M2010 SiteSentinel Nano Installation Manual
M2010 SiteSentinel Nano Installation Manual
11
Issue Date: 4/13/2018
Supersedes: 11/3/2017
NOTE: Before you use this guide, make sure you have the latest revision. Check the revision
level of this document against the most current revision found at
http://www.opwglobal.com/opw-fms/tech-support/manuals-how-to-videos . Download the
latest revision if necessary.
Copyright Information
Copyright © 2018 Delaware Capital Formation, Inc. All Rights Reserved. DOVER, the DOVER logo are
registered trademarks of Delaware Capital Formation, Inc., a wholly-owned subsidiary of Dover Corporation.
Table of Contents
Section 1 Get Started: Safety 7
1.1 Safety Alerts 8
1.2 Applicable Warnings 9
1.3 I.S. Barriers - Special Conditions for Safe Use 10
1.4 Installer Safety 11
1.5 Precision Leak Test 12
1.5.1 Before Initial Inspection 12
1.5.2 Initial Inspection 12
Section 2 SiteSentinel® Nano® Console 13
2.1 Communication Lights 13
2.2 Console Specifications 14
2.3 Console Installation 15
2.3.1 Installation Instructions 15
2.3.2 Installation Video 17
2.4 Wiring Requirements 17
2.4.1 Electrical and I.S. Barrier Wiring 17
2.5 Console and Peripheral Connections 21
2.5.1 Direct Connections 21
2.5.2 Ethernet Connections 21
2.5.3 RS-232 Communications Conduits 21
2.6 Complete the Installation 21
Section 3 OM4 Output Module 22
3.1 Safety Precautions 23
3.2 Codes 23
3.3 Hazardous Area Definition 23
Doc. No.: M2010 Rev.: 11
Page 4 of 170
NOTE: Only certified OPW technicians are authorized to install and program this automatic
tank gauge system. Failure to comply could result in a voided warranty.
DANGER: The coin cell battery may explode if mistreated. Do not recharge,
disassemble or dispose of in fire. Replace battery with Panasonic or
Matsushita Electric Part Number CR-2032 ONLY. Use of another battery
may present a risk of fire or explosion.
To avoid possible explosion or fire, do not replace the lithium battery with a
type that is not compatible.
The battery used in this device may present a risk of fire or chemical burn if
mistreated. Do not disassemble, heat above 50°C or incinerate.
The console can remain energized via the backup battery, even though the
line power has been removed.
The SiteSentinel® Nano® console has one (1) lithium battery. When the battery can no longer hold sufficient
electrical power it must be replaced.
IMPORTANT: Replace the battery with recommended replacement ONLY. Use of another
battery may present a risk of fire or explosion.
A used battery must be removed and brought to a battery-recycling center for approved disposal.
Doc. No.: M2010 Rev.: 11
Page 10 of 170
* All OPW-FMS Installation Guides and Field Wiring Diagrams can be found at
http://www.opwglobal.com/opw-fms/tech-support/manuals-how-to-videos.
Doc. No.: M2010 Rev.: 11
Page 11 of 170
Installation must be in accordance with the U.S. National Electrical Code (NFPA No. 70) and the Automotive
and Marine Service Station Code (NFPA No. 30A).
For installations outside the United States, make sure that the installation obeys all applicable local codes.
When installing in a hazardous area as defined by the NEC, only intrinsically safe devices can be installed in
or above the Class 1, Division 1 and 2 Hazardous Area.
It is the installer’s responsibility to examine and obey any local codes.
NOTE: Local codes may dictate special installation requirements. Installation is subject to
approval by the local authority having jurisdiction at the site.
Doc. No.: M2010 Rev.: 11
Page 12 of 170
NOTE: Most regulatory agencies will accept the ATG tank test as the acceptance test on new
tank installations. Make sure this applies to your local agency before testing any tank.
NOTE: Not all Site Survey questions will require an answer; for all unanswered questions,
please respond with “N/A.” Do not leave any field empty!
NOTICE: Be sure to remove the main board and set it in a static-free environment before
proceeding to the next step. This will prevent damage to the main board components when
removing the knockouts.
Following the guidelines below can minimize the potential for damage from Electrostatic
Discharge (ESD).
Handle ESDS components by the edges. Avoid touching any of the circuitry
6. Remove the knockouts from either the bottom or top of the unit (as determined in Step 1 above). The
knockouts can be removed by inserting a small screwdriver into the groove and hit it firmly with a
hammer.
TIP: As an alternative, for a safe and clean removal of the knockouts you can use a Greenlee
hole punch, or equivalent hardware if available.
7. Reinstall the main board and mount the unit to the wall with screws that match the size of the screw
holes or anchors that were installed in Step 5.
8. Install the conduits in the empty knockout holes.
9. Pull the electrical wires and probe/sensor wires through the conduit to the console.
Doc. No.: M2010 Rev.: 11
Page 17 of 170
IMPORTANT: Make sure the electrical wiring is routed to the left side of the console and the
probe/sensor wiring is routed to the right side.
CAUTION: Make sure that the I.S. ground wire and Earth ground are
properly attached to the console back to the electrical panel to prevent high-
voltage being sent to the I.S. wiring side in the event of a field short.
NOTICE: When wiring the connectors, be sure there are no exposed stripped wires
outside of the block. This is to prevent shorting the high-voltage on the electrical side and
to prevent damage to the barrier and/or the probe itself from shorting on the probe side.
Doc. No.: M2010 Rev.: 11
Page 18 of 170
NOTE: The SiteSentinel® Nano® console comes with a set IP address. Do not change this
address if using a crossover.
To establish a direct, wired connection between the console and a PC, a standard RJ45 crossover cable is
required. For details on setting up a direct connection between a PC/laptop and the console refer to the
introductory section Direct Connection with a Crossover Cable in the M2011 SiteSentinel® Nano®
Configuration Guide.
TIP: This distance can be extended through the use of hubs and routers. If more than 1.8 m (6
feet) of cable is required, the use of conduit to protect the cable is recommended.
NOTE: The maximum runs for serial communication cable is 15.2 m (50 feet).
High voltages exist inside the OM4. Only qualified technicians should open the
unit.
Output relays in the OM4 are not intrinsically safe! Before working on the OM4
Output Module, disconnect the power, including power to and from the relays.
Do not place probe and/or sensor wiring in conduit that contains wiring for
devices that are connected to the OM4 Output Module.
3.2 Codes
Relay wiring is classified as Class 1 wiring. Installations must be in accordance with the National Electrical
Code (NFPA No. 70) and the Motor Fuel Dispensing Facilities and Repair Garages Code (NFPA No. 30A). It
is the installer’s responsibility to investigate and obey any applicable local codes in the country\county of
installation.
DANGER: Do not mount the OM4 Output Module within a hazardous area.
Do not attach this unit to any devices that are located in the hazardous area.
Doc. No.: M2010 Rev.: 11
Page 24 of 170
NOTE: The overfill alarm can be programmed to operate with any alarm that has relay 1 or
relay 2 activation.
NOTE: Refer to the Field Wiring Diagram for your specific ATG system to connect wires
inside the Tank Alert box
Components
Each probe/sensor wiring kit will have all the necessary components you will need to complete the sealpack
assembly for waterproofing the electrical connections. You will need:
l Three (3) wire nuts
l Two (2) cable tie wraps
l 3M™ Scotchcast™ Electrical Insulating Resin packet
Tools Required
l Wire stripper/cutter
Doc. No.: M2010 Rev.: 11
Page 31 of 170
Instructional Video
If you have a QR code scanner/reader app for your smartphone you can scan this code to view the
instructional video, Multidrop Probe & Sensor Wiring Instructions. If you are viewing this manual on a
computer or tablet, simply click on the code.
