Guide for Electrical Installations on Merchant Vessels and Mobile
Guide for Electrical Installations on Merchant Vessels and Mobile
of Transportation
fill • •
Commandant (G-MTH-2)
United States Coast Guard
Mailing Address
Washington, DC 20593-0001
United States
Coast Guard Phone: (202) 267-2206
• COMDTPUB P16700.4
NVIC 2-89
• NAVIGATION ,AND VESSEL INSPECTION CIRCULAR NO. 2-89 14 AUG 1989
Subj: Guide for Electrical Installations on Merchant Vessels and Mobile
Offsho~e Drilling Units
1. PURPOSE. This Circular has been prepared to provide guidance concerning
electrical installations'on merchant vessels and mobile offshore drilling
units. It is intended to provide the marine industry with information on
regulatory intent and background, and on practices which have been found to
provide a level of safety equivalent to that provided for by the specific
regulations.
14 AUG 1gen
GUIDE FOR ELECTRICAL INSTALLATIONS ON MERCHANT VESSELS
AND MOBILE OFFSHORE DRILLING UNITS
TABLE OF CONTENTS
Chapter 1 Introduction. . 1
l.l Purpose. . . . . 1
l.2 Background . . 1
l.3 The Electrical Program . 2
l.4 Electrical Safety ... 2
Appendices
1
.. ,
1.3 The Electrical Program. The Marine Inspection Program uses plan
review, and on-site inspection to ensure that electrical installations are
designed, built and maintained.in a manner to promote the safety of the
vessel, its crew and passengers. The Electrical Engineering Regulations
provide uniform minimum requirements for electrical equipment and systems in
accordance with the intent of various statutes, the International Convention
for Safety of Life at Sea (SOLAS), and other treaties that contain
requirements regarding electrical installations. These requirements are
intended to ensure electrical installations aboard vessels provide services
necessary to protect passengers, crew members and other persons from
electrical hazards.
Fire is the greatest dread of seamen, and electricity is one of the most
frequent causes of fire. A fire hazard can exist wherever electrical
potential is present, and on a ship, the electrical installation covers a
far greater area than any other type of installation.
2
abrasion, or impact, or where faulty installation or operating conditions
result in loose connections, the threat of fire exists.
The regulations reference many industry standards. For the most part,
these standards are dynamic aridever-changing. The "official" referenced
edition of an industry standard is listed in the "Finding Aids" section of
the CFR. Often, that edition may not be the latest edition of the
standard. This could create availability problems; where the requirements
of a standard have changed, and where manufacturers have modified their
equipment to meet the later version, equipment may not be available that
meets the referenced edition. However, standard changes often respond to an
identified problem or hazard, and usually result in safer equipment. In
most instances, equipment constructed and tested in accordance with a more
recent edition of a referenced document can be accepted as providing a level
of safety equivalent to that provided by equipment constructed and tested to
the edition identified in the CFR.
3
·
I
situation. With the movement of u.s. flag construction abroad, there has
.been an influx of electrical equipment that is constructed to meet other
standards and that is listed by independent third party certifying agencies
similar to UL. Some equipment is built to manufacturer's standards and is
not third party certified. Both of these types of equipment need to be
evaluated for equivalence to the standards referenced in the Electrical
Engineering Regulations before acceptance for installation.
4
apparent during normal operations or will it be hidden and gradually
worsen? Does the system configuration provide additional safety
measures that mitigate the effect of the failure? How likely is this
failure?"
(3) The evaluator should look for the safety intent in referenced
standards. Industry standards have evolved over many years, and for the
most part, represent a national consensus by technical professionals of
what is required to ensure that electrical equipment is safe. It is not
easy to look at a standard, such as a UL standard and identify those
requirements that are not related to safety. Nearly all requirements
are safety related, either directly, such as by ensuring adequate
dielectric strength, or indirectly, such as by ensuring adequate
mechanical strength so the equipment can safely withstand the rigors of
installation and use. For equipment built to another standard, the
evaluator should see if that standard adequately addresses the concerns
addressed by the referenced standard.
5
•
(c) For specific items for which comparability has not been
established by comparing standards, such as would be the case if
the foreign standard was for "land type" equipment and did not have
requirements comparable to those in the marine supplement of a
referenced UL standard, the manufacturer should submit
documentation demonstrating compliance with the supplement
requirements.
(3) For issues that can be resolved based upon on-site visual
examination, the evaluator may defer the acceptability of that equipment
to the inspection activity (Officer-in-Charge, Marine Inspection or ABS
if acting on behalf of the Coast Guard). In such cases, the specific
issue deferred should be fully identified and documented. The
inspection activity should also document the acceptance or rejection,
and should provide the plan review activity with inspection comments on
the deferred issues.
6
Note that the Marine Safety Manual Vol. II, l2.E.4 permits the oeMI to
accept on vessels of the Military Sealift Command, equipment or materials
complying with any of the following: (1) technical bureaus of the U.S.
Navy; (2) MILSPEC's; (3) federal specifications for military purchases, and;
(4) National Military Establishment (NME) specifications.
3. Electrical Systems
7
limited resources for plan review and inspection, concentration should be on
proper application of equipment, effect of failures on required system
functions, and on vital safety features. Emphasis should be on evaluating
the "system" -
This is the ftsystems" approach. This does not imply that individual
equipment design details are not important, but stresses that where there
are limiting constraints, the system should be given a higher priority.
8
and placement. Subchapter J contains general requirements for electrical
equipment to ensure that passengers, crew, and other persons, and the vessel
are protected from electrical hazards. It also ensures that equipment
necessary under both normal and emergency conditions is located in a manner
that allows for routine maintenance and testing, thus helping to ensure that
the equipment will function properly when needed.
Porcelain. Porcelain should not be used for lamp sockets, switches, etc.
unless resiliently mounted. The concern is that rigidly mounted porcelain
may fail under shipboard vibration and create a shock, fire or other hazard
to the vessel and its personnel. Some off-the-shelf equipment, designed for
9
typical land installations, only comes with rigidly mounted porcelain
insulated components. In these instances, it may be necessary to add
resilient mounts to the porcelain insulating material. Only in instances
where porcelain failure would not create a hazard, or where there is data
available to support a shipboard application, such as vibration and shock
(impact) testing, should such rigid installations be evaluated for general
safety equivalency.
The National Electrical Code (Code) indicates that for Code applications
with Code wiring, the ampacity of the conductors connected to molded-case
circuit breakers should be limited to that of 60 or 75 degrees Celsius
wiring, even though the attached conductors may have a higher rating.
Shipboard requirements in IEEE-45 and in the Electrical Engineering
Regulations do not impose this limit; such a limitation does not apply on
ships and MODUs. Ship systems do not use Code wiring, and are not typical
of common applications addressed by the Code. IEEE-45 cable constructions
have ampacities based upon rated conductor temperatures up to 100 degrees
Celsius. Shipboard cables may be connected to circuit breakers without
consideration of the NEC limitation.
10
MODUs. For drilling installations, 600 and 750 v.d.c. are typical. For
large floating industrial plants, 13.8 K.v. has been generated and
stepped-up to 34.5 K.v. for undersea transmission. The regulations require
that non-standard distribution systems, voltages, or frequencies be accepted
by the Commandant. This does not imply some are unacceptable. The concern
is that equipment items are compatible with each other, and with their
environment, and that any unique hazards are adequately addressed. When
high voltage equipment is used, and marine standards and equipment are not
available for equipment at that voltage, technical evaluation is needed to
ensure the safe application of shores ide industrial standards to a marine
installation. Also, higher voltage equipment may need special maintenance
considerations.
11
.. '
12
low impedance ground can result in large fault currents. To provide for the
detection of grounds, the regulations require that ground detection means be
provided for each electric propulsion system, each ship's service power
system, each lighting system, and each power or lighting system that is
isolated from the ship's service power and lighting system by transformers,
motor generator sets, or other devices. This indication need not be part of
the main switchboard but should be co-located with the switchboard (i.e. at
the engineering control console adjacent to the main switchboard). The
indication may be accomplished by a single bank of lights with a switch
which selects the power system to be tested, or by a set of ground detector
lights for each system monitored.
3-PHASE B
SYSTEM
A
G
FUSES
GROVND
LAMPS
tow IMPEDANCE
GROUND
5 WI T CH
FIGURE 1
13
will still be within their rating and will not be damaged. For lesser
grounds, the lumen output of the lamps will vary approximately proportional
to the cube of the voltage. This exponential change in lamp brightness
(increasing in two and decreasing in one) provides the necessary contrast.
NEUTRAL
SATURABLE TEST
REACTOR S~T~ AMMETER
CURRENT
TRANSFORMER
FIGURE 2
Capacity. Determining the number and size of generating sets needed for a
vessel requires a careful analysis of the normal and maximum demands during
various phases of operation, including at sea, maneuvering. and in port.
14
Also, any special or unique operational considerations should be addressed.
It is the intent of the regulations to ensure all normal "ship's service"
loads can be kept energized with the largest generator out of operation, and
without use of the emergency generator. It is not the intent of the
regulations to ensure that the vessel can continue to perform an industrial
function, such as drilling or dredging, with a generator in reserve. Ship's
service loads are defined in detail in 46 CFR 111.10-1.
Main engine dependent generators. The most commonly used prime movers for
ship's service generators are dedicated diesel engines and steam turbines
supplied by the propulsion boiler(s). However, due to escalating fuel
costs, owners and designers are always looking for less expensive means to
provide the necessary electric power. Shaft-driven generators, power
take-off (PTO) generators, and waste heat driven turbogenerators offer
flexibility and greater efficiency. In many cases, however, they are
constrained to certain main engine speed and power operating ranges.
SOLAS states that the arrangements of the ship's main source of power
shall be such that the ships service loads can be maintained regardless of
the speed and direction of the main propelling engines or shafting. This is
reflected in 46 CFR 111.lO-4(b) and (c), which require that ship's service
electrical power be provided continuously, regardless of propulsion shaft
speed or direction. In the worst case, this means that an "engine stop" or
"full astern" command on the bridge propulsion control lever while operating
at the minimum engine speed for full generator output must not result in
interruption of ship's service power.
Waste heat energy from the main diesel engine can be recovered in an
exhaust gas boiler to generate low pressure stearn to drive a
turbogenerator. This generator can be operated only when sufficient exhaust
heat is available, so start-up and shutdown are usually manually initiated.
To optimize the recovery of exhaust heat, a generator loading control system
15
may be used with load-sharing and speed (governor) controls to max~m~ze
turbogenerator loading when operating in parallel with other generators.
Any main engine or waste heat driven generator which is not capable of
providing power under all operating conditions, including maneuvering and in
port, cannot be counted towards the required ship's service generating
capacity. Such a generator may, however, be provided as a supplemental
generator. In any case, one of the required generators must be independent
of the main propelling engines and shafting.
