Main Protection Relay and associated / auxiliary supply system Reinfocement work for TATA primary,
L&T primary and permanent Package Units.
AP – Approved AEN – Approved Except as Noted NA – Not Approved RET – If the documents
has been returned
Comments: ______________________________________________________________
Item Approval
Drawing/Document CSD No. Drawing/Document Title Rev.
No. Status
Method Statement for Power Transformer Differential and
1. A14235.2- CA-7000-M-002 REF Stability, Sensitivity Test (Typical-33/11kV Primary B NA
Substation)
Method Statement for Power Transformer Differential and
2. A14235.2- CA-7000-M-013 REF Stability, Sensitivity Test (Typical-33/11kV Package Unit B NA
Substation)
Comment: Reply:
1 Contractor not using stepdown transformer at site to carry out Step down transformer is required only for Primary
the transformer stability test. Kindly revise the method statement substation were the injecting point at 11kV side to
without step down transformer reduce the injecting current. Step down transformer is
not required at Package unit as per shown in the SLD.
Same methodlogy has been followed in previous
commissioned feeders.
2 20MVA transformers also present in the network. Accordingly 20MVA transformer is not available for Tata PY and PU
revise the method statement for SC currents of these substation, this is applicable only for L&T Station were
transformers already the calculation has been included in DTS 167.
3 Final Trip test & primary injection of CT circuit to be added in Already primary injection typical test report is submitted
sequence of test along with the test formats is submitted in DTS108 Rev-A. Also final trip test is
added in primary injection report. Same is attached in
annexure-1 is for your refernce.
4 Include the list of the stations where 11kv bus shutdown is 11kV bus shut down is not required to perform the
required to perform transformer stability test Transformer stability test.
5 Include all previous comment sheets along with the compliance Noted and included.
in next revision
Signature
Page 1 of 1
Main Protection Relay and associated/auxiliary supply
system Reinforcement Work for TATA primary, L&T
primary and permanent Package Units.”
CONTRACT NO. A – 14235.2
Comments:
1. Contractor not using stepdown transformer at site to carry out the transformer stability test.Kindly revise
the method statement without step down transformer.
2. 20 MVA transformers also present in the network. Accordingly revise the method statement for SC
currents of these transformers.
3. Final Trip test & primary injection of CT circuit to be added in sequence of test along with the test
formats.
4. Include the list of the stations where 11kv bus shutdown is required to perform transformer stability test.
5. Include all previous comment sheets along with the compliance in next revision.
Signed Signed
............................................. ….............................................
For GOPA- intec For AADC
Cc: AADC Projects Delivery Division Manager
Note: The above comments and/or approval in no way relieves the Contractor from his obligations in the Contract to ensure conformance to the
Specification as well as any modifications found necessary by AADC / GOPA- intec during installation for satisfactory commissioning
and operation of equipment works on contract. Any deviations from the Specification found subsequent to approval are to be corrected by
the Contractor to the satisfaction of AADC/GOPA- intec
Method Statement for Power Transformer Differential and REF Stability, Sensitivity Test Page 1 of 1
Main Protection Relay and associated/auxiliary supply
system Reinforcement Work for TATA primary, L&T
1 A NA - See Below
2 A NA - See Below
STATUS: AP = Approved, AEN = Approved except as noted, NA = Not approved, NR = Approval not required
RET = Drawing returned with this DTSCOM sheet (Yes/No)
Comments:
1. Contractor replies to previous comment no 4 is not acceptable. Kindly submit the station wise
method statement to clearly identify Point of isolation, Feeder Reference, GIS Name,
Primary/Additional Earth Requirements, which is required by AADC to process the shutdown
applications.
2. Refer to previous comment 7, contractor reply is incomple.Kindly mention detail procedure to
connect the external cable in 11kv CB rack out position along with the HSE requirements to operate
the switchgear shutter.
3. All other comments reply is noted.
Signed Signed
.............................................
For GOPA- intec For AADC
Cc: AADC Projects Delivery Division Manager
Note: The above comments and/or approval in no way relieves the Contractor from his obligations in the Contract to ensure conformance to the
Specification as well as any modifications found necessary by AADC / GOPA- intec during installation for satisfactory commissioning
and operation of equipment works on contract. Any deviations from the Specification found subsequent to approval are to be corrected by
the Contractor to the satisfaction of AADC/GOPA- intec
Method Statement for Power Transformer Differential and REF Stability, Sensitivity Test Page 1 of 1
Main Protection Relay and associated/auxiliary supply
system Reinforcement Work for TATA primary, L&T
primary and permanent Package Units.”
CONTRACT NO. A – 14235.2
1. PDF Page 6 of 67 Clause No.4. Of References /drawings /Standards, kindly include Transformer
marshalling box drawing, 11kV & 33kV Switchgear drawings.
2. Layout drawing with clear identification of placement of generator, step down transformer & cable laid up
to the switchgear terminations shall be submitted along with the method statement. Please include.
3. On page no.7 of 67 of Roles & responsibility of contractor staff kindly include Lead engineer role to carry
out the final checking as per approved GA drawing and as per the manufacturer recommendation. Safety
officer shall verify all prerequisites as per AADC HSE requirement prior to stability test and issue
clearance to start the testing. Please confirm and same shall be included in the method statement.
4. Details of work procedure mentioned on Page no.8 of 67 related to method statement is without any
equipment ID/Feeder detail /CB ID /DS ID of 33kV & 11kV switchgears. Please note that method
statement cannot be generic one .Kindly submit station wise method statement with equipment
designations as per as built SLD.
5. Contractor shall confirm the presence of OEM relay (approved) Engineer, AADC & Elmec engineer during
the test.
6. Three phase line drawing shall be provided for both Diff & REF stability and sensitivity testing to know
the way of connection of power supply to transformer for testing as well as panel selection for shorting.
