The document is an instruction manual for the HANYOUNG HX series Digital Temperature Controller, detailing safety information, operational guidelines, and technical specifications. It emphasizes the importance of following safety protocols to prevent electric shock and equipment failure, and outlines the various control output options available. Additionally, it provides instructions for installation, maintenance, and troubleshooting to ensure proper and safe usage of the device.

Uploaded by

pakistaninfo0
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
148 views

HX_Manual

The document is an instruction manual for the HANYOUNG HX series Digital Temperature Controller, detailing safety information, operational guidelines, and technical specifications. It emphasizes the importance of following safety protocols to prevent electric shock and equipment failure, and outlines the various control output options available. Additionally, it provides instructions for installation, maintenance, and troubleshooting to ensure proper and safe usage of the device.

Uploaded by

pakistaninfo0
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 8

MA0614E160901

Digital Temperature Controller

HX series
INSTRUCTION MANUAL HEAD OFFICE
Thank you for purchasing HANYOUNG product. HANYOUNGNUX CO.,LTD
Please check whether the product is exactly the same as you ordered. 1381-3, Juan-Dong, Nam-Gu Incheon, Korea,
Before using the product, please read this instruction manual carefully. TEL:(82-32)876-4697 FAX:(82-32)876-4696 http://www.hynux.com
Please keep this manual where you can view at any time.

Safety information Suffix code


Alerts declared in the manual are classified to Danger, Warning and Caution by their criticality. Model Code Description
DANGER indicates an imminently hazardous situation which, HX ☐- ☐ ☐ Multi-input and output digital temperature controller
DANGER if not avoided, will result in death or serious injury. 2 48(W) × 96(H) ㎜
WARNING indicates a potentially hazardous situation which, 3 96(W) × 48(H) ㎜
WARNING if not avoided, could result in death or serious injury.
Dimension 4 48(W) × 48(H) ㎜ P.I.D Auto-tuning
CAUTION indicates a potentially hazardous situation which,
CAUTION 7 72(W) × 72(H) ㎜
if not avoided, may result in minor or moderate injury.
9 96(W) × 96(H) ㎜
0 Standard
Danger Control output
1 Heating / Cooling (simultaneous control)
Do not touch or connect any undesirable conductive part to input-output terminal,
0 None
since there is a possibility of electric shock. HX2/3/9 option
1 RS485 communication + Heater break alarm (H.B.A)
0 None
Warning HX7 option 1 RS485 communication + D.I 2 contacts (SV2, SV3)
•Please install an appropriate protective circuit on the outside. Malfunction or an incorrect operation may be 2 RS485 communication + Heater break alarm (H.B.A)
a cause of leading to a serious accident.
•Since this product does not have the power switch or a fuse, please install those separately on the outside. (Fuse rating : 250 V 0.5 A) 0 None
•To prevent damage or failure of this product, please supply the rated power voltage. HX4 option 1 RS485 communication + D.I 1 contact (SV2)
•To prevent electric shock or equipment failure, please do not turn on the power until completing wiring.
•Since this is not explosion-proof structure, please do not use in a place where combustible or explosive gas is around. 2 RS485 communication + Heater break alarm (H.B.A)
•Never disassemble, modify or repair the product. There is a possibility of malfunction, electric shock or a risk of fire.
•Please turn off the power when mounting/dismounting of the product.This is a cause of electric shock, malfunction, or failure.
•If the product is used with methods other than specified by the manufacturer, it may lead to injury or property damage. Part name and function
•Since there is a possibility of electric shock, please use the product as mounted on a panel while the power is being supplied.
•If it is used with systems, machines and equipment that could lead to a risk of life or property damage, please
implement safety devices and protections for both lives and the applications and plan for preventing accidents.

CAUTION
•The contents of the instruction manual are subjective to change without prior notice.
•Please make sure that the specification is the same as exactly you have ordered. ⑦ ②
•Please make sure that the product is not damaged during shipping.
•Please use this product in a place where the ambient operating temperature is 0 ~ 50 ℃ (40 ℃ max, closely installed)
and the ambient operating humidity is 35 ~ 85 % R.H (without condensation).
•Please use this product in a place where corrosive gas (such as harmful gas, ammonia, etc.)
and flammable gas do not exist. ※ HX9 is
•Please use this product in a place where there is no direct vibration and a large physical impact to the product. chosen to explain
•Please use this product in a place where there is no water, oil, chemicals, steam, dust, salt, iron or
hazardous substances (Contamination class 1 or 2).
•Please do not wipe this product with organic solvents such as alcohol,
⑥ ⑤ ④ ③
benzene or others. (Please use mild detergent instead) Number Name Description
•Please avoid places where excessive amount of inductive interference and electrostatic or magnetic noise occurs.
•Please avoid places where heat accumulation occurs due to direct sunlight or radiant heat. ① Process value (PV) Displays the process value in the operation mode.
•Please use this product in a place where the elevation is below 2,000 m.
•Please make sure to inspect the product if exposed to water, since there is a possibility of electric leakage or a risk of fire.
② Set value (SV) Displays the set value in the operation mode
•For thermocouple (TC) input, please use a prescribed compensation lead wire. (There will be a temperature error if a general lead is used.) Increases the set value or used to move between groups and
•For resistance temperature detector (RTD) input, please use a small resistance of lead wire and the 3 lead wires should ③ Up key
to change an option in a parameter in setting mode
have the same resistance. (There will be a temperature error if the 3 lead wires do not have the same resistance.)
•Please keep the input signal wire away from the power lines and load lines to avoid the effect of inductive noise. Down Decreases the set value or used to move between groups and