Each transformer must have the capacity to supply the ship's service
loads. The duplicated supply should consist of transformers, overcurrent
devices, and cables. Automatic changeover upon a transformer failure is not
required. It could be inferred from the transformer/generator analogy of
SOLAS 11-1/45, that automatic transformer transfer is required by the SOLAS
11-1/53 requirements for automatic starting and connection of a stand-by
generator. That analogy has, however, not been applied to transformers
since the precise wording of Reg. 53 addresses generators, and not
16
"essential parts of the electric supply system." Additionally, the
reliability and availability of a "static" transformer, and its cable and
overcurrent device is much better than a rotating generator, its prime-mover
and control system. Transformer faults are rare, and the requirement for
duplication is considered from a "take-home" standpoint. (This is similar
to the requirement for a split bus arrangement on a ship with a large
electrical syscem . There is no requirement to autiomat.LcelIy disconnect
switchboard sections and attempt to maintain power upon 'a switchboard
fault. The requirement for splitting the bus is to provide the capability
for onboard engineers to be able to isolate a fault and restore limited
service.)
17
· ,I
18
loading; emergency power systems usually operate less frequently, for longer
periods, at lower current levels. Automotive batteries also have a shorter
life (3 - 5 years) than lead-acid storage batteries designed for use in
emergency power systems (15 - 20 years). Storage batteries for emergency
power service usually have either a threaded stud or a rectangular blade for
connection of a bus link. They commonly have external cell connectors.
Automotive batteries have either side terminals that can accept a threaded
bolt, or top round posts for the common automotive battery cable.
3.5 Switchboards
19
.. "
Bus bar bracing. Bus bars must be braced to withstand the mechanical
strains imposed by inrush currents and the maximum available short-circuit
current. These currents can generate electromagnetic fields of considerable
magnitude. The mechanical forces resulting from these fields can bend the
bus bars, shatter insulation, and physically tear the switchboard apart.
Switchboard manufacturers should indicate the fault current their boards are
designed to withstand. The spacing between bus bars and bare metal parts
within the switchboard must meet Section 384-26 of the National Electrical
Code.
Aluminum buses. There has been continued interest in the use of aluminum as
a bus bar material, due primarily to the relative costs of copper and
aluminum. Both marine and shore industrial experience has shown that
careful attention must be paid to materials, joint design, and quality of
workmanship if unsatisfactory and unsafe aluminum bus bar installations are
to be avoided.
Certain problems and properties associated with aluminum bus bars are
discussed below. For vessels operating only in fresh water, the corrosion
problem may be minimal; the other three problems are equally applicable to
fresh water and salt water service.
20
A. Corrosion - Aluminum in contact with certain other metals, such as
steel, forms a galvanic couple susceptible to accelerated corrosion in
the marine environment. Aluminum alloys containing copper are
particularly subject to corrosion in a damp salt atmosphere, even when
not in contact with a dissimilar metal.
B. Oxide Build-up - Most aluminum alloys form a hard, inert oxide coat
whenever a fresh surface is exposed to air. This layer "of aluminum
oxide has a high electrical resistance and can create a hot spot at
connection points.
D. Thermal Properties -
(1) As the load increases, the bus bar temperature will increase
and the bus bars will expand. The linear coefficient of thermal
expansion of aluminum alloys is significantly larger than that for
steel or copper. Provisions must be made in the design to account
for these different expansion rates. High stresses can occur in
aluminum-bodied connectors, especially when used with bolts of a
dissimilar metal or which have thermal expansion characteristics
different from those of the aluminum device.
21
"
A plated bus bar surface should not be wire brushed or treated with
abrasive cleansers prior to assembly.
22
Automated systems. SOLAS 11-1/53.2 requires electrical load shedding
arrangements for vessels with periodically unattended machinery spaces. 46
CFR 62.S0-30(k) requires that where the electrical power can normally be
supplied by one generator, load shedding be provided to maintain the
continuity of electrical power to propulsion, steering, and other vital
safety systems. In the case of loss of the (one) generator in operation, a
standby generator of sufficient capacity to supply the propulsion and
steering equipment must be automatically started and connected to the
switchboard in not more than 30 seconds. Where the electrical power is
normally provided by two or more generators in parallel operation, provision
must be made to ensure that, in case of the loss of one operating generator,
the remaining generators are kept in operation without overload to maintain
propulsion, steering, and the safety of the vessel.
3.6 SCR's
The term SCR refers to the solid state equipment for the conversion of
alternating current to direct current which has been called a silicon
controlled rectifier, semiconductor controlled rectifier, and semiconductor
rectifier. Many electric propulsion systems, thrusters, and pieces of
drilling machinery use DC motors in order to obtain more precise speed
control. SeR's are the most common means of converting the ship's service
AC power to DC. Solid state SCR power converters offer the advantages of
high efficiency and low maintenance (compared to motor-generator sets), but
are sensitive to heat and humidity and are frequently located in suitably
air-conditioned spaces.
3.7 Transformers
23
· "
See Appendix 4 for full load current ratings for single-phase and
three-phase transformers.
The reference to the ABS "Rules for Building and Classing Steel Vessels"
in 46 CFR 111.35-1 is out-of-date. Sections 35.79, 35.81, 35.84, 35.125,
35.127, and 35.129 of the latest revision of the ABS Rules may be used for
guidance. In addition, a portion of Table 62.35-50 (Vital System Automation
Rules) applies to electric propulsion systems. The general provisions of
the SOLAS 11-1/31, 49, and 52 are applicable to all propulsion arrangements,
including electric propulsion.
3.9 Panelboards
Ratings. The current rating of a panelboard must not be less than the
feeder circuit capacity. To meet 46 CFR 111.40-15, the load on any
overcurrent device in a panelboard must not exceed 80 percent of that
device's rating if the normal load duration is 3 hours or more. This
requirement does not apply, however, when the panelboard and the overcurrent
device are rated for continuous duty at 100% of the rating.
Number of Circuits. Note that each panelboard must meet UL 67 and the
Marine Supplement. This UL Standard states that lighting or appliance
panelboards must not have provision for more than 42 overcurrent-protective
devices (individual fuseholders or circuit breaker poles), other than those
in the mains. The edition of the UL Marine Supplement referenced in the
Finding Aids Section requires overcurrent protection in grounded conductors
of branch circuits, contrary to present 46 CFR 11l.50-3(a). The specific
regulation, 111.50-3(a), should be followed. UL 67 has been changed.
Purpose. Overcurrent devices, the two most common types being fuses and
circuit breakers, offer protection against currents in excess of the rated
current of equipment or the current-carrying capacity (ampacity) of a
conductor. The purpose of properly coordinated overcurrent protection is to
recognize, locate, and isolate faulted portions of the power system in order
to minimize the damage to equipment and conductors, danger to personnel, and
interruption of electrical power which may result from an overload, short
circuit, or ground fault.
24
Circuit Breakers. Circuit breakers are devices which permit manual opening
and closing of a circuit and which open the circuit automatically for a
predetermined fault condition (usually overcurrent, but sometimes reverse
power flow, undervoltage, or underfrequency) without damage to themselves
when applied within their ratings. In effect, they are high current
interrupting capacity switches with automatic trip elements. The circuit
breakers most commonly found in marine applications respond to overcurrent,
tripping when the current magnitude exceeds a specific value for a specific
length of time. Low voltage (600 volts AC and below) circuit breakers are
usually constructed with an integral overcurrent trip element within the
circuit breaker housing.
25
Sulfur hexafluoride, is a nonflammable, nontoxic gas with an insulating
value 2.5 times that of air at atmospheric pressure. Each SF6 interrupter
pole consists of two pairs of contacts sealed in a bottle filled with SF6
gas at slightly more than atmospheric pressure. A puff of gas directed
between the parting contacts cools the arc and allows deionization and
interruption of the current.
SF-6 and vacuum circuit breakers have been accepted aboard inspected
vessels for use in medium voltage metalclad switchgear, and it appears that
air circuit breakers may, in the not-too-distant future, be obsolete for
this service and become unavailable.
HA..'fDU
arHtTALlIC STRIP
HEATER n.rxrxr
I-RATED OR LESS
FIGURE 3
26
Electronic trip systems have been developed which replace the moving
thermal-magnetic devices with solid-s~Hte electronic sensors and a single
trip solenoid. By reducing the numb-rr of mechanical moving parts used to
release the operating mechanism, electronic trip units can be made
inherently more vibration and shock (impact) resistant. In addition, the
electronic trip unit can be more closely adjusted and is less sensitive to
ambient temperature because no motion of the trip actuator occurs until the
trip signal is sent to the solenoid by the electronic circuit. With these
advantages and the option for additional protection features, electronic
trip units may soon replace thermal-magnetic elements for overcurrent
protection.
only that no intentional time delay has been introduced, although some
finite minimum time is required for any circuit breaker to interrupt a
circuit. The curves indicate the length of time a particular current level
must be sustained in order to trip a particular breaker. These and similar
time-current curves for fuses are used in the process of coordinating the
various overcurrent devices in the power system.
27
"
...~i_----~-----+----_i-----
CI1
Q
:z:.
B
&oJ
CI1
~~~~~~----~------t_---
Z;
FIGURE 4
cu1tJlD{1' PEl.CDtt
IJ( or 11lF.J,.X£R.
nIP WIt SEttINC
The total clearing time curve shows the maximum time, including arcing
time and manufacturing tolerances, for the fusible element to open the
circuit. The minimum melt curve represents the minimum time required for
the fusible element to begin to melt. An assumed "fuse damage," curve,
approximated at 75% of the minimum melting curve, is used to provide a
margin of safety so that applications avoid operation in the time-current
band between the minimum melt curve and the total clearing curve, where
current levels may cause thermal damage to the fuse without opening the
circuit.
28
\
FIGURE 5
\
\
\
29
Due to the vital role of the steering system in the overall safety of a
vessel, only limited fault-current protection is permitted in steering gear
motor feeder, motor controller, control, and indicating and alarm circuits.
It would be dangerous to "protect" a steering gear motor against a moderate
overload if, by tripping the motor during a maneuvering situation, steering
were lost and the safety of the vessel jeopardized. The fault-current
protection required for steering systems is intended to protect against
fire; components of the system may be sacrificed in order to maintain
control of the vessel for as long as possible in emergency situations.
Steering gear and propulsion circuits must meet 46 CFR 111.93 and 111.35,
respectively.
The current which will flow toward the fault depends upon the power
available from the source(s), the voltage at the fault (assumed to be zero
for a bolted three-phase fault), and the impedance of the circuit components
such as transformers, conductors, and other equipment between the fault and
the power source(s), Short-circuit currents should be assumed to be
asymmetrical during the first few cycles after the short occurs. The
asymmetry will be maximum at the instant the short circuit occurs; in
practical circuits containing both resistance and reactance, the current
generally becomes symmetrical after several cycles. The rms value of the
available asymmetrical current must be within ~he interrupting rating of the
overcurrent device. Note that this maximum asymmetrical current is the
30
average of the three phases at a particular instant in time and is not the
maximum current in anyone phase.
31
· "
1......... ------
:f\ :~-: I
r-------- •
I
l~
1-
GENERATOR
.2.
I
I
1
.._-:-~-4~
L __ l- __ ~ _I
I
r--- --,
I
I
I
SWITCHBOARD
- _J TRANS.