7. Point of isolation & primary earthing point shall be clearly mentioned in the method statement
8. 33kV side and 11kV side ammeter reading shall consider in the format.
Note: The above comments and/or approval in no way relieves the Contractor from his obligations in the Contract to ensure conformance to the
Specification as well as any modifications found necessary by AADC / GOPA- intec during installation for satisfactory commissioning
and operation of equipment works on contract. Any deviations from the Specification found subsequent to approval are to be corrected by
the Contractor to the satisfaction of AADC/GOPA- intec
Method Statement for Power Transformer Differential and REF Stability, Sensitivity Test Page 1 of 2
Main Protection Relay and associated/auxiliary supply
system Reinforcement Work for TATA primary, L&T
primary and permanent Package Units.”
CONTRACT NO. A – 14235.2
9. 11kV injection point between CT & CB pole is not clear to us. Kindly elaborate further with proper method
statement showing physical arrangement of this connection details with photographs as per site condition to
avoid any consequences during execution at site.
10. Contractor shall take reading of REF as well as SBEF relay to ensure that there is no current flow to these
relays during transformer stability and sensitivity test.
11. Since transformer stability considering a primary injection of NCTs, the NCT terminals short and isolating
facility shall be verified during testing. Also WTI, REF & SBEF CT reading shall be included in the
format.
11. Measurement shall be taken from SWGR CT terminals as well as MK panel CT terminals. Kindly update
the test format for these reading in both REF & SBEF protection.
12. after transformer sensitivity test, stability test of the transformer as well as REF shall perform in all three
tap position (1st, 9th and 17th).please confirm.
13. Before proceeding this stability & sensitivity we have to complete Final Setting adaption & Testing.Please
confirm.
14. Kindly add OEM Engineer Signature in the footer of all pages of the document and ensure that OEM
engineer shall sign all document.
Signed Signed
............................................. ….............................................
For GOPA- intec For AADC
Cc: AADC Projects Delivery Division Manager
Note: The above comments and/or approval in no way relieves the Contractor from his obligations in the Contract to ensure conformance to the
Specification as well as any modifications found necessary by AADC / GOPA- intec during installation for satisfactory commissioning
and operation of equipment works on contract. Any deviations from the Specification found subsequent to approval are to be corrected by
the Contractor to the satisfaction of AADC/GOPA- intec
Method Statement for Power Transformer Differential and REF Stability, Sensitivity Test Page 2 of 2
GOPA-Intel STAMP
REVISIONS
ENGINEER:
Global Ascent Business Centre, P.O. Box: 93820 Abu Dhabi, U.A.E.
Tel: 02 555 0013
Fax: 02 555 0017
CONTRACTOR:
P.O. Box: 732, Abu Dhabi, U.A.E. Tel: 02 6262800, Fax: 02 6269871
CONTRACT TITLE:
Main Protection Relay and associated / auxiliary supply system Reinfocement work
for TATA primary, L&T primary and permanent Package Units
`
CLIENT:
AL AIN DISTRIBUTION COMPANY
(AADC)
MAIN CONTRACTOR:
ELECTRO MECHANICAL CO LLC (AGENTS FOR SIEMENS AG)
PO BOX:732, ABU DHABI,U.A.E
Table of Contents
1. Introduction .................................................................................................................................... 3
2. Scope (Work, Project Location) ...................................................................................................... 3
Contract .............................................................................................................................................. 3
Location ............................................................................................................................................... 3
Work.................................................................................................................................................... 3
3. Duration .......................................................................................................................................... 3
4. References / Drawings / Standards ................................................................................................ 4
5. Roles and Responsibilities ............................................................................................................... 4
Competent Person .............................................................................................................................. 4
Workmen ............................................................................................................................................ 5
6. Resources ........................................................................................................................................ 5
Manpower ........................................................................................................................................... 5
Materials & Equipment ....................................................................................................................... 5
7. Details of Work Procedure .............................................................................................................. 6
Transformer Stability, Sensitivity & REF test ...................................................................................... 6
8. Risk Assessment .............................................................................................................................. 7
9. Emergency Procedures ................................................................................................................... 8
In case of major Injuries ...................................................................................................................... 8
In case of fire ....................................................................................................................................... 8
First Aid ............................................................................................................................................... 8
Hospitals.............................................................................................................................................. 9
Emergency Contact ............................................................................................................................. 9
10. Daily Process Checks ................................................................................................................... 8
11. Annexure ..................................................................................................................................... 9
1. Introduction
This method statement provides the required guidelines to perform Power Transformer differential
and REF stability, sensitivity test at AL AIN primary Substation under Contract A14235.2 with
necessary safety and controls that shall be identified in risk assessment for maximum personnel
safety.
Location
33/11kV Switchgears at AL AIN primary (TATA) Substation
H03
H10
H03
H10
H03
3 Towayya Primary TWYA-PY
H07
H03
4 Al Saad Primary SAAD-PY
H07
Work
Power Transformer (HXX – represent 33 kV Transformer Feeder & KXX – represent 11 kV Incomer
Feeder) Differential and REF stability, sensitivity test.
3. Duration
1 working days
Definitions
Lead Engineer
To allocate sufficient resources, manpower and equipment, for the execution of the work in
a safe manner and in accordance with all contract requirements. Report to the Project
Manager.
To carry out to carry out the final checking as per approved GA drawing and as per the
manufacturer recommendation.
Competent Person
Start the work only after read, understand, receiving the safety documents.
Supervise 100% all activities as per safety document
Ensuring all necessary documents to perform the work and follow the approved method
statement.
Plan the necessary personnel and material resources.
Present at site all time while work in progress under the permit.
In case if the CP must leave the site due to any urgency, he shall stop the work, clear the site
activities and inform the authorized person.
In case of any doubt on the work, he shall suspend the work until he gets clarified.
Before the start of work, he must carry out toolbox talk with the workmen the hazards,
precautions, and the adopted control measures.
