0% found this document useful (0 votes)
5 views

Field and Group Setting

The document provides detailed instructions for field setting of indoor units using various types of remote controllers, including wired, wireless, and simplified models. It outlines the steps for entering field set mode, selecting mode numbers, and adjusting settings related to filter contamination, fan speed, and air flow direction. Additionally, it includes tables for setting contents and applicable ranges for different indoor unit types and configurations.

Uploaded by

tak shing chiu
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
5 views

Field and Group Setting

The document provides detailed instructions for field setting of indoor units using various types of remote controllers, including wired, wireless, and simplified models. It outlines the steps for entering field set mode, selecting mode numbers, and adjusting settings related to filter contamination, fan speed, and air flow direction. Additionally, it includes tables for setting contents and applicable ranges for different indoor unit types and configurations.

Uploaded by

tak shing chiu
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 30

Si38-606A Field Setting

3. Field Setting
3.1 Field Setting from Remote Controller
Individual function of indoor unit can be changed from the remote controller. At the time of
installation or after service inspection / repair, make the local setting in accordance with the
following description.
Wrong setting may cause malfunction.
(When optional accessory is mounted on the indoor unit, setting for the indoor unit may be
required to change. Refer to information in the option handbook.)

3.1.1 Wired Remote Controller <BRC1C62>

UNIT NO. MODE NO.


SECOND . FIELD
CODE NO. UNIT NO.
SET
FIRST MODE
. SETTING

CODE NO. 3 4

1 7 TEST

6 5 2

(V0292)

1. When in the normal mode, press the “ ” button for a minimum of four seconds, and the
FIELD SET MODE is entered.
2. Select the desired MODE NO. with the “ ” button (2).
3. During group control, when setting by each indoor unit (mode No. 20, 22 and 23 have been
selected), push the “ ” button (3) and select the INDOOR UNIT NO to be set. (This
operation is unnecessary when setting by group.)
4. Push the “ ” upper button (4) and select FIRST CODE NO.
5. Push the “ ” lower button (5) and select the SECOND CODE NO.
6. Push the “ ” button (6) once and the present settings are SET.
7. Push the “ ” button (7) to return to the NORMAL MODE.

(Example)
If during group setting and the time to clean air filter is set to FILTER CONTAMINATION,
HEAVY, SET MODE NO. to “10” FIRST CODE NO. to “0”, and SECOND CODE NO. to “02”.

Test Operation 77
Field Setting Si38-606A

3.1.2 Wireless Remote Controller - Indoor Unit


BRC7C type
BRC7E type
BRC4C type

1. When in the normal mode, push the button for 4 seconds or more, and operation
then enters the “field set mode.”
2. Select the desired “mode No.” with the button.
3. Pushing the button, select the first code No.
4. Pushing the button, select the second code No.
5. Push the timer button and check the settings.
6. Push the button to return to the normal mode.

(Example)
When setting the filter sign time to “Filter Dirtiness-High” in all group unit setting, set the Mode
No. to “10”, Mode setting No. to “0” and setting position No. to “02”.

78 Test Operation
Si38-606A Field Setting

3.1.3 Simplified Remote Controller


BRC2A51
BRC2C51

„ Group No. setting by simplified remote controller.


1. Remove the cover of remote controller.
2. While in normal mode, press the [BS6] BUTTON (field set) to enter the FIELD SET MODE.
3. Select the mode No. [00] with [BS2] BUTTON (temperature setting ▲) and [BS3] BUTTON
(temperature setting ▼).
4. Select the group No. with [BS9] BUTTON (set A) and [BS10] BUTTON (set B). (Group Nos.
increase in the order of 1-00, 1-01......1-15, 2-00,.....4-15. However, the unified ON/OFF controller
displays only group No. set within the range of control.)
5. Press [BS7] BUTTON (set/cancel) to set group No.
6. Press [BS6] BUTTON (field set) to return to the NORMAL MODE.

Test Operation 79
Field Setting Si38-606A

3.1.4 Setting Contents and Code No. – VRV Unit


VRV Mode Setting Setting Contents Second Code No.(Note 3)
system No. Switch
indoor Note 2 No. 01 02 03 04
unit
settings 10(20) 0 Filter contamination heavy/ Super Light Approx. Heavy Approx. — —
light (Setting for display long life 10,000 5,000
time to clean air filter) filter hrs. hrs.
(Sets display time to clean
air filter to half when there is Long life Approx. Approx.
heavy filter contamination.) filter 2,500 1,250
hrs. hrs.
Standard Approx. Approx.
filter 200 100
hrs. hrs.
1 Long life filter type Long life filter Super long life — —
filter
2 Thermostat sensor in remote controller Use No use — —
3 Display time to clean air filter Display No display — —
calculation (Set when filter sign is not
to be displayed.)
12(22) 0 Optional accessories output selection Indoor unit — Operation output Malfunction
(field selection of output for adaptor for turned ON by output
wiring) thermostat
1 ON/OFF input from outside (Set when Forced OFF ON/OFF control External —
ON/OFF is to be controlled from protection device
outside.) input
2 Thermostat differential changeover 1°C 0.5°C — —
(Set when remote sensor is to be
used.)
3 OFF by thermostat fan speed LL Set fan speed — —
4 Automatic mode differential (automatic 01:0 02:1 03:2 04:3 05:4 06:5 07:6 08:7
temperature differential setting for VRV
system heat recovery series cool/heat)
5 Power failure automatic reset Not equipped Equipped — —
13(23) 0 High air outlet velocity N H S —
(Set when installed in place with ceiling
higher than 2.7 m.)
1 Selection of air flow direction F (4 directions) T (3 directions) W (2 directions) —
(Set when a blocking pad kit has been
installed.)
3 Air flow direction adjustment (Set at Equipped Not equipped — —
installation of decoration panel.)
4 Field set air flow position setting Draft prevention Standard Ceiling Soiling —
prevention
5 Field set fan speed selection Standard Optional Optional —
(fan speed control by air discharge accessory 1 accessory 2
outlet for phase control)
15(25) 1 Thermostat OFF excess humidity Not equipped Equipped — —
2 Direct duct connection Not equipped Equipped — —
(when the indoor unit and heat reclaim
ventilation unit are connected by duct
directly.) ∗Note 6
3 Drain pump humidifier interlock Not equipped Equipped — —
selection
5 Field set selection for individual Not equipped Equipped — —
ventilation setting by remote controller
6 Field set selection for individual Not equipped Equipped — —
ventilation setting by remote controller

Notes: 1. Settings are made simultaneously for the entire group, however, if you select the mode No.
inside parentheses, you can also set by each individual unit. Setting changes however
cannot be checked except in the individual mode for those in parentheses.
2. The mode numbers inside parentheses cannot be used by wireless remote controllers, so
they cannot be set individually. Setting changes also cannot be checked.
3. Marked are factory set.
4. Do not make settings other than those described above. Nothing is displayed for functions
the indoor unit is not equipped with.
5. “88” may be displayed to indicate the remote controller is resetting when returning to the
normal mode.
6. If the setting mode to “Equipped”, heat reclaim ventilation fan conducts the fan residual
operation by linking to indoor unit.