L- _
--- I
LOAD
L
DIST. PANEL
-- --'
FIGURE 6
32
3.12 Motor Circuits
The nameplate on a motor rated at 0.5 horsepower or larger must list its
code letter (see 46 CFR 111.25-5 and NEC 430-7; this information is very
seldom available to the plan reviewer). Code letters are listed
alphabetically and represent the locked rotor kilovolt-amperes (KVA) per
horsepower. The branch circuit protective device chosen must be large
enough to allow sufficient time for the motor to start. Higher code letters
indicate greater locked rotor currents, requiring larger protective
devices. When starting a motor with full voltage, the locked-rotor current
does not diminish until the motor is very nearly up to its rated speed.
Most motors used have code letters ranging from "Fitto "V". For these
motors, the maximum rating or setting of the branch circuit protective
device, if a fuse, is 300 percent of the motor full-load current; if a
circuit breaker, this value must not exceed 250 percent (see 46 CFR 111.70-1
and NEC Table 430-152). The minimum value is not given but must be capable
of carrying the starting current of the motor (see NEC 430-52). For vital
systems, however, a minimum of 200 percent full-load current is recommended
for motors having "F" to "V" code letters, to ensure starting of the
motors. The trip setting values listed in the Quick Reference tables of
Appendix 6, columns I or J as applicable, may be used to check all motors
having code letters "F" through "V".
600 volts and above. The above requirement for conductor s1z1ng applies
only to low-voltage applications; Part J of Article 430 adds to or amends
the other provisions of the article for motor circuits over 600 volts.
Specifically, 430-124 permits motor conductors to have an ampacity not less
than the motor overload protective device trip current, which may be 100% of
the rated full-load current. This applies to medium-voltage motors for
33
.. "
Motor protection. Motor overload protective devices are required for most
motors in order to protect the motors, motor control equipment, and motor
branch-circuit conductors against excessive heating due to sustained motor
overload, failure to start, or motor stalling. Continuous-duty motors of
more than 1 horsepower must generally be provided with a separate overload
device set to trip at not more than 115% of the motor rated full-load
current. In most cases, overload relays with heater coils responsive to the
motor current are included in the motor controller. The Electrical
Engineering Regulations generally permit the use of only two motor overload
devices for three-phase motors in lieu of the three specified in NEC Table
430-37; see 46 CFR 11l.70-l(b). The size of the overload protective device
should be based upon the actual nameplate full-load current rating. The
values listed in columns "C" and "0" of the Quick Reference tables in
Appendix 6 may be used to check the maximum values for running protection.
LVR controllers are required for vital systems to ensure that the
equipment will re-start following either a loss of power or a reduction in
voltage below the "drop-out" value of the operating coil. These controllers
are usually energized by contacts which mechanically remain closed when
power is lost.
34
Motor controllers are furnished with the thermal overload elements
mentioned above. These elements are used to open (or close) contacts which
are used either in the control circuit itself or to provide an overload
alarm to another circuit. Some of these elements are adjustable but most
often the non-adjustable type is specified. Most motors are stopped by
these (normally closed) contacts when an overload occurs. For vital
systems, such as steering, these devices are used only to signal the
overload condition in a separate circuit.
4.1 General. Part 112 of the Electrical Engineering Regulations and SOLAS
11-1/42, 43, and 44 contain the requirements for emergency lighting and
power systems. The requirements of these two sets of requirements (USCG and
SOLAS) , are generally in agreement. Vessels in some categories are
permitted shorter periods of operation of the emergency power supply by 46
CFR Table l12.0S-S(a) than by the SOLAS regulations; these vessels would not
normally carry SOLAS certificates due to their size and/or limited operating
routes. The Electrical Engineering Regulations permit manually connected
emergency power sources only for cargo vessels less than 500 GT or cargo
vessels of less than 1600 GT on other than ocean, Great Lakes, or coastwise
routes and not on international voyages.
3S
Diesel and gas turbine engines used as emergency generator prime movers
must be capable of starting at an ambient temperature of 32 degrees F (0
degrees C). Electric water jacket heaters are permitted to ensure ready
starting. Due to the impracticality of testing this capability in warm
climates, the manufacturer's certification is generally accepted. A
thermostatically controlled electric lubricating oil heater may be provided
to reduce the accelerated wear which may result from placing the generator
load on a cold engine. Where detached electric motor-driven pumps are
provided to circulate warm oil through the engine while it is stopped, a low
oil level alarm should be installed to indicate any loss of oil through a
leak in the pumps or external piping.
4.2 Location. SOLAS 11-1/42.1.3 and 43.1.3 and 46 CFR l12.05-5(e) all state
that the emergency generator room and a category A machinery space should
not be adjoining, except where other arrangement is not practicable. The
intent is to maintain the integrity of the emergency electrical distribution
system if there is a fire, flooding, or other casualty in the main machinery
space. When the arrangement has been shown to be impractical, the
installation of an A-60 bulkhead between the emergency generator room and
the category A machinery space has been accepted. Although not required, it
was recommended that the steel bulkhead be insulated to A-60 on both sides.
Casualties such as the recent explosion and fire aboard a U. S. flag
tankship, however, demonstrate the vulnerability of an emergency power
source located in a space adjacent to the main machinery space. It is
preferable to avoid any contiguous boundaries between the emergency
generator room and any category A machinery space or space containing the
main source of electrical power, associated transforming equipment, if any.
and the main switchboard.
4.3 Emergency Loads. The temporary and final emergency loads listed in 46
CFR Subpart 112.15 must be supplied by the emergency power source(s).
Additional safety devices and systems (i.e., vital) may be connected to the
36
emergency power system provided the emergency source is sized to supply
these loads at 100% load factor. Additional loads which are intended to
improve the safety or survivability of the vessel in certain operating modes
(i.e., non-vital) and which have not been considered in sizing the emergency
generator (such as the addition of a secondary debal1asting system on a
semisubmersib1e MODU) may be allowed to be connected to the emergency power
supply when arranged to be functionally equivalent to a bus-tie
configuration. The following conditions would apply:
Cables from the emergency switchboard, other than those which supply
equipment in the machinery spaces, must not be run through the engineroom,
boilerroom, or the casings of these spaces. Emergency power cables must not
be run along decks or bulkheads which form'the boundaries of these spaces.
Again, the intent is to maintain the integrity of the emergency power system
by protecting emergency power cables from thermal damage should there be a
fire in the machinery spaces.
5.1 Fire detecting and alarm systems. An automatic fire detecting and
alarm system consists of a power supply, a control unit on which are located
visible and audible fire and trouble signalling devices, and fire detector
and alarm circuits, as required, originating from the control unit.
Detector and alarm circuits consist of initiating and indicating devices and
alarms. Initiating devices are smoke, heat or flame detectors and manual
fire alarm boxes. Indicating devices are audible and visual alarm devices
such as bells and strobe lights.
37
, "
The requirements for location of equipment for all systems are found in
46 CFR 76.27 and 3S. Additional requirements for vessels requiring SOLAS
Certificates are found in SOLAS 74, as amended, Chapter 11-2. Further
guidance on locating detectors can be found in NFPA 72. Ventilation effects
should be considered when locating detectors.
38
5.2 General Alarm. A general alarm system meeting 46 CFR Subpart 113.25
must be provided on each manned vessel of over 100 gross tons, except
barges, scows and similar vessels to alert the crew and passengers to the
existence of an emergency situation and the need to report to their muster
stations. Components of the general alarm system, including vibrating bells
and flashing lights, do not require type approval by the Commandant. The
requirement for component approvals was deleted from the regulations by the
revision of 46 CFR Subchapter J which became effective 1 June 1982. Only
the system design and equipment installation need now be approved.
An integrated general alarm, fire alarm and public address system may be
considered for equivalence to the intent of 46 CFR 113.25 and to satisfy
SOLAS chapter 11-2, Regulation 40.5 for a public address system. Any such
arrangement must give priority to the general alarm function. Such a system
would function similarly to the multi-purpose lMC Emergency Announcing
System commonly used on naval vessels. Speakers and electronic tone
generators may be used to produce a bell-like signal or tone distinct from
any other audible signal on the vessel. The location of speakers and the
generated sound level must meet 46 CFR 113.25-9. Either a distinct sound
signal or intermittent operation of the general alarm bells (or speakers
producing bell-like sounds) may be used to warn of fire. An integrated
system must meet the following criteria:
b) The general alarm signal must have priority over the fire alarm
signal.
c) The fire alarm switch should be marked "Fire Alarm" in red letters
on a corrosion-resistant plate or sign.
d) Operation of the fire alarm switch may also activate a fire alarm
page via the public address system. This must not interfere with the
normal operation of the general alarm.
f) The fire alarm signal must be distinct from those signals required
by 46 CFR 109.503 for MODUs.
39
, .
1
Flashing red lights which augment the general alarm bells must be
supplied by the general alarm system power supply, except for flashing red
lights in the main machinery space supplied from the emergency source of
power through relays operated by the general alarm system. In general, the
use of the emergency source of power for all general alarm system flashing
red lights meets the intent of 113.25-l0(c).
Sound-powered telephone headsets and jack boxes are not permitted on any
telephone system that includes any station required by the regulations,
except for use at engineroom local control stations; see 46 CFR
113.30-20(d). The objections to the use of these portable headsets are:
40
d) Jack boxes frequently corrode and short the circuit contacts,
causing unreliable circuit operation.
41
6. Industrial Systems
7. Hazardous Locations
42
The Electrical Engineering Regulations incorporate by reference Articles
500 through 503 of the National Electrical Code, with the exceptions listed
in 46 CFR 111.105-5(a) through (d). An error is contained in 111.105-5(b),
which excepts all of NEC Section 501-4 from incorporation into the
regulations. By deleting these sections, it was intended to recognize that
shipboard installations use marine cable, not conduit. It was not the
intent to delete the statement that "Boxes, fittings and joints shall not be
required to be explosionproof except as required by sections 50l-3(b)(1),
501-6(b)(l) and 501-l4(b)(l)." Non-explosionproof equipment can be allowed
in accordance with the NEC.
For Class I locations, gases and vapors are divided into groups A, B, C,
or D, depending upon experimentally determined maximum explosion pressure,
maximum safe clearance between parts of a clamped joint in an enclosure, and
the minimum ignition temperature of the atmospheric mixture. For Class II
locations, dusts are divided into Groups E, F, and G, depending upon the
tightness of the joints of assembly and shaft openings for preventing
entrance of dust into the dust/ignition proof enclosure, the blanketing
effect of layers of dust on the equipment that may cause overheating,
electrical conductivity of the dust and the ignition temperature of the
dust. In general, equipment must be approved not only for the Class, but
also for the specific Group of the gas, vapor, or dust that may be present.
Flammable and combustible liquid cargoes may be further classified according
to their vapor pressure and flashpoint. These liquids may be assigned both
a Group and a Grade (Grade designation relates to flashpoint). In cases
where differing requirements apply or several different hazardous
atmospheres may be present, the most hazardous condition is presumed to
exist and the most restrictive requirements should be applied. Appendix 7
contains a list of electrical hazard Group classifications for bulk liquid
cargoes.
43
Table 1
Class III-locations where easily ignitable fibers or flyings. such as cotton fibers. sawdust. and
wood shavings. may be present.
Table 2
Division 1: Where material can exist under normal operating conditions. or frequently
(Zone n because of repair, maintenance, or leakage.
