ELECTRICITY UTILITIES SPECIFICATION E10
CONTENTS
1- Scope 2
2- Definitions 2
3- Classification 3
4- Requirements 4
5- Marking 21
7- Sampling 23
8- Method of test 23
10- Delivery 24
12- Guarantee 26
13- Submittals 27
Last Page 38
- 1- Control Panels
ELECTRICITY UTILITIES SPECIFICATION E10
CONTROL PANELS
1- SCOPE
2- DEFINITIONS
Control panels shall be any form of board , cabinet , panel , box , case ,
etc. , used for protection or to contain of group instrumentation ,
telemetering equipment , control equipment , annunciation and alarm
equipment or mimic diagrams for a system .
- 2- Control Panels
ELECTRICITY UTILITIES SPECIFICATION E10
3- CLASSIFICATION
3.4 LOCATION
- 3- Control Panels
ELECTRICITY UTILITIES SPECIFICATION E10
4- REQUIREMENTS
- 4- Control Panels
ELECTRICITY UTILITIES SPECIFICATION E10
2- Atmospheric Temperature °C :-
Maximum mean daily 47*
Minimum mean daily -5
Yearly mean 30
3- Relative humidity %
Maximum relative humidity 100
Minimum relative humidity 20
Average relative humidity 75
Daily mean 95
- 5- Control Panels
ELECTRICITY UTILITIES SPECIFICATION E10
Parameter Value
Temperature
- Rated 30° C
Relative humidity.
- 6- Control Panels
ELECTRICITY UTILITIES SPECIFICATION E10
- 7- Control Panels
ELECTRICITY UTILITIES SPECIFICATION E10
- 8- Control Panels
ELECTRICITY UTILITIES SPECIFICATION E10
- 9- Control Panels
ELECTRICITY UTILITIES SPECIFICATION E10
1- Frequency Hz 50
2- Configuration 3phase
earthed through
3- Neutral arrangement resistance
4- Service system voltage KV r.m.s 22
5- Rated system voltage for equipment KV r.m.s 24
6- Rated short-time withstand current. KA r.m.s 25
7- Rated duration of short circuit . sec. 3
8- Rated peak withstand current. KA 63
9- Lightning impulse withstand voltage 1.2/50 s (LIWL) KV peak 125
10- One minute power frequency withstand voltage
KV r.m.s 50
11- Min. specific leakage path cm/KV service voltage for :
lightning arrester 4.5
Post insulator, disc insulator and equipment:-
Outdoor cm/KV 3.5
Indoor cm/KV 2.5
Inside metal clad switchgear cm/KV 2
1- Frequency Hz 50
2- Configuration 3phase
earthed through
3- Neutral arrangement resistance
4- Service system voltage KV r.m.s 11
5- Rated system voltage for equipment KV r.m.s 12
6- Rated short-time withstand current. KA r.m.s 25
7- Rated duration of short circuit . sec. 3
8- Rated peak withstand current. KA 63
9- Lightning impulse withstand voltage 1.2/50 s (LIWL) KV peak 75
10- One minute power frequency withstand voltage
KV r.m.s 28
11- Min. specific leakage path cm/KV service voltage for :
lightning arrester 4.5
Post insulator, disc insulator and equipment:-
Outdoor cm/KV 3.5
Indoor cm/KV 2.5
Inside metal clad switchgear cm/KV 2
- EUS
- IEC recommendations .
- Other referenced codes and standards .
- Acceptable alternative codes and standards .
4.4 DESIGN
4.4.1 GENERAL DESCRIPTION
4.4.1.1 The control panels shall be completely wired and assembled with
all instruments , devices and controls installed so that entire
assembly is an operatable unit ready for installation in the field .
The instruments , devices and controls required shall be detailed
by the purchaser under separate specification . The instrument
and control terminals (including all spare contacts) shall be wired
to terminal blocks for field connection in accordance with the
relevant loop and schematic diagrams . All accessories not herein
specified or mentioned, but which are required to complete the
control panels shall be supplied by the manufacturer .