80 Test Operation
Si38-606A Field Setting

3.1.5 Applicable Range of Field Setting

Ceiling mounted cassette Ceiling Slim Ceiling Ceiling Wall Floor Conceal Ceiling Ceiling
type mounted ceiling mounted suspend mounted standing ed Floor mounted mounted
built-in mounted duct type ed type type type standing built-in low
Multi Double Corner type duct type type (Rear silhouette
flow flow type suction duct type
type)
FXF FXC FXK FXS FXD FXM FXH FXA FXL FXN FXYB FXYD

Filter sign { { { { { { { { { { { {

Ultra long life filter


{ { — — — — — — — — — —
sign
Remote controller
{ { { { { { { { { { { {
thermostat sensor
Set fan speed when
thermostat OFF { { { { { { { { { { { {

Air flow adjustment


Ceiling height { — — — — — { — — — — —

Air flow direction { — — — — — — — — — — —

Air flow direction


adjustment
— — { — — — — — — — — —
(Down flow
operation)
Air flow direction
{ { { — — — — — — — — —
adjustment range
Field set fan speed
{ — — — — — { — — — — —
selection

Test Operation 81
Field Setting Si38-606A

3.1.6 Detailed Explanation of Setting Modes


Filter Sign Setting
If switching the filter sign ON time, set as given in the table below.
Set Time
Filter Specs. Standard Long Life Ultra Long Life Filter
Setting
Contamination Light 200 hrs. 2,500 hrs. 10,000 hrs.
Contamination Heavy 100 hrs. 1,250 hrs. 5,000 hrs.

Ultra-Long-Life Filter Sign Setting


When a Ultra-long-life filter is installed, the filter sign timer setting must be changed.

Setting Table
Mode No. Setting Switch No. Setting Position No. Setting
01 Long-Life Filter
10 (20) 1 02 Ultra-Long-Life Filter (1)
03 —

External ON/OFF input


This input is used for "ON / OFF operation" and "Protection device input" from the outside. The
input is performed from the T1-T1 terminal of the operation terminal block (X1A) in the electric
component box.

F2 T1 T2
Forced stop
Input A

Setting Table
Setting Setting
Mode No. Switch No. Position No. Operation by input of the signal A
ON: Forced stop (prohibition of using the remote
01 controller)
OFF: Permission of using the remote controller
12 (22) 1 02 OFF → ON: Permission of operation
ON → OFF: Stop
ON: Operation
03 OFF: The system stops, then the applicable unit
indicates "A0". The other indoor units indicate "U9".

Fan Speed Changeover When Thermostat is OFF


By setting to “Set Fan Speed,” you can switch the fan speed to the set fan speed when the
heating thermostat is OFF.
∗ Since there is concern about draft if using “fan speed up when thermostat is OFF,” you should
take the setup location into consideration.

Setting Table
Mode No. First Code No. Second Code No. Setting
01 LL Fan Speed
12(22) 3
02 Set Fan Speed

82 Test Operation
Si38-606A Field Setting

Auto restart after power failure reset


For the air conditioners with no setting for the function (same as factory setting), the units will be
left in the stop condition when the power supply is reset automatically after power failure reset
or the main power supply is turned on again after once turned off. However, for the air
conditioners with the setting, the units may start automatically after power failure reset or the
main power supply turned on again ( return to the same operation condition as that of before
power failure).

For the above reasons, when the unit is set enabling to utilize “Auto restart function after power
failure reset”, utmost care should be paid for the occurrence of the following situation.

Caution 1. The air conditioner starts operation suddenly after power failure reset or
the main power supply turned on again. Consequently, the user might be
surprised (with question for the reason why).
2. In the service work, for example, turning off the main power switch during
the unit is in operation, and turning on the switch again after the work is
completed start the unit operation (the fan rotates).

Air Flow Adjustment - Ceiling height


Make the following setting according to the ceiling height. The setting position No. is set to “01”
at the factory.
„ In the Case of FXA, FXH

Mode No. Setting Switch Setting Position Setting


No. No.
01 Wall-mounted type: Standard
13(23) 0 02 Wall-mounted type: Slight increase
03 Wall-mounted type: Normal increase

„ In the Case of FXF25~80

Mode First Second Ceiling height


code code Setting
No. No. No. 4-way Outlets 3-way Outlets 2-way Outlets
01 Standard (N) Lower than 2.7 m Lower than 3.0 m Lower than 3.5 m
13 (23) 0 02 High Ceiling (H) Lower than 3.0 m Lower than 3.3 m Lower than 3.8 m
03 Higher Ceiling (S) Lower than 3.5 m Lower than 3.5 m —

„ In the Case of FXF100~125


First Second Ceiling height
Mode
No. code code Setting
No. No. 4-way Outlets 3-way Outlets 2-way Outlets
01 Standard (N) Lower than 3.2 m Lower than 3.6 m Lower than 4.2 m
13 (23) 0 02 High Ceiling (H) Lower than 3.6 m Lower than 4.0 m Lower than 4.2 m
03 Higher Ceiling (S) Lower than 4.2 m Lower than 4.2 m —

Test Operation 83
Field Setting Si38-606A

Air Flow Direction Setting


Set the air flow direction of indoor units as given in the table below. (Set when optional air outlet
blocking pad has been installed.) The second code No. is factory set to “01.”

Setting Table
Second Code
Mode No. First Code No. No. Setting

01 F : 4-direction air flow


13 (23) 1 02 T : 3-direction air flow
03 W : 2-direction air flow

Setting of Air Flow Direction Adjustment


Only the model FXK has the function.
When only the front-flow is used, sets yes/no of the swing flap operation of down-flow.

Setting Table
Setting Mode No. First Code No. Second Code No.
Down-flow operation: Yes 01
13 (23) 3
Down-flow operation: No 02

Setting of Air Flow Direction Adjustment Range


Make the following air flow direction setting according to the respective purpose.

Setting Table
Mode No. First Code No. Second Code No. Setting
01 Upward (Draft prevention)
02 Standard
13 (23) 4
Downward (Ceiling soiling
03 prevention)

Air flow rate switching at discharge grille for field air flow rate switching
When the optional parts (high performance filter, etc.) is installed, sets to change fan speed for
securing air flow rate.
Follow the instruction manual for the optional parts to enter the setting numbers.