Division 2: Where material can exist under abnormal conditions (accidental rupture or
(Zone 2) breakdown, abnormal operations. etc.). or locations adjacent to a Division 1
location where material may occasionally be present.
Note: International standards and codes use the term "Zone instead of "Divisiori" and include
t
a "Zone O· d~ignation for locations where vapors are assumed to be present, such as inside a
tank or in a tankship pumproom. Although North American standards, such as the National
Electrical Code (NEC)do not include a comparable "Division O· designation, the Coast Guard's
Electrical Engin~ering Regulations achieve the same effect by limiting electrical installations in
these locations'to the type permitted for Zone 0 applications. i.e., intrinsically safe systems.
44
7.3 Specific Hazardous Areas. Locations where flammable gases or vapors
." can exist on commercial V-e'sselsinclude battery rooms, paint lockers,
pumprooms and weather deck locations above cargo tanks on tank vessels, mud
pit rooms and the drill floor of MQbile Offshore Drilling Units, and
operating rooms where anesthetics are administered on passenger vessels and
hospital ships. Subpart 111.105 defines specific hazardous locations for
combustible liquid cargo vessels, flammable liquid cargo vessels, liquid
sulphur carriers" Lnor'ganfcv.acfd ltankships,bulk liquefied gas and ammonia
carriers, MODU' s , vessels 'carr)ringcoal,{and vessels (such as ferries and
RO-RO's) with spaces for the carriage of vehicles using gasoline or other
highly volatile motor fuels. Typical hazardous location classifications are
illustrated in Appendix 8.
45
"
Drilling Rigs and Production Facilities on Land and on Marine Fixed and
Mobile Platforms," API RP 500B, Third Edition, October 1, 1987.
Coal carriers and vessels carrying bulk grain and other agricultural
products may be subject to dust explosion hazards. Just as with flammable
gas or vapor explosions, the initial ignition source of a dust explosion may
be a small spark or flame. However, an initial explosion may dislodge
settled dust from the surrounding areaiwhich,may thenbe\ignlted by the
residual energy to cause a second and larger explosion~ Undispersed dust
which has accumulated in layers will not explode but may burn or char,
generating heat which may ignite dispersed dust. NEC Article 502 lists the
primary hazards which must be avoided as the admission of dusts into
electrical equipment enclosures, reaching the heat of ignition due to the
insulating characteristics of accumulated dust, and the formation of current
paths of conductive dusts.
Battery rooms and paint stowage or mixing spaces must meet the
electrical requirements pf 46 CFR 111.15 and 111.105-43, respectively. The
regulations do not explicitly state that these spaces are defined as
hazardous. However, equipment within these spaces must be suitable for
installation in Division 1 locations. The hazardous locations are
considered to exist only inside these spaces; the regulations do not define
a hazardous area as extending any specific radius from doors, hatches, or
other openings into these spaces. The use of only explosionproof or
intrinsically safe electrical equipment and the avoidance of open flames and
sparking near such openings is, however, strongly recommended.
46
Industrial systems may use an armored type cable construction, but the
cable must also meet the installation and flammability test requirements of
46 CFR 111.107-1(b) if it penetrates a deck or bulkhead. Conduit systems
that meet the applicable requirements of the NEC provide an equivalent level
of safey and can be permitted.
47
" .,
48
circuits. Examples of make-and-break contacts include relays, circuit
breakers, servo-potentiometers, adjustable resistors, switches,
connectors, and motor brushes. A nonincendive circuit is a circuit in
which any arc or thermal effect produced under intended operating
conditions of the equipment is not capable of igniting the specified
flammable gas or vapor-air mixture. A hermetically sealed device is one
which is manufactured so that it is completely seal.ed against entrance
of an external atmosphere and in which the seal is made by soldering,
brazing, welding, or fusion of'glass, or the like.
f. Vent ducts have the same classification as the space they serve.
Fans for ventilating hazardous locations must be nonsparking; see 46 CFR
110.ls-1(b)(16) for the definition of nonsparking. Nonsparking
construction is not generally indicated by an independent laboratory
listing, and must usually be verified by review and/or inspection. Vent
fan motors must either be approved for the hazardous location or located
outside the duct, 10 feet from the duct termination, in a non-hazardous
area.
49
into two major categories: (1) protection by enclosure or other physical
separation between the electrical equipment and the hazardous atmosphere;
and (2) protection by electrical design (making the circuitry unlikely to
produce ignition of the hazardous atmosphere.) Examples of the first
category include explosionproof and purged and pressurized enclosures, as
well as oil immersion. The second category includes the intrinsically safe
and nonincendive safety techniques.
7.7 Intrinsic Safety and Nonincendive Systems. For low power applications,
such as instrumentation, control, and operation of solenoid valves, the use
of intrinsically safe and nonincendive systems can reduce the likelihood of
fire or explosion due to the ignition of flammable gas mixtures by
electrical arcs or high temperatures. However, safety depends on their
proper application, as these two forms of protection are not equal.
In the past, much of the nonincendive circuitry that found its way into
Division 2 locations was neither designed nor intended for use in hazardous
locations. Only when a Division 2 application arose for a specific item was
the circuit examined to see if it was nonincendive. Regulatory bodies
typically reviewed manufacturer's analyses to see if voltage and current
levels fell below the appropriate ignition curve with a reasonable margin of
safety. If they did, the circuit was accepted to be nonincendive.
50
safety standards for nonincendive equipment. Third-party certification
agencies are using these standards to evaluate and list or label
nonincendive equipment. Listed or labeled equipment provides the end user
with a greater degree of confidence that the nonincendive equipment has been
properly evaluated and will not present.an unnecessary risk of fire or
explosion. However, manufacturer certification of nonincendive circuits is
acceptable; certification by a third-party testing agency is not required,
and many acceptable nonincendive circuits bear no label or other marking by
these agencies.
Section 500-2 of the 1987 NEG states: "Equipment and associated wiring
approved as intrinsically safe shall be permitted in any hazardous
(classified) location for which it is approved ...Intrinsically safe
equipment and wiring shall not be capable of releasing sufficient electrical
or thermal energy under normal or abnormal (emphasis added) conditions to
cause ignition of a specific flammable or combustible atmospheric mixture in
its most easily ignitable concentration. " Additional guidance on
intrinsically safe installations is expected to be included in Article 504
of the 1990 NEG.
51
·.
I
g. More than one intrinsically safe circuit of the same system may be
run in a multiconductor cable (see ISA RP 12.6).
52
damage. The intrinsically safe circuit is less maintenance dependent and
provides a lifetime of protection with relatively little care.
There are three types of purging protection in NFPA 496, Type X, Y, and
Z:
53
is not considered essential to remove power from the equipment upon
failure of the purge system.
54
Typical Type X Purging
pressure or
flowa<tuat~
cutoff switch
purge
supply
pr~~ur~ or
flow .,larm
aeluator
flow
in<1icalof
p<~wr~or
flow aeluator
P<.1f9~ p(oM~Ur~ or
\upply flow ..larm
.a(tu .. tor Of
indiutor
FIGURE 7
55
Purged or pressurized equipment may be used in lieu of explosionproof •
equipment for all hazardous locations. Purged or pressurized equipment may
not be used as a substitute for intrinsically safe apparatus. Purged or
pressurized systems need not be approved by an independent testing agency,
but are reviewed and approved fot' the, pa1:'ticular application during vessel
plan review.
Special care must be taken to ensure that the protective gas is from a
nonhazardous source and cannot be contaminated by a hazardous source. Vent
fan operation should be monitored by air flow, not simply by motor
operation. Where it is necessary to open a purged or pressurized enclosure,
as for maintenance or repair, gas detection equipment may be required to
ensure that a flammable atmosphere does not become trapped within the
enclosure.
56
O"'y~dva_&
•• CCII,", iftNl Itt.
He:corclo ... A,,,,o.pf..,,,,
."..
i~{':'&'~t;(.t~&~~'i;l
"',.rnol Hot flaming
Pre" ..,. ~o, ••
THREADED JOINT ~ FLANGED JOIN T
FIGURE 8 9
FIGURE
57
Equipment which is required by the Electrical Engineering Regulations to
be explosionproof must be specifically tested and approved by a nationally
recognized testing laboratory (UL, FM, and CSA are presently acceptable) for
use in a Class I Division 1 location and the group of the hazard present, and
be labeled as such.
TABLE 3
NEC ART. 500 - TABLE 500-3(b)
MAX. TEMP.
·c ·F H.ARJ:ING
450 842 T 1
300 572 T 2
280 536 T 2 A
260 500 T 2 B
230 446 T 2 C
215 419 T 2 D
200 392 T 3
180 356 T 3 A
165 329 T 3 B
160 320 T 3 C
135 275 T 4
120 248 T 4 A
100 212 T 5 *
85 185 T 6 *
Marking .ball not exceed auto ignition temp. of the atmo.phere encountered.
* Kon-heat
be aarked.
producing equipment. and that vith a temp. of IOO·C or lea., need not
58
Flame arresters are sometimes used in explosionproof enclosures to reduce
maximum explosion pressure and to prot~ct any incoming air lines. Types of
flame arresters include porous metal plugs made of sintered metal, a
baffle-type breather similar to an automobile muffler, a special fitting with
a loosely fitted thread, and a spiral wound corrugated metal fitting. These
configurations causes the flame to spread through paths which cool the gases
by heat transfer to the metal from the atmosphere or make the escaping
explosion's hot gases turn sharp corners, allowing them to cool.
59
• "
ARMOR
EQUIPMENT ClAMPING
OR BOX RING
AR110R CABLE
CONE
FERRULE
CABLE GLAND
FIGURE 10
60
EX:P LOS ION PROOF
~-ENCLOSURE
NIPPLE
EXPLOSIONPROOF
SEAL COMPOUND
PACKING
SEAL
SEAL
ARMORED CABLE
FIGURE 11
1. All cover screws and bolts must always be tight while circuits are
alive. Leaving one screw or bolt loose can render equipment unsafe.
Bolts or screw types other than those provided with the equipment should
not be used.
2. Hammers and other tools must not be allowed to damage threaded joints
or flat machined surfaces of flanged joints. All surfaces that form part
of a flame path must be protected from scratches and other mechanical
defects.
61
4. Threaded covers, flat joints, surfaces, rotating shafts, bearings, and
operating shafts should be lubricated to protect against corrosion. \
Abrasives or files should never be used to remove corrosion products from
threaded or flanged joints. Equipment which is corroded should be
replaced.
8.1 General. A wire is a conductor with functional insulation only, for use
inside an enclosure. A cable consists of one or more insulated conductors
provided with a protective covering of either a watertight metallic sheath or
an impervious non-metallic sheath compatible with the insulation. Most
shipboard wiring is accomplished using multiconductor cable.
Wire and conduit may be used for shipboard wiring. However, Due to the
high cost, labor-intensive installation, susceptibility to corrosion, and
problems with flexing hull structures, conduit is rarely used. Where it is
used, the installation requirements of the NEC should be followed (i.e.,
requirements for sizes and fill, bends and bending methods, couplings and
connectors, and support methods and locations), and the additional aspects of
a marine installation (corrosion, moisture, watertight bulkhead penetrations,
and flexing) should be addressed. Additionally, the wire must meet the
requirements of 46 CFR Subpart 111.60 for insulated conductors.
