2.9m 5.3m 2.9m 5.3m GENERAL NOTES AND SPECIFICATION
A. ALL ELECTRICAL INSTALLATION SHALL BE DONE IN ACCORDANCE WITH THE PROVISION OF THE LATEST EDITION OF PHILIPPINE
PB1 GFCI
3 ELECTRICAL CODE (PEC) THE EXISTING LOCAL ORDINANCES AND REQUIREMENTS OF THE LOCAL ELECTRICAL COMPANY.
4 6 2 PB2 9
PB2 ACU
PB1 PB1 PB2 B. POWER SERVICE SHALL BE SINGLE PHASE 230V,60Hz.
5
PB2
2.3m C. ALL MATERIALS TO BE USED SHALL BE NEW AND OF THE APPROVED TYPE FOR BOTH LOCATION AND PURPOSE INTENDED.
7 D. ALL ELECTRICAL WORKS HEREIN SHALL BE UNDERTAKEN BY A LICENSED MASTER ELECTRICIAN UNDER THE STRICT
PB1 5
PB1 GFCI SUPERVISION OF A DULY REGISTERED ELECTRICAL ENGINEER.
ACU
3 4.m 4 PB2 8
PB1 PB2 PB2
E. FLEXIBLE CONDUITS SHALL HAVE AN EXCELLENT RESISTANCE TO VIBRATION, FLEXIBLE CONDUIT SHALL BE
MANUFACTURED BY MOLDEX OR CROWN ASIA.
5m 2
PB1 ACU
F. PVC CONDUITS SHALL BE RIGID NON METALLIC CONDUIT. SCHEDULE 40 AND SHALL ALSO BE MANUFACTURED BY
MOLDEX OR CROWN ASIA.
1.7m
GFCI
G. CONDUIT RUNS SHALL BE INSTALLED IN SUCH A MANNER AS NOT TO WEAKEN OR INTERFERE WITH THE STRUCTURE OF
THE BUILDING NO HORIZONTAL RUNS OF EMBEDDED CONDUITS OR TUBING SHALL BE PERMITTED IN SOLID WALL OR PARTITIONS.
GFCI
H. ALL CONDUIT COUPLINGS OR JOINTS TO BE INSTALLED UNDERGROUND OR ON CONDUIT RUNS ON AREAS OF THE BUILDING
GFCI GFCI
THAT MAY BE SUBJECTED TO WATER OR OTHER LIQUIDS SHALL BE SECURELY LIQUID TIGHT.
I. THE SWITCHES FOR LIGHTING OUTLETS.CONVINIENCE OUTLETS AND BLANK PLATES SHALL BE AS MANUFACTURED BY
6 NATIONAL OR BY OTHER MANUFACTURER AS WILL BE APPROVED BY DESIGNING ENGINEER.
ACU PB2
7
GFCI PB2 J. MOULDED CASE CIRCUIT BREAKERS SHALL BE AS MANUFACTURED BY GENERAL ELECTRIC AND THE ENCLOSURE
SHALL BE ORDERED TO FUJIHAYA OR OTHER PANEL BOARD MANUFACTURER.AS WILL BE APPROVED BY DESIGNING ENGINEER.
S11a S11b 3 250 Watts Refrigerator Outlet 1 250 230 1.10 20 AT 3-3.5mm2 THHN in 20mmØ PVC
S11c
S2c 4 3000 Watts Range Outlet 1 1000 230 4.35 20 AT 3-3.5mm2 THHN in 20mmØ PVC
S2a
S3b S3a S3b
S10a, S10b
5 3000 Watts Range Outlet 1 1000 230 4.35 20 AT 3-3.5mm2 THHN in 20mmØ PVC
S4b
S2c S11c
6 Washing Machine 1 750 230 3.27 20 AT 3-3.5mm2 THHN in 20mmØ PVC
S2b S4a S14b S14a S14b S10a S10b
S8b S8b
S14a
7 3TR Split Type Aircon 1 2450 230 10.65 30 AT 3-5.5mm2 THHN in 20mmØ PVC
S2b S14b
S2a, S2b, S6a, S4a, S14c S13a
S8a
S8b
TOTAL: 7888
S2c S4b, S4c
S2c S2c 1 S13b
S13b
S13c S13b
S8c Icb = (7888+2450(.25))/230 Use: 2-30mm2 THW Cu. Wire
PB1
1 Icb = 36.96 A 1-14mm2 TW Cu. Wire (Gnd)
PB2 S8a
S4c
STEP S7a in 32mm dia PVC
LIGHT S6a
S14c S14c
100 AT, 100AF, MCCB
S2b S2b S1a, S1b, S1c S7a S13a
S2a
S16a S8c S8c
S1b S1b
SCHEDULE OF LOADS PANEL BOARD-2 @ SECOND FLOOR
S16a
S15a
S15b