Ensure proper PPE of the work men and communicates the emergency procedures.
Safety Officer.
Safety officer shall verify all prerequisites as per AADC HSE requirement prior to stability test
and issue clearance to start the testing
Workmen
Wearing appropriate PPEs.
Understanding and following the instructions given by line staff.
No horseplay and shortcuts.
6. Resources
Manpower
Competent Person – 1
Technician – 2
Helper - 1
Trained person should perform testing as per AADC SSR
Supervision – all work will be carried out under supervision of competent person with site
representative.
The below steps are Mandatory to follow daily on basis before starting any work,
Obtain the approval from the DMS and SFT for work.
Conduct the toolbox talk to the people involved in the work.
Before entering the room, change the CO2 switch control to manual mode
Barricade the safe work area and fix warning signs as applicable
The work shall be carried out by Competent Person approved by AADC
Inform DMS with valid permit number before start the work.
Check all Existing alarm and condition of S/S before starting any work.
AADC Operation Engineer shall confirm isolation of bay.
Obtain Transformer feeder 33kV and 11kV switchgear shutdown with test Permit (SFT) in PY
Substation.
SWITCHING SEQUENCE:
Confirm 11kV side Bay K06 Incomer Feeder Q0 (CB) is withdrawn and kept in rack out
position.
Ensure all the CT secondary circuits are closed and there is no open circuit in CT for 11kV side
K06 Incomer Feeder.
Test setup Establishment and Transformer Differential and REF Stability sensitivity test:
1. Connect the 3 Phase 415 V AC Generator supply through step down transformer to 11kV
side K06 Incomer switchgear cable compartment (as per Test setup SLD and layout drawing).
2. While connecting the generator cable (for 220V LV Supply) proper clearance distance to be
maintained and insulated tools and hand glove to be used.
3. 33kV BB protection will be blocked by AADC during stability sensitivity test.
4. Switch on the Injection & Apply the 400 V AC supply in 11kV side K06 Incomer Feeder to
33kV side H03 Transformer as per test setup SLD
5. Measure the Differential CT circuits Secondary current in the Relay Terminal at 11kv & 33kv
side as per the SAT & Record the Value.
6. Record the Relay primary current, Differential & Restraining Current as per the SAT Report.
7. Now Reverse the 33kV R PH CT in the Terminal block & Record all the Measurement as per
the SAT Report.
Document No: A14235.2 CA 7000 M 002 REV.B P a g e | 6 of 9
CONTRACT No. A-14235.2
Keep Q0, Q1& Q5 Open position in 33kV side H03 Transformer Feeder & Ensure there is no open
circuit in CT.
Rack out the 11kV CB and Open the Earth switch in 11 kV K06 Incomer Feeder; ensure there is
no open circuit in CT.
Connect the 1 Phase 230V AC supply to 11kV side K06 Incomer switchgear cable compartment as
per test setup SLD.
Short 3 Ø in 33kV side through Earth switch via CB(Q0) in 33kV H03 Transformer feeder as per
attached SLD.
Keep the Tap Position 9 (Normal Tap) in the 15 MVA Transformer.
8. Risk Assessment
The Risks for the described job are the specific risks of the 33kV/11kV Switchgears and with Low
Voltage equipment
There is no risk of trip as the corresponding feeders are under shutdown and there is no risk
of disturbance to Protection relays, device or control circuit under work.
9. Emergency Procedures
In case of major Injuries
Do not panic. Call ambulance and notify emergency team at site.
Do not move the injured unless he is in danger.
If danger exists, he shall be assessed by a trained and qualified first aider before moving. Use
a stretcher
Do not crowd around the victim. Do not give anything to eat or drink. Ensure adequate air
and lighting.
Only trained and qualified first aider shall treat the victim and ensure that his airway is kept
clear.
Victim shall be transported to hospital in an ambulance.
Preserve the accident scene for further investigation.
In case of fire
Follow AADC’s approved emergency procedure as per HSE Plan.
First Aid
First aid kit available in Switchgear room.
Further treatment to be sought after first aid treatment.
Hospitals
AL AIN Hospital
Emergency Contact
Police: 999
Ambulance: 998
Fire Department (Civil Defence): 997
11. Annexure
33/11kV Transformer Differential and REF test setup Single Line Diagram
SAT Procedure
Documentary Category.:
TEST REPORT FOR TRANSFORMER DIFF & REF STABILITY / SENSITIVITY TEST for TATA PRIMARY SS (Typical)