(3) A cable with polyvinyl chloride (PVC) insulation with a nylon jacket
that meets 46 CFR 111.60-l(b) (Type N Cable); or
62
It should be noted that some types of cable constructed in accordance with
MIL-C-9l5 are not required to meet the flame propagation requirements of IEEE
Standard 45. Therefore, it may be necessary to verify that a MIL-C-9l5 cable
type meets the flammability test of IEEE-45. At this time, there is little
MIL-C-9l5 cable available; most has been replaced with the new low smoke
mil-spec cable.
Type N cable will have embossed or printed on the cable either information
required by Section 18.8 of IEEE-45, or information required by Section 310-11
of the NEC, the manufacturer's name, identification code, voltage rating,
number of conductors, and conductor size. Since this information is not
unique to shipboard cable, the manufacturer may need to provide certification
that the cable meets 11l.60-l(b) including the flammability test of IEEE-45.
The design emphasis for merchant vessel ',(ablehas historically been placed
on the harsh ship construction environment (nearby welding, pulling cable
through bulkheads, and subjecting cable to constant mechanical abuse), as well
as on the shipboard operating environment (clamped assemblies, large cable
bundles, and exposure ·to a wide range of temperatures, high humidity, and
oil). Additional considerations for naval vessels have included longitudinal
water propagation resistance, overload conditions, and circuit integrity under
fire conditions. The U.S. Navy has also had to explore smaller diameter,
lighter weight cable constructions in order to conserve space and reduce
topside weight. Only in recent years, however, have several disastrous
shipboard fires focused attention on the damage to health and property caused
by fire propagated by cables. In fires aboard ships,-cableways have been
blamed for spreading relatively small and confined fires and generating dense
smoke and toxic and corrosive products of combustion, compounding the
firefighting problem.
63
the International Association of Drilling Contractors (IADC) Standard DCCS-l,
"Interim Guidelines for Industrial System DC Cable for Mobile Offshore
Drilling Units", attached as Appendix 5. In accordance with this standard,
marine cables may be listed by UL for up to 110°C. The current-carrying
capacity of IlO°C rated cables is 1.14 times the 90°C (E,X) rating column in
IEEE-45. If the UL listing is for 100°C or less, however, the cable cannot be
used at the 110°C rating. Industrial system cable rated and utilized (sized)
at 110°C may be run with other cables, without maintained spacing (i.e.,
banked) if derated in accordance with Note 6 of Table A6 of IEEE-45.
The Naval Sea Systems Command (NAVSEA) has published two new military
specifications on the construction of shipboard electrical cable. The first,
MIL-C-24640 (Cable, Electrical, Lightweight, for Shipboard Use), addresses
lightweight power, lighting, and communication cable with a crosslinked
polyolefin jacket. The second, MIL-C-24643 (Cable and Cord, Electrical, Low
Smoke, for Shipboard Use), addresses electrical cable which exhibits low smoke
generation characteristics when subjected to specific smoke and flame tests.
The ampacities for these Navy cables may be found in "Cable Comparison
Handbook, HDBK-299, issued 3 April 1989." Although this handbook addresses
standard Navy cable size designations, it should also be used for the AWG
sized cables of MIL-C-24640 having similar (not necessarily identical)
cross-sectional areas.
The first standard in the United States that included testing typical
cable installations for flame propagation resistance was IEEE Standard
383-1974, developed as a test standard for cabling in nuclear power plants.
The IEEE Marine Transportation Committee subsequently adopted a similar method
for fire testing in IEEE Standard 45-1977. The Electrical Engineering
Regulations require shipboard cable to meet these IEEE-45 flammability
requirements. The IEEE-45 test attempts to simulate a realistic cableway fire
situation in evaluating flame propagation parameters of a bunched vertical
cable installation. At this time, the IEEE-45 procedure does not address
toxicity, smoke evolution, or corrosive gas generation. The procedure of the
International Electrotechnical Commission (IEC) Report 332 Part 3 is another
practical method of testing the flame propagation characteristics of cables in
a bunched configuration. The test is similar to the IEEE-45 procedure, but is
more specific in defining the chamber size and heat input and is basically
concerned with the total volume of combustible material in a cable run.
Category A'of this test uses a sufficient number of 3.5 meter lengths of cable
to obtain 7 liters/meter of total combustible material, with the cables
touching and mounted vertically on a steel ladder. Cables constructed in
accordance with IEC 92-3 (Electrical Installations in Ships, Part 3: Cables
(Construction, Testing, and Installations» may be accepted as equivalent to
those required by 46 CFR 111.60 provided they meet the flame propagation test
64
requirements of lEC Report 332 Part 3, Category A. Flame proagation
resistance should be verified by an independent third party testing
organization. The ampacities tabulated in the ABS Rules, Table 35.2, should
be used for cables constructed to lEC 92-3, except that notes 2 and 3 to that
table should not be used, as they are not comparable to lEEE-45. The values
shown in the table may be used for a single bank installation. For
double-bank installations, the correction factor of IEEE-46 table A6 applies.
The IEC is in the process of replacing IEC 92-3 with significantly revised
requirements in 92-350 series documents. While completion of this task is
several years away, at this time it appears that the newer standards will not
be comparable to present marine cable standards and will not be equivalent to
the cable standards referenced in Subchapter J.
Type N cable (PVC-insulated cable with a nylon jacket over each conductor,
and an outer cable jacket) is based upon shoreside type T building wire
construction, the use of which is addressed in NEC Table 310-13. Shipboard
Type N cable is required by 46 CFR 111.60-l(b)(1) and (3) to meet the PVC
insulation and nylon insulation covering thickness requirements of UL 83 for
type THWN wire, and the other requirements of IEEE-45 for a Type T cable, such
as outer jacket requirements and conductor stranding. The nylon jacket
material must meet the requirements of ASTM D789 Type VIII.
Although NEC Article 310-3 permits solid conductors for size No. 10 AWG
and smaller, solid conductors are unacceptable for shipboard power cables.
Nicks on solid conductors from insulation removal are likely to lead to
conductor breakage with shipboard vibration.
65
(i) to at least 1 meter in every 14 meters for horizontal runs;
and,
(B) be fitted with fire stops having at least B-O penetrations every
second deck or approximately 6 meters for vertical runs and at every
14 meters for horizontal runs.
(4) Cable constructed in accordance with IEC 92-3 and meeting lEC Report
332-3 Category A (independent test laboratory certification should be
provided);
8.3 Unique Applications. Special purpose cables may be used for unique
applications where there is a compelling reason for deviating from the cable
construction standards discussed above in order to satisfy system
requirements. Such special purpose cables may include coaxial, triaxial, and
low noise signal cables. Exceptions to the construction and testing
requirements for such cables exist in both Section 19.1 of IEEE-45 and SOLAS
11-1/45.5.2. The primary concern with these cables is flame propagation. If
a particular cable type cannot be shown to comply with the IEEE-45 or IEC
332-3 (Cat A) fire tests, then the special precautions discussed earlier
should be used to achieve a flame propagation resistant installation. If
special purpose cables are run singly (not in or near bundles or cable trays
with other cables), then self-extinguishing construction is acceptable.
66
comply with the IEEE-45 or IEC 332-3 (Cat. A) fire tests, or be installed
using the special precautions to achieve a flame propagation resistant
installation.
67
~ "
Where ribbon cables or similar small conductor size cables are recommended
for use in low-power instrumentation, monitoring, and control circuits by the
equipment manufacturer(s), the use of such cables may be pe-rmitted.
Additional mechanical protection may be required to protect the conductors
from parting due to mechanical damage or flexing. Ribbon cables are usually
found within equipment or consoles. However, they are sometimes used
externally to interconnect modules. The location of the cable aboard the
vessel and the function of the circuit will determine the extent of mechanical
protection required, if any.
The requirement for 14 AWG m~n~mum wire in switchboards was written with
full voltage, field-wired switchboard equipment in mind. Wire smaller than 14
AWG may be considered for low voltage, low-power circuits within switchboards.
8.6 Flexible Cord. Flexible electric cords and cables may be used only as
allowed by Table 400-4 and Sections 400-7 and 400-8 of the NEC, per 46 CFR
111.60-13. They must not be used for fixed wiring, unless they are dual rated
as both flexible cable or cord and shipboard cable listed by UL. No. 18 AWG
conductors are permitted in power and lighting circuits only for portable
applications. The lADC Standard DCCS-l for DC cables on MODU's accepts
high-flex single conductor cables constructed to the requirements of the
American Association of Railroads (AAR) Specifications S-50l and 591. Certain
high-flex strandings for large conductor sizes (such as 535,000 circular
mils.), originally developed for locomotive use, have been incorporated (with
flame propagation resistance) into the IEEE-45 cable construction standards.
8.7 Color Coding. The Electrical Engineering Regulations do not require the
use of any particular conductor color coding scheme. The only requirement is
that an insulated equipment grounding conductor in a cable must have green
braid or insulation, per 46 CFR 111.05-33(b). Different color codes for
circuit conductors may be found in lEEE-45 Section 18.5 and NEC Sections 210-5
and 310.12. Although the regulations do not require the use of a specific
color scheme for the ungrounded conductors of a circuit, it is recommended
that some consistent coloring or marking practice be used for multiwire
circuits in order to provide positive identification of circuit conductors and
facilitate troubleshooting and repair.
68
8.8 Cable Installation. Each cable installation must meet the general
requirements of IEEE-45 Sections 20 and 22, with the exception of 20.11 which
is superseded by 46 CFR 111.60-19. The use of nylon or plastic cable straps
is explicitly recognized in 20.5 for horizontal runs where the cable will not
fall if the strap fails. They are permitted where the cable strap is used to
maintain spacing and not for support of the cables.
When pressure type connectors are used, the proper size is important. The
connection must be tight, yet it must not be necessary to remove strands to
fit the connector body to the conductor. This can sometimes present problems
since marine cable has a different conductor diameter than NEC constructions.
69
•
70
Cable routing and segregation requirements are contained in 46 CFR
111.60-9 and 111.60-5, which references IEEE-45 Sections 20 and 22, except
20.11. Section 20.3 requires cables to be so routed as to avoid, so far as
practicable, galleys, firerooms, and other spaces where excessive heat and
high risk of fire may be encountered. SOLAS 11-1/45.5.3 includes laundries in
this category of spaces to be avoided.
9.2 Navieation Lights. The requirements for navigation light systems are
contained in 46 CFR 111.75-17. Note that dual light sources are required for
certain lights. Annex I of the International Regulations for Preventing
Collisions at Sea, 1972, (72 COLREGS) and the 1980 Inland Navigation Rules,
(80 RULES), specify navigation light requirements in terms of color, arcs,
range of visibility, and position.
Ranges. Compared to the 1960 Rules, the range requirements of the 72 COLREGS,
for most lights, have increased. The relationship between range of visibility
and luminous intensity has also changed. However, many lights on vessels
built to the 1960 Rules were much brighter than required and may meet the
present Rules. It should be noted that with the change in the value of
assumed atmospheric transmissivity, the old 5-mile lights were required to be
brighter than the COLREGS 6-mile lights.