Setting of the static pressure selection (for FXD model)


Model No. First Code No. Second Code No. External static pressure
01 Standard (15Pa)
13 (23) 5
02 High static pressure (44Pa)

84 Test Operation
Si38-606A Field Setting

3.1.7 Centralized Control Group No. Setting


BRC1C Type In order to conduct the central remote control using the central remote controller and the unified
ON/OFF controller, Group No. settings should be made by group using the operating remote
controller.
Make Group No. settings for central remote control using the operating remote controller.
1. While in normal mode, press and hold the switch for a period of four seconds or
TEST

more to set the system to "Field Setting Mode".


2. Select the MODE No. “00” with the “ ” button.
3. Use the “ ” button to select the group No. for each group.
(Group numbers increase in the order of 1-00, 1-01, ... 1-15, 2-00, ... 4-15.)
4. Press “ ” to set the selected group No.
5. Press “ TEST
” to return to the NORMAL MODE.

MODE NO.
GROUP NO.
UNIT NO.
FIELD SET
SETTING MODE

TEST
2
4 3
1,5

Note:
„ For wireless remote controller, see the following.
„ For setting group No. of HRV and wiring adaptor for other air conditioners, etc., refer to the
instruction manual attached.

NOTICE
Enter the group No. and installation place of the indoor unit into the attached installation table.
Be sure to keep the installation table with the operation manual for maintenance.

Test Operation 85
Field Setting Si38-606A

BRC7C Type „ Group No. setting by wireless remote controller for centralized control
BRC7E Type 1. When in the normal mode, push button for 4 seconds or more, and operation then
BRC4C Type enters the “field set mode.”
2. Set mode No. “00” with button.
3. Set the group No. for each group with button (advance/backward).
4. Enter the selected group numbers by pushing button.
5. Push button and return to the normal mode.

要有這個中控才可set
Group No. Setting group address
Example

Centoral Remote
Controller
Indoor/Outdoor Outdoor/Outdoor Indoor/Outdoor Outdoor/Outdoor

F1 F2
F1 F2 F1 F2 F1 F2 F1 F2

F1 F2 P1 P2 F1 F2 P1 P2 F1 F2 P1 P2 F1 F2 P1 P2

RC
Group Control by Remote Contoller
1-00 Main RC RC Sub RC
(autmatic unit address)
1-01 1-02

F1 F2 P1 P2 F1 F2 P1 P2 F1 F2 P1 P2 F1 F2 P1 P2

No Remote Controller
RC
1-03 (V0917)
1-04

Caution When turning the power supply on, the unit may often not accept any operation while "88" is
displaying after all indications were displayed once for about 1 minute on the liquid crystal
display. This is not an operative fault.

86 Test Operation
Si38-606A Field Setting

3.1.8 Setting of Operation Control Mode from Remote Controller


(Local Setting)
The operation control mode is compatible with a variety of controls and operations by limiting
the functions of the operation remote controller. Furthermore, operations such as remote
controller ON/OFF can be limited in accordance with the combination conditions. (Refer to
information in the table below.)
Centralized controller is normally available for operations. (Except when centralized monitor is
connected)

3.1.9 Contents of Control Modes


Twenty modes consisting of combinations of the following five operation modes with
temperature and operation mode setting by remote controller can be set and displayed by
operation modes 0 through 19.
‹ ON/OFF control impossible by remote controller
Used when you want to turn on/off by central remote controller only.
(Cannot be turned on/off by remote controller.)
‹ OFF control only possible by remote controller
Used when you want to turn on by central remote controller only, and off by remote controller
only.
‹ Centralized
Used when you want to turn on by central remote controller only, and turn on/off freely by
remote controller during set time.
‹ Individual
Used when you want to turn on/off by both central remote controller and remote controller.
‹ Timer operation possible by remote controller
Used when you want to turn on/off by remote controller during set time and you do not want
to start operation by central remote controller when time of system start is programmed.

Test Operation 87
Field Setting Si38-606A

How to Select Whether operation by remote controller will be possible or not for turning on/off, controlling
Operation Mode temperature or setting operation mode is selected and decided by the operation mode given on
the right edge of the table below.

Example
ON by remote OFF by remote
Temperature Operation mode Control
controller controller OFF by control by setting by mode is "1."
(Unified ON by (Unified OFF by remote remote controller remote controller
central remote central remote controller
controller) controller)
↓ ↓ ↓ ↓ ↓
Rejection Rejection Rejection Acceptance Acceptance (VL069)

Control by remote controller


Operation
Unified operation,
Control mode Unified OFF,
individual operation
individual stop by OFF Temperature Operation Control mode
by central remote control mode setting
controller, or central remote
operation controlled controller, or timer
by timer stop

Acceptance 0
Rejection
ON/OFF control Rejection 10
Rejection
impossible by (Example) Acceptance
remote controller Acceptance (Example) 1(Example)
(Example)
Rejection (Example) Rejection 11
Acceptance 2
Rejection
OFF control only Rejection (Example) Rejection 12
possible by
remote controller Acceptance 3
Acceptance
Rejection 13
Acceptance 4
Rejection
Rejection 14
Centralized
Acceptance 5
Acceptance
Rejection 15
Acceptance Acceptance
Acceptance 6
Rejection
Rejection 16
Individual Acceptance
Acceptance 7 ∗1
Acceptance
Rejection 17
Acceptance 8
Rejection
Timer operation Acceptance Acceptance Rejection 18
possible by (During timer at ON (During timer at ON
remote controller position only) position only) Acceptance 9
Acceptance
Rejection 19
Do not select “timer operation possible by remote controller” if not using a remote controller.
Operation by timer is impossible in this case.
∗1. Factory setting

88 Test Operation
Si38-606A Field Setting

3.2 Field Setting from Outdoor Unit


3.2.1 Field Setting from Outdoor Unit
„ Setting by dip switches
The following field settings are made by dip switches on PC board.
Dipswitch
Setting item Description
No. Setting
ON
DS1-1 Cool / Heat select Used to set cool / heat select by remote controller
OFF (Factory set) equipped with outdoor unit.

DS1-2 ON
Not used Do not change the factory settings.
~DS1-4 OFF (Factory set)

DS2-1 ON
~4 Not used Do not change the factory settings.
OFF (Factory set)

DS3-1, ON
2 Not used Do not change the factory settings.
OFF (Factory set)

Caution DIP switch Setting after changing the main P.C.Board(A1P) to spare parts P.C.B.
When you change the main P.C.Board(A1P) to spare parts P.C.B., please carry out the following
setting.