NOTE: This link starts the video at a midway point where the relevant section begins.
Safety Information
For detailed product hazard information see the MSDS for the 3M™ Scotchcast™ 3570G-N (Parts A & B). If
you have a QR code scanner/reader app for your smartphone you can scan this code, then go to the
Documents tab and select the MSDS:
Doc. No.: M2010 Rev.: 11
Page 32 of 170
Assembly Procedure
The procedure for assembling the wire connections and resin sealpacks is outlined below.
Figure 5-1 Assembling the Epoxy Sealpack for Waterproof Electrical Connections
NOTICE: It is VERY important to seal all probe and sensor connections in the junction box
to prevent corrosion of the wires.
To make the connections waterproof, use the supplied Scotchcast™ epoxy-resin Insulating Resin Sealpacks.
They are provided to seal the electrical connections from moisture and water and prevent corrosion of the
connections. Install one for each cable connection.
Doc. No.: M2010 Rev.: 11
Page 33 of 170
1. Strip approximately 1.5 inches of the cable jacket from the end of the probe/sensor cable to expose the
four (4) wires inside (power, signal ground and shield).
IMPORTANT: When stripping cables and wires do not cut so deep as to nick the wiring
inside the jacket material.
NOTE: Refer to the wiring diagrams in the product manual for specific information on
probe/sensor wiring.
8. Fold one of the fastened wire nuts back as shown in the photo. This will allow the entire wire nut
assembly to fit completely into the epoxy bag.
10. Insert the wire-nut assembly all the way into the bottom of the bag. Fold the bag tightly around the tied
cables. Attach a second tie wrap around the bag just above the tie wrap holding the wires (this will
prevent the wire-nut assembly from slipping out of the bag.
11. Move the epoxy around to thoroughly cover all of the wires and wire nuts inside the bag. Once the
epoxy has set this will provide a secure, waterproof electrical connection and will prevent corrosion of
the wiring connections.
Doc. No.: M2010 Rev.: 11
Page 35 of 170
WARNING: To prevent explosive vapors from entering the I.S. barrier, seal-
off the probe cables before they enter the I.S. barrier.
1. Remove enough of the jacket to allow approximately 7.6 cm (3 inches) of wire leads to extend past
each seal-off. DO NOT nick the wire insulation.
2. Probe or sensor wires using prepared Belden or Alpha cable go through NPT bushings into a
weatherproof junction box. Bushings must be used in all junction boxes.
3. The cable is then routed—via rigid steel conduit—out of the box and directly to the I.S. barrier.
4. Label each cable and wire.
CAUTION: The console must have a dedicated power circuit, and must be
on the same phase as all other OPW equipment.
Only OPW probe cables and sensor wiring can share the conduit to the I.S.
barriers.
NOTICE: Improper cables, wiring, or conduit allow electronic noise to interfere with
probe/sensor measurements. This may cause measurement readings at the console
resembling hardware failure. The warranty is voided if improper cables, wiring and/or
conduit are installed. The ground wire must be properly installed for the operation of the
noise-filtering circuitry. Do not rely on the conduit for the operation of the ground.
Model 924B probes are safe for Class 1, Div 1, Group D hazardous
locations. This includes tanks containing regular, super, diesel and unleaded
gasoline; antifreeze; kerosene; mineral spirits; oxinol, methanol and
methanol blends; motor, torque and transmission oil; and alcohol. If you have
any questions about whether a product is included in this classification,
please contact your product specialist or OPW distributor.
The ideal location for a probe is in the center of the tank (See the illustration below).
The probe should be located at least 91.4 cm (3 feet) from the tank fill pipe. If this distance is less than 91.4
cm (3 feet), the force of the product entering the tank can cause the water float to rise up the shaft of the
probe. This may cause the controller to generate a false high-water alarm.
Adjust the drop tube of the fill pipe so that the product flow is diverted away from the probe.
Similarly, a Submersible Turbine Pump (STP) should be located at least 91.4 cm (3 feet) from the probe. If
this distance is less than 91.4 cm (3 feet), the force of the product being pumped from the tank can adversely
impact readings of both, the water and product floats.
NOTE: If the fitting is not in the center of the tank, additional measurements are required for
probe compensation.
2. When installing the probe, allow enough cable from the probe to reach a weatherproof junction box.
3. Leave minimum 30.5 cm (12 inches) of extra, coiled wiring (probe wire and field wire) inside the
weatherproof junction box. The box must be large enough to contain a 12.7 mm (0.5 inch) conduit,
coiled field wiring and epoxy pack, as shown in field wiring diagram.
CAUTION: Seal-offs are required any time I.S. wiring enters conduit.
4. Install the 1/2-inch NPT bushing (supplied with each probe) in the weatherproof junction box.
IMPORTANT: The two types of water floats are NOT interchangeable. Because diesel is
denser than gasoline, the water/diesel floats are heavier than the water/gasoline floats. If the
wrong water float is installed in a diesel tank, it does not sink through the product to the water
below. As a result, the tank will have unusually high water measurements and possibly erratic
product measurements as the water float interferes with the product float.
NOTICE: The product float for LPG is not certified for applications in which it will be subjected
to pressures at or above 300PSI. Pressures higher than 300PSI will damage the device,
preventing it from providing accurate measurements.
IMPORTANT: Seal packs are required with all wiring applications in the field. Weatherproof
junction boxes are REQUIRED with ALL I.S. field connections.
To avoid a build-up of static charge, do not rub with a dry cloth or clean in any
manner that would result in a charge build-up. Discharge the outside of the
hazardous area before putting into service.
These devices have not been evaluated for use across a boundary wall.
The upper housing cover in the top of the enclosure is aluminum. Care must
be taken to avoid ignition hazards due to impact or friction.
NOTE: *Maximum Wiring Length is the maximum length of cable to be used to connect all
sensors on an individual channel. The length includes run of cable from an I.S. Barrier to each
sensor board in the string.
Doc. No.: M2010 Rev.: 11
Page 42 of 170
NOTE: **ONLY 924B Probes built after September 1, 2007, (version 7.xx firmware) can be
installed in multi-drop applications.
Doc. No.: M2010 Rev.: 11
Page 43 of 170
NOTE: As density sensing is no longer an option in the system, the sensor itself will be picked
up by the system once the device is installed and after redoing Auto-Detection of the probe.
1. Remove the probe from the tank and detach the clip and nylon probe foot from the bottom of the probe.
2. Remove the water float, slide the density sensor on and tighten the screws of the sensor onto the probe
shaft (the umbrella should be facing down). Leave a space of 10.2 cm to 15.2 cm (4 to 6 inches) at the
bottom of the probe shaft so the water float can detect at least 7.6 cm (3 inches) of water.
3. Replace the water float, nylon probe foot and end clip.
4. Place the probe back in the tank.
Doc. No.: M2010 Rev.: 11
Page 44 of 170
NOTICE: The Density Measurement Sensor is not certified for applications in which it will
be subjected to pressures at or above 20.7 bar (300 psig). Pressures higher than 20.7 bar
(300 psig) will damage the device, preventing it from providing accurate measurements.
Diesel
Jet Fuel
Kerosene
Diesel Motor Oil 26 < API < 45 0.80 < d < 0.90
Toluene
Gear Oil
Transmission Oil
NOTICE: To prevent damage to the I.S. barrier, you must power down the module that the
probe is connected to before you begin the procedure below.