MANUFACTURER AEG
CONTINOUS MAXIMUM RATING 15MVA
TRANSFORMER RATIO 33kV/ 11KV SIDE (Ur) 33kV/11.5kV
RATED CURRENT 33kV / 11KV SIDE (Ir) at
262/750
Normal Tap
% IMPEDENCE Volts 9.62
TRANSFORMER VECTOR GROUP DYn11
NUMBER OF TAPS 17
NOMINAL TAP 9b
TRANSFORMER SR.NO
220 V, 3phase Applied through 400V/220V step down Transformer on 11kV Side & 33kV Side Shorted.
CURRENT ON 33 kV SIDE:
I 33KV = (Calculated 11KV SIDE Current * 11KV SIDE Rated Current)/ 33KV SIDE Rated Current
= (149 *262 / 750) =52 A
5. TEST FORMAT FOR STABILTY AND SENSITIVITY TEST FOR TRANSFORMER DIFFERENTIAL RELAY BY USING THREE PHASE INJECTION:
a. Injected Phase: R-Y-B Short Circuit current in 33kV: 52 A Short Circuit Current in 11.5kV: 149 A
Primary Current Measured at 33KV Side Primary Current Measured at 11KV side Differential protection Relay Display Diff & Rest. current
Relay Display(A) Relay Display(A) (I/Ino)
Phases R Y B N R Y B N Differential current Restraining Current
IL1 IL2 IL3 3I0 IL1 IL2 IL3 3I0
L1 L2 L3 L1 L2 L3
Terminal Reference M1 M1 M1 M1 M2 M2 M2 M2
R Phase CT Normal
R Phase CT Reversal at 33KV
Side
R Phase CT Reversal at 11KV
side
R Phase CT Normal
b. Injected Phase: R-Y-B Short Circuit current in 33kV: 52 A Short Circuit Current in 11.5kV: 149 A
Primary Current Measured at 33KV Side Primary Current Measured at 11KV side Differential protection Relay Display Diff & Rest. current
Relay Display(A) Relay Display(A) (I/Ino)
TESTED BY TESTED BY WITNESSED BY WITNESSED / APPROVED BY
Signature Signature Signature Signature
Name Name Name Name
Date Date Date Date
Relay Approved Engineer INTEC GOPA AADC
ELMEC
Page 4 of 14
Documentary Category.:
Y Phase CT Normal
Y Phase CT Normal
c. Injected Phase: R-Y-B Short Circuit current in 33kV: 52 A Short Circuit Current in 11.5kV: 149 A
Primary Current Measured at 33KV Side Primary Current Measured at 11KV side Differential protection Relay Display Diff & Rest. current
Relay Display(A) Relay Display(kA) (I/Ino)
B Phase CT Normal
B Phase CT Normal
6. TEST FORMAT FOR STABILTY AND SENSITIVITY TEST FOR 11KV SIDE REF PROTECTION RELAY:
11KV SIDE Secondary Current Measured at Terminals (mA) Current Measured Measured Measured Relay
REF O/P Secondary Secondary Secondary Display
Inj. Phase After Current/Volt Current/Vol Current/Vol current 87-
:R-E Summatio age at tage at tage at R
51/N (SBEF)
Transformer Marshalling Box Control and Protection Panel
27 28
11kV SIDE Y Phase X10-7 X10-6 TB4-81 TB4-80
400/220V, 3 Phase
step Down Transformer
Close
Close
Current
injection point
in cable
compartment
Site survey report at Towayya Primary (TWYA-PY)
Date: 09/09/2020 A14235.2-CA-7600-G-035
Page 13 of 16
4 x 50 Sqmm Cable
EMPLOYER CONTRACTOR ENGINEER
Annexure-1
SITE ACCEPTANCE TEST
CONTRACT No. A-14235.2
Main Protection Relay and associated / auxiliary supply system
Reinfocement work for TATA primary, L&T primary and
permanent Package Units.
Contractor: ELMEC Equipment:
Client: AADC Feeder :
Substation: Date :
TEST REPORT FOR CT PRIMARY INJECTION
CT – T1 CT – T91 CT – T1 CT – T91
Core-No.
(1S1-1S2-1S3) (1S1-1S2-1S3) (2S1- 2S2- 2S3) (2S1- 2S2)
Core data
CORE 1 CORE 1 CORE 2 CORE 2
Nominal Power VA VA VA VA
Class PX 10P10 PX
Uknee,
Imag
Rct.
Star Point Towards Bus(4S1) Towards Bus(4S1) Towards Bus (4S1) Towards Bus (4S1)
Precaution taken:
Confirm no open circuit in all the CT secondary circuits.
Test procedure:
1. Normalize all the CT secondary circuit terminals & confirm, there is no open circuit in the CT secondary circuit.
2. Inject a small current from R-E and confirm, corresponding secondary current appears for OC/EF CT91 T1
core.
3. Increase the primary current to the required level – minimum 10% of the CT rated current, measure the
secondary currents at various points for OC/EF CT91 T1 core and record the readings.
4. Connect the primary injection kit across R–Y,R-B phases and follow step 2,3
R–E 300
R–Y 300
R-B 300
1) Core Identification Checked - R: Ok, Y: Ok, B: Ok, 1S1-E, 1S2-E, and 1S1-1S2
2) Single point Earthing Checked : Ok
3) CT Star Point: 1S2 towards Protected Object (Bus): Ok
4) Final Trip Test by Primary injection: Ok
2. Instruments used:
3. Reference:
4. Remarks:
Risk Assessment
Project : Main Protection Relay and Associated / Auxiliary Supply System Reinforcement
Work for TATA Primary, L & T Primary and Permanent Package Units
Project No : A-14235.2
Activity : POWER TRANSFORMER DIFFERENTIAL AND REF STABILITY, SENSITIVITY TEST
Revision :0
HSE RISK ASSESSMENT
Risk Accept
Risk Rating Refer to Hierarchy of control Measures Residual Risk
able
Potential
S/N Activity Hazard
Harm/Damages
Rating
H/M/L
(P*S)
P S Existing Controls P S R Y/N
1 Site acceptance • Un Authorized entry • Personal Injury. 3 3 9 1.1. Testing area shall be separated with warning signage and 1 3 3 L Y
testing of 33kV • Obstacles in the • Property Damage. barriers. Standby man shall be provided.
protection function. access. 1.2. Authorized personnel shall be deployed for the work.
Protection Relay • Improper testing 1.3. valid calibration certificate holding equipment shall be used
testing. equipment. for testing
Axillary Relay. • Poor Lighting. 1.4 Proper and adequate lighting shall be ensured.
TCS Scheme. 1.5. Access and egress shall be kept free from obstacles.
Trip Logic. 1.6. Appropriate (electric Insulated) PPE to be worn.
1.7. Workers deployed for testing and nearby working crew shall
be inducted activities, safety measures and emergency procedure
through the TBT prior to start work.
1.8.Athorised competent engineer shall conduct the testing
activities and Competent supervision shall be ensured.
2 Working on Step • Falling from Ladder. • Personal Injury. 3 2 6 2.1.Sutable ladder to be used for testing activity. 1 2 2 L Y
ladder •Unauthorized entry. • Property Damage. 2.2.Tools or materials Shall not be carry while climbing the
ladder.
