0% found this document useful (0 votes)
19 views

10 Fuses Copy Copy Copy

Fuses are essential components for protecting against overcurrents and faults, acting quickly and reliably in various applications such as transformers and motors. Their characteristics vary based on design, rated voltage, current, and service type, with international standards differing across regions. The operation of a fuse involves a melting process that interrupts the circuit, and understanding the I²t characteristic is crucial for ensuring compatibility with downstream equipment during fault conditions.

Uploaded by

edigosuprapto
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
19 views

10 Fuses Copy Copy Copy

Fuses are essential components for protecting against overcurrents and faults, acting quickly and reliably in various applications such as transformers and motors. Their characteristics vary based on design, rated voltage, current, and service type, with international standards differing across regions. The operation of a fuse involves a melting process that interrupts the circuit, and understanding the I²t characteristic is crucial for ensuring compatibility with downstream equipment during fault conditions.

Uploaded by

edigosuprapto
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 6

8

Fuses

l
ria
8.1 GENERAL COMMENTS

ate
Fuses are used when it is possible to use a simple and economic method of protection against
overcurrents and faults. They are fast to act when a major fault occurs and are very reliable.
The characteristics of fuses vary widely depending upon the application for example:-



dM
Distribution feeders to transformers.
Induction motors.
• AC and DC services.
• Rectifier and thyristor circuits.
• Static load service, such as heaters.
• High voltage and low voltage services.
hte

The terminology and standards vary considerably between countries. Typical international standard
codes are:-

• Europe. IEC60282 and 60644 for high voltage fuses


IEC60269 for low voltage fuses.
rig

• USA. UL 248-1/CSA-C22.2 (15 parts)


Reference 1 gives a description of the standards used in the USA as well as a theoretical
treatment of the subject.
py

Reference 2 gives a comprehensive description of most aspects of fuses including mathematical


models together with comments on European and US practice. It also contains a full listing of the
most useful IEC standards in its Chapter 8. See also Reference 3 article 110, sub-section 10, for
applications where the rated voltages are up to 600 volts.
Co

The melting process of a fuse is a complicated subject. However, for the practising electrical
engineer in the design and application side of the industry it is usually only necessary to be familiar
with some of the basic characteristics of fuses. Fuse manufacturers are able to vary the shape and
steepness of the characteristics by carefully designing the shape of the fuse element, by surrounding
the element with different heat removing media and by selecting different fusable metals and alloys.
The main parameters concerning an application are,

Handbook of Electrical Engineering: For Practitioners in the Oil, Gas and Petrochemical Industry. Alan L. Sheldrake
 2003 John Wiley & Sons, Ltd ISBN: 0-471-49631-6

Copyright © 2003 John Wiley & Sons Retrieved from: www.knovel.com


174 HANDBOOK OF ELECTRICAL ENGINEERING

• Rated voltage.
• Rated current.
• Rated frequency.
• AC and DC service and type of load current.
• Time versus current characteristic.
• Time versus I 2 t characteristic.

l
ria
• Rated breaking capacity.
• Rated power dissipation of the fuse.
• Cut-off current in AC service.
• Pre-arcing and arcing times.

ate
• Dimensions.

8.2 OPERATION OF A FUSE


The operating sequence of a fuse is:-
1.
2.
3.
dM
The fuse element heats up and finally melts.
As soon as melting occurs a gap is formed at one or more points along the element.
An arc is then established across each gap.
4. The heat of the arc further melts the ends of the elements at each gap and so the gap is increased.
5. Hence the arc length increases and the arc becomes weaker. A point is reached when the arc
becomes unstable and cannot be maintained.
hte

6. The arc is extinguished and the circuit is isolated by the fuse.

8.3 INFLUENCE OF THE CIRCUIT X-TO-R RATIO


The following discussion will only relate to AC circuits. Fuses are used mainly to interrupt large
rig

fault currents and so the discussions will concentrate on short circuits. Fuses can operate within
a quarter of a cycle and so it is often the case that the short-circuit current is asymmetrical, see
sub-section 7.2.7.
All circuits which contain inductive reactance and resistance have an X-to-R ratio, in practice
py

between 2.0 and 100.00. In short-circuit analysis it is usually necessary to relate the asymmetrical
current to the symmetrical current. This can only be done if the short-circuit power factor of the cir-
cuit and hence the X-to-R ratio is known. Table 8.1 shows the relationship between these parameters
and currents. Normally the short-circuit power factor is low, between 0.01 and 0.45. It is custom-
Co

