0% found this document useful (0 votes)
10 views3 pages

Eaton DS 278831 FAZ Z63 2 en - GB 20250102

The FAZ-Z63/2 is a miniature circuit breaker (MCB) rated at 63 A with a two-pole configuration and a Z tripping characteristic, designed for industrial and advanced commercial applications. It complies with various certifications including UL, CSA, and IEC standards, and features a rated operational voltage of up to 400 V and a short-circuit breaking capacity of 10 kA. The device has a compact design with dimensions of 80mm x 75.5mm x 36mm and is suitable for various mounting positions.

Uploaded by

dwi yulianto
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
10 views3 pages

Eaton DS 278831 FAZ Z63 2 en - GB 20250102

The FAZ-Z63/2 is a miniature circuit breaker (MCB) rated at 63 A with a two-pole configuration and a Z tripping characteristic, designed for industrial and advanced commercial applications. It complies with various certifications including UL, CSA, and IEC standards, and features a rated operational voltage of up to 400 V and a short-circuit breaking capacity of 10 kA. The device has a compact design with dimensions of 80mm x 75.5mm x 36mm and is suitable for various mounting positions.

Uploaded by

dwi yulianto
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 3

DATASHEET - FAZ-Z63/2

Miniature circuit breaker (MCB), 63 A, 2p, characteristic: Z

Part no. FAZ-Z63/2


278831
EL Number 1695276
(Norway)
General specifications
Product name Eaton Moeller series xEffect - FAZ MCB

Part no. FAZ-Z63/2

EAN 4015082788315

Product Length/Depth 80 millimetre

Product height 75.5 millimetre

Product width 36 millimetre

Product weight 0.246 kilogram

Compliances UL CSA09 (with supplementary protector only)


RoHS conform

Certifications North America (UL recognized, CSA certified)


UL 1077
IEC/EN 60947-2
IEC 61373
CSA (Class No. 3215-30)
UL (Category Control Number QVNU2, QVNU8)
CSA-C22.2 No. 235
IEC/EN 60898
CE marking
CSA (File No. 204453)
EN45545-2
UL (File No. E177451)

Product Tradename xEffect - FAZ

Product Type MCB

Product Sub Type None

Delivery program
Application xEffect - Switchgear for industrial and advanced commercial applications
Switchgear for industrial and advanced commercial applications
Branch circuits, not as BCPD

Number of poles Two-pole

Number of poles (total) 2

Number of poles (protected) 2

Tripping characteristic Z

Release characteristic Z

Amperage Rating 63 A

Type Miniature circuit breaker


FAZ

Technical Data - Electrical


Voltage type AC

Voltage rating 240 V AC / 415 V AC

Voltage rating at DC 60 V DC (per pole)

Voltage rating (UL CSA 13) 480 Y/277 V AC; 96 V DC

Rated operational voltage (Ue) - max 400 V

Rated insulation voltage (Ui) 440 V

Rated impulse withstand voltage (Uimp) 4 kV

Frequency rating - min 50 Hz

Frequency rating - max 60 Hz

Rated switching capacity (IEC/EN 60947-2) 10 kA

Operational switching capacity 7.5 kA

Rated short-circuit breaking capacity (EN 60898) at 230 V 0 kA

Rated short-circuit breaking capacity (EN 60898) at 400 V 0 kA

Rated short-circuit breaking capacity (IEC 60947-2) at 230 V 10 kA

Rated short-circuit breaking capacity (IEC 60947-2) at 400 V 10 kA

Admissible back-up fuse - max 125 A gL/gG

01/03/2025 Eaton 278831 ED2023 V1.0 EN 1/3


Selectivity class 3

Lifespan, electrical 10000 operations

Overvoltage category III

Pollution degree 2

Direction of incoming supply As required

Technical Data - Mechanical


Frame 45 mm

Enclosure width 80 mm

Width in number of modular spacings 2

Built-in depth 70.5 mm

Mounting width per pole 17.5 mm

Mounting width 17.5 mm

Mounting Method Top-hat rail IEC/EN 60715

Mounting position As required

Degree of protection IP20


UL/CSA Type: -
IP20 (IEC)
IP40 (when fitted)

Terminals (top and bottom) Twin-purpose terminals

Connectable conductor cross section (solid-core) - min 1 mm²

Connectable conductor cross section (solid-core) - max 25 mm²

Connectable conductor cross section (multi-wired) - min 1 mm²

Connectable conductor cross section (multi-wired) - max 25 mm²

Terminal capacity of screw terminals for main cable 10 mm² (2x)

