flowmeterdata
flowmeterdata
ENGINEERING
Venturi Styles
MODEL-K METERS
-- RATING 500 PSI -- -- RATING 275 PSI --
(Buttweld, Grooved, (150# Flanged)
BUTTWELD METAL IDENTIFICATION TAG
300# Flanged)
GERAND
GERAND
FLANGED
WELD-NECK FLANGES METAL IDENTIFICATION TAG
RAISED FACE
GERAND
A
WWW.GERAND.COM FOR MORE INFORMATION
6” DIAL METER
MOUNTS ON
VENTURI BRACKET
OPERATING INSTRUCTIONS
*SPECIFY RAISED OR FLAT FACE
GERAND GPM METER - VENTURI PACKAGE
“B” - Butterfly Throttle Valve OSY or Indicating
Butterfly Bypass Valve Flow SUGGESTED
TO RESERVOIR Air Vent PIPING
OR WASTE
DIAGRAM
(2) (5)
Optional to
Pump Inlet Min. Straight Pipe Diameters same line size as Venturi
1. Close system OSY valve “A” 4. Start the fire pump, and read meter in GPM.
2. Open by-pass valve and “B” butterfly throttle valve 5. Refer to pump GPM requirement and
3. Purge meter, located on venturi, as follows: adjust throttle valve to meet the requirement.
a) Open station shut-off valves on venturi & vent valves 6. After the test, open valve “A” and
attached to meter. When a steady stream of water close the by-pass and “B” valves.
passes through hose, meter is purged of air.
b) Close the vent valves after purging.