1. Power down the module that the probe is connected to before you remove the probe from the tank.
2. Remove the probe from the tank and detach the clip and nylon probe foot from the bottom of the probe.
3. Remove the water float, slide the density float on and tighten the screws of the float onto the probe shaft
(the umbrella should be facing down). Leave a space of 10.2 cm to 15.2 cm (4 to 6 inches) at the
bottom of the probe shaft so the water float can detect at least 7.6 cm (3 inches) of water.
4. Replace the water float, nylon probe foot and end clip.
5. Place the probe back in the tank.
6. Power up the module.
Doc. No.: M2010 Rev.: 11
Page 47 of 170
For DMF configuration and calibration please refer to your M2011 SiteSentinel® Nano® Configuration
Guide.
You will need the A and B Factors that are etched into the body of the float. See the image below.
This technology allows the Nano's internal I.S. barrier to automatically detect sensor connection, sensor type
and sensor status. IntelliSense will minimize user entry errors and identify hardware issues with minimal
troubleshooting.
IMPORTANT: Seal packs and weatherproof junction boxes are REQUIRED with ALL I.S.
field connections.
Description
IMPORTANT: This float body is identical to the 30-0232-D10 & D20 and 30-0232-D-10B &
D-20B. Check the label to make sure you are using the correct sensor for the intended
purpose.
The dual level sump sensor is designed to detect the presence of liquid hydrocarbons and water in sumps,
dispenser pans and other locations where the presence of a liquid could indicate that a leak has occurred.
The DH-10 is intended for use on dispenser pans and transition sumps, the DH-20 is intended for use in tank
sumps.
The sensor contains a carbon/polymer material (Belcor®) that changes its resistance when exposed to liquid
hydrocarbons.
Dual float switches are incorporated into the body that cause an alarm condition when low and high levels
are detected. The system will also cause an alarm condition in the event of a break in the cable or sensor
malfunction.
Doc. No.: M2010 Rev.: 11
Page 51 of 170
Specifications
DH-10: Dispenser Pan/Sump
Primary Use(s):
DH-20: STP Sumps
DH-10: STP Sumps
Alternate Uses:
DH-20: Dispenser Pan/Sump
Detects: Low Liquid, High Liquid, Fuel
Operating Temperature: -40°C to +70°C (-40°F to 158°F)
DH-10 Dimensions: Diameter: 5.8 cm (2.3 in.), Length: 28.2 cm (11.1 in.)
DH-20 Dimensions: Diameter: 5.8 cm (2.3 in.), Length: 53.6 cm (21.1 in.)
Float Requirements: Low: 3.8 cm (1.5 in.), High: 27.9 cm (11 in.)
Nominal resistance (uncontaminated) 1K – 5K ohms
Nominal resistance (contaminated) 30K – 200K ohms
Belden #88760 or Alpha #55371
Cable: 3.6 m (12 feet) of gas & oil resistant cable to
inline ISIM + 1.3 m (4 feet) ISIM tail
Maximum Wiring Length*: 305 m (1,000 ft.) field wiring
Doc. No.: M2010 Rev.: 11
Page 52 of 170
Specifications
Alarm Threshold Configuration: Fully Automatic
Diagnostic Reading from sensor setup:
12 to 13 (normal),
Belcor Clean
3 to 4 (lower float in alarm - raised),
(no Hydrocarbon)
1 to 2 (lower and upper float in alarm - raised)
3.5 to 3.7 (normal),
Belcor Active
1.8 to 2.0 (lower float in alarm - raised),
(Hydrocarbon present)
1.2 to 1.4 (lower and upper float in alarm - raised)
Multi-Drop Restriction: See Mixed Multi-drop Installation
Connections: Red = Power, Black = Signal, Shield = Ground
NOTE: *Maximum Wiring Length is the maximum length of cable to be used to connect all
sensors on an individual channel. This length includes run of cable from VSmart to each
sensor board in the string.
Installation
NOTE: To ensure safe operating conditions this sensor has been designed to connect to
OPW Tank Gauges Smart Sensor 12V IS Module ONLY. Smart sensors CANNOT be used
with SS1, 2 or 3, iTouch or any EECO consoles.
Ensure the cabling (gas and oil resistant FMS part # 12-1030) back to the
controller is in conduit that is dedicated to intrinsically safe wiring.
l Connect the sensor wires to the field wires in the junction box. Use the supplied cable gland and
silicon wire nuts.
l Seal the electrical connections with the epoxy seal packs (refer to M00-390008 Waterproof
Electrical Connections for detaied instruction).
l Install seal-offs at both ends of the conduit run.
Connections
Controller Setup
l On the console, the sensor should be Auto Detected (see the console configuration manual). Alarm
thresholds are configured automatically through the Intellisense mechanism between the sensor and
the console.
Doc. No.: M2010 Rev.: 11
Page 54 of 170
Description
The Discriminating Interstitial optical liquid sensor is used primarily to monitor the interstitial area of double-
walled tanks. This sensor incorporates a long-life, solid-state optical prism and can also be used in sumps,
dispenser pans and other locations where the presence of a liquid could indicate that a leak has occurred.
The sensor distinguishes between water and hydrocarbons. Detection of liquid will cause an alarm
condition.The system will also cause an alarm condition in the event of a break in the cable or sensor
malfunction.
Specifications
Liquid detection in the interstitial space of double-walled
Primary Use:
tanks.
Alternate Use(s): Dispenser Pans and STP Sumps
Detects: Liquids: Hydrocarbon and Water
Operating Temperature: -40°C to +70°C (-40°F to 158°F)
Length: 8.2 cm (3.22 in.), Width: 2.8 cm x 1.6 cm (1.1 in. x
Dimensions:
.62 in.)
Nominal resistance (uncontaminated) 1K – 5K ohms
Nominal resistance (contaminated) 30K – 200K ohms
Belden #88760 or Alpha #55371
Cable: 4.5 m (15 feet) of gas & oil resistant cable to
inline ISIM + 1.3 m (4 feet) ISIM tail
Maximum Wiring Length*: 305 m (1,000 ft.) field wiring
Alarm Threshold Configuration: Fully Automatic
0.02 to 0.03 and 0.23 to 0.25 (normal),
Diagnostic Reading from Sensor Setup:
0.02 to 0.03 and 0.02 to 0.03 (water alarm),
Doc. No.: M2010 Rev.: 11
Page 56 of 170
Specifications
0.23 to 0.25 and 0.23 to 0.25 (hydrocarbon alarm)
Multi-Drop Restriction: See Mixed Multi-drop Installation
Connections: Red = Power, Black = Signal, Shield = Ground
NOTE: *Maximum Wiring Length is the maximum length of cable to be used to connect all
sensors on an individual channel. This length includes run of cable from VSmart to each
sensor board in the string.
Installation
NOTE: To ensure safe operating conditions the sensor has been designed to connect to
OPW Tank Gauges Smart Sensor 12V IS Module ONLY. Smart sensors CANNOT be used
with SS1, 2 or 3, iTouch or any EECO consoles.
Ensure the cabling (gas and oil resistant FMS part # 12-1030) back to the
controller is in conduit that is dedicated to intrinsically safe wiring.
