135,000
3 INSULATED DOOR
Supply and installation of high quality uPVC Single leaf door fully insulated and air tight including all necessary fittings
3.1 hinges,handle , door seal, Kick Plate, Door Lock, Door Closer and automatic Door bottom seal.Overall size of door Nos. 20 65,000 1,300,000
shall be 1.2x 2.1m

Supply and installation of Cold room Led Lights with Ip-65 rated 40 watt each Vapour Proof Lights considered - 4 Nos. for
4 Nos. 80 3,500 280,000
each chamber

Supply & installation of dual speed air curtain(ss plate) sutaible for 1.2mtr Length with required Accessories/LS MAG
5 Nos. 20
Single Flap/Limit Switch Limit Switch; Magnetic Type; for a Single Flap Push Pull Door.

SUB HEAD 'B' - PIPING

5 COPEER REFRIGERANT PIPING

Supply,Installation,testing and commissioning including vaccumiazation and Nitrogentesting of following


nominal sizes of soft/hard drawn copper refrigerant piping for VRV/VRFsystem,complete with fittings,with
suitable adjustable ring type hanger supports,jointing/brazing including accessories,insulated with XPLE Class-
Otubular insulation/withClass-O closed cell elastometric nitrile rubber tubular sleeves sections of specified
thickness as given below for Suction and Liquid lines,all accessories as per specifications etc. as required :

12.7 / 15.8 mm dia(OD) (Softdrawn) with tube thickness 1.2mm with 19mm thick insulation Mtrs. 85 1,100 We have considered Hard Run copper piping
5.1
93,500
28.575 mm dia(OD) (Softdrawn) with tube thickness 1.2mm with 19mm thick insulation Mtrs. 50 2,100 We have considered Hard Run copper piping -
5.2
105,000 22.22 mm
NOTE:-1) The Copper Piping & Piping Circuit should be with MinimumNumber of joints,which shall be attained by :
(i) Using One End Expanded Tubes
(ii) Bending the tubes instead of using elbow joints wherever 90 degree bending is required.
(2)Piping should be routed at site in such a manner,that brazed joints in the refrigeration piping are kept to a
minimum.
(3) The makes of tube fittings shall be same as that of tubes.
(4) The thickness of fittings used shall be same as that of the pipe.

6 Drain Piping
Providing & fixing of heavy duty PVC Pipe complete with fittings, supports as per specifications and duly
insulated with 9mm thickness of XPLE Class-O tubular/ closed cell tubular nitrile rubber as required & as per
specifications.
6.1 50 mm dia with 9 mm thick insulation Mtrs. 120 500 60,000 Considered uPvc Pipes instead of PVC
6.2 40 mm dia with 9 mm thick insulation Mtrs. 80 375 30,000
6.3 32 mm dia with 9 mm thick insulation Mtrs. 245 300 73,500
6.4 25 mm dia with 9 mm thick insulation Mtrs. 225 200 45,000
6.5 20 mm dia with 9 mm thick insulation Mtrs. 10 150 1,500
SUBHEAD-E: ELECTRICAL WORKS

Design, Manufacture, Supply, Unloading, Handling, Installation, Testing & Commissioning of free standing, front
operated, fully compartmentalized cubical type, extendable on both sides Panel Boards suitable for indoor
installation & for use on 415Volts 3-phase, 4wire, 50Hz system having (with-stand) fault current carrying
capacity as specified, with suitable manual interlock arrangement, outgoing feeders, busbar & necessary
metering with interconnections etc. Complete as per schematic drawing, Specification, relevant IS standards &
7
including all accessories as per site conditions to make the system fully operational.Note : All MCCB should be
thermal magnetic with Adjustable upto 400A.microprocessor based for above 400A. All MCCBs with Ics rating
should be 100% Icu. Low Voltage switchgear shall comply to IS13032, IS13947, IEC60439
Panel manufacture should be CPRI(50kA) approved vendor. For more details pl refer SLD No-TN-VZG-1-
ELECTRICAL SCHEMATIC.
7.1 Shall be in customer scope as discussed
PACKAGING UNIT MDB
SET 2 during the call

Supply, laying testing and commissioning of following sizes of XLPE insulated PVC sheathed armoured
8 aluminium/ Copper conductor cable of 1.1 KV grade on existing cable tray / surface including clamps, ties etc.
as required.

8.1 4 Core 10 Sqmm. AL. Shall be in customer scope as discussed


Mtrs. 2640 during the call

Supplying and making end termination with brass compression glands and Al./copper lugs for following size of
9
PVC insulated and PVC sheathed / XLPE Al. conductor cable of 1.1 KV grade as required.
9.1 4 Core 10 Sqmm. Shall be in customer scope as discussed
Nos 80 during the call

Providing & fixing of control wiring/power cabling with following sizes of copper conductor armoured cable
10 between indoor and outdoor units directly on surface of wall/ existing channel i/c making connection etc. as
reqd.
10.1 4 x 1.5 sq.mm Mtrs. 50 250 12,500
10.2 3 x 1.5 sq.mm Mtrs. 40 200 8,000
10.3 2 x 1.5 sq.mm Mtrs. 50 150 7,500

Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray (Galvanisation
thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with
11
connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required

11.1 300 mm. Width x 50mm. Depth x 1.6mm. Thickness. Mtrs. 100 930 93,000

Earthing with GI earth plate 600 mm x 600 mm x 6 mm thick including accessories, and providing masonry Shall be in customer scope as discussed
12 enclosure with cover plate having locking arrangement and watering pipe of 2.6 metre long etc. with charcoal / 4 during the call
coke and salt as required. Set

Providing and fixing 6 SWG dia. GI wire on surface or in recess for loop earthing along with the existing surface / Shall be in customer scope as discussed
13 2640
recessed conduits / submain wiring / cable as required. Mtrs. during the call

Providing and fixing 25 x 5 mm G.I. Strip on surface /on existing cable tray for connections etc. as required. Shall be in customer scope as discussed
14 150
Mtrs. during the call
GRAND TOTAL 26,916,750
GST @ 18% Extra
Freight till site Included
Unloading & Shifting of material Customer Scope