ON ON
OFF OFF
1 2 3 4 1 2 3 4
DS1 DS2

DIP Switch Detail


DS No. Item Contents
DS1-1 Cool/Heat change ON The Cool/Heat change over setting is carried out by COOL/
over setting HEAT changeover remote controller fitted to outdoor unit.
OFF The Cool/Heat change over setting is not carried out by COOL/
HEAT changeover remote controller fitted to outdoor unit.
DS1-2 Domestic/Overseas ON Domestic Japan
setting
OFF Overseas
DS1-3 Cooling only/Heat- ON Cooling only
pump setting
OFF Heat-pump
DS1-4 OFF Do not change the factory settings.
Not used
DS2-1 OFF (Refrigerant classification)
DS2-2 HP setting 8 10 HP
(Horse power)
DS2-2 OFF ON
DS2-3
DS2-3 ON ON
DS2-4 DS2-4 OFF OFF

„ Setting by pushbutton switches


The following settings are made by pushbutton switches on PC board.
In case of multi-outdoor unit system, various items should be set with the master unit.
(Setting with the slave unit is disabled.)
The master unit and slave unit can be discriminated with the LED indication as shown below.
H1P H2P H3P H4P H5P H6P H7P H8P
One outdoor
unit installed 7 7 8 7 7 7 7 7
(Factory setting)

Test Operation 89
Field Setting Si38-606A

BS1 BS2 BS3 BS4 BS5

MODE SET RETURN TEST RESET


(V2760)

There are the following three setting modes.


c Setting mode 1 (H1P off)
Initial status (when normal) : Used to select the cool/heat setting. Also indicates during
“abnormal”, “low noise control” and “demand control”.
d Setting mode 2 (H1P on)
Used to modify the operating status and to set program addresses, etc. Usually used in
servicing the system.
e Monitor mode (H1P blinks)
Used to check the program made in Setting mode 2.

„ Mode changing procedure

Using the MODE button, the modes can be changed as follows.

Push and hold the BS1 (Normal) Push the BS1(MODE button)
(MODE button) for 5 seconds. one time.
Setting mode 2 Setting mode 1 Monitor mode

MODE Push the BS1(MODE button) one time. MODE MODE

On Off Blinking

H1P H1P H1P


(V2761)

„ Mode changing procedure

(Set): Select mode with BS2 (SET button) in each selection step.

Press BS1 (MODE button) for more than 5 sec. Setting mode 1 Press BS1(MODE button).
(Initial condition)

Setting mode 2 Monitor mode

Setting item selection (Set) Check item selection (Set)

Press BS3 Press BS3


(RETURN button). (RETURN button).
Setting condition
Contents display
selection (Set)
Press BS3 Press BS3
(RETURN button). (RETURN button).
Setting condition
(Contents) display
Press BS3
(RETURN button). Press BS1
(MODE button).

Press BS1
(MODE button).

(V2762)

90 Test Operation
Si38-606A Field Setting

a. “Setting mode 1”
This mode is used to check the following items.
1. Check items ······· The following items can be checked.
(1) Current operating conditions (Normal / Abnormal / In check operation)
(2) Setting conditions of COOL/HEAT selection (Individual / Batch master / Batch slave)
(3) Low noise operating conditions (In normal operation / In low noise operation)
(4) Demand operating conditions (In normal operation / In demand operation)

Procedure for checking check items

The system is normally set to "Setting


mode 1".
Should the system be set to any
mode other than that, press the Page Preparation COOL/HEAT select Low Demand
MODE (BS1) button to set the alarm IND MASTER SLAVE noise
H1P H2P H3P H4P H5P H6P H7P
system to "Setting mode 1".
7 7 8 7 7 7 7

Current operating conditions


7Normal 8Abnormal
9In preparation or in check
operation
Check the system for each condition
Setting of COO/HEAT selection
through LED displays. (Refer to
877By individual outdoor
information in table on the right.)
unit
787In a batch of outdoor unit
group with master unit
778In a batch of outdoor unit
group with slave unit
Low noise operating conditions
Pressing the RETURN (BS3) button
will bring the system to the initial 7In normal operation
state of "Setting mode 1". 8In low noise operation
Demand operating conditions
(V2763) 7In normal operation
8In demand operation

Test Operation 91
Field Setting Si38-606A

b. “Setting mode 2” No. Setting item Description


Operates by Standard compressor only when inverter
Push and hold the MODE button compressor malfunctions. Temporary operation until the
0 EMG (Emergency compressor is replaced. Since the comfortability is
(BS1) for 5 seconds and set to operation 1)
“Setting mode 2”. extremely deteriorated, immediately replace the
compressor.
Cool/heat unified
1 address Sets address for cool/heat unified operation.
Low noise/demand
2 address Address for low noise/demand operation
<Selection of setting items> Indoor unit forced Allows forced operation of indoor unit fan while unit is
5
fan H stopped. (H tap)
Push the SET button (BS2) and set
the LED display to a setting item 6 Indoor unit forced Allows forced operation of indoor unit.
shown in the table on the right. operation
↓ 8 Te setting Target evaporation temperature for cooling
Push the RETURN button (BS3) and
decide the item. (The present setting 9 Tc setting Target condensation temperature for heating
condition is blinked.) Sequential
11 operation setting Sets sequential operation
External low noise
12 setting / Demand Reception of external low noise or demand signal
setting
13 AIRNET address Set address for AIRNET.
18 High static pressure Make this setting in the case of operating in high static
setting pressure mode with diffuser duct mounted.
<Selection of setting conditions> Emergency Used to operate system only with inverter compressor
operation when STD compressor malfunctions. This is a temporary
Push the SET button (BS2) and set 19 (STD compressor operation extremely impairing comfortable environment.
to the setting condition you want. operation Therefore, prompt replacement of the compressor is
↓ prohibited) required.
Push the RETURN button (BS3) and Additional
decide the condition. 20 refrigerant charge Carries out additional refrigerant charge operation.
operation setting
Refrigerant
21 recovery/
vacuuming mode Sets to refrigerant collection mode.
setting
Sets automatic nighttime low noise operation in a simple
Night-time low way.
22 noise setting The operating time is based on “Starting set” and “Ending
Push the RETURN button (BS3) and set”.
set to the initial status of “Setting Sets low noise level when the low noise signal is input
mode 2”. 25 Low noise setting from outside.
Night-time low
26 noise control Sets starting time of nighttime low noise operation.
starting setting (Nighttime low noise setting is also required.)
∗ If you become unsure of how to
proceed, push the MODE button Night-time low
27 noise control Sets ending time of nighttime low noise operation.
(BS1) and return to setting mode 1. (Nighttime low noise setting is also required.)
ending setting
Power transistor
(V2764)
check mode Used for trouble diagnosis of DC compressor. Since the
28 ∗Check after waveform of inverter is output without wiring to the
disconnection of compressor, it is convenient to probe whether the trouble
comes from the compressor or PC board.
compressor wires
If the capacity control is required, the low noise control is
29 Capacity automatically released by this setting during carrying out
precedence setting
low noise operation and nighttime low noise operation.
Changes target value of power consumption when
30 Demand setting 1 demand control 1 is input.
Normally enables demand control 1 without external
32 Normal demand input. (Effective to prevent a problem that circuit breaker
setting of small capacity is shut down due to large load.