2.3. Ladder shall be in good condition and inspected before use.
2.4. Ensure ladder placed properly and level ground.
2.5. Working area shall be barricaded with proper signage,
standby watchman to be provided.
3 Using hand tools. • Improper hand tools. •Personal Injury. 3 2 6 3.1. All hand tools shall be inspected prior to use. 1 2 2 L Y
• Damaged Hand • Property Damage. 3.2. Any defect occurring during the work, tool shall be removed
Tools. from site.
3.3.Ensure appropriate tools(electric insulated) shall be used for
testing activity.
Page 1 of 4
Project : Main Protection Relay and Associated / Auxiliary Supply System Reinforcement
Work for TATA Primary, L & T Primary and Permanent Package Units
Project No : A-14235.2
Activity : POWER TRANSFORMER DIFFERENTIAL AND REF STABILITY, SENSITIVITY TEST
Revision :0
HSE RISK ASSESSMENT
Risk Accept
Risk Rating Refer to Hierarchy of control Measures Residual Risk
able
Potential
S/N Activity Hazard
Harm/Damages
Rating
H/M/L
(P*S)
P S Existing Controls P S R Y/N
4 Cable differential •Electrocution • Personal Injury. 3 3 9 5.1. Competent person shall operate the testing equipment. 1 3 3 L Y
stability test. • Electric shock. • Property Damage. 5.2. Valid Calibration certificate holding equipment to be used for
• Unauthorized entry. testing.
• Fire Hazard. 5.3. Testing equipment shall be inspected for proper working
before use.
5.4. Ensure all connection in the test circuit are tight before use.
5.5. Testing equipment to be earthed where ever it is required.
5.6. Double insulated tools shall be used wherever possible.
5.7. Sing boards indicating “un authorized entry prohibited” shall
be fixed in the testing area.
5.8. Testing Area (Basement Ground floor) shall be barricaded
and standby person and suitable sign boards to be fixed.
5.9. While testing the other end of the cable shall be barricaded
and standby personnel shall be provided.
5.10. Cable end to be isolated to prevent accidental contact.• HI
POT kit vehicle parked area shall be barricaded with warning
signage.
5.11. Testing equipment shall be Switched off after every use and
secure at safe place.
5.12. Proper cable management shall be followed.
5 Using Diesel • Electric shock • Personal Injury. 3 3 9 6.1. Diesel Generator shall be kept inside barricade. 1 3 3 L Y
Generator for • Fire • Property Damage. 6.2. Pre-use Inspection check list of Generator to be maintained.
Testing. • Fuel spillage. 6.3. Generator to be properly grounded and turned off at the end
of the shift.
6.4. Ensure the generator operating area free from flammable and
combustible materials.
6.5. Drip tray to be provided to the generator for spillage
prevention.
6.6. Suitable fire extinguishers shall be provided near the DG.
Page 2 of 4
Project Main Protection Relay and Associated / Auxiliary Supply System Reinforcement
Work for TATA Primary, L & T Primary and Permanent Package Units
Project No A-14235.2
Activity POWER TRANSFORMER DIFFERENTIAL AND REF STABILITY, SENSITIVITY TEST
Revision 0
RISK MATRIX
SEVERITY
PROBABILITY
INSIGNIFICANT (1) MINOR (2) MODERATOR (3) MAJOR (4) CATASTROPHIC (6)
RARE (1) 1 2 3 4 5
POSSIBLE (2) 2 4 6 8 10
LIKELY (3) 3 6 9 12 15
OFTEN (4) 4 8 12 16 20
FREQUENT/ALMOST CERTAIN 5 10 15 20 25
15-25 EXTREME RISK Absolutely unacceptably high Activity or Industry should not proceed in current form
Unacceptably high Activity or Industry should be modified to include remedial planning and action and be Subject to detailed EHS
8-12 HIGH RISK
assessment.
Acceptable but must be Manage at AS LOW AS REASANABLY PRACTICABLE(ALARP)
4-6 MODERATE RISK
Activity or industry can operate Subject to Management and/or Modification
1-3 LOW RISK Acceptable without required further actionNo action required unless escalation of risk is possible.
Hierarchy of Control (Controls Identified May be a Mixture of the hierarchy in order to provide minimum operator exposure)
ELIMINATION Eliminate the hazard
SUBSTITUTION Provide an alternative that is capable of performing the same task and is safer to use.
ENGINEER CONTROL Provide or construct a physical barrier or guard or technical measures.
Develop policies, procedures practices and guidelines in consultation with employees to mitigate the risk provide training instruction and
ADMINISTRATIVE CONTROL
supervision about the hazard.
PERSONAL PROTECTIVE EQUIPMENT. Personal equipment designed to protect the individual from the hazard.
Page 4 of 4
GOPA-Intel STAMP
REVISIONS
ENGINEER:
Global Ascent Business Centre, P.O. Box: 93820 Abu Dhabi, U.A.E.