Terminal capacity (control cable) 25 mm² (1x)

Terminal protection Finger and hand touch safe, DGUV VS3, EN 50274

Busbar material thickness 0.8 mm - 2 mm

Design verification as per IEC/EN 61439 - technical data


Rated operational current for specified heat dissipation (In) 63 A

Heat dissipation per pole, current-dependent 0W

Equipment heat dissipation, current-dependent 8.5 W

Static heat dissipation, non-current-dependent 0W

Heat dissipation capacity 0W

Ambient operating temperature - min -25 °C

Ambient operating temperature - max 75 °C

Design verification as per IEC/EN 61439


10.2.2 Corrosion resistance Meets the product standard's requirements.

10.2.3.1 Verification of thermal stability of enclosures Meets the product standard's requirements.

10.2.3.2 Verification of resistance of insulating materials to normal heat Meets the product standard's requirements.

10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects Meets the product standard's requirements.

10.2.4 Resistance to ultra-violet (UV) radiation Meets the product standard's requirements.

10.2.5 Lifting Does not apply, since the entire switchgear needs to be evaluated.

10.2.6 Mechanical impact Does not apply, since the entire switchgear needs to be evaluated.

10.2.7 Inscriptions Meets the product standard's requirements.

10.3 Degree of protection of assemblies Does not apply, since the entire switchgear needs to be evaluated.

10.4 Clearances and creepage distances Meets the product standard's requirements.

10.5 Protection against electric shock Does not apply, since the entire switchgear needs to be evaluated.

10.6 Incorporation of switching devices and components Does not apply, since the entire switchgear needs to be evaluated.

10.7 Internal electrical circuits and connections Is the panel builder's responsibility.

10.8 Connections for external conductors Is the panel builder's responsibility.

10.9.2 Power-frequency electric strength Is the panel builder's responsibility.

10.9.3 Impulse withstand voltage Is the panel builder's responsibility.

10.9.4 Testing of enclosures made of insulating material Is the panel builder's responsibility.

10.10 Temperature rise The panel builder is responsible for the temperature rise calculation. Eaton will
provide heat dissipation data for the devices.

10.11 Short-circuit rating Is the panel builder's responsibility. The specifications for the switchgear must be
observed.

01/03/2025 Eaton 278831 ED2023 V1.0 EN 2/3


10.12 Electromagnetic compatibility Is the panel builder's responsibility. The specifications for the switchgear must be
observed.

10.13 Mechanical function The device meets the requirements, provided the information in the instruction
leaflet (IL) is observed.

Additional information
Current limiting class 3

Features Additional equipment possible

Special features Ambient temperature hint: a 1 °C increase results in a 0.5% linear reduction of
current carrying capacity

Used with Miniature circuit breaker


FAZ

Technical data ETIM 9.0


Circuit breakers and fuses (EG000020) / Miniature circuit breaker (MCB) (EC000042)

Electric engineering, automation, process control engineering / Electrical installation, device / Miniature circuit breaker system (MCB) / Miniature circuit breaker (MCB) (ecl@ss13-27-14-19-01
[AAB905019])

Built-in depth mm 70.5

Release characteristic Z

Number of poles (total) 2

Number of protected poles 2

Rated current A 63

Rated voltage V 400

Rated insulation voltage Ui V 440

Rated impulse withstand voltage Uimp kV 4

Rated short-circuit breaking capacity Icn according to EN 60898 at 230 V kA 0

Voltage type AC

Rated short-circuit breaking capacity Icn according to EN 60898 at 400 V kA 0

Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 230 V kA 10

Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 400 V kA 10

Frequency Hz 50 - 60

Power loss W 8.5

Current limiting class 3

Flush-mounted installation No

Concurrently switching neutral conductor No

Over voltage category 3

Pollution degree 2

Additional equipment possible Yes

Width in number of modular spacings 2

Degree of protection (IP) IP20

Ambient temperature during operating °C -25 - 75

Connectable conductor cross section multi-wired mm² 1 - 25

Connectable conductor cross section solid-core mm² 1 - 25

Explosion-proof No

01/03/2025 Eaton Industries GmbH 3/3


© 04/2023 by Eaton Industries GmbH
Eaton 278831 ED2023 V1.0 EN