•The input signal wires and output signal wires should be separated from each other. key to change an option in a parameter in setting mode
If it is not possible, please use shielded wires for the input signal wires. ⑤ Shift key Used to move the position of the digit
•For thermocouple (TC), please use ungrounded sensors. (There is a possibility of
malfunction of the product by electric leakage, if a grounded sensor is used.) Sets (confirm) the set value, displays the output amount, or set an
Set key option
•If there is a lot of noise from the power line, installing an insulated transformer or a noise filter in a parameter in setting mode and moves between the
⑥ parameters in a group. By pressing for 3 seconds, it enters the
is recommended. The noise filter should be grounded on the panel and the wire between
the output of the noise filter and the power of the instrument should be as short as possible. display setting mode (setting mode) or returns to the operation mode
•It is effective against noise, if the power lines of the product are made twisted pair wiring. Lights when SV2 is displayed.
•Please make sure the operation of the product before using, since the product may not
operate as it intends to if the alarm function is not properly set. Lights when SV3 is displayed.
•While replacing the sensor, please turn off the power.
•In case of the high frequent operation, such as proportional operation, please use an auxiliary OUT1 indicator.
relay since the life span of the output relay will be shortened if it connects to the load without Operation
⑦ OUT2 indicator.
the rated margin. In this case, SSR output is recommended. Indicator
*For Electromagnetic switch : set cycle time : minimum 20 sec. Auto-tuning indicator (blink).
*For SSR : set cycle time : minimum 1 sec.
•Please do not connect anything to the unused terminals.
Alarm 1 operation indicator.
•Please connect wires properly after making sure the polarity of the terminals. Alarm 2 operation indicator.
•Please use a switch or breaker (IEC60947-1 or IEC60947-3 approved)
when the product is mounted on a panel. Hot
Hot key is designated for AT or Manual MV
•Please install a switch or break near the operator to facilitate its operation. ⑧ + key(run/
configuable in the group of "G.CtL"
•If a switch or breaker is installed, please put a name plate that the power is off when the switch or breaker is activated. stop)
•In order to use this product properly and safely, we recommend periodic maintenance.
Quick
•Some parts of this product have limited expected life span and aged deterioration. ⑨ + Sets the value: SV1, SV2, AL1, AL2
•The warranty of this product (including accessories) is menu
1 year only when it is used for the purpose it was intended to under normal condition.
•When the power is being supplied there should be a preparation time for the contact output. Please
use a delay relay together when it is used as a signal on the outside of interlock circuit or others.
•When the user replaces with a spare unit due to product failure or other reason,
█ External Contact Input (D.I) Selection
please check the compatibility since the operation can be varied by 3 predetermined set values (temperature values) could be changed with using
the difference of setting parameters even though the model name and code are the same. ON/OFF of the external 2 contact inputs
•Before using a temperature controller, there could be a temperature difference between OFF (contact input is not used) ON (contact input is used)
PV of the temperature controller and the actual temperature, so please operate the temperature External input
controller after correcting the temperature difference appropriately. contact External contact input SV2 SV3
selection Set value 1 display (SV1) OFF OFF
No display
Set value 2 display (SV2) ON OFF
( )
Set value 3 display (SV3) OFF ON
-1-
█ Control Output Composition
HX series is a multi-control-output temperature controller. It can have relay ON/OFF,
SSR voltage pulse output, 4 – 20 mA current output as a control output by selecting an option in the parameter.
If the option is chosen like below in the output parameter ( ) of the output group ( ) in standard temperature controller
0 : Relay ON/OFF control is as a control output.
1 : SSR output is as a control output. (2) Heating / Cooling Type ( simultaneous control)
2 : 4 – 20 mA d.c current output is as a control output.
3 : Relay PID control is as a control output. Output OUT1(Heating) OUT2
Type Default
code Relay SSR/SCR/RET Relay(AL2) SSR/SCR/RET
4 SSR
(1) Standard type
5 SCR(4 - 20 mA)
Output OUT1(Heating) OUT2 SSR
Type Default Control RET AL2
code Relay SSR/SCR/RET Relay SSR/SCR/RET 6 (retransmission
output (PID) output) (Alarm 2
Control output
0 -
(ON/OFF) 7 SSR output )
AL2 RET Heating /
Standard 1 SSR 8 SCR(4 - 20 mA) SCR
- (Alarm 2 (retransmission 1 Cooling 4
Type 2 SCR(4 - 20 mA) type
Control RET (4 - 20 mA)
output) output) 9 (retransmission
Control output output (PID) output)
3 -
(PID)
10 SSR RET
※ In standard type, retransmission is not selected to OUT1(Heating). Control output
11 SCR(4 - 20 mA) (Retransmission
Control (PID)
12 output)
output (PID)
Setting Mode

1) Operation
mode

PV
Process value
SV
1 2 3
Set value
DISP 3
DISP 2
PV
DISP 1
Process value
SV
Output amount for 3 seconds
 ® 3 4 5 6 7 8 9 
Control group Setting value group Auto-tuning group PID group HBA group Alarm group RET. group COM. group Output group Input group
for 3 seconds
+
HOTKEY
for
3 seconds
for 3 seconds
+
Level Ramp
function
for 3 seconds type A
+

Quick menu

Ramp
function
type B

Input code for input type and range


Input signal Input signal Input type Range (℃) Accuracy Note
1 K *1 -200 ~ 1370
2 K *1 -199.9 ~ 999.9
3 J *1 -100.0 ~ 999.9
4 E *1 -100.0 ~ 999.9 •F.S is the measurable range
from the maximum to the minimum
5 T *1 -199.9 ~ 400.0 ±0.5 % of FS ±1 Digit for each range.
6 R 0 ~ 1700
Thermocouple • Digit is the minimum display value
7 B *2 0 ~ 1800
(TC)
8 S 0 ~ 1700 ❇1 below 0 ℃ :
9 L *1 -100.0 ~ 900.0 ±1.0 % of F.S ± 1 digit
10 N -200 ~ 1300 ±1.0 % of FS ±1 Digit
❇2 0 ~ 400℃ range :
11 U *1 -199.9 ~ 400.0 ±10 % of F.S ± 1 digit
12 W 0 ~ 2300 ±0.5 % of FS ±1 Digit
❇3 20 → KPt100 Ω (C1603)
13 Platinel II 0 ~ 1390
21, 22 → Pt100 Ω(IEC751)
Resistance 20 KPt100 Ω *3 -199.9 ~ 500.0
temperature *4 In case of using Current input,
21 Pt100 Ω *3 -199.9 ~ 640.0 ±0.5 % of FS ±1 Digit
detector Resistor 250 Ω 0.1 % should be
(RTD) 22 Pt100 Ω *3 -200 ~ 640 installed in the input terminal.
DC voltage 30 1.000 - 5.000 V d.c.
(VDC / ㎷ DC) -1999 ~ 9999
31 0.0 - 100.0 ㎷ d.c. ±0.5 % of FS ±1 Digit
Scaling function(SL-H/SL-L) necessary
DC current 30 4 - 20 ㎃ d.c. *4
-2-
Operation Method  Set value (SV) setting group
█ When turn the power on after completing wiring Symbol Parameter Option Available Default
(1) After the firmware version of the temperature controller appears for a short period of time, the operation condition
mode is running like the number ① that process value (current temperature) Set value setting group Options for set values - -
and the set value are displayed.
Set value Number 1~3 (the chosen set value is
(2) In the number ①, if button is pressed for 3 seconds, it enters 1
display setting mode. setting displayed and controlled)
It can be selected as DISP 1, DISP 2 and DISP 3 to limit displaying setting groups Always
Set value 1 (SV1) setting EU (0 ~ 100 %) EU(0 %)
(3) In the operation mode, if button is pressed, the output amount is displayed like the picture ⑤ - ⑥ below. on
Set value 2 (SV2) setting EU (0 ~ 100 %) EU(0 %)

● Switching between modes Set value 3 (SV3) setting EU (0 ~ 100 %) EU(0 %)

POWER ON  Auto-tuning (AT) group


Output amount ①
display
Symbol Parameter Option Available Default
condition
⑥ Standard type
Auto-tuning group Options for auto-tuning (AT) group - -

Auto-tuning type Standard (STD) :


Control STD
setting Low PV (LOW) : output:
Auto-tuning start PID
for 3 seconds OFF / 1 ~ 3 / (AUTO) OFF
② setting
⑤Heating-
Cooling type  P.I.D group
Symbol Parameter Option Available
condition Default
PID group Options for PID mode - -
③ ④
for 3
seconds ANTI RESET PID
Auto / 50.0 ~ 200.0 % 100 %
WIND-UP setting control