4.4.2 CABINETS
Cabinets shall not be less than 600mm wide and the depth shall
not exceed the width . The height shall not exceed 2300mm . The
width between apparatus mounted on the cabinet side walls shall
be sufficient to provide full and easy access to all terminals and
to apparatus mounted in the front panel . Relays and other
sensitive equipment shall not be fitted on hinged panels and
A lamp (AC power) shall be fitted inside each cabinet and shall
be so arranged that all wiring is illuminated evenly without
dazzle . The lamp shall be controlled by a door switch . A switch
for the purpose of isolation the supply to the lamp shall be
provided . In addition , when requested in the tender .
Adequate single and three phase outlets for tools and testing
equipment shall be provided where necessary . Cabinets shall be
floor mounted and provision shall be made for bottom entry of
cables .Removable gland plates of an approved type, non-
flammable , insulating , vermin – proof material shall be
provided. The gland plates shall be drilled on site to suit the
cables . Blank glands for the number of cables required to enter
the cabinet in the ultimate development of the station shall be
provided . All cables shall enter vertically from below . The
cabinets shall be sealed at their point of entry . Panels shall be
ventilated (vermin proof) for cooling of internal components . A
built in fan may be used if necessary . However , failure of the
fan to operate should activate an alarm .
4.4.3 Condensation
4.4.5.1 General
4.4.9 Painting
4.4.9.1 General
4.4.9.2 Painting
5- MARKING
* Degree of protection .
* Dimensions .
* Weight .
6.1 Testing
6.1.1 General
All material shall be tested in accordance with the latest standards and as
specified herein .
The supplier shall provide acceptable type test certificates for his
material .
If the supplier has carried out type tests on the offered equipment in the
last ten years according to the relevant standard then the supplier shall
provide type test certificates for the approval of the purchases, other
wise type tests have to be carried out .
6.2 Inspection :
The purchaser has the right to witness tests or to visit the factory during
manufacture of any or all items covered by this specification .
Accordingly , the supplier shall give the purchaser adequate notice of
manufacturing and test schedules .
7- SAMPLING
One unit of each different design shall be subjected to the type testing
8- METHOD OF TESTS
Any item not meeting the type test requirements shall result in rejection
of all units on order .
In case of rejection , the purchaser shall not be liable for the cost of type
tests .
The purchaser , at his discretion , may allow the supplier to carry out
repeat type tests to prove his design , but any such repeat tests shall be at
the supplier’s expense .
Any item not meeting the routine test requirements shall be rejection .
10- DELIVERY
Panels shall be skid mounted for shipping . Panels and all other
equipment shall be packaged so that it will arrive at the site undamaged
by handling or weather . Temporary wood or steel braces , guides ,
skids, crates or other shipping devices necessary for transporting the
finished panels shall be furnished by the manufacturer . Lifting lugs
shall be provided .
10.2 Delivery
12- GUARANTEE
13- SUBMITTALS
14.1 The control panels shall be completely wired and assembled , with all
instruments , devices and controls installed so that the entire assembly is
an operable unit ready for installation in the field .
15.1 Tenderer shall submit a reference list that the proposed equipment have
been in successful operation in an integrated system for a period of three
years minimum on three different substations of same or higher capacity
outside country of manufacture and / or in EEHC network for a period
not less than three years during the last ten years .The experience of
manufacturer and the submanufacturers shall be evaluated on the above
basis .
ENQURY SCHEDULES
SCHEDULE 1
Enquiry Schedules
( To be completed purchaser )
DESCRIPTION REQUIRED
SIGNED : ____________
COMPANY : ____________
SCHEDULE 2
1. General requirements
Switchboard arrangement :
SIGNED : ____________
COMPANY : ____________
POSITION IN COMPANY : ____________
DATE : ____________ _____________
COMPANY STAMP
FIGURES