The numbers in the “No.” column represent the number of times to press
the SET (BS2) button.

92 Test Operation
Si38-606A Field Setting

Setting item display


No. C/H selection Low Setting condition display
MODE TEST Demand
Setting item H1P H2P IND Master Slave noise H7P
H3P H4P H5P H6P ∗ Factory set
EMG (emergency
operation)
Normal operation 8777778 ∗
0 INV compressor 8 7 7 7 7 7 7
operation inhibited. Emergency operation 8777787
Address 0 8777777 ∗
1
Cool / Heat
8 7 7 7 7 7 8
Binary number 1 8777778
Unified address (6 digits) ~
31 8788888
Address 0 8777777 ∗
2
Low noise/demand
8 7 7 7 7 8 7
Binary number 1 8777778
address (6 digits) ~
31 8788888
5 Indoor forced fan H 8 7 7 7 8 7 8
Normal operation 8777778 ∗
Indoor forced fan H 8777787
6 Indoor forced
8 7 7 7 8 8 7
Normal operation 8777778 ∗
operation Indoor forced operation 8777787
High 8777877
8 Te setting 8 7 7 8 7 7 7 Normal (factory setting) 8777787 ∗
Low 8777778
High 8777877
9 Tc setting 8 7 7 8 7 7 8 Normal (factory setting) 8777787 ∗
Low 8777778
Sequential operation
11 setting 8 7 7 8 7 8 8
OFF 8777778
ON 8777787 ∗
External low noise/demand:
NO 8777778 ∗
12 External low noise/ 8 7 7 8 8 7 7
demand setting External low noise/demand:
YES
8777787
Address 0 8777777 ∗
13 Airnet address 8 7 7 8 8 7 8
Binary number 1 8777778
(6 digits) ~
63 8788888
High static pressure setting:
OFF 8777778 ∗
18 High static pressure
setting 8 7 8 7 7 8 7 High static pressure setting: 8777787
ON

Emergency OFF 8777777 ∗


19 operation 8 7 8 7 7 8 8 STD 1, 2 operation: Inhibited 8777778
(STD compressor is
inhibited to operate.) STD 2 operation: Inhibited 8777787
20 Additional refrigerant 8 7 8 7 8 7 7
Refrigerant charging: OFF 8777778 ∗
operation setting Refrigerant charging: ON 8777787
Refrigerant recovery/
21 vacuuming mode 8 7 8 7 8 7 8
Refrigerant recovery: OFF 8777778 ∗
setting Refrigerant recovery: ON 8777787
OFF 8777777 ∗
22 Night-time low noise 8 7 8 7 8 8 7
Level 1 (outdoor fan with 6 step or lower) 8777778
setting Level 2 (outdoor fan with 5 step or lower) 8777787
Level 3 (outdoor fan with 4 step or lower) 8777788
Level 1 (outdoor fan with 6 step or lower) 8777778
25 Low noise setting 8 7 8 8 7 7 8 Level 2 (outdoor fan with 5 step or lower) 8777787 ∗
Level 3 (outdoor fan with 4 step or lower) ∗ 8777877

Test Operation 93
Field Setting Si38-606A

Setting item display


No. C/H selection Low Setting condition display
Setting item MODE TEST noise Demand
H1P H2P IND Master Slave H7P
H3P H4P H5P H6P ∗ Factory set
Night-time low noise
About 20:00 8777778
26 operation start
setting
8 7 8 8 7 8 7 About 22:00 (factory setting) 8777787 ∗
About 24:00 8777877
Night-time low noise
About 6:00 8777778
27 operation end 8 7 8 8 7 8 8 About 7:00 8777787
setting
About 8:00 (factory setting) 8777877 ∗
28 Power transistor
8 7 8 8 8 7 7
OFF 8777778 ∗
check mode ON 8777787
29 Capacity
8 7 8 8 8 7 8
OFF 8777778 ∗
precedence setting ON 8777787
60 % demand 8777778
30 Demand setting 1 8 7 8 8 8 8 7 70 % demand 8777787 ∗
80 % demand 8777877
32 Normal demand
8 8 7 7 7 7 7
OFF 8777778 ∗
setting ON 8777787

94 Test Operation
Si38-606A Field Setting

c. Monitor mode LED display


No. Setting item Data display
H1P H2P H3P H4P H5P H6P H7P
To enter the monitor mode, push the Number of units for sequential
MODE button (BS1) when in
0
starting, and others 9 7 7 7 7 7 7 See below
“Setting mode 1”.
1 C/H unified address 9 7 7 7 7 7 8
2 Low noise/demand address 9 7 7 7 7 8 7
3 Not used 9 7 7 7 7 8 8
4 Airnet address 9 7 7 7 8 7 7 Lower 6 digits
Number of connected indoor units
5
*1 9 7 7 7 8 7 8
<Selection of setting item>
Number of connected zone units
Push the SET button (BS2) and set 7 (Fixed to 0) 9 7 7 7 8 8 8
the LED display to a setting item.
8 Number of outdoor units *2 9 7 7 8 7 7 7
Number of zone units (excluding
11
outdoor and BS unit) 9 7 7 8 7 8 8 Lower 6 digits

Lower 4 digits:
12 Number of indoor units *3 9 7 7 8 8 7 7 upper
Lower 4 digits:
13 Number of indoor units *3 9 7 7 8 8 7 8 lower
<Confirmation on setting contents>
Contents of malfunction (the Malfunction
Push the RETURN button (BS3) to 14
latest) 9 7 7 8 8 8 7 code table
display different data of set items. Contents of malfunction
15 9 7 7 8 8 8 8 Refer to page
(1 cycle before) 118, 119.
Contents of malfunction
16 (2 cycle before) 9 7 8 7 7 7 7
20 Contents of retry (the latest) 9 7 8 7 8 7 7
21 Contents of retry (1 cycle before) 9 7 8 7 8 7 8
22 Contents of retry (2 cycle before) 9 7 8 7 8 8 7
The numbers in the “No.” column represent the number of times to press the SET (BS2) button.
Push the RETURN button (BS3) and
switches to the initial status of
“Monitor mode”. Setting item 0 Display contents of “Number of units for sequential start,
and others”
EMG operation / ON 9 7 7 8 7 7 7
∗ Push the MODE button (BS1) and
backup operation
setting OFF 9 7 7 7 7 7 7
returns to “Setting mode 1”.
Defrost select setting Short 9 7 7 7 8 7 7
(V2765)
Medium 9 7 7 7 9 7 7
*1: Number of indoor units
Long 9 7 7 7 7 7 7
connected
Used to make setting of the Te setting H 9 7 7 7 7 8 7
number of indoor units M 9 7 7 7 7 9 7
connected to an out door unit.
L 9 7 7 7 7 7 7
*2: Number of outdoor units
connected Tc setting H 9 7 7 7 7 7 8
Used to make setting of the M 9 7 7 7 7 7 9
number of outdoor units
L 9 7 7 7 7 7 7
connected to DIII-NET that is
one of the communication
lines.
*3: Number of terminal units
Used to make setting of the
number of indoor units
connected to DIII-NET that is
one of the communication
lines.
(Only available for VRV indoor
units)