PID group setting 0/1~3 Always on 0


Selecting one
for 3 n. Proportional band (P) 0.1(H/C TYPE : 0.0) ~ 999.9 % 5.0 %
seconds of PID groups
How to set access levels [Level (LEVL)] and a group display [Display (dISP)] n. Integral time (I) OFF / 1 ~ 6000 s Always on 240 s
- Setting group is displayed as shown in the configuration parameters according to the
setting group is displayed [Display (dISP)]. n. Derivative time (D) OFF / 1 ~ 6000 s Always on 60 s
- Setting group is editable depending on setting Access Level [Level (LEVL)]. Integral time:
n. Manual reset -5.0 ~ 105.0 % 50.0 %
OFF
Access level [Level (LEVL)] n. Proportional band (PC)
LEVL 3 : parameter values can be changed for all setting groups with the key of controller in front. 0.0(ON/OFF) / 0.1 ~ 999.9 % 5.0 %
for cooling
LEVL 2 : parameter values can not be changed for output group and input group with
n. Integral time (IC) for
the key of controller in front. OFF / 1 ~ 6000 s 240 s
cooling heating·
LEVL 1 : parameter values can not be changed for Auto-tuning group(G.At), PID cooling
group(G.PId), Alarm Group (G.ALM), retransmission group(G.trn), communication n. Derivative time (DC) for
OFF / 1 ~ 6000 s 60 s
group(G.CoM), output group(G.oUt), input group (G.In) with the key of controller in front. cooling
n. hysteresis (dead band) -100.0 ~ 50.0 % 3.0 %
Caution EU(0) < 1.RP < 2.RP < PID group 1 EU
In the operation mode, if and button are pressed simultaneously for 3 seconds, n. Zone position setting or
EU(100 %) PID group 2 (100 %)
it enters setting mode which prevents an operator to change parameter setting as
limiting access to the group. The default is 3rd level. The level setting mode limits the
 Heater Break Alarm (HBA) group
Available
display setting mode. Symbol Parameter Option condition Default

