57-SDMS-01 (1)
57-SDMS-01 (1)
57-SDMS-01 Rev. 00
SEC DISTRIBUTION MATERIALS SPECIFICATION
DATE: April 2017G
57-SDMS-01
REV. 00
SPECIFICATIONS
FOR
TABLE OF CONTENTS
1.0 SCOPE
4.1 General
4.2 Ratings and Performance Characteristics
4.3 Materials
5.0 TESTS
Page 2 of 13
Saudi Electricity Company الشركة السعودية للكھرباء
57-SDMS-01 Rev. 00
SEC DISTRIBUTION MATERIALS SPECIFICATION
DATE: April 2017G
1.0 SCOPE
This SEC Distribution Material Standard Specification (SDMS) specifies the minimum
technical requirements for design, engineering, manufacture, inspection, testing and
performance of Indoor/Outdoor Neutral Grounding Resistor rated 11 kV up to 34.5 kV,
intended to be used in the Distribution Network of Distribution Sector of the Saudi
Electricity Company, Saudi Arabia.
This Material Standard Specification shall always be read in conjunction with SEC
General Specification No. 01-SDMS-01, titled "General Requirements for All
Equipment/Materials", which shall be considered as an integral part of this SDMS.
This SDMS shall also be read in conjunction with SEC Purchase Order or Contract
Schedules for project, as applicable.
The latest revision/amendments of the following Codes and Standards shall be applicable
for the equipment/material covered in this SDMS. In case of conflict, the
vendor/manufacturer may propose equipment/material conforming to one group of
Industry Codes and Standards quoted hereunder without jeopardizing the requirements of
this SDMS.
3.3 IEC 62271-200 A.C Metal Enclosed Switchgear and Controlgear for Rated
Voltage above 1 kV and up to and including 52 kV
3.5 IEC 60137 Insulated Bushings for Alternating Voltages above 1000
Volts
3.6 IEC 60273 Characteristics of Indoor and Outdoor Post Insulators for
Systems with Nominal Voltages greater than 1000 volts
Page 3 of 13
Saudi Electricity Company الشركة السعودية للكھرباء
57-SDMS-01 Rev. 00
SEC DISTRIBUTION MATERIALS SPECIFICATION
DATE: April 2017G
3.7 IEC 60168 Tests on Indoor and Outdoor Post Insulators of Ceramic
Material or Glass for Systems with Nominal Voltages greater
than 1000 volts
4.1 General
4.1.1 The Neutral Grounding Resistor shall meet or exceed the requirements of
this specification in all respects.
4.1.3 The Neutral Grounding Resistor shall be designed for outdoor / Indoor use.
4.3 Materials
4.3.1 Enclosure
Page 4 of 13
Saudi Electricity Company الشركة السعودية للكھرباء
57-SDMS-01 Rev. 00
SEC DISTRIBUTION MATERIALS SPECIFICATION
DATE: April 2017G
d. The enclosure shall have four lifting eyebolts on top with minimum
hole diameter of 20mm for balanced lifting.
a. The neutral bushing with M12 brass stud in an air insulated cable box
shall be mounted on the side of the enclosure with undrilled
removable gland plate and cover. The cable box shall be suitable for
terminating the incoming cable(s), and shall house one current
transformer (or more as specified in DATA SCHEDULE). The CT(s)
ratings as approved by SEC shall be wired down to a terminal box
mounted between 1.0 m to 1.5 m height from ground level.
b. For neutral bushing mounted on the top cover, the enclosure shall be
mounted on a plinth or structure to raise the height of the bushing 2.5
meters from the ground level to avoid accidental contact. The steel
plinth shall be part of supply.
d. The NGR shall have provision for connection of neutral of more than
one transformer (in parralel) as specified in DATA SCHEDULE.
A ground terminal bushing with M12 brass stud shall be provided through
the enclosure wall for the resistor earth connection to the substation earth
mesh. The connection between the resistor and earth mesh shall be through.
