Line Distance Protection_091526
Line Distance Protection_091526
Relay checks
Ok,Yes,No
Visual Inspection Yes
Relay damaged No
Rating information correct for installation Yes
Case earth installed Yes
Test block connections checked Yes
Relay energized
Measured auxiliary supply Yes
Relay healthy (green) LED working Yes
Trip (red) LED working Yes
Line Data
Rated Frequency 50 Hz
VT Ratio 132 kV / 110 V
CT Ratio 1600 / 1 A
Broken Conductor
Threshold: 0.25 Time Setting: 0.0 s
Trip Test
Phase Current (A) Phase Angle Measured Trip Actual Trip time (s)
time(s)
R 1.25 A 0
Y 0.90 A 226.10 1.031 sec 1.0 sec
B 0.90 A 133.90
SOTF
X/Ω
30
20
10
-10
-20
-10 0 10 20 30 40
R/Ω
X/Ω
30
20
10
-10
-20
-10 0 10 20 30 40
R/Ω
X/Ω
30
20
10
-10
-20
-10 0 10 20 30 40
R/Ω
X/Ω
30
20
10
-10
-20
-10 0 10 20 30 40
R/Ω
X/Ω
30
20
10
-10
-20
-10 0 10 20 30 40
R/Ω
X/Ω
30
20
10
-10
-20
-10 0 10 20 30 40
R/Ω
X/Ω
30
20
10
-10
-20
-10 0 10 20 30 40
R/Ω
Remarks:
All testing results are found satisfactory. Line differential protection is disabled in relay. VT Fuse fail alarm not shown in SCADA.