Color. Compared to the 1960 Rules, color coordinates for green lights have
narrowed. This has resulted in a shift toward a bluish tint in the
manufacturing of "green" dyes for navigation light lenses. The most commonly
manufactured green plastic dyes have not had good ultraviolet stabilization;
constant exposure to solar ultraviolet radiation will alter the green tint in
71
a few years. This may be beneficial, in that it moves the color coordinates
of an older light lens into the region required by the present Rules.
However, it may also move them beyond the acceptable region. [NOTE: Tests
can determine the color coordinates of the lens only at the time of testing;
these coordinates continually change as navigation lights are exposed to
ultraviolet radiation].
Horizontal Sector. Annex I of both sets of Rules gives specific arcs in which
certain intensities of light are required. For example, sidelights as fitted
the vessel must, in the forward direction, reach "practical cut-off" (i.e.,
Q.I!
one-eighth of the minimum required sector intensity) between 1 and 3 degrees
outside the prescribed sector. Prior to adoption of the 72 COLREGS and the
Inland Rules, lights were "eyeballed" for a "reasonable decrease" in intensity
in the cut-off region.
72
Premature Bulb Failure. On vessels such as tugs and barges, problems with
vibration and shock (impact) have been reported. Although navigation lights
are subjected to stringent vibration testing, with bulb failure as a rejection
factor (evidenced by one manufacturer failing this test and having to
re-design the fixtures), the accepted fixtures are not tested for impact shock.
When shock or vibration is a problem, shock mounting the fixture is
recommended. This shock mounting can take two forms. The first is internal
isolation of the bulb. This is a manufacturer's modification and could
involve retesting of the fixture. The second is to isolation mount the
fixture on the vessel.
73
.10. SOURCES OF ADDITIONAL INFORMATION
10.1 The Federal Register preambles to the 27 June 1977 Notice of Proposed
Rulemaking, 3 March 1980 Supplemental Notice of Proposed Rulemaking,
and 8 April 1982 Final Rules for Subchapter J contain discussions of
the philosophy and intent of the Electrical Engineering Regulations.
These discussions can provide amplifying and clarifying information
on a number of the regulations.
10.2 The National Electrical Code Handbook, published by the National Fire
Protection Association, is a valuable reference for those parts of
the NEC which are incorporated by reference into the Electrical
Engineering Regulations as well as for other areas of general
interest such as Article 700 on emergency power systems.
10.7 IEEE Std .. 141, IEEE Recommended Practice for Electric Power
Distribution for Industrial Plants, (the IEEE "Red Book").
10.8 IEEE Std .. 142, IEEE Recommended Practice for Grounding of Industrial
and Commercial Power Systems, (the IEEE "Green Book").
10.9 IEEE Std .. 242, IEEE Recommended Practice for Protection and
Coordination of Industrial and Commercial Power Systems, (the IEEE
"Buff Book").
74
10.13 ISA-S12.10 Area Classification in Hazardous Dust Locations.
75
APPENDIX 1
INDEX FOR REFERENCE DRAWING TO TITLE 46 CFR, NATIONAL ELECTRICAL CODE (NEe),
INSTITUTE OF ELECTRICAL AND ELECTRONIC ENGINEERS (IEEE) STD. 45-1983.
UNDERWRITERSLABOR!TORIES (UL). ETC.
76
APPENDIX 1 (cont'd)
77
. "
APPENDIX 1 (cont'd)
78
..... t;t z -
-alii ; t:
~
.., !:! ~
_, i c
:e ::;3 :;
\U ...
~ ~ ...I.M i~t i
~~~Ot.n
e.... 00
:a ~
~!®
cr
~ f \11- W
• .J ~
X 0 tS :!~
,,;,
~c
-e
......&
;~
Ws til
50 Q-
a::
79
APPENDIX 2
LOAD ANALYSIS
~l A motor may be oversized for its attached load and thus not
operate at its rated capacity.
(c) Formulas for the determination of load factors for major steam
propulsion vessels may be found in SNAME T&R Bulletin 3-11,
"Marine Steam Power Plant Heat Balance practices", Section
3.2.15.
or
80
(e) A singl~ load factor for group loads may be assigned if they
meet one of the following cr1ter1a:
(i11) When low power loads in the same space can be assigned
roughly the same load factors (e.g., radios and
electronics).
(f) Known load use data should always be used in lieu of demand
factors, if available.
(8) Power conversions and their efficiency should be considered
(e.g. power factors, transformers, semiconductor controlled
rectifiers (SCR's). Due to efficiency below 1.0, apparent
connected loads may be increased due to the conversion
equipment).
(h) Loads that are provided individual factors in the analysis
should not be addit10nally ass1gned a group factor, and vice
versa (e.g., 0.3 (1ndividual factor) x 0.4 (group factor) -
0.12 (final factor) (either 0.3 or 0.4 could be used, but
not 0.12».
(1) Factors of zero (0) are assigned to equipnent that is seldom
used.
(j) Factors of 0.9 and 1.0 are used where motors operate at full
load for an extended period of time.
81
_ I
(i)' Steering;
(vi) Alarms;
(vii) Bilge pumps;
(viii)Emergency lighting;
(ix) Radar; and
(x) ControIs.
82
APPENDIX 2
TABLE 1
0')
TABLE 1 (cont'd)
84
TABLE 1 (cont'd)
Radio .4 .4
Searchlights 0 0
Mach. space ltg. .9 .9 .9
General ltg. .6 .4 .4 .6
Emergency ltg. .6 .4 .9
Navigation Itg. .6 .2 .4 .5
Service area ltg .4 .35
SS. reefer circ. pump .4
SSe reefer compreS80r .3 0 .1 .4
Cargo reefer cmp. .3 0 .6
A.C. compressor .7 .4 .8 .75
A.C. chill wtr. PUlllp .7 .4 .9 .75
A. C. s.w. circ. pump .7 .4 .75
A.C. Fan .75
A.C. H.W. circ. pump .6 .75
Unit coolers .2 0
Oven/range .4 0
Galley equip. .3 0 .3
Refrig/freez:er .5 0
Refrig. small .3 .3
Pantry ~quip. .2 0 .3
La undry equip. .2 0 .2
Hospital equip. .1 .1 .2
Electronics .5 .2 .5 .45
Distiller plant .7 0
Distiller brine ovbd. .8 .75
Distiller cond. pump .3 .6
Distiller feed pump .8 .75
F.W. transfer pump 0
Ice water eire. pump 1 .7
Potable water ·pump .3 .2
Drinking fountain .4
H.P. air compressor .1
S.S. air compressor .1 .1 .3
Control air compre8sor .6 .2 .4
Sewage pump .1 1.0 .2
Sewage r:acerator .1 1.0
Sewage blower 1
Cathodic protection .7
Ice water circ. pump 1.0 .7
Brine eire. pump 1.0
Reefer container recept. .9
Winches
Bow thruster
Main control console .6
Boiler console .6
R.A.I., E.O.T., fllarms 1
85
APPENDIX 2
TABLE 2
Bilge Pump 5 KW o o
Ballas t Pump 10 KW 0.1 1 KW
AIC - Heater 10/20 KW 0.8 8/16 KW *
Cargo Circ. Pump 15 KW 0.6 9 KW
Dist. A Total 0 + 1 + 16 + 9 -= 26 KW
DISTRIBUTION B
DISTRIBUTION D
86
TABLE 2 (cont'd)
MAIN SWBO
Dist. A 26 KW
Oist. B 25.9 KW
Transformer 11 26.9 KW
Generator Demand Load 78.8 KW
Full Load Gen. Capacity 85 KW
* Relationship exists. take larger load. *** Similar loads given group
** One pump is the standby. factor.
**** Reduced efficiency increases
demand load. type transformer eff
.96-.99
87
· ,
APPENDl1C 3
(d) Cooling.
APPENDIX 4
Miscellaneous Tables.
up to #2 18
#2 #0 #6
#0 3/0 #4
3/0 350 HCM #2
350 HeM 600 HeM #0
600 HeM 1100 MeM 2/0
greater than 1100 HCH 3/0
89
Generator Continuous Full Load Ampere Ratings.
:>.0 37.5 104.1 120 94.1 108 90.2 104 47.1 54 45.1 52 36.1 42
).0 50.0 138.8 160 125.5 144 120.3 138 62.7 72 60.1 69 48.1 55
).0 62.5 173.5 200 156.9 180 150.3 173 78.4 90 75.2 86 61.1 70
).0 75.0 208.2 239 188.3 217 180.4 207 94.1 108 90.2 ._104 72.2 83
5.0 93.8 260.4 300 235.4 271 225.6 259 117.7 135 112.8 130 90.3 104
)0.0 125.0 347.0 399 313.8 361 300.7 346 156.9 180 150.4 173 120.3 138
~5.0 156.0 433.0 498 391.6 450 375.3 432 195.8 225 187.6 216 150.1 173
50.0 187.0 519.1 597 469.4 540 449.8 517 234.7 270 224.9 259 179.9 207
75.0 219.0 607.9 699 549.6 632 526.7 606 274.8 316 263.3 303 210.7 242
)0.0 250.0 694.0 798 627.6 722 601.4 692 313.8 361 300.7 346 240.6 277
>0.0 312.0 866.1 996 783.2 900 750.5 863 391.6 450 375.3 432 300.2 345
)0.0 375.0 1040.1 1196 941.3 1082 902.1 1037 470.7 541 451.1 519 361.0 415
90
Transformer Full Load Currents.
91
.. "
[VA
Rating 120 208 240 480 600 2400
92
APPENDIX 5
INTERNATIONAt. sar.,r Addreu: 15110Patte Ten P&IIce, SuIte 242
ASSOCIATION- OF . Houlton, ...... 7'7'064-6134
Phone 7tU1'8-7171
..... '518885
DRILLING CONTRACTORS Telefax7'~
M'ERJM GUIDELINES
I. Purpose
These interim guidelines have been prepared to establish a method for the selection, installation
and acceptance of DC electrical cables used on industrial drilling systems on mobile offshore
drilling units. These systems are drawworks,pumps and rotary table. These interim guidelines
will provide the necessary guidelines for DC cable on MODUs until a final standard has been
prepared and issued.
B. The cable size per polarity shall have a current-carrying capacity determined by multiplying
the duty factor times the lesser of:
G. For this specification. the cable insulation and jacket shall meet or exceed the requirements
of the latest edition of one or more of the following standardsas it 'appliesto the construction
of a single conductor power cable; Where the following standards do not specifically list ",
AAR-sized cable, the insulation and jacket thicknesses shall conform to the next larger size J
cable listed.
1. Rubber-insulated Wire and Cable for the Transmission and Distribution of Electrical
Energy (ICEA 5-19-81);
7. General Specifications for Cable and Cord Electrical for Shipboard Use (Military
Specification MIL-C-915E).
94
APPENDIX 6
FIGURE 1
A B C D E F G H I J
95
· "
-/..
' .
