Features :
3Ø (True RMS) Voltage
3Ø (True RMS) Current
Frequency
Run hour (Hour - Mins)
RPM
Programmable CT/PT Primary/Secondary
Certifications :
96 x 96 mm
Technical specifications
Display specifications
Display 3 Rows, LED Display
Digit 3
Digit height 0.58" (14.7 mm)
Input specifications
Electrical connection 3Ø-4W, 3Ø-3W, 2Ø-3W, 1Ø-2W
Input voltage rated 11 to 300V AC, (Phase to neutral), 19 to 519V AC, (Phase to phase)
Input current rated Nominal 5A (Min-30mA, Max-6A)
Frequency 50 or 60 Hz
Display scrolling Automatic / Manual (Programmable)
RPM 1350 - 1950 [Pole: 0 (Range: 0 - 98, Selectable in steps of 2), Frequency: 45 - 65Hz]
Resolution Current & voltage: Depending on CT & PT RPM: 0.1, Run Hour: 0.1hr
Voltage(L-N/L-L): ±0.5% of F.S. ±2 digit
Average Voltage (L-N / L-L): ±0.5% of F.S. ±2 digit
Current: ±1% of F.S. ±2 digit
Accuracy Average current: ±1% of F.S. ±2 digit
Frequency: ±0.1Hz ±1digit
Run Hour: ±1%
RPM: ±0.5%
1) 3Ø Voltage (L-N, L-L, Avg.)
2) 3Ø Current (I1, I2, I3, Avg.)
Measurements 3) Frequency
4) RPM
5) Run hour
Supply specifications
Auxiliary supply 230V AC, ±20% (50/60Hz), 110V AC, ±20% (50/60Hz)
Burden 0.5VA @ 5A Per phase
Settable Parameters
CT Primary 5A to 10,000A (Programmable for any value)
CT Secondary 1A/5A (Programmable)
PT Primary 100V to 500kV (Programmable for any value)
PT Secondary 100 to 500V AC (L-L) (Programmable for any value)
Environment specifications
Operating: -10ºC to +55ºC
Temperature
Storage: -20ºC to +75ºC
Humidity (Non - condensing) Upto 85% RH
www.selec.com 1
VAF Meters - Digital VAF39A-1
Mechanical specifications
Mounting Panel mount
Weight 344gm
91.5mm
90.5mm
99mm
L1 L
L2 O
99mm 5mm 50mm 91.5mm
L3 A
Front bezel Side view Panel cutout
N D
S1 S2 S1 S2 S1 S2 N V1 V2 V3
I1 I2 I3
www.selec.com 2