Tel: 02 555 0013
Fax: 02 555 0017
CONTRACTOR:
P.O. Box: 732, Abu Dhabi, U.A.E. Tel: 02 6262800, Fax: 02 6269871
CONTRACT TITLE:
Main Protection Relay and associated / auxiliary supply system Reinfocement work
for TATA primary, L&T primary and permanent Package Units
`
CLIENT:
AL AIN DISTRIBUTION COMPANY
(AADC)
MAIN CONTRACTOR:
ELECTRO MECHANICAL CO LLC (AGENTS FOR SIEMENS AG)
PO BOX:732, ABU DHABI,U.A.E
Table of Contents
1. Introduction .................................................................................................................................... 3
2. Scope (Work, Project Location) ...................................................................................................... 3
Contract .............................................................................................................................................. 3
Location ............................................................................................................................................... 3
Work.................................................................................................................................................... 4
3. Duration .......................................................................................................................................... 4
4. References / Drawings / Standards ................................................................................................ 4
5. Roles and Responsibilities ............................................................................................................... 4
Competent Person .............................................................................................................................. 4
Workmen ............................................................................................................................................ 5
6. Resources ........................................................................................................................................ 5
Manpower ........................................................................................................................................... 5
Materials & Equipment ....................................................................................................................... 5
7. Details of Work Procedure .............................................................................................................. 6
Transformer Stability, Sensitivity & REF test ...................................................................................... 6
8. Risk Assessment .............................................................................................................................. 7
9. Emergency Procedures ................................................................................................................... 8
In case of major Injuries ...................................................................................................................... 8
In case of fire ....................................................................................................................................... 8
First Aid ............................................................................................................................................... 8
Hospitals.............................................................................................................................................. 9
Emergency Contact ............................................................................................................................. 9
10. Daily Process Checks ................................................................................................................... 8
11. Annexure ..................................................................................................................................... 9
1. Introduction
This method statement provides the required guidelines to perform Power Transformer differential
and REF stability, sensitivity test at AL AIN Package Unit Substation under Contract A14235.2 with
necessary safety and controls that shall be identified in risk assessment for maximum personnel
safety.
Location
33/11kV Switchgears at AL AIN Package Unit Substation
Work
Power Transformer (H02 – represent 33 kV Transformer Feeder & M04 – represent 11 kV Incoming
Feeder) Differential and REF stability, sensitivity test.
3. Duration
1 working days
Definitions
Lead Engineer
To allocate sufficient resources, manpower and equipment, for the execution of the work in
a safe manner and in accordance with all contract requirements. Report to the Project
Manager.
To carry out to carry out the final checking as per approved GA drawing and as per the
manufacturer recommendation.
Competent Person
Start the work only after read, understand, receiving the safety documents.
Supervise 100% all activities as per safety document
Ensuring all necessary documents to perform the work and follow the approved method
statement.
Plan the necessary personnel and material resources.
Present at site all time while work in progress under the permit.
In case if the CP must leave the site due to any urgency, he shall stop the work, clear the site
activities and inform the authorized person.
In case of any doubt on the work, he shall suspend the work until he gets clarified.
Before the start of work, he must carry out toolbox talk with the workmen the hazards,
precautions, and the adopted control measures.
Ensure proper PPE of the work men and communicates the emergency procedures.
Safety Officer.
Safety officer shall verify all prerequisites as per AADC HSE requirement prior to stability test
and issue clearance to start the testing
Workmen
Wearing appropriate PPEs.
Understanding and following the instructions given by line staff.
No horseplay and shortcuts.
6. Resources
Manpower
Competent Person – 1
Technician – 2
Helper - 1
Trained person should perform testing as per AADC SSR
Supervision – all work will be carried out under supervision of competent person with site
representative.
The below steps are Mandatory to follow daily on basis before starting any work,
Obtain the approval from the DMS and SFT for work.
Conduct the toolbox talk to the people involved in the work.
Before entering the room, change the CO2 switch control to manual mode
Barricade the safe work area and fix warning signs as applicable
The work shall be carried out by Competent Person approved by AADC
Inform DMS with valid permit number before start the work.
Check all Existing alarm and condition of S/S before starting any work.
AADC Operation Engineer shall confirm isolation of bay.
Obtain Transformer feeder 33kV and 11kV switchgear shutdown with test Permit (SFT) in PU
Substation.
SWITCHING SEQUENCE:
Confirm 11kV side Bay M04 Incomer Feeder Q0 (CB) is withdrawn and kept in rack out
position
Ensure all the CT secondary circuits are closed and there is no open circuit in CT for 11kV side
M04 Incomer Feeder.
External Primary Earth to be provided from cable compartment R,Y,B shown as per test setup
SLD.
Test setup Establishment and Transformer Differential and REF Stability sensitivity test:
1. Connect the 3 Phase 415 V AC Generator supply through step down transformer to 33kV
side H02 switchgear cable compartment (as per Test setup SLD).
2. Switch on the Injection & Apply the 400 V AC supply in 33kV side Transformer H02 Feeder to
11kV side Incomer feeder M04 as per test setup SLD
3. While connecting the generator cable proper clearance distance to be maintained and
insulated tools and hand glove to be used.
4. Measure the Differential CT circuits Secondary current in the Relay Terminal at 11kv & 33kv
side as per the SAT & Record the Value.
5. Record the Relay primary current, Differential & Restraining Current as per the SAT Report.
6. Now Reverse the 33KV R PH CT in the Terminal block & Record all the Measurement as per
the SAT Report.
7. Normalize the 33KV R PH CT.
8. Now Reverse the 11KV R PH CT in the Terminal block & Record all the Measurement as per
the SAT Report.
9. Normalize the 11KV R PH CT.
10. Take the Final reading for R phase Transformer Stability.
11. Switch OFF the AC power supply in Generator.
12. Repeat the Same point- 6 to point -14 for Y ph & B Ph Stability
8. Risk Assessment
The Risks for the described job are the specific risks of the 33kV/11kV Switchgears and with Low
Voltage equipment
There is no risk of trip as the corresponding feeders are under shutdown and there is no risk
of disturbance to Protection relays, device or control circuit under work.
9. Emergency Procedures
In case of major Injuries
Do not panic. Call ambulance and notify emergency team at site.
Do not move the injured unless he is in danger.
If danger exists, he shall be assessed by a trained and qualified first aider before moving. Use
a stretcher
Do not crowd around the victim. Do not give anything to eat or drink. Ensure adequate air
and lighting.
Only trained and qualified first aider shall treat the victim and ensure that his airway is kept
clear.
Victim shall be transported to hospital in an ambulance.
Preserve the accident scene for further investigation.
In case of fire
Follow AADC’s approved emergency procedure as per HSE Plan.
First Aid
First aid kit available in Switchgear room.