.\
FIGURE 1 (cont'd)
HP K L M N 0 p
.25 1.54 14 14 14 4 4
.33 1.85 14 14 14 4 4
.5 2.51 14 14 14 4 4
.75 3.5 14 14 14 4 4
1 4.5 14 14 14 4 4
1.5 7.13 14 14 14 4 4
2 9.75 14 14 14 4 4
3 12 .5 14 14 14 4 4
5 21.3 12 14 14 9 9
7.5 30.0 10 10 12 9 9
10 38.8 7 8 10 9 14
15 57.5 5 6 7 23 23
20 73.8 3 4 5 30 30
25 93.8 1 2 3 40 50
30 110.0 1/0 1 2 50 60
40 142.5 3/0 2/0 1/0 75 100
50 178.8 4/0 3/0 2/0 125 125
60 212.5 300 250 4/0 150 150
75 265.0 400 350 250 200 250
100 341.3 600 500 400 300 400
125 428.8 400
150 495.0
200 660.0
96
APPENDIX 6
FIGURE 2
A B c D E F G H I J
HP FLA Running Prot. Start- Disconnect Max. Prot. Device
115%.FLA er size size Full Volt Start
Adj. Non- Code B-E Code F-V
Adj. C.B. Fuse C.B. Fuse
200% 250% 250% 300%
---- ----
.5 1 1.15 2 00 30 15 IS 15 15
.75 1.4 1.61 2 00 30 15 15 15 15
1 1.8 2.07 3 00 30 15 15 15 15
1.5 2.6 2.99 3 00 30 15 15 15 15
2 3.4 3.91 4 00 30 15 15 15 15
3 4.8 5 ..
5'- 6 0 30 15 15 15 15
5 7.6 8.74 10 0 30 20 20 20 25
7.5 11 12.65 15 1 30/60 25 30 30 35
10 14 16.1 20 1 30/60 30 35 35 45
15 21 24.15 25 2 60/100 45 60 60 70
20 27 31.05 35 2 60/100 60 70 70 90
25 34 39.1 40 2 100/200 70 90 90 110
30 40 46 50 3 100/200 90 100 100 125
40 52 59 60 3 200 125 150 150 175
50 65 74.75 80 3 200 150 175 175 200
60 77 88.55 90 4 200/400 175 200 200 250
75 96 110.4 125 4 400 200 250 250 300
100 124 142.6 150 4 400 250 350 350 400
125 156 179.4 200 5 400/600 350 400 400 500
150 180 207 225 5 600 400 450 450 600
200 240 276 300 5 600 500 600 600
97
"
~\
~
j
FIGURE 2 (cont'd)
HP K L M N 0 P
98
APPENDIX 6
E - Starter size is 2.
Std. Max.
Adj. Disc. Branch
Full Over Start- Size, Circ. 50·C
Horse- Load Load er If Bkr. 125% TSGA-( )
Power Amps Size Size Used (250%) F.L.A.
30 40 .;.(; 3 100 100 50 23
15 21 24'.2 2 60 60 26.3 9
5 7.6 8.7 0 30 N/A 9.5 4
99
« \
Subchapter J does not address ~otor control centers directly; one must-refer
to NEC 430-24 and 430-62(a). Per 430-24, bus or cable in MCC must be sized
for 125 percent of the largest plus 100 percent of the remaining motor full
load currents, 50 + 21 + 7.6 + 7.6 - 86.2 amperes. If the MCC has spare
sections, allowance shall be made for future growth. Breaker protecting
entire MCC must not be larger than the largest rating or setting of the
branch-circuit short-circuit and ground fault protection (based on Table
430-152) for any motor in the group, plus the sum of the full load currents of
the other motors in the group, or 100 + 21 + 7.6 + 7.6 - 136.2 amperes.
The 5 HP steering pump motor should be protected with a circuit breaker having
adjustable, instantaneous (magnetic) type tripping only. This breaker must be
set to open the motor circuit at 175 to'200 percent of the locked rotor
current. As will be shown below, this setting should be 79 to 90 amperes.
NEMA AC General Pur~se, Class A Full Voltase Controllers,
Single-Speed Squ1rr Cage Motors.
0 lB 1.5 1.5 2 21
1 27 3 3 5 32
2 45 7.5 10 15 52
3 90 15 20 30 104
4 135 25 30 60 156
5 270 60 75 150 311
6 540 125 150 300 621
HP 115V HP 115V
.33 7.2 2 24.0
.5 9.8 3 34.0
.75 13.8 5 56.0
1.0 16.0 7.5 80.0
1.5 20.0 10 100.0
NOTES: (1) Values are for motors of normal speed and torque.
AMPS c: KW x 1000
1.732 x Volts x PF
101
,. \
-~
/
NOTES: (1) These values are to be used only if motor code letter
is not provided.
- 577 x HP x (KVA/HP)
Volts
102
3-Phase Motor Ap;eroximate F.L.A. (cont. )
HP Sg,uirrel Ca~e Wound Rotor
208V 220V 440V 208V 220V 440V
7.5 23 21 10.5 25:"3 23 ---rr:-5
9.0 27.3 24.8 12.4 28.6 26 13
10 28.6 26 13.5 31.9 29 14.5
20 57.2 52 26 59 54 27
25 71.5 65 32 75- 68 34
30 86 78 39 88 80 40
35 101 92 46 103 94 47
40 112 102 51 114 104 52
45 128 116 58 128 116 58
50 139 126 63 141 128 64
60 167 152 76 169 154 77
75 207 188 94 207 188 94
100 275 250 125 275 250 125
125 341 310 155 341 310 155 ~
150 407 370 185 407 370 185
200 539 490 245 539 490 245
NOTES : (1) To be used in lieu of nameplate data (see NEC 430-6).
103
APPENDIX 7
NOTES:
104
, .
C Acetaldehyde
D Acetic acid
D Acetic anhydride
H Acetone cyanohydrin
D Acetonitrile
D Acrylic acid
D Acrylonitrile
H Adiponitrile
C Allyl alcohol
D Allyl chloride
NA Aluminum sulfate solution
H Aminoethyl ethanolamine
D Ammonia, anhydrous (press.)
D Ammonia, anhydrous (atmosphere)
NA Ammonium bisulfite solution (70% or less)
D Ammonium hydroxide (28% or less NH3)
H Aniline
D Anthracene oil (coal tar fraction)
NA Argon, liquified
D Benzene
D Benzene-hydrocarbon mi~tures
B Butadiene
B Butadiene, butene mixtures
D n-Butyl acrylate
D iso-Butyl acrylate
D Butylamine
C Butylmethacrylate
C Butyraldehydes (crude)
C n-Butyraldehyde
C iso-Butyraldehyde
D Camphor oil (light)
H Carbolic oil
A Carbon disulfide
NA Carbon dioxide (liquefied)
N Carbon tetrachloride
N Caustic potash solution
N Caustic soda solution
N Chlorine
D Chlorobenzene
N Chloroform
D Chlorohydrins (crude)
B Chlorosulfonic acid
D Coal tar
D Coal tar naphtha solvent
D Coal tar pitch (molten)
H Creosote
H Cresols
N Cresylate spent caustic
C Crotonaldehyde
D Cyclohexanone
D Cyclohexylamine
H iso-Decyl acrylate
D Dichlorobenzene (all isomers)
105
N Dichlorodlfluoromethane
D l,l-Dichloroethane
D 2,2-Dicbloroethyl ether
N Dichloromethane
NA 2,4-Dichloropbenoxyacetic
acid, diethanolamine
salt solution
NA 2,4-Dichlorophenoxyacetic
acid, dlmethylamine
salt solution
NA 2,4-Dichlorophenoxyacetic
acid, triisopropanol-
amine salt solution
D Dichloropropane
D Dichloropropene, Dichloropropane mixtures
NA 2,2-Dichloropropionic acid
H Diethanolamine
C Diethylamine
H Diethylenetriamine
C Diisobutylamine
H Diisopropanolamine
C Diisopropylamine
D N,N-Dimethylacetamide
C Dimethylamine
C Dimethylethanolamine
D Dimethyl Formamide
C l,4-Dioxane
C Di-n-propylamine
NA Diphenylmethane Diisocyanate
C Epicblorohydrin
H Ethanolamine
D Ethyl acrylate
D Ethylamine (72% or less)
C Ethyl n-butylamine
D Ethyl chloride
C Ethyl cyclohexylamine
D Ethylene ch+orohydrin
H Ethylene cyanohydrin
D Ethylene diamine
N Ethylene dibromide
D Ethylene dichloride
NA Ethylene glycol propyl ether
B Ethylene oxide
C Ethyl ether
H 2-Ethyl bexyl acrylate
C Ethylidene norbornene
D Ethyl methacrylate
C 2-Ethyl-3-proply acrolein
B Ferric chloride solutions
H Formaldehyde solution (37%-50%)
D Formic acid
C Furfural
NA Glutaraldehyde solution (50% or less)
D Bexamethylenediam1ne solutions
C Hexamethylene1mine
B Hydrochloric acid
B Hydrochloric acid, spent (IS! or less)
B Hydrofluorosiliclc acid (25% or less)
106
B Hydrogen chloride
B Hydrogen fluoride
H 2-Hydroxyethyl acrylate
D Isoprene
NA Kraft pulping liquors (free alkali content 3% or more)
D Mesityl oxide
C Methylacetylene Propadiene mixture
D Methyl acrylate
D Methylamine (anhydrous)
D Methylamine solution (42% or less)
D Methyl bromide
D Methyl chloride
B Methylcyclopentadiene dimer
C Methyldiethanolamine
H 2-Methyl-5-ethyl pyridine
D Methyl methacrylate
D 2-Methyl pyridine
D alpha-Methyl styrene
N Monochlorodifluoromethane
H Ethanolamine
C Morpholine
D Motorfuel antiknock compounds
B Nitric acid (70% or less)
D Nitrobenzene
NA Nitrogen, Liquified
C 1- or 2- Nitropropane
NA Octyl nitrates (all isomers)
B Oleum
NA Pentachloroethane
D 1,3-Pentadiene
N Perchloroethylene
H Phenol
H Phosphorous, elemental
B Phosphoric acid
H Phthalic anhydride
H Polyethylene polyamine
H Polymetbylene polyphenylisocyanate
H iso-Propanolamine
D Propionic acid
D iso-Propylamine
B Propylene oxide
D iso-Propyl ether
D Pyridine
NA Sodium aluminate solution
N Sodium chlorate solution (50% or less)
NA Sodium dichromate solution (70% or less)
NA Sodium hypochlorite solution (15% or less)
N Sodium sulfide, hydrosulfide solutions (H2S l5ppm or less)
N Sodium sulfide, hydrosulfide solutions (H2S greater than lSppm but less
than 20Oppm)
N Sodium sulfide, hydrosulfide solutions (H2S greater than 200ppm)
NA Sodium thiocyanate solution (56% or less)
D Styrene mono~e~
C Sulfur (molten)
N Sulfur dioxide
107
B Sulfuric acid
B Sulfuric acid, spent
NA l,1,2,2-Tetrachloroethane
H Tetraethylene pentamine
C Tetrahydrofuran
H Toluene diisocyanate
D 1,l,2,-Trichloroethane
D Trichloroethylene
H l,2,3-Trichloropropane
H Triethanolamine
C Triethylamine
H Triethylene tetramine
H Tiiisopropanolamine
C Velaraldehyde (iso-,n-)
NA Vanillan black liquor (free alkali content 3% or more)
D Vinyl acetate
D Vinyl chloride
D Vinylidene chloride
D Vinyl toluene
D Urea, Ammonium nitrate (containing more than 2% NH3)
108
APPENDIX 8
____ (d) Elementary and one-line wiring diagrams, showing all wiring;
____ (b) Intended application by a NRTL (currently UL, FM, CSA, and MET are
acceptable to the Coast Guard):
109
.,
...
