Eaton DS 278831 FAZ Z63 2 en - GB 20250102
Eaton DS 278831 FAZ Z63 2 en - GB 20250102
EAN 4015082788315
Delivery program
Application xEffect - Switchgear for industrial and advanced commercial applications
Switchgear for industrial and advanced commercial applications
Branch circuits, not as BCPD
Tripping characteristic Z
Release characteristic Z
Amperage Rating 63 A
Pollution degree 2
Enclosure width 80 mm
Terminal protection Finger and hand touch safe, DGUV VS3, EN 50274
10.2.3.1 Verification of thermal stability of enclosures Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation Meets the product standard's requirements.
10.2.5 Lifting Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact Does not apply, since the entire switchgear needs to be evaluated.
10.3 Degree of protection of assemblies Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances Meets the product standard's requirements.
10.5 Protection against electric shock Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material Is the panel builder's responsibility.
10.10 Temperature rise The panel builder is responsible for the temperature rise calculation. Eaton will
provide heat dissipation data for the devices.
10.11 Short-circuit rating Is the panel builder's responsibility. The specifications for the switchgear must be
observed.
10.13 Mechanical function The device meets the requirements, provided the information in the instruction
leaflet (IL) is observed.
Additional information
Current limiting class 3
Special features Ambient temperature hint: a 1 °C increase results in a 0.5% linear reduction of
current carrying capacity
Electric engineering, automation, process control engineering / Electrical installation, device / Miniature circuit breaker system (MCB) / Miniature circuit breaker (MCB) (ecl@ss13-27-14-19-01
[AAB905019])
Release characteristic Z
Rated current A 63
Voltage type AC
Frequency Hz 50 - 60
Flush-mounted installation No
Pollution degree 2
Explosion-proof No