IMPORTANT: To prevent false alarms, the sensor should not touch the bottom of the
monitoring tube
l Connect the sensor wires to the field wires in the junction box. Use the supplied cable gland and
silicon wire nuts.
l Seal the electrical connections with the epoxy seal packs (refer to M00-390008 Waterproof
Electrical Connections for detaied instruction).
l Install seal-offs at both ends of the conduit run.
Connections
Controller Setup
l On the console, the sensor should be Auto Detected (see the console configuration manual). Alarm
thresholds are configured automatically through the Intellisense mechanism between the sensor and
the console.
Doc. No.: M2010 Rev.: 11
Page 58 of 170
TIP: This sensor can be wiped clean and does not require any recovery time before being put
back into active service again.
NOTE: If the controller fails to go into alarm, check all wiring and junction boxes to verify
continuity without shorts. Any sensor or wiring fault will trigger a system alarm.
Doc. No.: M2010 Rev.: 11
Page 60 of 170
Description
The Hydrocarbon Liquid/Water Sensor (available in lengths of 6 feet [1.8 m], 15 feet [4.6 m] and 20 feet [6.1
m]), is used primarily for monitoring wet wells with fluctuating groundwater tables. This sensor uses a
carbon/polymer material that changes its resistance when exposed to liquid hydrocarbons.
A water sensor is also used that relies on the conductivity of water to detect its presence. This functionality
lets the sensor discern between hydrocarbon liquid and water.
The sensor will alert the system to the absence of ground water in a monitoring well or the presence of water
in containment areas. It will also alert the system of any fuel leaks into the containment area. In the event of a
break in the cable or sensor malfunction, the system will also result in an alarm condition.
Specifications
Primary Use: Monitoring Wells
Detects: liquid Hydrocarbons and Water
Operating Temperature: -40°C to +70°C (-40°F to 158°F)
Length: 6’ (1.9 m), 15’ (4.6 m) or 20’ (6.1 m)
Dimensions:
Diameter: 0.7” (1.8 cm)
Nominal resistance (uncontaminated) 1,000 – 3,000 ohms/ft
Nominal resistance (contaminated) 30,000 – 200,000 ohms/ft
Cable: Belden #88760 or Alpha #55371
Maximum Wiring Length*: 1,000’ (305 m) field wiring
Multi-Drop Restriction: See Mixed Multi-drop Installation
Connections: Red = Power, Black = Signal, Shield = Ground
NOTE: *Maximum Wiring Length is the maximum length of cable to be used to connect all
sensors on an individual channel. This length includes run of cable from the console to each
sensor board in the string.
Doc. No.: M2010 Rev.: 11
Page 61 of 170
Installation
NOTE: To ensure safe operating conditions the sensor has been designed to connect to
OPW Tank Gauges Smart Sensor 12V IS Module ONLY. Smart sensors CANNOT be used
with SS1, 2 or 3, iTouch or any EECO consoles.
Ensure the cabling (gas and oil resistant FMS part # 12-1030) back to the
controller is in conduit that is dedicated to intrinsically safe wiring.
REMINDER: Hydrocarbons float on water. If the sensor is fully submerged in water, the
polymer is unable to detect hydrocarbon liquid.
Connections
Controller Setup
l On the console, the sensor should be Auto Detected (see the console configuration manual). Alarm
thresholds are configured automatically through the Intellisense mechanism between the sensor and
the console.
Doc. No.: M2010 Rev.: 11
Page 63 of 170
NOTE: The sensor should return to nearly its original resistance, however, it might be
necessary to readjust the controller’s thresholds.
Doc. No.: M2010 Rev.: 11
Page 65 of 170
Description
The Interstitial Hydrocarbon Liquid/Water Sensor is designed for use in the interstitial area of a fiberglass
double-walled tank. The hydrocarbon liquid/water sensor uses a carbon/polymer material that changes its
resistance when exposed to liquid hydrocarbons.
A conductive strip is also used to detect the presence of water. This functionality lets the sensor discern
between hydrocarbon liquid and water.
In the event of a break in the cable, the system will activate the alarm.
Specifications
Operating Temperature: -40°C to +70°C (-40°F to 158°F)
Dimensions: Length: 35 cm (13.8 in.), Width: 2.5 cm (1.0 in.)
Nominal resistance (uncontaminated) 1,000 – 3,000 ohms
Nominal resistance (contaminated) 10,000 – 200,000 ohms
Cable: Belden #88760 or Alpha #55371
Maximum Wiring Length*: 1,000’ (305 m) field wiring
Multi-Drop Restriction: See Mixed Multi-drop Installation
Connections: Red = Power, Black = Signal, Shield: = Ground
NOTE: *Maximum Wiring Length is the maximum length of cable to be used to connect all
sensors on an individual channel. This length includes run of cable from I.S. Barrier to each
sensor board in the string.
Doc. No.: M2010 Rev.: 11
Page 66 of 170
Installation
Ensure the cabling (gas and oil resistant FMS part # 12-1030) back to the
controller is in conduit that is dedicated to intrinsically safe wiring.
REMINDER: Hydrocarbons float on water. If the sensor is fully submerged in water, the
polymer is unable to detect hydrocarbon liquid.
Connections
Controller Setup
l On the console, the sensor should be Auto Detected (see the console configuration manual). Alarm
thresholds are configured automatically through the Intellisense mechanism between the sensor and
the console.
NOTE: The sensor should return to nearly its original resistance, however, it might be
necessary to readjust the controller’s thresholds.
Doc. No.: M2010 Rev.: 11
Page 69 of 170
Description
These two types of interstitial level sensors are used primarily in the interstitial area of a double walled tank.
The sensors have a float switch that activates in the presence of a liquid. The 30-0230-S is constructed from
brass and the 30-0321-S is constructed from chemical resistant, non-metallic material.
These sensors can also be used in sumps, dispenser pans and other locations where the presence of a
liquid could indicate that a leak has occurred. Combined with a vapor sensor, this interstitial sensor can be
used to monitor wet wells to ensure that a liquid is normally present. In the event of a break in the cable the
system will activate an alarm.
Specifications
30-0230-S: STP Sumps and Dispenser Pans
Primary Use:
30-0231-S: Interstitial Area
30-0230-S: Steel Tank Interstitial
Alternate Use:
30-0231-S: Sumps and Dispenser Pans
Detects: Liquid
Operating Temperature: –20°C to +50°C (–4°F to +122°F)
Dimensions - 30-0231-S Diameter: 1.3 inches (3.4cm), Length: 3.9 inches (10 cm)
Specifications
4.5m (15 feet) of gas & oil resistant cable to
inline ISIM + 1.3m (4 feet) ISIM tail.
Maximum Wiring Length*: 1,000’ (305 m) field wiring
Alarm Threshold Configuration: Fully Automatic
0 - 0.5 (normal),
Diagnostic Reading from sensor setup: 485 - 495 (in alarm)
Installation
NOTE: To ensure safe operating conditions the sensor has been designed to connect to
OPW Tank Gauges Smart Sensor 12V IS Module ONLY. Smart sensors CANNOT be used
with SS1, 2 or 3, iTouch or any EECO consoles.
Ensure the cabling (gas and oil resistant FMS part # 12-1030) back to the
controller is in conduit that is dedicated to intrinsically safe wiring.
Connections
Controller Setup
l On the console, from the Home\Settings\Probe and Sensor screen the sensor should be Auto Detected
(see the console configuration manual). Alarm thresholds are configured automatically through the
Intellisense mechanism between the sensor and the console.
When conducting testing or decontamination of the sensor work in a well ventilated area with no hot surfaces
or open flames near by.