ary in short-circuit analysis to assume that one of the phases has the worst-case situation of fully
asymmetrical current. Figure 8.1 shows an example, together with the various definitions of times
and currents.
The fuse will operate during the first half-cycle if it is properly selected. As the current
increases the fuse element melts and eventually the melting causes the circuit to become interrupted.
During melting the period is called the ‘melting time’ (US terminology) or ‘pre-arcing time’ (UK
terminology). After the melting time an arc is maintained for a short period called the ‘arcing time’.
If the fuse failed to operate, or was not included in the circuit, the current would continue to rise to

Copyright © 2003 John Wiley & Sons Retrieved from: www.knovel.com


FUSES 175

Table 8.1. Characteristic currents that are related to the X-to-R ratio of a circuit
Ratio to rms symmetrical current

Short Short Max 1-phase Max 1-phase Avg 3-phase


circuit circuit peak current rms current rms current
X-to-R power at 1/2 cycle at 1/2 cycle

l
ratio factor

ria
Infinity 0.0 2.828 1.732 1.394
100 0.01 2.785 1.696 1.374
49.993 0.02 2.743 1.665 1.355
33.322 0.03 2.702 1.630 1.336
24.979 0.04 2.663 1.598 1.318

ate
19.974 0.05 2.625 1.568 1.301
9.9501 0.1 2.455 1.436 1.229
6.5912 0.15 2.309 1.330 1.171
4.8990 0.2 2.183 1.247 1.127
3.1798 0.3 1.978 1.130 1.066
2.2913
dM 0.4 1.819 1.062 1.031
1.7321 0.5 1.694 1.026 1.013
1.3333 0.6 1.594 1.009 1.004
1.0202 0.7 1.517 1.002 1.001
0.75 0.8 1.460 1.0002 1.00005
0.6198 0.85 1.439 1.00004 1.00002
Zero 1.0 1.414 1.0 1.0
hte
rig
py
Co

Figure 8.1 Fuse cut-off curves for different X-to-R ratios of the fault circuit. The curves show how the
clearance time varies with the ratio..

Copyright © 2003 John Wiley & Sons Retrieved from: www.knovel.com


176 HANDBOOK OF ELECTRICAL ENGINEERING

its maximum possible value, called the ‘maximum asymmetrical’ (US) or ‘asymmetrical prospective’
(UK) current. The peak value of the actual fault current that the fuse allows to pass is called the
‘peak let-through’ current.
Clearly the higher the fault current the faster the fuse will operate, which is the required
characteristic of a fuse. However, the application engineer must balance speed of operation with
other factors such as the type of load. For example when an induction motor is started direct-on-line,

l
the starting current will be as much as 7 times the running current. This starting current will actually

ria
fall within the range of currents that can cause the fuse to operate. Therefore a compromise is required
between fast action during a fault and allowing the motor sufficient time to run up. Static loads do
not require such a compromise and so fast action can be optimised by choosing a lower fusing factor
(see sub-section 7.4). Rectifiers and thyristors require extra-fast fuses since permanent damage can

ate
be done very quickly when fault currents occur.

8.4 THE I 2 t CHARACTERISTIC


During operation the fuse may be regarded as a constant resistance (R) until interruption occurs.

approximately:-
dM
The power dissipated by the fuse is therefore I 2 R. The energy release by the fuse is therefore

Energy U = I 2 Rt

Where t is the melting time plus the arcing time and I is the current flowing in the fuse.
Therefore a fuse can be described by its I 2 t characteristic as being a measure of the energy
hte

released during its operation. Obviously the mechanical design of the fuse must be capable of con-
taining this energy, which is released in an explosive manner.
Historically early designs began to fail until it was realised that the prospective fault currents
in typical power systems had gradually increased. This was due to the natural development and
expansion of those systems. Reference 1 gives a good description of the I 2 t characteristic.
rig

Different types of fuse for the same rated voltage and current will release different amounts
of energy since their characteristics are deliberated designed to be different. The energy released is
due to two separate functions, melting the fuse element and extinguishing the arc.
The actual value of let-through current for a given fuse will depend upon the nature and
py

magnitude of the prospective fault current e.g. asymmetrical or symmetrical. This is because a greater
current has to be reached in the symmetrical case than in the asymmetrical case to create the same
amount of melting energy. This is due to the shape of the current waveform in the first cycle, which
can be seen in Figure 8.1.
Co