Test Operation 95
Field Setting Si38-606A

Push the SET button and match with the LEDs No. 1 - 15, push the RETURN button, and
enter the data for each setting.

★ Data such as addresses and number of units is expressed as binary numbers; the two
ways of expressing are as follows:

The No. 1 cool/heat unified address is expressed as a binary


9 797997 number consisting of the lower 6 digits. (0 - 63)
16 4 1
32 8 2
In c the address is 010110 (binary number), which translates to
16 + 4 + 2 = 22 (base 10 number). In other words, the address is
22.

977 7979
The number of terminal blocks for No. 12 and 13 is expressed as
64 16
No.12 128 32 an 8-digit binary number, which is the combination of four upper,
and four lower digits for No. 12 and 13 respectively. (0 - 128)
977 7997 In d the address for No. 12 is 0101, the address for No. 13 is
4 1 0110, and the combination of the two is 01010110 (binary
No.13 8 2 number), which translates to 64 + 16 + 4 + 2 = 86 (base 10
number). In other words, the number of terminal block is 86.

★ See the preceding page for a list of data, etc. for No. 0 - 22.

96 Test Operation
Si38-606A Field Setting

3.2.2 Setting of Low Noise Operation and Demand Operation


Setting of Low Noise Operation
By connecting the external contact input to the low noise input of the outdoor unit external
control adapter (optional), you can lower operating noise by 2-3 dB.

When the low noise operation is carried out automatically at night (The external control
adapter for outdoor unit is not required)
1. While in "Setting mode 2", select the setting condition (i.e., "Mode 1", "Mode 2", or "Mode 3")
for set item No. 22 (Setting of nighttime low noise level).
2. If necessary, while in "Setting mode 2", select the setting condition (i.e., "20:00", "22:00", or
"24:00") for set item No. 26 (Setting of start time of nighttime low noise operation).
(Use the start time as a guide since it is estimated according to outdoor temperatures.)
3. If necessary, while in "Setting mode 2", select the setting condition (i.e., "06:00", "07:00", or
"08:00") for set item No. 27 (Setting of end time of nighttime low noise operation).
(Use the end time as a guide since it is estimated according to outdoor temperatures.)
4. If necessary, while in "Setting mode 2", set the setting condition for set item No. 29 (Setting
of capacity precedence) to "ON".
(If the condition is set to "ON", when the air-conditioning load reaches a high level, the
system will be put into normal operation mode even during nighttime.)

Image of operation

Test Operation 97
Field Setting Si38-606A

Setting of Demand Operation


By connecting the external contact input to the demand input of the outdoor unit external control
adapter (optional), the power consumption of unit operation can be saved suppressing the
compressor operating condition.

Set item Condition Content


Demand Mode 1 The compressor operates at approx. 60% or less of rating.
Mode 2 The compressor operates at approx. 70% or less of rating.
Mode 3 The compressor operates at approx. 80% or less of rating.

When the normal demand operation is carried out. (Use of the external control adapter
for outdoor unit is not required.)
1. While in "Setting mode 2", make setting of the set item No. 32 (Setting of constant demand)
to "ON".
2. While in "Setting mode 2", select the set item No. 30 (Setting of Demand 1 level) and then
set the setting condition to targeted mode.

Image of operation
Power consumption When the
"Normal demand
setting" is set to ON
("OFF" has been set
Rated power consumption at factory.) , the
power consumption
80 % of rated power consumption can be set with the
70 % of rated power consumption "Demand 1 level
60 % of rated power consumption setting". ("70 % of
The power consumption set with "Demand 1 level setting". rated power
consumption" has
been set at factory.)

(V3082)

98 Test Operation
Si38-606A Field Setting

Detailed Setting Procedure of Low Noise Operation and Demand Control

1. Setting mode 1 (H1P off)


c In setting mode 2, push the BS1 (MODE button) one time. → Setting mode 1 is entered and
H1P off.
During the setting mode 1 is displayed, “In low noise operation” and “In demand control” are
displayed.

2. Setting mode 2 (H1P on)


c In setting 1, push and hold the BS1 (MODE button) for more than 5 seconds. → Setting
mode 2 is entered and H1P lights.
d Push the BS2 (SET button) several times and match the LED display with the Setting No.
you want.
e Push the BS3 (RETURN button) one time, and the present setting content is displayed.
→ Push the BS2 (SET button) several times and match the LED display with the setting
content (as shown on next page) you want.
f Push the BS3 (RETURN button) two times. → Returns to c.
g Push the BS1 (MODE button) one time. → Returns to the setting mode 1 and turns H1P off.

Test Operation 99
Field Setting Si38-606A

{: ON z: OFF 9: Blink
c d e
Setting Setting Setting No. indication Setting No. indication Setting Setting contents indication (Initial setting)
No. contents contents
H1P H2P H3P H4P H5P H6P H7P H1P H2P H3P H4P H5P H6P H7P H1P H2P H3P H4P H5P H6P H7P
12 External NO
low noise / { z z z z z z { z z { { z z (Factory { z z z z z 9
Demand set)
setting
YES { z z z z 9 z
22 Night-time OFF
low noise { z { z { { z (Factory { z z z z z z
setting setting)
Mode 1 { z z z z z 9
Mode 2 { z z z z 9 z
Mode 3 { z z z z 9 9
26 Night-time { z { { z { z PM 8:00 { z z z z z 9
low noise
start setting PM 10:00
(Factory { z z z z 9 z
setting)
PM 0:00 { z z z 9 z z
27 Night-time { z { { z { { AM 6:00 { z z z z z 9
low noise
end setting AM 7:00 { z z z z 9 z
AM 8:00
(Factory { z z z 9 z z
setting)
29 Capacity Low noise
precedence precedence
setting
{ z { { { z { (Factory
{ z z z z z 9
setting)
Capacity
precedence
{ z z z z 9 z
30 Demand 60 % of
setting 1 { z { { { { z rated power { z z z z z 9
consumption
70 % of
rated power
consumption { z z z z 9 z
(Factory
setting)
80 % of
rated power { z z z 9 z z
consumption
32 Normal OFF
demand { z z z z z z (Factory { z z z z z 9
setting setting)
ON { z z z z 9 z
Setting mode indication section Setting No. indication section Set contents indication section

100 Test Operation


Si38-606A Field Setting

3.2.3 Setting of Refrigerant Additional Charging Operation


When additional refrigerant is not charged all with outdoor unit in stop mode, operate the
outdoor unit and charge the liquid refrigerant from the service port of liquid stop value. The
additional charging operation is activated by pushbutton switch on the outdoor unit PC board.