Further treatment to be sought after first aid treatment.
Hospitals
AL AIN Hospital
Emergency Contact
Police: 999
Ambulance: 998
Fire Department (Civil Defence): 997
11. Annexure
33/11kV Transformer Deferential and REF test setup Single Line Diagram
TEST REPORT FOR TRANSFORMER DIFF & REF STABILITY / SENSITIVITY TEST for PU(Typical)
5. TEST FORMAT FOR STABILTY AND SENSITIVITY TEST FOR TRANSFORMER DIFFERENTIAL RELAY BY USING THREE PHASE INJECTION:
a. Injected Phase: R-Y-B Short Circuit current in 33kV: 33.06 A Short Circuit Current in 11.5kV: 94.4 A
Primary Current Measured at 33KV Side Primary Current Measured at 11KV side Differential protection Relay Display Diff & Rest. current
Relay Display(A) Relay Display(A) (I/Ino)
Phases R Y B N R Y B N Differential current Restraining Current
IL1 IL2 IL3 3I0 IL1 IL2 IL3 3I0
L1 L2 L3 L1 L2 L3
Terminal Reference M1 M1 M1 M1 M2 M2 M2 M2
R Phase CT Normal
R Phase CT Reversal at 33KV
Side
R Phase CT Reversal at 11KV
side
R Phase CT Normal
b. Injected Phase: R-Y-B Short Circuit current in 33kV: 33.06 A Short Circuit Current in 11.5kV: 94.4 A
Primary Current Measured at 33KV Side Primary Current Measured at 11KV side Differential protection Relay Display Diff & Rest. current
Relay Display(A) Relay Display(A) (I/Ino)
Y Phase CT Normal
Y Phase CT Normal
c. Injected Phase: R-Y-B Short Circuit current in 33kV: 33.06 A Short Circuit Current in 11.5kV: 94.4 A
Primary Current Measured at 33KV Side Primary Current Measured at 11KV side Differential protection Relay Display Diff & Rest. current
Relay Display(A) Relay Display(kA) (I/Ino)
B Phase CT Normal
B Phase CT Normal
6. TEST FORMAT FOR STABILTY AND SENSITIVITY TEST FOR 11KV SIDE REF PROTECTION RELAY:
11KV SIDE Secondary Current Measured at Terminals (mA) Current Measured Measured Measured Relay
REF O/P Secondary Secondary Secondary Display
Inj. Phase After Current/Volt Current/Vol Current/Vol current 87-
:R-E Summatio age at tage at tage at R
51/N (SBEF)
11kV SIDE Y Phase Transformer Marshalling Box Control and Protection Panel
27 28
X10-7 X10-6 TB4-81 TB4-80
11KV SIDE Secondary Current Measured at Terminals (mA) Current Measured Measured Measured Relay
REF O/P Secondary Secondary Secondary Display
Inj. Phase After Current/Volt Current/Vol Current/Vol current 87-
:R-E Summatio age at tage at tage at R
Open
400/220V, 3 Phase
Generator Open
Current Injection
Point In Cable
Compartment.
Site survey report at Wadi Suliami PU (WDSL-PU)
Date: 27/08/2020 A14235.2-CA-7600-G-199
Page 11 of 13
EMPLOYER CONTRACTOR ENGINEER
Earth Point
4 x 50 Sqmm Cable
EMPLOYER CONTRACTOR ENGINEER
Annexure-1
SITE ACCEPTANCE TEST
CONTRACT No. A-14235.2
Main Protection Relay and associated / auxiliary supply system
Reinfocement work for TATA primary, L&T primary and
permanent Package Units.
Contractor: ELMEC Equipment:
Client: AADC Feeder :
Substation: Date :
TEST REPORT FOR CT PRIMARY INJECTION
CT – T1 CT – T91 CT – T1 CT – T91
Core-No.
(1S1-1S2-1S3) (1S1-1S2-1S3) (2S1- 2S2- 2S3) (2S1- 2S2)
Core data
CORE 1 CORE 1 CORE 2 CORE 2
Nominal Power VA VA VA VA
Class PX 10P10 PX
Uknee,
Imag
Rct.
Star Point Towards Bus(4S1) Towards Bus(4S1) Towards Bus (4S1) Towards Bus (4S1)
Precaution taken:
Confirm no open circuit in all the CT secondary circuits.
Test procedure:
1. Normalize all the CT secondary circuit terminals & confirm, there is no open circuit in the CT secondary circuit.
2. Inject a small current from R-E and confirm, corresponding secondary current appears for OC/EF CT91 T1
core.
3. Increase the primary current to the required level – minimum 10% of the CT rated current, measure the
secondary currents at various points for OC/EF CT91 T1 core and record the readings.
4. Connect the primary injection kit across R–Y,R-B phases and follow step 2,3
R–E 300
R–Y 300
R-B 300
1) Core Identification Checked - R: Ok, Y: Ok, B: Ok, 1S1-E, 1S2-E, and 1S1-1S2
2) Single point Earthing Checked : Ok
3) CT Star Point: 1S2 towards Protected Object (Bus): Ok
4) Final Trip Test by Primary injection: Ok
2. Instruments used:
3. Reference:
4. Remarks:
Risk Assessment
Project : Main Protection Relay and Associated / Auxiliary Supply System Reinforcement
Work for TATA Primary, L & T Primary and Permanent Package Units
Project No : A-14235.2
Activity : POWER TRANSFORMER DIFFERENTIAL AND REF STABILITY, SENSITIVITY TEST
Revision :0
HSE RISK ASSESSMENT
Risk Accept
Risk Rating Refer to Hierarchy of control Measures Residual Risk
able
Potential
S/N Activity Hazard
Harm/Damages
Rating
H/M/L
(P*S)
P S Existing Controls P S R Y/N
1 Site acceptance • Un Authorized entry • Personal Injury. 3 3 9 1.1. Testing area shall be separated with warning signage and 1 3 3 L Y
testing of 33kV • Obstacles in the • Property Damage. barriers. Standby man shall be provided.
protection function. access. 1.2. Authorized personnel shall be deployed for the work.