The maximum value of the let-through current is called the ‘peak let-through current Ip ’.
The importance of the peak let-through current is in relation to the thermal and mechanical
stresses that occur in the downstream equipment e.g. contactors, cables.
Furthermore the I 2 t characteristics of any of the downstream equipment must be greater than
the fuse, otherwise the equipment will suffer thermal damage. (For a given fault current the fuse
clearance time must always be at least several times lower than the corresponding I 2 t time of the
downstream device.)

Copyright © 2003 John Wiley & Sons Retrieved from: www.knovel.com


FUSES 177

l
ria
ate
dM
Figure 8.2 Melting, nominal and clearance time curves versus current for a typical 250 A fuse.

The melting time and clearing time are of related significance when two fuses, which are in
hte

series, need to be coordinated, e.g. a feeder fuse and a large outgoing fuse. The feeder fuse must not
melt during the clearing time of the outgoing fuse when a common fault current passes. Figure 8.2
shows the important times and currents of a typical 250 amp fuse. The shape of the curve is typical.
A fuse may be called upon to operate in one of two ways:-
rig

— Current limiting-short time duty.


— Non-current limiting-long time duty.

In a 60 Hz system the peak of the fault current will occur in 0.0042 sec (symmetrical) or
py

0.0084 sec (fully asymmetrical). For a 50 Hz system the times are 0.005 sec and 0.01 sec respectively.
If the fuse clears the fault in less than about 0.003 sec then the fuse is said to be current limiting.
However if the prospective current is not at its maximum then several cycles of current may
occur before sufficient heat is created to melt the fuse. In this situation the fuse is said to be non-
Co

current limiting. This applies to times beyond about 0.01 sec on the fuse curve of Figure 8.2. As the
prospective current is reduced the non-current limiting time, or operating time, increases considerably.
A particular design of fuse may take several hours to operate if the prospective current is only a small
amount above the asymptotic value of the fuse. Four hours is used by manufacturers as a reference
value. It can be seen therefore that times less than 0.003 sec are important when high currents occurs.
It should be noted that when the melting time exceeds about 0.1 sec the corresponding arcing
time is less than 0.01 sec. Therefore for times above 0.1 sec it may be assumed that the melting or
pre-arcing time is in fact the clearance time. The fuse manufacturers normally give curves for the

Copyright © 2003 John Wiley & Sons Retrieved from: www.knovel.com


178 HANDBOOK OF ELECTRICAL ENGINEERING

time range of 0.01 to 1000 seconds. For times less than 0.01 sec it is better to seek the advice of a
particular manufacturer.
During the current limiting phase the operating time is influenced by whether the prospective
current is asymmetrical or fully symmetrical. The time is determined by the integrated amount of
heat generated and this is a function of the current waveform shape. To help overcome difficulties
in relating the terminology used in the non-current limiting phase to that applicable in the current

l
limiting phase, the term ‘virtual time’ was introduced some years ago.

ria
Note that during current limiting operation the melting time and the arcing time are of the
same order, see Figure 8.2. The term virtual time (tv ) can be used in conjunction with the melting,
arcing and clearing times by using the following mathematical expressions:-

ate
Melting energy (amp2 secs)
Melting tv =
Prospective current (rms sym amps)2

1 tm 2
= 2 i dt seconds
I o

Similarly,
dM
Arcing energy
Arching tv =
Prospective current2

1 tc 2
hte

= 2 i dt seconds
I tm

And,
 tc
1
Clearing tv = 2 i 2 dt seconds
I
rig

Where, tm is the melting time period.


py

tc is the clearing time period.


tc − tm is the arcing time period.
Co

The manufacturers use this procedure to extrapolate their curves below 0.01 sec and tv is
therefore a theoretical time. Virtual time is related to the prospective current by definition and so
the manufacturer will quote the maximum prospective current that can be used in conjunction with
his curves. At this point the engineer is encouraged to consult the manufacturers for advice on the
selection of fuses for current-limiting duty.
The above discussion on current limiting and virtual time have been included for completeness
so that the reader is made aware of their significance.

Copyright © 2003 John Wiley & Sons Retrieved from: www.knovel.com

You might also like