[Additional refrigerant charge total flow]


[Additional refrigerant charge total flow]

STEP 1 Confirm LIQ & SUCTION Stop valve closed

Additional
charge Turn off the power.
without
Compressor
operation Charge through Service port of
LIQ. Stop valve.

YES
Is all refrigerant charged?

Open LIQ & SUCTION Stop


valve.

STEP 2 Open Gas Stop valve.


(Liquid side stop valve : close)

Additional Disconnect charge hose.

charge
with Start additional refrigerant
Compressor charge mode.
(Setting Mode 2 : Refer END of charge method.
operation
operation procedure detail on
next page.)

YES
Is all refrigerant charged? Open LIQUID Stop valve.

NO

STOP refrigerant charge model

(V2892)

Test Operation 101


Field Setting Si38-606A

[Operation procedure detail]


c After turning the respective remote switch of indoor and outdoor units off and charging the
refrigerant, turn on the power of indoor and outdoor units.
Do not fail to turn the power off and charge the refrigerant with outdoor unit in stop mode
before adding the refrigerant following this procedure, otherwise resulting in trouble.
d Fully open the stop valve on the gas side and do not fail to fully close the stop valve on the
liquid side. (If the stop valve on the liquid side is open, the refrigerant cannot be charged.)
e In Setting mode 2 (H1P : ON) with outdoor unit in stop mode, Set “A Additional refrigerant
charging operation” switch to ON to start the operation. (H2P turns to display TEST
OPERATION (blinks), and “TEST OPERATION” and “IN CENTRALIZED CONTROL” are
displayed on the remote controller.)
f When the refrigerant is charged up to the specified amount, press the RETURN button
(BS3) to stop charging.
The charging operation is automatically stopped after operating for a maximum of about 30
minutes.
If the charging is not complete within 30 minutes, set the A Additional refrigerant charging
operation again to start charging. When the charging immediately stops even by restarting,
the refrigerant is charged excessively. The refrigerant cannot be charged any more.
g Do not fail to fully open the stop valve on the liquid side as soon as disconnecting the
refrigerant charging hose.
(The piping may be burst due to the liquid sealing.)

[Operation state]
• Compressor frequency : 210Hz
• Y1S Solenoid valve : Open
• Outdoor unit fan : High pressure control
• Indoor unit expansion valve (All unit) : 1024 pulse
• Indoor unit fan : H tap

3.2.4 Setting of Refrigerant Recovery Mode


Since this unit is not available for pump-down operation, recover the refrigerant in this mode.
When carrying out the refrigerant collection on site, fully open the respective expansion valve of
indoor and outdoor units.

[Operation procedure]
c In setting mode 2 with units in stop mode, set “B Refrigerant Recovery / Vacuuming mode”
to ON. The respective expansion valve of indoor and outdoor units are fully opened. (H2P
turns to display “TEST OPERATION” (blinks), “TEST OPERATION” and “IN CENTRALIZED
CONTROL” are displayed on the remote controller, and the operation is prohibited.
d Collect the refrigerant using a refrigerant recovery unit. (See the instruction attached to the
refrigerant recovery unit for more detal.)
e Press Mode button “BS1” once and reset “Setting Mode 2”.

102 Test Operation


Si38-606A Field Setting

3.2.5 Setting of Vacuuming Mode


In order to perform vacuuming operation at site, fully open the expansion valves of indoor and
outdoor units to turn on some solenoid valves.

[Operating procedure]
c With Setting Mode 2 while the unit stops, set (B) Refrigerant recovery / Vacuuming mode to
ON. The expansion valves of indoor and outdoor units fully open and some of solenoid
valves open.
(H2P blinks to indicate the test operation, and the remote controller displays "Test
Operation" and "In Centralized control", thus prohibiting operation.)
After setting, do not cancel “Setting Mode 2” until completion of Vacuuming operation.
d Use the vacuum pump to perform vacuuming operation.
e Press Mode button “BS1” once and reset “Setting Mode 2”.

3.2.6 Check Operation


To prevent any trouble in the period of installation at site, the system is provided with a test
operation mode enabling check for incorrect wiring, stop valve left in closed, coming out (or
misplacing with suction pipe thermistor) of discharge pipe thermistor and judgment of piping
length, refrigerant overcharging, and learning for the minimum opening degree of motorized valve.

CHECK OPERATION FUNCTION

LED display (H1P~H7P) (8:ON 9:BLINKING 3:OFF)


Unit stopping
3383333
Press the TEST button for 5 seconds.
Step 1 Pressure equalizing
3933338
10 sec to 10 minutes

Step 2 Cooling start control


3933383
20 sec to 2 minutes
Step 3 Stability waiting operation
3933388
10 minutes
Step4~6 Judgement function
• Stop valve close check 3933833
• Wrong wiring check
3933838
• Refrigerant over change check
• Piping length check 3933883
3 minutes

Step 7 Pump down residual operation


3933888
5 minutes

Step 8 Standby for restarting


3938333
5 minutes

Completion 3383333 Normal


3883333 Abnormal

3.2.7 Power Transistor Check Operation


When the inverter system malfunctions (malfunction of inverter, INV compressor), to locate
where the malfunction occurs, switching to the power transistor check mode of inverter in the
service mode setting enables not to judge the position detection signal malfunction but to output
waveform only during inverter operation. (The waveform can be checked by disconnecting the
wiring of compressor.)

Note: Be sure to disconnect the compressor wiring when conducting the check operation mentioned
above.
When the output voltage is approx. 50 V (10 Hz) and the voltage balance between phases U-V,
V-W, W-U is within ±5%, the inverter PC board is normal.