Heater break alarm group Options for HBA mode. - -


 Control group Current setting of HBA output OFF / 1 ~ 50 A HBA OFF
Available Option
Symbol Parameter Option condition Default Hysteresis setting of HBA
0 ~ 50
(Refer to EUS
output “model (0.5 %)
Control group Options for control mode - - name and
Current measurement value of Only indicates current measurement code”
Control HBA output value (0 ~ 50 A) table)
Zone setting OFF / ON OFF
output: PID
Ramp function type A/B Always on A  Alarm group
Available
Ramp rising temperature OFF/ EUS (0 ~ 100%) OFF Symbol Parameter Option condition Default
Ramp
Ramp falling temperature OFF/ EUS (0 ~ 100%) function OFF Alarm group Options for alarm mode - -
type A
Ramp time unit HOUR / MIN HOUR Alarm 1 type setting OFF / 1 ~ 21 1
Ramp rising temperature OFF/ EUS (0 ~ 100%) OFF Alarm 2 type setting Refer to “Alarm type and code” 2
Ramp rising time 0.01 ~ 99.59(hh.mm) Ramp 0.01 Hysteresis (dead band)
function
of alarm 1 EUS
EUS(0 ~ 100 %)
Ramp falling temperature OFF/ EUS (0 ~ 100%) type B OFF Hysteresis (dead band) (0.5 %)
of alarm 2 Always on
Ramp falling time 0.01 ~ 99.59(hh.mm) 0.01 Absolute alarm : EU
Set value of alarm 1 (100 %)
EU(-100 ~ 100 %)
External contact input OFF / ON OFF
Deviation alarm : EU
Set value of alarm 2
Hot key setting AT / A-M AT EUS(-100 ~ 100 %) (0 %)
Always on
Auto/manual setting AUTO / MAN (1) AUTO
 Retransmission (RET) group
Control mode TRAD / 2DOF TRAD Available
Symbol Parameter Option condition 초기값
Control
2DOF
0 ~ 100 % mode: 50 % RET. Group Options for RET. Group. - -
Alpha coefficient
2DOF Retransmission type Process value(PV) / set value
(SV) / output amount (MV) / RET. PV
Factory reset function 0/1 [PASSWORD: 1304] (2) Always on 0 or power for sensor power for sensor (SPS) option
(1) When manual output function is selected with 'ON', 'AT indicator' lights on at the front panel. Retransmission value 4 - 20 mA / 0 – 20 mA (1) - 4 - 20 mA
(When auto-tuning (AT) is running, 'AT indicator' flashes at the front panel) High limit of TC / RTD: FR-H ~ FR-L
retransmission EU(100 %)
(2) If you select "1" in factory reset function, PASSWORD is displayed. If you input the DC voltage: SL-H ~ SL-L PV / SV
PASSWORD [1304], controller power turns on and off for initializing parameter value. Low limit of EU(0 %)
retransmission ( Must be RET.H > RET.L )
(1) If you want retransmission 0-5V, a 250 Ω 0.1% resistor must be connected to retransmission output terminal.
If you want retransmission 0-10V, a 500 Ω 0.1% resistor must be connected to retransmission output terminal.
-3-
 Communication group Alarm type and code
Available Pay atteontion in selecting relay type. Using inverse relay ( such as use nomally closed
Symbol Parameter Option condition Default
instead of nomally open) will not output anything even though the indicator is on.
Communication Options for
- -
group communication mode.
PC.LINK (code : 0) Hysteresis
(△ : set value, -▲ : alarm set value, ▲ : alarm set value)
RS485/RS422 PC.LINK SUM (code : 1)
0
Protocol MODBUS-ASCII (code : 2)
MODBUS-RTU (code : 3) Code Alarm type Operation
2400(code : 2), 4800(code : 3), 1 High absolute value (NO)
Communication
9600(code : 4), 14400(code : 5), 4 2 Low absolute value (NO)
speed (BPS)
19200(code : 6)
3 High deviation value (NO)
NONE(code : 0),
Parity Bit 1 4 Low deviation value (NO)
EVEN(code : 1), ODD(code : 2) Option
Stop Bit 1bit (code : 1), 2bit (code : 2) 1 5 High deviation value (NC)
7bit (code : 7), 8bit (code : 8) 6 Low deviation value (NC)
Data length 8
(code 8 is not available for PC LINK) 7 High-Low deviation value
Address 1 ~ 99 but, max 31 units 1 8 High-Low deviation range
0 ~ 10. Response time = 9 High absolute value (NC)
Response time processing time + 0
10 Low absolute value (NC)
(response time X 25 ms)
11 High absolute (NO, Hold)
※ Please note that frequent communicational data recording may exceed life of EEPROM
and cause malfunction. 12 Low absolute (NO, Hold)
13 High deviation (NO, Hold)
 Output group 14 Low deviation (NO, Hold)
Please make sure to choose “input code” in “input code setting” of the input 15 High deviation (NC, Hold)
group first and then select “output code” in “output type setting” and other
16 Low deviation (NC, Hold)
Caution options in other groups. If “input code” is set later, the options in the other
groups will be lost. 17 High-Low deviation value (Hold)
Available 18 High-Low deviation range (Hold)
Symbol Parameter Option Default
condition
19 High absolute value (NC, Hold)
Options for output type and
Output group - - 20 Low absolute value (NC, Hold)
mode
Refer to “control output Std : 1 * 21 Heater break alarm 1 (HBA1)
Output type setting Always on HC : 4
composition”
Output operation REV: reverse, DIR: direct Output code REV Function
Cycle time 1 ~ 1000 s 0~3  Function Description
relay : 20s
Output code SSR : 2 s Function 1 : Auto-tuning
Cycle time for cooling 1 ~ 1000 s
4~12 Auto-tuning is a function that the controller automatically measures the characteristics of
ON/OFF the target system and calculates the optimal values for proportional band (P), integral time
Standard : EUS(0 ~ 100 %) EUS(0.5 %) (I), and derivative time (D) and then set the optimal value for each PID parameters.
control
Hysteresis During auto-tuning, the control output is changed to ON/OFF control to get response from
Heating / Cooling: Heating /
0.5% the target system. From the response, the most appropriate PID values are obtained for
0.0 ~ 10.0 % Cooling
the system. This is called " Limit Cycle".
ON/OFF
Hysteresis type Cntr / EdGE Cntr HX series has two types of auto-tuning : standard type and low PV type.
Control
① Standard auto-tuning : This auto-tuning is based on the set value (SV).
Output amount of Standard : -5.0 ~ 105.0 % ② Low PV auto-tuning : This auto-tuning is based on the value 10 % lower than the set
Always on 0.0 %
OUT1 when input break Heating - Cooling : 0.0~105.0 % value (SV).
Select auto-tuning type(At.M) with standard(Std)
Output amount of Heating / a) Standard auto-tuning
0.0 ~ 105.0 % 0.0 % in auto-tuning group(G.At)
OUT2 when input break Cooling
AT start Auto-tuning running AT end
High limit of output Standard : OL-L + 1Digit~ 105.0 % ℃
100.0 %
amount Heating - Cooling : 0.0 ~ 105.0 % PID
Set value (SV)
Standard : -0.5 % ~ OL-H-1Digit control 0.0 %
Low limit of output
amount Heating - Cooling : 0.0 ~ 105.0 % 100.0 % Process value (PV)
* Std : Standard, HC : Heating / Cooling Time(t)
Control output ON OFF ON OFF ON Time(t)
 Input group ON/OFF operation Control starts with PID values
Available obtained from the auto-tuning
Symbol Parameter Option Default
condition
b) Low PV auto-tuning Select auto-tuning type with PV(LoW) in auto-tuning group (G.At)
Options for input type and input
Input group - - AT start
mode ℃ Auto-tuning running AT end
Input signal and measurable
Input code setting Always on Code : 1 Set value(SV)
range code
SV-10 %
Temperature unit setting ℃ / ℉ TC or RTD ℃
High limit setting Within range (refer to “input 1370 Process value (PV)
code for input type and Always on
Low limit setting -200 Time (t)
range”) , FR-H > FR-L
Fixed for T.C or RTD / DC Control output ON OFF ON OFF ON
Decimal point position Time (t)
voltage: 0~3 setting for 1 Control starts with
(voltage input) operation P.I.D values obtained
decimal point position
Voltage input from the auto-tuning
High limit of scale (voltage
-1999 ~ 9999 but, SL-H > (mV,V) 100.0 Meaning of auto-tuning (AT) start in auto-tuning Group(G.At) is as follows:
input)
SL-L decimal point according to 1 is auto-tuning for SV1.
Low limit of scale (voltage DP-P 2 is auto-tuning for SV2.
0.0
input) 3 is auto-tuning for SV3.
Process value filter OFF / 1 ~ 120 sec OFF - AUTO proceed with the Auto-tuning in the order of the SV1, SV2, SV3.
Process value bias If you want to use the auto-tuning, there are 2 ways:
EUS(-100 ~ 100 %) Always on EUS(0 %) 1. When you select the number for set value(SV) you want in start auto-tuning(AT)
(compensation)
of auto-tuning Group(G.At), auto-tuning will start.
Operation after input 2. After selecting auto-tuning(At) in hot-key(Hk.SL) of control group(G.At), auto-tuning will start with
OFF / UP / DOWN UP
break (burn-out) pressing hot-key(SET + UP) in the operation mode of controller for 3 seconds and auto-tuning
will stop with pressing hot-key(SET+UP) for 3 seconds.
Note: When auto-tuning(AT) runs, 'AT indicator' flashes at the front panel.
(When manual output is 'ON', 'AT indicator' lights on at the front panel.)
-4-
Function 2 : PID auto-tuning in Zone Function 6 : Output limit
Within the input range, 3 different PID groups can be applied to each of the 3 zones. Since some This function is used to set the high limit and low limit as the operating range of the control output.
systems have a wide range of temperature to control and the optimal P.I.D values are different for The output limit (the high limit and low limit) can be set -5 ~ 105 % of the output amount.
their temperature ranges, this function can be used to apply different optimal PID values to their
temperature ranges.
Output signal
When select ON in Zone of control group(G.CtL) and set the location of temperature in n.rP
of PID group(G.PID), that distinguishes Zone 1, Zone 2, Zone 3. 20 ㎃

12 ㎃
Max of input range
Zone 3 (PID 3) 4㎃
2.rP
Zone 2 (PID 2) Output limit (%)
-5 % 50 % 105 %
1.rP
Zone 1 (PID 1) Low limit Setting range High limit
Min of input range (OL-L) (OL-H)
Time (t)
Function 7 : Heater break alarm
Function 3 : 2 degrees of freedom PID ① This function detects heater break and immediately turns the alarm on.
In order to get better response against disturbance in the steady state, there is usually ② Please use the current transformer (CT) designed by Hanyoung NUX.
a large overshoot in the transient state. To reduce this overshoot in the transient state, 2 ③ The electric current value and alarm operating point (hysteresis) are set in “HBA group”.
degrees of freedom PID control is used while obtaining good disturbance response in ④ This function cannot be used if phase control method (SCR output) is used by thyristor.
the steady state. The parameter “ALPA” is used to control the amount of overshoot.
Note: If you want to use HBA, please set parameter in HBA group(G.HbA) referring to alarm type and codes.
℃ ALPA : 0 %