Page 5 of 13
Saudi Electricity Company الشركة السعودية للكھرباء
57-SDMS-01 Rev. 00
SEC DISTRIBUTION MATERIALS SPECIFICATION
DATE: April 2017G
a terminal with M12 brass stud and shall be suitable to accept a 240mm2
hard drawn circular stranded copper conductor to form part of the earth grid
mesh.
b. The ends of each resistor element made of stainless steel alloy shall
be connected by tig weld or connected by nickel plated copper
jumpers using two bolts per joint.
4.3.5 Nameplate
Page 6 of 13
Saudi Electricity Company الشركة السعودية للكھرباء
57-SDMS-01 Rev. 00
SEC DISTRIBUTION MATERIALS SPECIFICATION
DATE: April 2017G
5.0 TESTS
Neutral Grounding Resistor shall be tested in accordance with the latest relevant referenced
standards and as specified herein. The assigned serial number of the Neutral Grounding
Resistor shall be engraved on its body before testing to ensure the proper identity of the
equipment to be tested. All test results shall be provided for review and approval of SEC.
5.1.1 All type (design) tests prescribed in the relevant IEC and ANSI/IEEE
standards shall be performed on the first unit of every new design, rating
and size of Neutral Grounding Resistor to be supplied to SEC. The
following type tests, which are not covered by ANSI/IEEE 32 and
IEC60529 shall be performed :
a. Measurement of Degree of Protection of Enclosure.
b. Temperature Rise Test
c. Measurement of Resistance Value at Stable Temperature.
Page 7 of 13
Saudi Electricity Company الشركة السعودية للكھرباء
57-SDMS-01 Rev. 00
SEC DISTRIBUTION MATERIALS SPECIFICATION
DATE: April 2017G
5.2.1 All routine (production) tests prescribed in the relevant IEC and
ANSI/IEEE standards, shall be performed on each Neutral Grounding
Resistor. Test results shall be provided for review and acceptance/approval
by SEC prior to delivery. The following Routine tests, which are not
covered by ANSI/IEEE 32, shall be performed:
Page 8 of 13
Saudi Electricity Company الشركة السعودية للكھرباء
57-SDMS-01 Rev. 00
SEC DISTRIBUTION MATERIALS SPECIFICATION
DATE: April 2017G
4.3 Material
Enclosure
IP code *
Type of material *
Weight ( kg) *
Neutral Bushing
Manufacturer *
Type *
Page 9 of 13
Saudi Electricity Company الشركة السعودية للكھرباء
57-SDMS-01 Rev. 00
SEC DISTRIBUTION MATERIALS SPECIFICATION
DATE: April 2017G
Page 10 of 13
Saudi Electricity Company الشركة السعودية للكھرباء
57-SDMS-01 Rev. 00
SEC DISTRIBUTION MATERIALS SPECIFICATION
DATE: April 2017G
Material *
Rated Voltage ( kV rms) *
Power Frequency Voltage (kV rms) *
Power Frequency Withstand Voltage (kV rms) *
Nos.
Type *
CT Ratio *
Accuracy Class *
Burden (VA) *
Short Time Withstand Current Rating ( kA/s) *
*
Resistance Grid
Manufacturer
Type of elements *
No. of Resistor Bank *
No. of Resistor Bank *
Guaranteed Resistance ± 10 % (Ohm) *
Rated Short –Time Withstand Current Rating *
(kA rms)
Rated Duration of Short Circuit (sec) *
Temperature Coefficient of Resistance at 20
°C *
Guaranteed steady State Hotspot Temperature
Rise (20 °C) *
Page 11 of 13
Saudi Electricity Company الشركة السعودية للكھرباء
57-SDMS-01 Rev. 00
SEC DISTRIBUTION MATERIALS SPECIFICATION
DATE: April 2017G
Dimensions:
Enclosure with HV Cable Box:
Height (mm) *
Width (mm) *
Depth (mm) *
Page 12 of 13
Saudi Electricity Company الشركة السعودية للكھرباء
57-SDMS-01 Rev. 00
SEC DISTRIBUTION MATERIALS SPECIFICATION
DATE: April 2017G
(Page 6 of 6)
Date
Page 13 of 13