Test Operation 103


Field Setting Si38-606A

104 Test Operation


Si38-606A

Part 6
Troubleshooting
1. Troubleshooting by Remote Controller ...............................................107
1.1 The INSPECTION / TEST Button.........................................................107
1.2 Self-diagnosis by Wired Remote Controller .........................................108
1.3 Self-diagnosis by Wireless Remote Controller .....................................109
1.4 Operation of the Remote Controller’s Inspection /
Test Operation Button ..........................................................................112
1.5 Remote Controller Service Mode .........................................................113
1.6 Remote Controller Self-Diagnosis Function .........................................115
2. Troubleshooting by Indication on the Remote Controller ....................120
2.1 “A0” Indoor Unit: Error of External Protection Device............................120
2.2 “A1” Indoor Unit: PC Board Defect ........................................................121
2.3 “A3” Indoor Unit: Malfunction of Drain Level Control System (S1L) ......122
2.4 “A6” Indoor Unit: Fan Motor (M1F) Lock, Overload...............................124
“A6” Indoor Unit: Malfunction of Indoor Unit Fan Motor.........................126
“A6” Indoor Unit: Overload / Overcurrent /
Lock of Indoor Unit Fan Motor..............................................................127
2.5 “A7” Indoor Unit: Malfunction of Swing Flap Motor (M1S).....................128
2.6 “A9” Indoor Unit: Electronic Expansion Valve
Malfunction / Dust Clogging .................................................................130
“A9” Indoor Unit: Malfunction of Electronic Expansion Valve Coil.........132
2.7 “AF” Indoor Unit: Drain Level above Limit .............................................134
2.8 “AJ” Indoor Unit: Malfunction of Capacity Determination Device ..........135
2.9 “C4” Indoor Unit: Malfunction of Thermistor (R2T) for
Heat Exchanger....................................................................................136
2.10 “C5” Indoor Unit: Malfunction of Thermistor (R3T) for Gas Pipes .........137
2.11 “C9” Indoor Unit: Malfunction of Thermistor (R1T) for Suction Air.........138
2.12 “CJ” Indoor Unit: Malfunction of Thermostat Sensor
in Remote Controller ............................................................................139
2.13 “E1” Outdoor Unit: PC Board Defect .....................................................140
2.14 “E3” Outdoor Unit: Actuation of High Pressure Switch..........................141
2.15 “E4” Outdoor Unit: Actuation of Low Pressure Sensor..........................143
2.16 “E5” Outdoor Unit: Inverter Compressor Motor Lock.............................145
2.17 “E6” Outdoor Unit: STD Compressor Motor Overcurrent/Lock..............147
2.18 “E7” Outdoor Unit: Malfunction of Outdoor Unit Fan Motor ...................148
2.19 “E9” Outdoor Unit: Malfunction of Moving Part of
Electronic Expansion Valve (Y2E)........................................................151
2.20 “F3” Outdoor Unit: Abnormal Discharge Pipe Temperature..................153
2.21 “F6” Outdoor Unit: Refrigerant Overcharged.........................................155
2.22 “H7” Outdoor Unit: Abnormal Outdoor Fan Motor Signal ......................156
2.23 “H9” Outdoor Unit: Malfunction of Thermistor (R1T) for Outdoor Air.....158
2.24 “J2” Outdoor Unit: Current Sensor Malfunction ....................................159
2.25 “J3” Outdoor Unit: Malfunction of Discharge Pipe Thermistor
(R31, 32T) ............................................................................................160
2.26 “J5” Outdoor Unit: Malfunction of Thermistor (R2T) for
Suction Pipe .........................................................................................161
2.27 “J7” Outdoor Unit: Malfunction of Liquid Pipe Thermistor (R4T)...........162
Troubleshooting 105
Si38-606A

2.28 “J9” Outdoor Unit: Malfunction of Subcooling Heat Exchanger Gas Pipe
Thermistor (R5T) ..................................................................................163
2.29 “JA” Outdoor Unit: Malfunction of High Pressure Sensor......................164
2.30 “JC” Outdoor Unit: Malfunction of Low Pressure Sensor ......................166
2.31 “L4” Outdoor Unit: Malfunction of
Inverter Radiating Fin Temperature Rise .............................................168
2.32 “L5” Outdoor Unit: Inverter Compressor Abnormal ...............................169
2.33 “L8” Outdoor Unit: Inverter Current Abnormal.......................................170
2.34 “L9” Outdoor Unit: Inverter Start up Error .............................................171
2.35 “LC” Outdoor Unit: Malfunction of Transmission between
Inverter and Control PC Board .............................................................172
2.36 “P1” Outdoor Unit: Inverter Over-Ripple Protection...............................174
2.37 “P4” Outdoor Unit: Malfunction of Inverter Radiating Fin
Temperature Rise Sensor ....................................................................175
2.38 “PJ” Outdoor Unit: Faulty Field Setting after Replacing Main PC Board or
Faulty Combination of PC Board..........................................................176
2.39 “U0” Low Pressure Drop Due to Refrigerant Shortage or
Electronic Expansion Valve Failure......................................................177
2.40 “U1” Reverse Phase, Open Phase ........................................................178
2.41 “U2” Power Supply Insufficient or Instantaneous Failure ......................179
2.42 “U3” Check Operation not Executed......................................................181
2.43 “U4” Malfunction of Transmission between Indoor Units.......................182
2.44 “U5” Malfunction of Transmission between
Remote Controller and Indoor Unit.......................................................184
2.45 “U7” Malfunction of Transmission between Outdoor Units ....................185
2.46 “U8” Malfunction of Transmission between
MAIN and SUB Remote Controllers .....................................................187
2.47 “U9” Malfunction of Transmission between Indoor and Outdoor Units in the
Same System .......................................................................................188
2.48 “UA” Excessive Number of Indoor Units ................................................190
2.49 “UC” Address Duplication of Centralized Controller...............................191
2.50 “UE” Malfunction of Transmission between Centralized Controller and
Indoor Unit............................................................................................192
2.51 “UF” System is not Set yet.....................................................................195
2.52 “UH” Malfunction of System,
Refrigerant System Address Undefined ...............................................196
3. Troubleshooting (OP: Central Remote Controller) ..............................198
3.1 “M1” PC Board Defect ...........................................................................198
3.2 “M8” Malfunction of Transmission between Optional Controllers for
Centralized Control...............................................................................199
3.3 “MA” Improper Combination of Optional Controllers for
Centralized Control...............................................................................200
3.4 “MC” Address Duplication, Improper Setting .........................................202
4. Troubleshooting (OP: Unified ON/OFF Controller) .............................203
4.1 Operation Lamp Blinks .........................................................................203
4.2 Display “Under Centralized Control” Blinks (Repeats Single Blink) .....205
4.3 Display “Under Centralized Control” Blinks (Repeats Double Blink) ....208

106 Troubleshooting

You might also like