SV
Function 8 : Heating / Cooling control
In Heating / Cooling control, it divides the PID computation result into two control signals and outputs
ALPA :
to heating and cooling output terminal. The control method for each heating and cooling can be
100 %
selected either PID control or ON/OFF control. Also, it is possible to choose one of the control outputs:
Time relay output, SSR, and current output as the heating output and cooling output.
Transition Normal
state If both heating and cooling are controlled by ON/OFF control,
Step response Disturbance the dead band (hysteresis) is shown as below.
response
Select 2-DOF in control mode(Ctr.M) of control group(G.CtL)
If ALPA = 0%, it's same with previous PID control. HYSTERESIS HYSTERESIS
If ALPA = 100%, it may takes long to reach normal state.
ON ON
Function 4 : Ramp function Heating-side output Cooling-side output
OFF
Ramp function Type: A
Select A in Ramp function type(rMP.t) of control group(G.CtL)
Ramp function is a gradient of the set value to reach setting value(SV). DEAD BAND
Setting method is as shown below,
1. Set ramp rising temperature value or falling temperature value
<ON/OFF control for heating/cooling>
2. Set ramp time unit and (Hour/Min.)
The dead band of PID control for Heating / Cooling is shown as below.
Ramp function Type: B
Select B in Ramp function type(rMP.t) of control group(G.CtL) Output (%)
This is similar function with Ramp function type A. except that type B sets time in detail, 100 % 100 %
0.01~99.59(hh.mm).
Output of heating Output of cooling
0
℃ 0% 0%
100
DEAD BAND
80
60 <PID control for Heating / Cooling: Dead band of “+” set value>
40 Also, the dead band of “-” set value and the dead band of PID control for both heating and
Current temperature 20 ℃ cooling are shown as below. At this time, there is an overlapped output from the both.
Time Output (%)
1 2 3 4
100 % 100 %

Output of heating Output of cooling


Function 5 : External contact input
0% 0 0%
This function is used to select one of the set values (SV1, SV2, SV3) by the external contact input
signal and it is used as the step control.
External contact input should be "ON" to use this function. DEAD BAND

℃ <PID control for Heating / Cooling: Dead band of “-” set value>
SV3 150 ℃

SV2 100 ℃
Function 9 : Output during emergency
SV1 50 ℃
When there is A/D Error or input break (Burn-out), it stops the PID control and outputs the preset
Time value. ( parameter in output group)
External contact External contact
signal SV2 : ON signal SV3 : ON Function 10 : Alarm hold function
If alarm hold function is not set up, low alarm is active when temperature is rising with power on.
If you select alarm hold function, there is no limit alarm ON during the temperature rise, until set-point.

Note : If you want to use the alarm hold function, please set proper parameter referring to alarm group(G.ALM).

-5-
Function 11 : Hysteresis type Function 13 : Factory reset function
According to selection of Hysteresis type in ON/OFF control, ON/OFF turning point is as follows: This function is used for parameter values to revert to initial setting values.
ex) HYS.t: Cntr(center) 1 . Select factory reset function (PArA) in control group (G.CtL).
- Hysteresis type sets center, 2 . If “1” is selected, input for password will be prompt.
• In heating control, OFF point is SV + HYS/2 and ON point is SV - HYS/2. 3 . Entering correct password [1304] will reset parameter values to initial setting values and controller
• In cooling control, OFF point is SV - HYS/2 and ON point is SV + HYS/2. will be restarted (power OFF and ON).
4. In case of input wrong password for 3 times, display will go back to operation screen.
Temperature (℃)
105
Function 14 : Quick menu setting
SV : 100 HYS : 10 ℃
95 This function is for selecting frequently used parameters quickly and easily.
1 . Press SET+DOWN key for 3 sec. it will go to the quick menu setting.
2 . SV1, SV2, AL-1, AL-2 values can be set from quick set menu.
3 . Press SET key for 3 sec. to go back to operation screen.
Time
100 %
Function 15 : HOT key
Output signal
0% Time This function is for activating/deactivating most frequently used function on operation screen.
1 . Press SET+UP key for 3 sec. to activate hot-key function.
Control direction: rEV(Heating) 2 . Press SET+UP key for 3 sec. again to deactivate hot-key function.

One of the following two functions can be assigned as hot-key function


Temperature (℃) from the hot-key select menu (HKSL) in control group (G.CtL).
1 . AT (Auto-tuning) : ON / OFF
2 . A-M : Automatic control / Manual control
15
SV : 10
5
HYS : 10 ℃ Specification
Time Power supply 100 - 240 V ac (±10 %), 50/60 Hz
100 %
Power consumption 6 W max, 10 VA max
Output signal
Time Type Refer to input type and range
0%
S ampling cycle 62.5 ㎳
Control direction: dlr(cooling)
A c c u r a c y ±0.5 % of FS (Refer to input type and range)
Allowable voltage Within ±20 V dc (VDC), within ±10 V dc (TC, RTD)
Input
Reference
ex) HYS.t: EdGE(edge) junction
±3.5 ℃ (0 ~ 50 ℃)
- Hysteresis type sets with edge, compensation
• In heating control, OFF point is SV and ON point is SV - HYS. accuracy
• In cooling control, OFF point is SV and ON point is SV + HYS. Operation after
T.C: OFF, UP/DOWN RTD: UP
Temperature (℃) input break
NO : 5 A 250 V ac, 5 A 30 V dc (resistive load)
Relay
NC : 3 A 250 V ac, 1 A 30 V dc (resistive load)
SV : 100
Control SSR ON voltage : 12 V dc min, OFF voltage : 0.1 V dc max
HYS : 10 ℃
output (voltage pulse) Load resistance 600 Ω min
90
SCR range : 4 – 20 mA (±5%), accuracy : ±0.2 mA
(current) Load resistance 600 Ω max
Time
range : 4 – 20 mA (±5%), accuracy : ±0.2 mA
100 %
Load resistance 600 Ω max
Output signal Retransmission output
range : 0 – 20 mA (±5%), accuracy : ±0.2 mA
0% Time
Load resistance 600 Ω max
Control direction: rEV(Heating) Alarm output 5 A 250 V a.c, 5 A 30 V d.c (resistive load)
Contact input OFF resistance : 10 ㏀ min, ON resistance : 1 ㏀ max
Method ON/OFF, P.I.D control
Temperature (℃)
Control Output operation Reverse operation, Direct operation
20 Anti-reset windup Auto(A=0), 0.1 ~ 100.0 %
HYS : 10 ℃
Standard EIA RS485
SV : 10
Max connection
31 units (but, ADDRESS setting : 1 ~ 99)
unit
Time
100 % Communication
2 wire half duplex
method
Output signal
Time Data
0% asynchronous
transmission
Control direction: dlr(cooling) Communication
None
sequence
Communication
Interface Within 1.2 km
distance
Function 12 : Manual output function Communication
2400, 4800, 9600, 14400, 19200 BPS (parameter selectable)
Speed
If you want to use manual output function, there are 2 ways as follows. Start bit 1 BIT
1. Select ON in manual output(MV.Mo) of control group(G.CtL) and current control output amount Data length 7 or 8 BIT
converts manual output value. When choose OFF, manual output converts back to auto-output
control. Parity bit NONE, EVEN, ODD
2. Select manual output function in hot-key(Hk.SL) of control group(G.CtL) and press Stop bit 1 or 2 BIT
hot-key(SET+UP) for 3 seconds at the front panel for manual control output. Protocol PC-LINK, PC-LINK SUM, MODBUS-ASCII, MODBUS-RTU
When press hot-key(SET+UP)again, manual output converts back to auto-output control.
Response time Processing time in receiving + (response time x 25 ㎳)
Note: When auto-tuning(AT) runs, 'AT indicator' flashes at the front panel. Storage Non-volatile memory(EEPROM) writing 1,000,000 times
(When manual output is 'ON', 'AT indicator' lights on at the front panel.) Insulation resistance 20 ㏁ min (primary terminal – secondary terminal)
2,300 V a.c, for 1 minute
Output amount for manual output is adjusted by UP and DOWN key in monitor MV screen. Dielectric strength
(primary terminal – secondary terminal)
Operating ambient
0 ~ 50 ℃, (without condensation)
temperature
Operating ambient
35 ~ 85 % R.H (without condensation)
humidity