Doc. No.: M2010 Rev.: 11
Page 72 of 170
9.9 Single Level Sump Sensor – Smart Sensor Equipped with Intel-
lisense Technology
30-0231-L
Description
The single-level sensor is designed to detect the presence of liquid in sumps, dispenser pans and other
locations where the presence of a liquid could indicate that a leak has occurred.. The sensor contains a float
switch that activates in the presence of liquid. In the event of a break in the cable, the system will activate the
alarm.
Specifications
Primary Use(s) Sumps and Dispenser Pans
Detects Liquid
Operating Temperature: -40°C to +70°C (-40°F to 158°F)
Dimensions: Diameter: 7.4 cm (2.90 inches), 9.5 cm (3.70 inches)
Belden #88760 or Alpha #55371
Cable Requirements: 3.6m (12 feet) of gas & oil resistant cable to
inline ISIM + 1.3m (4 feet) ISIM tail.
Maximum Wiring Length*: 305 m (1,000 ft.) field wiring
Doc. No.: M2010 Rev.: 11
Page 74 of 170
Specifications
Alarm Threshold Configuration: Fully Automatic
0 to 5 (normal),
Diagnostic Reading from sensor setup:
485 to 495 (in alarm)
Multi-Drop Restriction: See Mixed Multi-drop Installation
Connections: Red = Power, Black = Signal, Shield = Ground
NOTE: *Maximum Wiring Length is the maximum length of cable to be used to connect all
sensors on an individual channel. This length includes run of cable from the console to each
sensor board in the string.
Installation
NOTE: To ensure safe operating conditions the sensor has been designed to connect to
OPW Tank Gauges Smart Sensor 12V IS Module ONLY. Smart sensors CANNOT be used
with SS1, 2 or 3, iTouch or any EECO consoles.
Ensure the cabling (gas and oil resistant FMS part # 12-1030) back to the
controller is in conduit that is dedicated to intrinsically safe wiring.
NOTE: If monitoring a normally dry well, use a meter to set the float so the sensor is in the
closed state with NO liquid present (float in the lower position). If monitoring a normally wet
well, use a meter to set the float so that it is in the closed state WITH liquid present (float in the
upper position).
l Seal the electrical connections with the epoxy seal packs (refer to M00-390008 Waterproof
Electrical Connections for detaied instruction).
l Install seal-offs at both ends of the conduit run.
Connections
Controller Setup
l On the console, from the Home\Settings\Probe and Sensor screen the sensor should be Auto Detected
(see the console configuration manual). Alarm thresholds are configured automatically through the
Intellisense mechanism between the sensor and the console.
Description
IMPORTANT: This float body is identical to the 30-0232-D-10B & D-20B and 30-0232-DH-
10 & DH-20 (DH-XX has a carbon-polymer strip in the base). Check the label to make sure you
are using the correct sensor for the intended purpose.
The dual level sump sensor is designed to detect the presence of liquid hydrocarbons and water in sumps,
dispenser pans and other locations where the presence of a liquid could indicate that a leak has occurred.
This sensor is similar to the 30-0232-DH-XX but is NON-DISCRIMINATING (i.e. the sensor does NOT
contain a carbon/polymer material to sense liquid hydrocarbons). The DH-10 is intended for use on
dispenser pans and transition sumps, the DH-20 is intended for use in tank sumps. Dual float switches are
incorporated into the body to detect low and high levels. In the event of a break in the cable, the system will
activate the alarm.
Specifications
D-10: Dispenser Pan/Sump
Primary Use(s):
D-20: STP Sumps
D-10: STP Sumps
Alternate Uses:
D-20: Dispenser Pan/Sump
Detects: Low Liquid, High Liquid, Fuel (non-discriminating)
Operating Temperature: -40°C to +70°C (-40°F to 158°F)
Doc. No.: M2010 Rev.: 11
Page 78 of 170
Specifications
D-10 Dimensions: Diameter: 5.8 cm (2.3 in.), Length: 28.2 cm (11.1 in.)
D-20 Dimensions: Diameter: 5.8 cm (2.3 in.), Length: 53.6 cm (21.1 in.)
Float Requirements: Low: 3.8 cm (1.5 in.), High: 27.9 cm (11 in.)
Belden #88760 or Alpha #55371
Cable: 3.6m (12 feet) of gas & oil resistant cable to
inline ISIM + 1.3m (4 feet) ISIM tail.
Maximum Wiring Length*: 305 m (1,000 ft.) field wiring
Alarm Threshold Configuration: Fully Automatic
12 to 13 (normal),
Diagnostic Reading from sensor setup: 3 to 4 (lower float in alarm - raised),
1 to 2 (upper and lower float in alarm - raised)
Multi-Drop Restriction: See Mixed Multi-drop Installation
Connections: Red = Power, Black = Signal, Shield = Ground
NOTE: *Maximum Wiring Length is the maximum length of cable to be used to connect all
sensors on an individual channel. This length includes run of cable from VSmart to each
sensor board in the string.
Installation
NOTE: To ensure safe operating conditions the sensor has been designed to connect to
OPW Tank Gauges Smart Sensor 12V IS Module ONLY. Smart sensors CANNOT be used
with SS1, 2 or 3, iTouch or any EECO consoles.
Doc. No.: M2010 Rev.: 11
Page 79 of 170
Ensure the cabling (gas and oil resistant FMS part # 12-1030) back to the
controller is in conduit that is dedicated to intrinsically safe wiring.
Connections
Controller Setup
l On the console, from the Home\Settings\Probe and Sensor screen the sensor should be Auto Detected
(see the console configuration manual). Alarm thresholds are configured automatically through the
Intellisense mechanism between the sensor and the console.
Description
IMPORTANT: This float body is identical to the 30-0232-D10 & D20 and 30-0232-DH-10 &
DH-20. Check the label to make sure you are using the correct sensor for the intended
purpose.
The dual-level reservoir sensor, either 10 inch (25cm) or 20 inch (50cm), is designed for use in the brine-
filled reservoir of the interstitial area of a doubled-walled tank. This sensor contains a dual-level float switch
that detects level changes of fluid in the reservoir of the tank. The sensor expects the liquid to be at a
constant level midway between the upper and lower floats. The system will activate the alarm when the brine
level in the interstitial space either rises or falls.
Since this sensor is not intended for detection of hydrocarbons it does not use a carbon/polymer strip.
No Carbon/Polymer Strip
Dual float switches are incorporated into the body that cause an alarm condition when low and high levels
are detected. The bottom float of the brine sensor will remain in the up position in a normal condition. When
in alarm, the sensor will have either triggered the upper float or the level has dropped below the bottom float.
Doc. No.: M2010 Rev.: 11
Page 83 of 170
Specifications
Primary Use: Measure level of brine solution
Detects: Low Liquid, High Liquid
Operating Temperature: -40°C to +70°C (-40°F to 158°F)
D-10B Dimensions: Diameter: 5.8 cm (2.3 in.), Length: 28.2 cm (11.1 in.)
D-20B Dimensions Diameter: 5.8 cm (2.3 in.), Length: 53.6 cm (21.1 in.)
D-10B Dimensions: Diameter: 5.8 cm (2.3 in.), Length: 28.2 cm (11.1 in.)
D-20B Dimensions: Diameter: 5.8 cm (2.3 in.), Length: 53.6 cm (21.1 in.)
Float Requirements: Low: 3.8 cm (1.5 in.), High: 27.9 cm (11 in.)