S15a CKT # LOAD DESCRIPTION No. of Outlets VA Voltage Current Circuit Breaker Size of Wire and Conduit
S13c
S1a S1a S1a S16b
S15c
S2b S2b
9 watts LED Downlight 25 22
S13b S13b
S16b
S8c S8c
1 45 watts LED Centerlight 4 180 441 230 1.91 20 AT 2-3.5mm2 THHN in 20mmØ PVC
S1b S1b
S15c 6 watts LED Wall Light 6 36
S15b
200 Watts Convenience
S1c 2 9 1800 230 7.83 20 AT
Outlet 2-3.5mm2 THHN in 20mmØ PVC
200 Watts Convenience
3 9 1800 230 7.83 20 AT
Outlet 3-3.5mm2 THHN in 20mmØ PVC
S1c
GROUND FLOOR LIGHTING LAYOUT SECOND FLOOR LIGHTING LAYOUT
4 3 TR Split Type Aircon 1 2450 230 10.65 30 AT 3-5.5mm2 THHN in 20mmØ PVC
NTS
NTS
5 1.5 HP Window Type Aircon 1 1118.55 230 4.86 20 AT 3-5.5mm2 THHN in 20mmØ PVC
6 1.5 HP Window Type Aircon 1 1118.55 230 4.86 20 AT 3-5.5mm2 THHN in 20mmØ PVC
Single Phase, 230 V, 60Hz 7 Instant Water Heater 1 2000 230 8.70 30 AT 3-5.5mm2 THHN in 20mmØ PVC
To Service Entrance
To Service Entrance 2-30mm2 THW Cu. Wire LEGEND 8 Instant Water Heater 1 2000 230 8.70 30 AT 3-5.5mm2 THHN in 20mmØ PVC
1-14mm2 TW Cu. Wire (Gnd)
2-30mm2 THW Cu. Wire in 32mm dia PVC Conduit 9 1.5 HP Water Pump 1 1500 230 6.52 30 AT 3-5.5mm2 THHN in 20mmØ PVC
1-14mm2 TW Cu. Wire (Gnd) 2
2-30mm THW Cu. Wire INCANDESCENT LAMP
in 32mm dia PVC Conduit 14228.1
1-14mm2 TW Cu. Wire (Gnd)
in 32mm dia PVC Conduit CENTER LAMP Icb = (14228.1+2450(.25))/230 Use: 2-30mm2 THW Cu. Wire
PIN LIGHT OUTLET Icb = 64.52 A 1-14mm2 TW Cu. Wire (Gnd)
100 AT
M CONVENIENCE OUTLET
in 32mm dia PVC
100 AT, 100AF, MCCB
100 AT GFCI
SCHEDULE OF LOADS
GROUND FAULT CIRCUIT INTERRUPTER CONSOLIDATED LOAD
Lighting 20AT 20AT Convenience
Outlet 1b 3 Outlet CKT # LOAD DESCRIPTION No. of Outlets VA Voltage Current Circuit Breaker Size of Wire and Conduit
Lighting 20AT 30AT Convenience
1a 2 AIR CONDITION UNIT OUTLET
Convenience 20AT 30AT Outlet Outlet ACU 2-30mm2 THW Cu. Wire
Outlet 4 10 ACU PB1 PB2 Panel Board -1 1 7888 230 34.30 100 1-14mm2 TW Cu. Wire (Gnd)
Refrigerator 20AT 20AT Range Ground Floor Second Floor PB1 CIRCUIT NUMBER
20AT 30AT Outlet 5 6 Outlet
ACU 2-30mm2 THW Cu. Wire
ACU 11 12 Panel Board -2 1 14228.1 230 61.86 100
Range 20AT 30AT Washing Sa SINGLE SWITCH 1-14mm2 TW Cu. Wire (Gnd)
30AT 30AT Outlet 7 8 Machine
Heater 13 14 Heater
30AT Sab 2-GANG SWITCH
22116.1
30AT ACU 9 Ifeeder = (22116.1)/230 Use: 2-30mm2 THW Cu. Wire
Water
Pump 15 See Panel See Panel S3W 3-WAY SWITCH
Board Details Board Details Ifeeder = 96.16 A 1-14mm2 TW Cu. Wire (Gnd)
PANEL BOARD in 32mm dia PVC
M METER BASE
PANEL BOARD DETAILS - PB2 SECOND FLOOR
PANEL BOARD DETAILS - PB1 GROUND FLOOR SINGLE LINE DIAGRAM
SERVICE ENTRANCE
PREPARED BY: TITLE AND LOCATION OWNER SIGN AND SEAL SHEET CONTENT SHEET NO.