-6-
HX communication - instructions about the D register address
D-register Parameter Parameter D-register Parameter Parameter
Parameter meaning Parameter setting Parameter meaning Parameter setting
address name division address name division
0001 NPV Current present value (PV) Read only *1 Process 0334 3.Pc PID group 3 cooling proportional band 0.0 ~ 999.9 % *2 PID Group
0002 NSV Current set value (SV) Read only *1 Process 0335 3.Ic PID group 3 cooling integral time 0 ~ 6000 sec PID Group
0004 SSV Current set value (SV) Read only *1 Process 0336 3.Dc PID group 3 cooling derivative time 0 ~ 6000 sec PID Group
OUT1 control output value of standard type, Total *2 PID group 3 Heating / Cooling dead
0005 MVOUT Read only Process 0337 3.DB -100.0 ~ 50.0 % *2 PID Group
control output value of heating/cooling type. band
OUT1 control output value of standard type, *2 Heater break
0400 HBA Heater break alarm (HBA) current set 0: OFF, 1 ~ 50 A
0006 CH1OUT OUT1 control output value of heating/ Read only Process alarm group
cooling type. Heater break alarm (HBA) Hysteresis Heater break
0401 HDB 0 ~ 50
OUT2 control output value of heating/ (deadband) set. alarm group
0007 CH2OUT Read only *2 Process
cooling type. 0410 A1TY Alarm 1 type setting 0: OFF, 1 ~ 21 Alarm Group
When ZONE is OFF, currentlly 0411 A2TY Alarm 2 type setting 0: OFF, 1 ~ 21 Alarm Group
applied set value (SV) and PID group
0413 A1DB Hysteresis (dead band) of alarm 1 EUS(0 ~ 100 %) Alarm Group
number
0001: SV1, PID group 1 0414 A2DB Hysteresis (dead band) of alarm 2 EUS(0 ~ 100 %) Alarm Group
0002: SV2, PID group 2 0416 AL-1 Set value of alarm 1 PV alarm: EU (-100 ~ 100 %) *1 Alarm Group
0008 PIDNO 0003: SV3, PID group 3 Read only Process 0417 AL-2 Set value of alarm 2 Deviation alarm: EUS (-100 ~ 100 %) Alarm Group
When ZONE is OFF, currentlly
0: Indicated value
applied PID group number
1: Set value (SV) Retransmission
0001: PID group 1 0500 RET Retransmission output type selection
2: Control output value (MV) group
0002: PID group 2
3: Power SPS for the sensor
0003: PID group 3
Retransmission
Current state of Alarm 1 and Alarm 2: 0501 RET.H Retransmission output upper limit setting -1999 ~ 9999
group
0000: Alarm 1 OFF, Alarm 2 OFF
Retransmission
0009 ALMSTS 0001: Alarm 1 ON, Alarm 2 OFF Read only Process 0502 RET.L Retransmission output lower limit setting -1999 ~ 9999
group
0002: Alarm 1 OFF, Alarm 2 ON
Retransmission
0003: Alarm 1 ON, Alarm 2 ON 0503 RET.T Retransmission output form 0: 4 - 20 mA, 1: 0 - 20 mA
group
When the OUT2 control output is SCR 0~12 (refer to the number of
(4-20mA) in Heating / Cooling type, 0600 OUT Output type selection Output group
0013 OUT2_IND Read only Process control output type selection)
it shows the temperature controller
0: Reverse operation (heating),
"OUT2 indicator" status. 0601 o.ACT Output operation selection Output group
1: Direct action (cooling)
Current measurement value of the
0014 H1CM Read only Process 0602 CT Cycle type (Control cycle) 1 ~ 1000 sec Output group
heater break alarm output
0603 CTC Cooling cycle type (cooling control cycle) 1 ~ 1000 sec Output group
Current situation of the AD error.
0016 ADESTS Read only Process General type. ON/OFF control hysteresis Standard type,EUS(0~100%) *1
0001: AD conversion error
Current situation of the input error. 0604 HYS Heating / Cooling type. Heating / Cooling type *2 Output group
0001:Input sensor Burn-out ON/OFF control hysteresis 0 ~ 10.0%
0017 ERRSTS 0002: RJC error Read only Process 0605 PO Output1 setting when input breaks -5.0~105.0% *2 Output group
0004: Input range exceeded 0606 POC Output2 setting when input breaks 0~105.0% *2 Output group
0008: Less than input range
Standard type, *2
Autotuning (AT) current state OL-L +1 digit ~ 105.0 %
0000: AT type 0607 OL-H Output upper limit function Output group
Heating / Cooling type,
0018 AT_STS 9999: AT in progress ("AT indicator" in Read only Process 0.0 ~ 105.0 %
the temperature controller front display
Standard type, *2
blinking)
-0.5 % ~ OL-H-1 digit
Zone function set (For the zone position 0608 OL-L Output lower limit function Output group
0102 ZONE 0: OFF, 1: ON Control Group Heating / Cooling type,
setting, set in RP parameter of each PID group 0.0 ~ 105.0 %
0104 ARW ARW (Anti-reset windup) setting 0: AUTO, 50.0 ~ 200.0 % *2 Control Group 0610 INP Input type selection 1~31 Input group
0106 DI.SL External contact input (DI) function 0: OFF, 1: ON Control Group 0611 UNIT Temperature unit selection 0: ℃, 1: ℉ Input group
0107 ALPHA Alpha factor of 2 DOF PID 0 ~ 100 % Control Group 0612 FR-H Upper range selection EU(0 ~ 100 %) *1 Input group
0108 UP.RT Ramp-up temperature setting 0: OFF / EUS(0~100 %) *1 Control Group 0613 FR-L Lower range selection EU(0 ~ 100 %) *1 Input group
0109 DN.RT Ramp-down temperature setting 0: OFF / EUS(0~100 %) *1 Control Group 0: No decimal points
0110 RTMU Ramp-time unit setting 0: Hour, 1: Min Control Group Decimal point position selection 1: 1 decimal place
0614 DP-P Input group
0111 UPTM Ramp-up time setting 0.01 ~ 99.59 [hh.mm] *2 Control Group during the voltage input) 2: 2 decimal places
3: 3 decimal places
0112 DNTM Ramp-down time setting 0.01 ~ 99.59 [hh.mm] *2 Control Group
Scale upper limit setting
0113 RAMPT Ramp type selection 0: A Type, 1: B Type Control Group 0615 SL-H -1999 ~ 9999 Input group
(during voltage input)
Manual output function (when selecting
0: AUTO , Scale lower limit setting
0120 MVMOD the manual output, the "AT indicator" in the Control Group 0616 SL-L -1999 ~ 9999 Input group
1: MANUAL (during voltage input)
temperature controller front display is steady)
0617 FILT Measurement value filter selection 0: OFF, 1 ~ 120 sec Input group
0121 MANMV Manual output value (Manual MV) set 0 ~ 100 % Control Group
0618 BIAS Measurement value correction setting EUS(-100 ~ 100%) *1 Input group
0: Traditional,
0122 CTRM Control mode selection Control Group 0619 B.OUT Operation selection when input breaks 0: OFF, 1: UP, 2: DOWN Input group
1:2 2 DOF PID (2DOF)
0: Auto-tuning (AT) function 0: CENTER ,
0124 HKSL Hot-key selection Control Group 0624 HYST Hysteresis type Output group
1: Manual output function 1: EDGE
0300 SVNO Set value (SV) number selection 1~3 Set value setting group *1: Please check the presence or absence of the decimal points according to the
0301 SV1 Set value 1 (SV) setting EU(0 ~ 100 %) *1 Set value setting group input type and range settings
0302 SV2 Set value 2 (SV) setting EU(0 ~ 100 %) *1 Set value setting group
0303 SV3 Set value 3 (SV) setting EU(0 ~ 100 %) *1 Set value setting group · Set value with decimal points : if you want to input an SV1 of 100.0℃ through
0: Standard Automatic Operation communication, transmit 03E8(100). (03E8 is the hex value of 1000)
0305 AT MODE Auto-tuning (AT) type selection 1: Low value (PV) type Auto-tuning Group · Set value without decimal points: if you want to input an SV1 of 100.0℃ through
automatic operation
communication, transmit 0064(100). (0064 is the hex value 100)
0306 AT Auto-tuning (AT) 0: OFF, 1 ~ 4 Auto-tuning Group
0310 1.P ID 1 proportional band 0.0 ~ 999.9 % *2 PID Group *2 : Set value with decimal places.
0311 1.I PID group 1 integral time 0 ~ 6000 sec PID Group ※ For the instructions of the protocol regarding the communication please refer to the
0312 1.D PID group 1 derivative time 0 ~ 6000 sec PID Group Hanyoung protocol instruction manual on Hanyoung Nux homepage(www.hynux.com).
0313 1.MR PID group 1 manual reset -5.0 ~ 105.0 % *2 PID Group
0314 1.PC PID group 1 cooling proportional band 0.0 ~ 999.9 % *2 PID Group
0315 1.IC PID group 1 cooling integral time 0 ~ 6000 sec PID Group
0316 1.DC PID group 1 cooling derivative time 0 ~ 6000 sec PID Group
How to dismantle case
0317 1.DB PID group 1 Heating / Cooling dead band -100.0 ~ 50.0 % *2 PID Group ● HX4 ● HX2 ● HX3
0318 1.RP PID group 1 zone position setting EU(0 ~ 100 %), (1.RP < 2.RP) *1 PID Group
0320 2.P PID 2 proportional band 0.0 ~ 999.9 % *2 PID Group
0321 2.I PID group 2 integral time 0 ~ 6000 sec PID Group
0322 2.D PID group 2 derivative time 0 ~ 6000 sec PID Group
0323 2.MR PID group 2 manual reset -5.0 ~ 105.0 % *2 PID Group
0324 2.Pc PID group 2 cooling proportional band 0.0 ~ 999.9 % *2 PID Group
0325 2.Ic PID group 2 cooling integral time 0 ~ 6000 sec PID Group ● HX7 ● HX9
0326 2.Dc PID group 2 cooling derivative time 0 ~ 6000 sec PID Group
0327 2.DB PID group 2 Heating / Cooling dead band -100.0 ~ 50.0 % *2 PID Group
0328 2.RP PID group 2 zone position setting EU(0 ~ 100 %), (1.RP < 2.RP) *1 PID Group
0330 3.P PID 3 proportional band 0.0 ~ 999.9 % *2 PID Group
0331 3.I PID group 3 integral time 0 ~ 6000 sec PID Group
0332 3.D PID group 3 derivative time 0 ~ 6000 sec PID Group
0333 3.MR PID group 3 manual reset -5.0 ~ 105.0 % *2 PID Group