Belden #88760 or Alpha #55371
Cable: 3.6 m (12 feet) of gas & oil resistant cable to
inline ISIM + 1.3 m (4 feet) ISIM tail
NOTE: *Maximum Wiring Length is the maximum length of cable to be used to connect all
sensors on an individual channel. This length includes run of cable from VSmart to each
sensor board in the string.
Installation
NOTE: To ensure safe operating conditions this sensor has been designed to connect to
OPW Tank Gauges Smart Sensor 12V IS Module ONLY. Smart sensors CANNOT be used
with SS1, 2 or 3, iTouch or any EECO consoles.
Ensure the cabling (gas and oil resistant FMS part # 12-1030) back to the
controller is in conduit that is dedicated to intrinsically safe wiring.
Connections
Controller Setup
l On the console, the sensor should be Auto Detected (see the console configuration manual). Alarm
thresholds are configured automatically through the Intellisense mechanism between the sensor and
the console.
If the controller fails to go in to alarm, check that the thresholds programmed in the system are correct. Check
the orientation of the float as described earlier. A sensor or wiring fault will trigger a system alarm. Check all
wiring and junction boxes to ensuring continuity without shorts.
Doc. No.: M2010 Rev.: 11
Page 87 of 170
Description
The hydrocarbon vapor sensor is designed to detect hydrocarbon vapors in monitoring wells and the
interstitial areas of a double-walled tank. The presence of these vapors could indicate a potentially
dangerous leak that could lead to safety and environmental problems. The sensor is made from a long-life
resistive element that increases dramatically in resistance in the presence of hydrocarbon vapors. After the
vapors have dissipated, the sensor returns to normal and is ready to detect hydrocarbon vapors again. In the
event of a break in the cable, the system will activate the alarm.
Specifications
Primary Use: Monitoring wells
Alternate Use(s): Interstitial areas of a double-walled tank
Detects: Hydrocarbon vapor
Operating Temperature: -40°C to +70°C (-40°F to 158°F)
Dimensions: Length: 8.9 cm (3.5”), Diameter: 2.3 cm (0.9”)
Nominal resistance (uncontaminated) Uncontaminated: 3,000 - 5,000 ohms
Nominal resistance (contaminated) Contaminated: 10,000 - 200,000 ohms
Belden #88760 or Alpha #55371
Cable:
Doc. No.: M2010 Rev.: 11
Page 88 of 170
Specifications
12 feet (3.6m) of gas & oil resistant cable to inline ISIM + 4
feet (1.3m) ISIM tail.
Maximum Wiring Length*: 305 m (1,000 ft.) field wiring
Alarm Threshold Configuration: Fully Automatic
Diagnostic Reading from Sensor Setup: 0 to 1 (normal) above 5 (in-alarm)
Multi-Drop Restriction: See Mixed Multi-drop Installation
Connections: Red = Power, Black = Signal, Shield = Ground
NOTE: *Maximum Wiring Length is the maximum length of cable to be used to connect all
sensors on an individual channel. This length includes run of cable from VSmart to each
sensor board in the string.
Installation
Ensure the cabling (gas and oil resistant FMS part # 12-1030) back to the
controller is in conduit that is dedicated to intrinsically safe wiring.
NOTE: If this sensor becomes fully immersed in water it will NOT be able to detect
hydrocarbon vapor.
Connections
Controller Setup
l On the console, the sensor should be Auto Detected (see the console configuration manual). Alarm
thresholds are configured automatically through the Intellisense mechanism between the sensor and
the console.
l Place the sensor in the air space of a container filled halfway with Mineral Spirits.
l Wait approximately 10 minutes. This should cause an alarm condition in the controller.
l If the controller fails to go into alarm, check that the thresholds programmed in the system are correct. A
sensor or wiring fault will trigger a system alarm. Check all wiring and junction boxes to ensure
continuity without shorts.
Certification Leak rate of 0.2 gph with PD = 98.18% and PFA = 1.82% using 924B probe with 2” dia float.
Leak Threshold 0.1 gph for leak rate of 0.2 gph using 924B probe with 2” dia floats. A tank system should not be declared tight if the test
result indicates a loss or gain that equals or exceeds this threshold.
Applicability Gasoline, diesel, aviation fuel. Other liquids with known coefficients of expansion and density may be tested after con-
sultation with the manufacturer.
Tank Capacity Maximum of 20,000 gallons. Tank must be minimum 50% full for leak rate of 0.2 gph using 924B probe.
Waiting Time Minimum of 6 hours between delivery and testing using 924B probe. There must be no delivery during waiting time.
Test Period Average data collection time of 2 hours using 924B probe for leak rate of 0.2 gph. Test data are acquired and recorded by
system's computer. There must be no dispensing or delivery during test.
Water Sensor Minimum detectable water level that can be detected by the 2” dia float is 0.75 inch. Minimum detectable change in water
level that can be detected by the 2” dia float is 0.080 inch.
Calibration Thermistors (or RTDs) and probe must be checked and, if necessary, calibrated in accordance with manufacturer's
instructions.
Comments Not evaluated using manifolded tank systems. Therefore, this certification is only applicable when there is a probe used
in each tank and the siphon is broken during testing.
Tests only portion of tank containing product. As product level is lowered, leak rate in a leaking tank decreases (due to
lower head pressure).
Consistent testing at low levels could allow a leak to remain undetected.
EPA leak detection regulations require testing of the portion of the tank system which routinely contains product.
2012 console comparison with OPW iSite; which was based on 2-26-2008 evaluation of OPW iSite.
IMPORTANT: ProGauge probes cannot be connected to the internal I.S. barrier of the OPW-
FMS SiteSentinel NANO. The XMT-SI-485 probe must be connected to either a MagDirect
active or passive I.S. barrier device that will communicate with the NANO through an RS485
serial connection. The XMT-SI-RS wireless probe first sends a signal to an RF Receiver that
will then communicate with the NANO through an RS485 serial connection. The appendices
that follow will give all of the necessary information on the installation of these devices.
General Information
Safety
Read these instructions carefully
The manufacturer is not responsible for any operation not given in these instructions.
Any failure or faulty operation of this equipment should be referred to authorized personnel for maintenance
or, contact the manufacturer directly.
NOTICE: The manufacturer is not responsible for injury and/or property damage.
IMPORTANT: Please refer to "Installer Safety" on page 11 for important safety information
related to installation of this equipment.
Technical Characteristics
XMT-SI-485
l Power supply 12 VDC through an intrinsically safe barrier
l Consumption < 15 mA @ 12 Vdc normal function
l Consumption < 200 uA @12 Vdc in sleep mode
l Connection cable: hydrocarbons resistant, suitable for underground pose with insulation 0,6-1KV, 2
shielded and twisted pairs, section of the power cable pair of at least 1mm2.
l Type of cable supplied: LiYstCYY INSULATION LEVEL 4 (0,6/1KV) - (4x0.50mm²) + CEI 20-22II IEC
60332-3A ENI 00.181.00.
l Maximum transmission distance: up to 2 Km based on standard of RS485 interface.
