0% found this document useful (0 votes)
54 views3 pages

EPI User manual for easy configuration at Site

The document provides detailed instructions for configuring an EPI flow meter, including unlocking the meter, changing the cross-section area, configuring pulse output, resetting the totalizer, and adjusting the C-factor. It also outlines steps for setting up Modbus parameters such as address, baud rate, and parity. A connection diagram for RS485 Modbus communication is included, emphasizing the use of appropriate cabling for effective communication.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
54 views3 pages

EPI User manual for easy configuration at Site

The document provides detailed instructions for configuring an EPI flow meter, including unlocking the meter, changing the cross-section area, configuring pulse output, resetting the totalizer, and adjusting the C-factor. It also outlines steps for setting up Modbus parameters such as address, baud rate, and parity. A connection diagram for RS485 Modbus communication is included, emphasizing the use of appropriate cabling for effective communication.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 3

A) EPI Instructions against the changing of cross section area, C-factor and to

check the full scale flow:


Basically there are 4 keys “Shift”, “Mode”, “UP”, “Down” function are as follows.

Shift = To Enter to any particular menu or to shift left when changing values.
Mode = To Change main mode/menu or to shift right when changing values.
UP = To Increase sub Menu/Value.
Down = To Decrease sub menu/Value.

1st step: Meter unlock: (meter unlock required every time when you need to change anything in flow meter)

Press “Mode” twice you will see menu 200 at the upper line of display and 201 at the lower line. Now, press “Up”
key till menu 219 reaches.

Press “Shift” to enter to the menu, the word “9” now using “Mode” button skip to next word and by using “Up” key
enter value “0” (The password is 9001) type the password in the same manner and then by further pressing “Mode”
key you can auto exit the menu and your meter will be unlocked.

2nd step: Changing of Cross Section Area: (only required when calibrated line size and actual line size is different.)

After above meter unlock press “Mode” key to reaches to the menu “800” at the top of the line and “801” at the
bottom line. Now by “Up” Key move to the menu “813”, press “Shift” to enter in the menu. As per manual the cross
section area of 3 Inch line size will be configured which is “0.00477 m2” by using “Mode” & “Up” / “Down” Keys
change this value to “0.00821 m2” which is the cross section area for 4 Inch (Sch 40) pipe size and in the same way
by further pressing “Mode” button you can exit from this menu # 813.

3rd step: Configuration of Pulse output for Terberg (If required): (normally for all AESL meter Pulse already
configured from EPI, USA)

Now, after exiting from menu 813, where “800” is at the upper line and “813” at the lower line your meter is still
unlocked and you can do the further changing as required, now by using “Down” key you can decrease the lower line
menu till 801 then further decreasing by using “Down” key the lower line shows other menu and you will have to go
at menu # 400 at lower line, then press “Shift” key, menu # 400 will appear at the upper line an 401 will appear at
the lower line, press “Shift” to enter to menu # 401 put the value as follows and exit all the menus by using “Mode”
Key.

Menu # 401 = 1
Menu # 407 = 2
Menu # 401 = 2
Menu # 410 = 1

Connection diagram is provided in the “EPI Imp Papers” file, which are 10 & 11 at the above strip.

4th step: full scale Value & Meter totalizer RESET: (this RESET required when you need to Zero the Total flow)

In the same way mentioned above at menu # 410, start pressing “Down” key your lower menus will start decreasing
press it till menu # 100 appears at lower line, then press “Shift” key, now menu # 100 will appear at upper line and
“101” will appear at lower line by using “Up” key you can go to menu # 140 and by pressing “Shift” key you can enter
to the menu # 140, this menu will show you the maximum flow range @ 20 mA output, this simply means that this if
you want this output at any other totalizer / Screen you can see it remotely.

Note: you can decrease this output range as per requirement but can’t increase it due to the pre-calibration of
flow velocity.

Now, exit this menu by using “Mode” or “Shift” key and by using “Up” key go to menu # 160 which is next to menu #
140 and press “Shift” your meter’s Totalizer value will be Zero.
5th step: Changing of C-Factor (menu # 811) (if required): (Please do not change this menu without consulting
Innovative Engineers, Inc)

Reference with the manual the value of C-Factor should be “0.868” for ½” OD probe at 4 Inch line size (Sch 40), but
currently (since 2013) EPI is configuring the value of “1” for C-factor, initially you should not require to change this C-
Factor and observe the flow results against the power generation but if you observe that the results should be 0.275
Nm3/Kw and currently its 0.285 Nm3/Kw, this could be happened due to the following reasons.

 In correct installation, like insertion or direction.


 Due to disturbed flow profile, not taking care of 10xDia at upstream & 5xDia at Down Steam
 More bends, which are disturbing flow profile.
 Mole % Composition is natural gas is disturbed and not as per calibrated

Due to all above reasons the results could be varied, that’s why you can decrease the C-Factor between 1 ~ 0.868
(not further), to get the accurate required results of 0.275 Nm3/hr.

B) Configuration of Modbus Parameters at EPI flow meter with its connection


diagram:
First you will have to inform the RS485 Modbus Dynamic Data registers and its details to the person who is retrieving
data on the other end / Panel End. The major details are as follows.
The dynamic data available:
40001 – 40002: flow rate (convert Hex to 32 bit IEEE 754 Encoded)
40003 – 40004: flow total (convert Hex to 32 bit IEEE 754 Encoded)

Now, you will required to ask the following from M/s: Enercon to configure it at your EPI flow Meter.

1) Modbus Address / Nod ID: ( Normally Enercon ask it to set at “1”)


2) RS485 Baud Rate: (Normally Enercon Ask it to set at “19,200” menu Value = 0 or 3)
3) RS485 Parity: (Normally Enercon Ask it to set at “None” menu Value = 0)

Follow Step # 1 to unlock the flow meter:


Complete meter unlocking is mentioned above at step # 1 follow it and then do the following.

Step # 2: (Configuration of Modbus Address / Nod ID):


After unlocking the meter press “Mode” key 2 times to go to the menu # 200 at the upper line and menu # 201 at
the lower line. Start pressing “max” key till it reaches to the “Menu # 210” at the lower line. Press “shift” Key at
“Menu 210” to enter in to the menu. Now by using “max” key set the Value “1” and press “Mode” key 2/3 times you
will get out of this menu.

Step # 3: (Configuration of RS485 Baud Rate):


After exiting “Menu # 210” at step # 1, Press “Max” key till you reaches to “Menu # 226” , Press “Shift Key” to enter
to the menu and set the Value “0” or “3” (both means the same baud rate of 19,200) now, press “Mode” or “Shift
Key” till you exit this menu.

Step # 4: (Configuration of RS485 Parity):


After Exiting “Menu # 226”, press “Max” key further to go to the “Menu # 233”, Press “Shift” key to enter in to the
“Menu # 233” now by using “Max” or “Min” key place the Value “0” to make Parity “None”. Press “Mode” or “Shift
Key” till you exit this menu.

Step # 5: (To Exit to the main Screen):


Now at “Menu # 233” press “Min” key till you see “Menu # 500” at the lower line of the screen, Press “Shift” key
Menu # 500 the flow meter main scree will be shown normally.
Connection Diagram for RS485 Modbus Communication:
Only use Twisted pair, Shielded breaded cable, of 2 core + 1 Ground/drain (Shield) Modbus
Communication cable (normally 0.6 ~ 0.7 mm thickness cable is being used at this application).

You might also like