-7-
PV

Appearance, Panel cutout and Connection Diagram


PV

PV SV PV

(Units : ㎜)
SV

SV SV2 SV
SV2
SV2 SV3 OUT1 OUT2 AT AL1 AL2 SV3

HX2
OUT1
OUT2 AT AL1 AL2 OUT1

OUT2 AT AL1 AL2


SET SET
SET
SET
1
OUT1
● Appearance 1 OUT1 13
● Panel
OUT2
SSRAL1
7
cutout 1
OUT1 ● Connection Diagram
19 RTX(+) 10
2
RELAY
SCR AL1

RS485
2 14 RET 8 RELAY 20 11
AL2 2 RTX(-) 3 OUT1
3 OUT1 15 RTX(+) 9 1 13 SSR/SCR
1 OUT1 13 OUT2 7 SSR 3 21 SG 12OUT1 4 RET
1 19 RTX(+) 10 AL1
RELAY
2AL2
SSR AL1 SCR A
4 RET 16 RTX(-) 10 OUT1 14
SCR AL1 4 22 13 5

RS485
PV 2 14 RET 8 RELAY 20 11 OUT1 OUT2 OUT2
AL2 B 2 RTX(-) SSR/SCR SSR/SCR 3 15
5 17 11 OUT1 SSR/SCR
3 OUT1 15 RTX(+) 9 CT TC 5 RET 23 RET 14
SSR/SCR AL2 6 RET
SSR SV2 3 21 SG 12 PV
RS485
6 18 12 4 RET 16
4
SCR A B AL2 6 24 15 7
RET 16 RTX(-) 10
SV PV 4 OUT1 22 OUT2 13 5 RTX(+) 17
B POWER A OUT2
11 SV SSR/SCR SSR/SCR
5 17 11 100 - 240 V~ Current 7 25 16
SSR/SCR 8 SV2
CT TC 50/60 Hz Voltage 5 RET 23 RET 14 SV2 RTD 6 RET RTX(-) 18 SV3
SV2 B RS485
6 18 12 5.5 VA 12 8 26 17 SV2 9 SV
B
CT Current
SV2 SV3 OUT1 OUT2 AT AL1 AL2 6 24 15 Voltage 7 TC SV3 SG 19
POWER
SV3 10
11 A 9 27 18 OUT1
100 - 240 V~ 7 25 16 8B SV2 20 R
Current RTD OUT2 AT AL1 AL2
SET SV3 11
HX4
50/60 Hz Voltage SV2 CT Curre
SET 5.5 VA 12 B POWER 9 21
8 26 Current 17 Volta
CT 100
TC - 240 V~ 50/60 Hz 5.5 VA SET 12
SV3 Voltage A
9 27 18 10 22
B RTD POWER
B
11 23 100 - 240 V~ 50/60 Hz 5.5 VA
HX4
Current
POWER
HX7
Voltage TC
100 - 240 V~ 50/60 Hz 5.5 VA 12 24
PV
B