Doc. No.: M2010 Rev.: 11
Page 97 of 170
XMT-SI-RF
l Internal power supply through an instrinsically safe battery 3.6V, 16Ah
l Low frequency transmission to a receiver located in a safety zone
l Consumption <15 mA @ 12 Vdc normal function
l Consumption < 200 uA @12 Vdc in sleep mode
Measurement Characteristics
l Electronics based on a Microprocessor
l Support telediagnostics and telemaintenance
l Possibility to configure remotely the functional parameters
l When maintenance is necessary, the internal parts of the probe can be removed and it will not be
necessary to remove fuel from the tank. This is good for LPG applications where tanks are pressurized.
l Tank connection:
n Not needed if probe is inserted into a riser with internal diameter 2”
n 2” sliding connection (optional).
n Other type of optional connections under request (nippled fixed, flanged, …)
l Stainless steel case, IP68.
l Probe shaft Stainless Steel AISI 304 / 316
l Measurement range: from 200 mm. to 12.500 mm.
l Maximum mechanical length: 13.000 mm.
l Data transmitted:
n Product level in 0.01 mm
n Water level in 0.01 mm
n Medium temperature detected through digital temperature sensor placed along the probe shaft
(standard 1, max 5)
l Measurement accuracy: Better than +/- 0.5 mm.
l Measurement resolution: +/- 0.01 mm.
l Temperature accuracy: +/- 0,2°C
l Approvals :
n OIML-R85 for fixed applications
n OIML-R80 per mobile applications (pending)
Doc. No.: M2010 Rev.: 11
Page 98 of 170
Connector Wiring
The serial number is applicable to each probe and is used as the probe address for configuration in the
console. See "XMT-SI-485 DIP-Switch Settings" on page 110 for more information.
Installation
NOTICE: Install this electronic device carefully. Make sure the stainless steel tube does
not bend when installed in a tank man-hole. This could cause damage to the electronic
components inside.
The standard version of the XMT-SI probe is supplied with a sliding 2 inch gas "M" fitting. This fitting is not
supplied when the installation occurs in a protection riser.
The probe assembly with the sliding 2 inch gas "M" fitting and floats can be easily put through the 2 inch tank
opening without dis-assembly.
Probe placement: Please refer to "Probe Placement" on page 36 for instructions on probe installation
location and distances from fill tubes and pumps.
Before you install the probe, be sure the floats are positioned correctly. Make sure the plastic probe shaft end
cap is correctly installed on the bottom of the probe shaft so that the floats can correctly identify water and fuel
levels.
Make sure that when a riser is used, that the probe is installed high enough so it cannot get flooded. Put the
probe through the 2 inch opening and carefully lower it until it touches the bottom of the tank.
Doc. No.: M2010 Rev.: 11
Page 99 of 170
l Seal the threads at the sides of the flange with plumber's hemp and sealant to make a tight seal.
l Carefully install the assembled probe through the riser and flange into the tank.
Doc. No.: M2010 Rev.: 11
Page 101 of 170
l Install the PA 2 inch protective sleeve (purchased option when the XMT-SI-RF is installed in a riser).
Apply a thread sealant to the male threads of the riser and the female sleeve flange and between the
male threads of the PA2 and the female sleeve flange.
IMPORTANT: Do not use a permanent type sealant. The sealant is used only to keep water
out of the riser. It is necessary for the PA2 to be easily unscrewed to gain access to the battery
housing and other probe components.
Doc. No.: M2010 Rev.: 11
Page 102 of 170
Doc. No.: M2010 Rev.: 11
Page 103 of 170
Installation is the same as for an RF probe but with the differences that follow:
l The riser must be long enough to contain the full length of the probe.
l The inside diameter of the riser must be tapped with the correct thread so that the riser cap can be
tightened correctly.
l A cable gland must be installed at the top of the cap to correctly hold the wire cable.
l All components of the riser assembly must be sealed correctly so outside contamination cannot enter
the tank.
Electrical Connection
Refer to the safety instructions and procedures found in "Installer Safety" on page 11, "Probe Installation in
Underground Storage Tanks" on page 37 and "Probe-Cable Seal-offs" on page 35.
l The installation should only be done by approved persons.
l Obey all safety rules and regulations.
l Read these instructions carefully.
l The manufacturer is not responsible for property damage or costs related to incorrect installation.
Doc. No.: M2010 Rev.: 11
Page 104 of 170
The probe is supplied with 1.5 meters (5 ft) of cable connected through a 7/8" connector to the probe head.
This cable must be connected to the field wiring in a junction box.
IMPORTANT: Use a junction box rated IP68 of the IP Code, International Protection Marking,
IEC standard 60529 (International Electrotechnical Commission).
The 4 wire connection cable has red (or black)-brown-blue and white wire colors.
At the terminal box, connect wires to the same color, red to red, white to white etc.
The cable shield must be connected in parallel as a fifth wire and connected to the earth ground in the office.
The ground tap must not be shared with other power systems or motors.
XMT-SI-RF Housing
To get access to the probe's inner components (battery housing, probe board with jumper block and DIP-
Switches), turn the cap counter-clockwise and carefully remove it from the housing.
Doc. No.: M2010 Rev.: 11
Page 105 of 170
Jumper Setting
Jumper settings are shown below. The Jumpers are read during device startup. When changes are made,
the device must be switched off and restarted for the changes to be applied.
Jumper
Inserted Removed
#
1 1 Float 2 Floats
2 Diagnostic Mode (for production use only) NORMAL Mode (recommended)
3 Wired Probe RF Probe
Select Protocol 1 (applicable only for RS485 Select Protocol 2 (applicable only for RS485
4
probe) probe)
The illustration below shows the location of the Jumper Block on the probe board.
Doc. No.: M2010 Rev.: 11
Page 106 of 170
NOTE: RF probes use a frequency of 169,4 Mhz, transmit on channel 5 (169,468 MHz),
power 80 mW (standard) up to 200 mW.
The illustration below shows the location of the DIP-Switch Block on the probe board.
DIP-Switch settings are shown below. The DIP-Switches are read during device startup. When changes are
made, the device must be switched off and restarted for the changes to be applied.
To optimize battery life, the probe usually operates in Sleep Mode.
The probe will be awakened at the time increment set by the selected Operation Mode and will make its
measurement. If the product or water level measurement is ±1 mm compared to the last measurement, the
probe will transmit the measurement. If the measurement comparison is less than 1 mm, the probe will return
to Sleep Mode.
NOTE: To prevent a time-out of the system the probe will always transmit data after 10
minutes of non-transmission.
The probe is not supplied with the battery because the lithium battery is a Class 9 Hazmat. The battery must
be purchased separately. Before the probe is installed, open the probe housing to connect the battery. More
information on the battery can be found in the section "Important Battery Information" on page 113 below.
If the Operation Mode is set between 1 - 5, the probe will transmit data after power-up every five (5) seconds
for the first 24 hours. After that period, the probe will begin to transmit at the selected Operation Mode.
Doc. No.: M2010 Rev.: 11
Page 107 of 170
NOTE: This feature lets you do a check of the signal and not have to wait for the longer
periods of Sleep Mode. This feature is not available for Operation Modes 12 - 16.
Battery
Life (in
SW SW SW SW
Mode Transmission Interval years) at
1 2 3 4
200 mW
Power
Data calculation uses worst conditions (for example, if the probe is programmed to transmit every one
minute and effectively transmits every minute). The battery life will be extended if the probe does not
transmit with a reading difference of ±1 mm.
Doc. No.: M2010 Rev.: 11
Page 109 of 170
IMPORTANT: This data is calculated with a 16.5 Ah battery. This is a certified Intrinsically
Safe device and the battery recommended by the manufacturer complies with the conditions of
certification. Use of a type of battery other than that specified by the manufacturer will
compromise the Intrinsically Safe certification. OPW-FMS, Tokheim/Pro Gauge or Start
Italiana cannot be held responsible for equipment failures or safety issues related to use of an
non-certified battery.
More information on the battery can be found in the section "Important Battery Information" on page 113
below.