Protection Relay • Improper testing 1.3. valid calibration certificate holding equipment shall be used
testing. equipment. for testing
Axillary Relay. • Poor Lighting. 1.4 Proper and adequate lighting shall be ensured.
TCS Scheme. 1.5. Access and egress shall be kept free from obstacles.
Trip Logic. 1.6. Appropriate (electric Insulated) PPE to be worn.
1.7. Workers deployed for testing and nearby working crew shall
be inducted activities, safety measures and emergency procedure
through the TBT prior to start work.
1.8.Athorised competent engineer shall conduct the testing
activities and Competent supervision shall be ensured.
2 Working on Step • Falling from Ladder. • Personal Injury. 3 2 6 2.1.Sutable ladder to be used for testing activity. 1 2 2 L Y
ladder •Unauthorized entry. • Property Damage. 2.2.Tools or materials Shall not be carry while climbing the
ladder.
2.3. Ladder shall be in good condition and inspected before use.
2.4. Ensure ladder placed properly and level ground.
2.5. Working area shall be barricaded with proper signage,
standby watchman to be provided.
3 Using hand tools. • Improper hand tools. •Personal Injury. 3 2 6 3.1. All hand tools shall be inspected prior to use. 1 2 2 L Y
• Damaged Hand • Property Damage. 3.2. Any defect occurring during the work, tool shall be removed
Tools. from site.
3.3.Ensure appropriate tools(electric insulated) shall be used for
testing activity.
Page 1 of 4
Project : Main Protection Relay and Associated / Auxiliary Supply System Reinforcement
Work for TATA Primary, L & T Primary and Permanent Package Units
Project No : A-14235.2
Activity : POWER TRANSFORMER DIFFERENTIAL AND REF STABILITY, SENSITIVITY TEST
Revision :0
HSE RISK ASSESSMENT
Risk Accept
Risk Rating Refer to Hierarchy of control Measures Residual Risk
able
Potential
S/N Activity Hazard
Harm/Damages
Rating
H/M/L
(P*S)
P S Existing Controls P S R Y/N
4 Cable differential •Electrocution • Personal Injury. 3 3 9 5.1. Competent person shall operate the testing equipment. 1 3 3 L Y
stability test. • Electric shock. • Property Damage. 5.2. Valid Calibration certificate holding equipment to be used for
• Unauthorized entry. testing.
• Fire Hazard. 5.3. Testing equipment shall be inspected for proper working
before use.
5.4. Ensure all connection in the test circuit are tight before use.
5.5. Testing equipment to be earthed where ever it is required.
5.6. Double insulated tools shall be used wherever possible.
5.7. Sing boards indicating “un authorized entry prohibited” shall
be fixed in the testing area.
5.8. Testing Area (Basement Ground floor) shall be barricaded
and standby person and suitable sign boards to be fixed.
5.9. While testing the other end of the cable shall be barricaded
and standby personnel shall be provided.
5.10. Cable end to be isolated to prevent accidental contact.• HI
POT kit vehicle parked area shall be barricaded with warning
signage.
5.11. Testing equipment shall be Switched off after every use and
secure at safe place.
5.12. Proper cable management shall be followed.
5 Using Diesel • Electric shock • Personal Injury. 3 3 9 6.1. Diesel Generator shall be kept inside barricade. 1 3 3 L Y
Generator for • Fire • Property Damage. 6.2. Pre-use Inspection check list of Generator to be maintained.
Testing. • Fuel spillage. 6.3. Generator to be properly grounded and turned off at the end
of the shift.
6.4. Ensure the generator operating area free from flammable and
combustible materials.
6.5. Drip tray to be provided to the generator for spillage
prevention.
6.6. Suitable fire extinguishers shall be provided near the DG.
Page 2 of 4
Project Main Protection Relay and Associated / Auxiliary Supply System Reinforcement
Work for TATA Primary, L & T Primary and Permanent Package Units
Project No A-14235.2
Activity POWER TRANSFORMER DIFFERENTIAL AND REF STABILITY, SENSITIVITY TEST
Revision 0
RISK MATRIX
SEVERITY
PROBABILITY
INSIGNIFICANT (1) MINOR (2) MODERATOR (3) MAJOR (4) CATASTROPHIC (6)
RARE (1) 1 2 3 4 5
POSSIBLE (2) 2 4 6 8 10
LIKELY (3) 3 6 9 12 15
OFTEN (4) 4 8 12 16 20
FREQUENT/ALMOST CERTAIN 5 10 15 20 25
15-25 EXTREME RISK Absolutely unacceptably high Activity or Industry should not proceed in current form
Unacceptably high Activity or Industry should be modified to include remedial planning and action and be Subject to detailed EHS
8-12 HIGH RISK
assessment.
Acceptable but must be Manage at AS LOW AS REASANABLY PRACTICABLE(ALARP)
4-6 MODERATE RISK
Activity or industry can operate Subject to Management and/or Modification
1-3 LOW RISK Acceptable without required further actionNo action required unless escalation of risk is possible.
Hierarchy of Control (Controls Identified May be a Mixture of the hierarchy in order to provide minimum operator exposure)
ELIMINATION Eliminate the hazard
SUBSTITUTION Provide an alternative that is capable of performing the same task and is safer to use.
ENGINEER CONTROL Provide or construct a physical barrier or guard or technical measures.
Develop policies, procedures practices and guidelines in consultation with employees to mitigate the risk provide training instruction and
ADMINISTRATIVE CONTROL
supervision about the hazard.
PERSONAL PROTECTIVE EQUIPMENT. Personal equipment designed to protect the individual from the hazard.
Page 4 of 4