HX2
POWER
PV

PV SV PV 100 - 240 V~ 50/60 Hz 5.5 VA


SV

HX7
SV2
SV SV2 SV

HX3
SV2 SV3
SV2 SV3 OUT1 OUT2 AT AL1 AL2 SV3
OUT1
OUT2 AT AL1 AL2 OUT1 OUT1

HX2
OUT2 AT AL1 AL2
SET SET OUT2 AT AL1 A

SET
SET
1 13 SET
OUT1
● Appearance ● Panel cutout
2
RELAY AL1
14
● Connection Diagram
3 15 13 14 15 16 17 18 19 20 21 22 23 24
1 13 OUT1
TC
OUT1 SSR/SCR AL2 PV

RTX(+)

RTX(-)

SG
AL1
RELAY 4 RET 16 A B B
PV
2 14
SV 5 RTX(+) 17 CT RTD
3 15 OUT2
SSR/SCR
13 14 15 16 17 18 19 20 21 AL1
22 23 AL224 RS485 SV2
OUT1
SSR/SCR AL2 RET RS485 TC Current
RTX(-) 18

RTX(+)

RTX(-)

SG
SV2 6 SV
Voltage
4 RET 16 SV3
A B B SV3
SV2 SV3 OUT1 OUT2 AT AL1 AL2
OUT1 OUT1 OUT2
OUT1 7 SG 19 OUT1
5 RTX(+) 17 CT RTD SSR/SCR
RELAY SSR/SCR SV2
AL2 AL1 AL2
OUT2 OUT2 AT AL1 RS485 RET RET
SET SSR/SCR
8 SV2 20 Current
SV3 OUT2
RET RS485 18
6 RTX(-)
SV3 CT Voltage
1 2 3 4 5 6 7 8 9 10 11 12
PV

SET 9 21
OUT1 OUT1 OUT2
7 SG 19 SSR/SCR SSR/SCR SV2
PV

A
RELAY
RET
SV

RET PV SET
10 22 SV3
SV

8 SV2 20 POWER
B
SV

SV3 CT
SV2
RTD SV2 SV3 OUT1 OUT2 AT AL1 AL2

100 - 240 V~ 50/60 Hz 5.5 VA


OUT1
OUT2 AT AL1 AL2
11 123 2 3 4 5 6 7 8 9 10 11 12
HX4 9
A
21 SET

12
Current
Voltage TC
24
SET
SET

10 22 B
POWER
● Appearance RTD B
●23PanelPOWER
cutout ● Connection Diagram OUT1 13 OUT2
HX3
11 100 - 240 V~ 50/60 Hz 5.5 VA
100 - 240 V~ 50/60 Hz 5.5 VA 1 7
PV Current SSR AL1
TC
Voltage SCR
HX9
12 24 2 14 RET 8
B
AL2
POWER 3 OUT1 15 RTX(+)
HX3
100 - 240 V~ 50/60
SV Hz 5.5 VA
9
PV PV SSR
SCR SV A

SV
HX9 4 RET 16 RTX(-)
B
10
SV2
OUT1
SV2 SV3 OUT1 OUT2 AT 5 AL1 AL2 17 11
OUT2 AT AL1 AL2
CT TC
SV2
SET
6 18 12
SET PV
PV B
SET PV

PV SV PV POWER
SV

100 - 240 V~ 11
SV2 SV
SV2
SV
Current
50/60 Hz
SV
2
1
SV2 SV3 OUT1 OUT2 AT AL1 AL2 SV3
SV3
Voltage
HX7 12
OUT1

5.5 VA
2 AT AL1 AL2 OUT1

OUT2 AT AL1 AL2


SET SET OUT2 AT AL1 AL2

SET
SET
SET

●Appearance ● Panel cutout 1 OUT1 13


● Connection
OUT2
SSR AL1
7
Diagram 1

HX4
SCR
2 14 RET 8
AL2 2
PV 3 OUT1 15 RTX(+) 9
SSR 3
1 OUT1 13 OUT2 7
SSR AL1 4
SCR 1 A 19 RTX(+) 10
PV RET 16 RTX(-) 10OUT1
SCR AL1 4

RS485
2 14 RET 8 B RELAY 20 11
AL2 5 17 2 11 RTX(-) SSR
3 OUT1 15 RTX(+) 9
CT TC 5
SV2 3 21 SG 12
SSR 6 18 12
SV2
SCR A SV B AL2 6
SV2 SV 4 RET 16 RTX(-) 10
SV3
POWER 4 OUT1 22 OUT2 13
SV3 B 11
5 OUT1 17 11 100 - 240 V~ SSR/SCR
Current SSR/SCR 7
OUT1 CT TC 50/60 Hz 5
Voltage RET 23 RET 14
OUT2 AT AL1 AL2 SV2 5.5 VA 12
6 OUT2 18 AT 12 AL1 AL2 8
B
6 24 15
SET POWER A 9
100 - 240 V~ 11 7 25 16
Current RTD
SETHz
HX48 1
50/60 Voltage SV2
5.5 VA 12 B POWER
OUT1
26 Current 17 100 - 240 V~
CT TC RELAY
PV
SV3 Voltage
PV
9 27 18 2
PV B

HX4
SV

SV2 SV
SV2
SV
POWER 3
SV2 SV3 OUT1 OUT2 AT AL1 AL2 SV3
SV3
OUT1
OUT1 OUT1 100 - 240 V~ 50/60 Hz 5.5 VA SSR/SCR
OUT2 AT AL1 AL2

HX9 4 RET
SET OUT2 AT AL1 AL2

SET
POWE
SET 100 -
5
●Appearance ● Panel cutout ● ConnectionHX7
Diagram OUT2
SSR/SCR
RET RS485
6
1 13
OUT1
AL1
RELAY 7
2 14

PV PV 3 15 8 SV2
1 OUT1
13 SSR/SCR AL2 SV3
OUT1
RELAY AL1 4 RET 16 9
2 14
5 OUT2
RTX(+) 17
3 15 13SSR/SCR
14 15 16 17 18 19 10 21
20 22 23 24
OUT1
SV2
SV2
SV SV SSR/SCR AL2 6 RET RS485 RTX(-) 18 TC
RTX(+)

RTX(-)

SG

RTD
SV3 4 RET 16 11 A B B
SV3
7 SG 19 Current
OUT1
OUT1
5 RTX(+) 17 CT RTD Voltage
OUT2 AL1 AL2 RS485 12
OUT2
OUT2
AT
AT
AL1
AL1
AL2
AL2 SSR/SCR 8 SV2 20 Current
RET RS485 18
6 RTX(-) SV3 CT Voltage
9 OUT1 OUT1 21
OUT2 POWER
7 SG 19 RELAY SSR/SCR SSR/SCR 100 -SV2
240 V~ 50/60 Hz 5.5 VA
SET SET RET A RET
10 22 SV3

HX9
8 SV2 20 B
RTD
SV3 CT 11 1 236
9 21 2 3
Current4 5 7 8 9 1011 12
Voltage TC

A
12 24
10 22 B

B POWER POWER
RTD
11 23 100 - 240 V~ 50/60 Hz 5.5 VA 100 - 240 V~ 50/60 Hz 5.5
Current
CT-50N BracketTC

HX9
Voltage
12 24
B

● Appearance POWER
100 - 240 V~ 50/60 Hz 5.5 VA
HX3
HX9

-8-