TAN KS
CARGO TANKS· NA NA NA NA
CARGO HANDLING ROOMS· NA NA NA HA
COFFERDAMS * NA NA NA NA
BATTERY ROOMS 'X 'itA NA NA
PAINT STORAGE ROOMS X NA NA HA
PAINT MIXING ROOMS X NA NA HA
OIL STORAGE ROOMS X NA NA HA
ANESTHETIC HANDLING AREA X NA NA NA
TANK VESSEL WEATHERDECK
10 FT. RULE x NA HA
TANK VESSEL WEATHERDECK
CARGO BLOCK x NA NA NA
FLAMMABLE GAS HANDLING
ROOM· NA NA NA NA
FLAMMABLE LIQUID
HANDLING ROOM· NA NA NA NA
AD~ACENT TO CLASS I,
DIV. 1 W/COHMUNICATION X NA NA NA
TANK VESSEL ENCLOSED SPACES
ADJACENT TO CARGO TANK· NA NA NA NA
CRAIN HANDLING AREA NA NA X NA
COAL HANDLING AREA NA NA X NA
COAL PULVERIZING AREA NA NA X NA
CARPENTER SHOP NA NA NA X
FIBER HANDLING AREA NA NA NA X
VENT DUCT SAME AS SPACE SERVED
TANK VESSEL CARGO HOSE
STOWAGE S~A9E~ NA NA NA NA
SPACE CONTAINING CARGO PIPING
ONLY, ON TANK VESSELS. NA NA NA NA
LPG BARRIER SPACE* NA NA NA NA
ENCLOSED SPACE OPENING TO
WEATHER DECK HAZ. AREA X NA NA NA
TANK VESSELS WITHIN 8' OF
CARGO CONTAINMENT SYSTEM X NA HA NA
TANK VESSELS, WITHIN 10' OF
CARGO HANDLING ROOM OOOR
OR VENT X NA NA NA
VESSEL FUEL OIL TANKS,
10' RULEDOES NOT APPLY X NA HA HA
TANK VESSEL, .A-D CARGOES,
AREA FROM~3m TO Sm OF (see SOLAS 11-2/59.1.7.2)
PV VALVES NA X NA NA
TANK VESSEL. A-D CARGOES,
(see SOLAS 11-2/59.1.9.3)
AREA FROM 3m TO 10m OF
VENT OU'fLEIS fOR fREE
FLOW OF VAPORS AND H. V •
VENTS FOR LOADING OR
DISCHARGE NA X NA NA
* These area. are considered .ore hazardoul than C1a.s I, Dlv1810n 1 and
therefore carry apecific requirements in 46 CPR111.105-29,111.105-31. and
111.105-32 •
111
APPENDIX 9
112
APPEtmIX 10
113
4. Initial Electrical Inspections.
114
FIGURE A-4
IRSULATIOli;, RESISTANC E
MINIMUH
CI RCUI T INSULATION RESISTANCE
d. Group Control Panels. When two or more motor controllers are grouped
into 8 central panel and supplied by a co~on feeder, the panel shall
be checked for compliance with the requirementg of 46 CFR 111.10.
Each controller, its a8~ociated motor overcurrent protective device,
its motor branch circuit overcurre~t protective device, and
disconnecting mechanism shall be mounted in a common enclosure vith a
disconnect device that prevents the door being opened vheo the circuit
is energized. The enclosure shall be either dripproof or vatertight.
depe~ding on its location. Adequate vorking apace should also be
provided. Thi8 generally ehould ~ no less than ;6 inches in front,
,, ~
'~
116
k. Accessibility. The accessibility of electrical apparatus for
inspection and maintenance shall be observed. The accessibility of
junction boxes and ·similarapparatus in vay of paneling shall also be
noted,. Hinged doors 'of lDotor--atart ers-and-simi-la-r-appara
tU8-8ha-ll~'be
checked for interference with adjacent structural parts or apparatus.
1. General Alarm Systems. The general alarm system shall be checked with
a sound level meter, the sound level of the bells being measured in
each stateroom with the doors closed. Where the background.noise
level is questionable. the sound level should be measured while the
vessel is underway (see 46 CFR ll~.25-9).
117
q. (cont'd) second teat shall then be conducted with the remaining
motora, Done of the motors in this second test should start
8utomatlCiIry.
118
d. (cont1d) winches. Casualty investigations have indicated the need to
specifically examine the clutch interlock switches on dual winches,
such as those on Victory-type cargo ships. It is essential that
satisfactory limit switches and emergency disconnect switches be used
with gravity davits and power-operated winches. Therefore, a test
operation of the lifeboat winch controls, including limit switches,
emergency disconnects, and clutch interlocks where employed, sha~l be
conducted at each reinspection and as the inspector may require.
119
1. Portable Electrical Equipment. Portable electrical equipment may be
accepted in several ways. Portable cargo lights are covered under
the Underwriters Laboratories Inc. "Standards for Marine-Type
Electric Lighting Fixtures." These lights are labeled to indicate UL
approval as "marine types"; portable items covered by this category
are considered satisfactory. Portable items not labeled by UL must
be checked to ensure compliance with 46 CFR Subchapter J. Portable
fixtures should be referred to the Marine Safety Center for
determination. Approval of portable lighting devices by inspectors
is not advisable. Portable tools can be accepted if the design
appears to be commercially sound. This can be verified by a UL
listing under the classification "Tools -- Commercial Type."
j. Fire and Smoke Detection Systems. Fire and smoke detection systems
shall be checked regularly, and faulty detectors shall be
recallbrated or replaced. The following test methods may be used:
(1) Thermal detectors may be tested by replacing the guard and globe
with a sheet metal shield and using a portable light as the heat
source; this will not cause damage to the adjacent paintwork.
The activation temperature range should be as specified in 46
CFR 161.002-11.
120
I •
121
(c) Required loads will be transferred to the emergency power
source when the voltage reaches 85-95 percent of the final .
(nominal) value, i.e., the generator circuit breaker closes. Th1s
will happen immediately for a battery source.
122
equipment and cables in hazardous locations, such as cargo pump rooms and areas
adjacent to cargo tanks, for defective explosionproof lights and fixtures,
improperly installed wiring, non-approved lighting and fixtures and dead-ended
wiring, and testing the insulation resistance of the circuits. Except in
cases where a proper record of testing is maintained, consideration should be
given to accepting recent readings by the crew. If any of the readings are
marginal, or if the condition of the cables, fixtures, or equipment appears
defective in any way, verification measurements may be required. These
measurements should not be attempted until the ship is in a gas-free or
inerted condition and should be carried out within an acceptable time period.
123
APPENDIX 11
(2) Exp1osionproof; or
d. Belt drives must use conducting belts, pulleys, and shafts to prevent
the buildup of static electrical charges.
g. Oil tank vents must be fitted with flame screens and must have a
cross sectional area at least as large as the f11l lines.
124
Most oil recovery vessels are designed for use with Grades D and E
liquids. If use ,dtlJ more flammable grades or with hazardous chemicals 1s
d~s!red, Commandant (G-}ITH) should be consulted. Vessels engaged in other
service when not operating as oil recovery vessels must meet normal
requirementf for that service.
b. Wiring. Only the electrical wiring that will be energized during any
part of the voyage shall be subject to inspection. Any unsafe or
unsatisfactory condition detected shall be made a matter of record
and the owner of the vessel so advised in writing by the OCMI.
125
(2) Temporary Installations. For temporary installations, equipment
approved by an independent laboratory acceptable to the coastal
state may be permitted by the OCM! in whose zone the vessel is
operating. Where the coastal state has no certification
requirements, equipment must be listed by one of the North
American "nationally recognized testing laboratories", by one of
the agencies listed at the end of this section, or by another
agency acceptable to Commandant (G-MTH-2). In no case should
equipment required by 46 CFR 111.105 to be listed, i.e.,
explosionproof equipment or intrinsically safe
systems, be permitted based on manufacturer or classification
society certification. Upon return to U.S. waters and prior to
engaging in OCS activities, MODU's must utilize equipment listed
by one of the North American laboratories. Listed below are
independent laboratories that are acceptable, provided they are
recognized by the coastal state. This list is-not intended to
be all-inclusive; other laboratories acceptable to the coastal
state may be acceptable.
Ex d IIA T2
126
"Ex" is the IEC symbol meaning protected for use in
flammable atmospheres. It is followed by a small letter
indicating the type of protection as follows:
d Flameproof (explosionproof)
e Increased Safety
ia Intrinsically Safe for Zone 0
ib Intrinsically Safe for Zone 1
0 Oil-immersion
p Pressurization
q Sand Filling
s Special Protection
Tl 450 degrees C.
T2 300 degrees c.
13 200 degrees C.
T4 135 degrees C.
T5 100 degrees C.
T6 85 degrees C.
127
APPENDIX 12
1. Introduction
128
c. Handling of "Existing" Vessels. The regulations do not include
requirements for vessels existing before the effective date of the
regulation. Persons mbst refer to the regulations in effect for older
existing vessels in order to determine electrical construction'
requirements for those vessels.
This NVIC may oe used as a guide by the plan reviewer, and should not be
considered as containing hard-and-fast requirements. The user's
discretion should be applied during its application.
b. Subsequent reV1Slons may be acted upon directly by the OeMI, or they may
be forwarded to the Mse for action. ~en major changes or reV1Slons are made
on these plans. they should be forwarded to the Mse for review.
129
APPE1mIX 13
a amperes
AC alternating current
A1 aluminum
alt alteration
amb ambient
AVC asbeatos-varnished, cambric-insulated cable
AWe American Wire Gage
bhd bulkhead-mounted
aiM bill of material
C degrees Centigrade
chg change
Class I, Class II, etc. (see NEe 500)
cond conductor
corr corrosive
CSA Canadian Standards Association
Cu copper
130
Cu in cubic inches
cy cycles
DC direct current
DIG diesel generator
dp double pole
dp dr1pproof
dpdt double pole, double throw
dpst double pole, single throw
d"'g drawing
EP explosionproof
F degrees Fahrenheit
fig figure
FM Factory Mutual
gnd ground
Group A, Group B, etc. (see NEe 500)
haz hazardous
HP horsepower
IC interrupting capacity
incand incandescent
incl inclusive
inst ins tantaneous
IS intrinsically safe
KVA kilo volt amperes
KW kilowatt
L.C. L. light center length
LVP low voltage protection
LVR low voltage release
m.a.x • maximum
M. r. mineral insulated, metal sheathed
min minimum
mod model
mtg mounting
NEC National Electrical Code
nwt non-watertight
p pole
ped pedelital
pend pendant
PF power factor
ph phase
port portable
psi pounds per square inch
pt point
PYRO pyrometer
R rubber-insulated cable
refl reflector
rev revision
SCR semiconductor controlled rectifier
Bp single pole
spdt single pole, double throw
S.P. Phone sound-powered phone
SS ship service
SWBD BWitchboard
sym symbol
131
, ,
132