Doc. No.: M2010 Rev.: 11
Page 110 of 170
SW 1 SW 2 SW 3 SW 4 Address
Transmission Protocol
Protocol is valid only for XMT-SI-485 probes. Do not use this protocol for RF probes.
Transmission parameters:
l Speed: 9600 bps
l Parity: none
l Data bit: 8
l Stop bit: 1
l Flow control: none
When this setting is used, the probe does not go into Sleep Mode but stays in operation. All data
transmission is received and answered only when a message comes in on its address.
Two (2) different replies (see the jumper settings below) are available to be compatible with earlier protocols.
Jumper
Inserted Removed
#
1 1 Float 2 Floats
2 Diagnostic Mode (for production use only) NORMAL Mode (recommended)
3 Wired Probe RF Probe
Select Protocol 1 (applicable only for RS485 Select Protocol 2 (applicable only for RS485
4
probe) probe)
LED Behavior
There are two (2) LEDs inside the probe that give important status information.
GREEN LED:
The GREEN LED shows the status of the probe's float detection.
l GREEN LED flashes quickly: This is an indication that the probe is in normal operation.
l GREEN LED flashes slowly: The probe cannot detect the float. This could be caused by:
n A missing float
n The float was installed upside-down
n A bent probe shaft
n A damaged float
RED LED:
The RED LED identifies the status of serial communication.
l RED LED is OFF: No data is received on the serial communication RS485 port.
l RED LED is ON: Serial communication is received but the probe address is not read.
l RED LED is ON then turns OFF: Three (3) seconds of timeout has passed without any serial
communication or the probe has been addressed and it is in reply.
NOTE: The polling cycle and frequency as well as the number of probes installed on the
same bus will have a direct effect on the RED LED behavior.
Doc. No.: M2010 Rev.: 11
Page 113 of 170
The lithium battery can cause fire or explosion if they are not used correctly.
Replace the battery with SAFT LS33600 ONLY. Use of another battery can
cause a risk of fire or explosion.
To prevent possible explosion or fire, do not replace the lithium battery with a
type that is not compatible.
The battery used in this device can cause a risk of fire or chemical burn if
used incorrectly. Do not recharge, short circuit, crush, disassemble, heat
above 100° C, let contents touch water or put in fire.
Certifications
Doc. No.: M2010 Rev.: 11
Page 115 of 170
Doc. No.: M2010 Rev.: 11
Page 116 of 170
Doc. No.: M2010 Rev.: 11
Page 117 of 170
Doc. No.: M2010 Rev.: 11
Page 118 of 170
Doc. No.: M2010 Rev.: 11
Page 119 of 170
Doc. No.: M2010 Rev.: 11
Page 120 of 170
Doc. No.: M2010 Rev.: 11
Page 121 of 170
Technical Information
Features
Power Supply 12-24V
RF Module 169MHZ 1
RF Module 434MHz (currently not available; for future usage) 1
Serial RS485 1
Antenna 169.4 MHz 1
Antenna 434 MHz (currently not available; for future usage) 1
LED Diagnostics TX-RX 4
LED Diagnostics functioning 4
Repeater/Receiver functionality SI
Power supply 220Vac Optional
Antenna Harmattan 169,4MHz 1
Dipswitch functions programming 4-Way
Dimensions 24x16x9cm
Doc. No.: M2010 Rev.: 11
Page 122 of 170
Electrical Connection
Power Supply
White Terminal, GND - CN1 position 4
Red terminal, +Vcc - CN1 position 1
RS485 Connection
Blue Data RS485 A - CN1 position 3
Brown Data RS485 B - CN1 position 2
ELECTRICAL
Frequency range: (V.S.W.R. < 2 : 1) 162-174 MHz
Impedance: 50 Ω
V.S.W.R. at 169 Mhz: <2:1
Max power: 15 W
Polarization: Linear
Irradiation: Omnidirectional
Gain at 169 MHz: 2.1 dBi
MECHANICAL
Dimensions (approximate): 830 x 150 x 85 mm
Connection: BNC male
Operating temperature range: -40° / +80° C
Weight: 0.250 kg
Radiating element material: Whip made of steel and brass, thermoretractable sheath.
Accessories: Bracket for pole mounting (from Ø min. 40 mm to max. 60 mm)
Doc. No.: M2010 Rev.: 11
Page 124 of 170
Antenna Installation
Each antenna has its own radiation diagram.
The radiation diagram shows the directions where the antenna can transmit the signal with the most power.
The diagrams below show the directional patterns of the probe antenna and the receiver antenna.
To have the best reception without signal loss, the antennas must be pointed in the same direction.
EXAMPLE:
You cannot set up the receiver antenna horizontally if all of the probe transmitters are all set up
vertically. This would result in almost complete loss of signal because of different polarization
(horizontal instead of vertical).
The probe antenna does not transmit or receive from its top, but through its side (see the illustration above).
The antennas must always be kept parallel to each other.
If it is necessary to install a probe antenna under asphalt horizontally, the receiver antenna must also be
installed horizontally.
Wireless probes use a battery with a low frequency for data transmission. The bandwidth used is 169.4 MHz
with a narrow canalization of 12.5 KHz. Since the transmission occurs underground, his band has low
attenuation because of blockage or surrounding land.
This transmission must not be mistaken for wi-fi which uses higher frequencies of 1.2-2.4 GHz. Wi-fi does not
have the minimum requirement to transmit through the manhole.
If the antennas are installed outdoors, the transmission can reach to 1 km. For usage at service stations
where the antennas are installed underground (integrated into the probe head) the distance of transmission
in normal conditions is 100-200 m.
Normal conditions include installations where it is not necessary to have a Faraday Cage that would block
the signal transmission.
Common manhole constructions that block signal transmission like a Faraday Cage include:
Doc. No.: M2010 Rev.: 11
Page 125 of 170
NOTE: When a highly attenuated signal can occur, put the probe antenna outside of the
manhole. "Repeaters" can be installed to boost or extend the signal if necessary.
Doc. No.: M2010 Rev.: 11
Page 126 of 170
Installer Notes:
(to find out if RF
Topic Condition
Probes are possible
before installation)
LED Diagnostics
On startup, refers to
DL2 Must flash and indicates that the board is working properly.
RUN.
Wired on RX line of
Flashing indicates that a valid frame has been received by
DL8 the 169,4MHz mod-
the module and transmitted to the microprocessor.
ule.
wired on TX line of the Flashing indicates that a valid frame has been sent to the
DL9
169,4MHz module. module to be transmitted.
Information about the probes registered and received:
DL4 Refers to the units. Flashes from 0 to 9.
DL1 Refers to the tens. Flashes from 0 to 6.
Example: If 16 probes have been registered there will be 1 flash for DL1 and 6 flashes for DL4.
DL3 Off (currently not available; for future usage)
Doc. No.: M2010 Rev.: 11
Page 128 of 170
DIP-Switch Settings
Setting 1:
Normal functioning, answers through the new protocol both on RS485 and RS232.
EXAMPLE:
D) M03744+chr(13)
R) 03744N0=+250=00129.37=00031.00=082+chr(10)+chr(13)
Probe address: 03744
Probe status: (0 = OK) in case of error status=1
Temperature: +25,0 °C
Product level: 129,37 mm
Water level: 31,00 mm
Setting 2:
Normal functioning, answers through the old protocol both on RS485 and RS232.
EXAMPLE:
D) M03744+chr(13)
R) 03744=0=+250=01294=0031=237+chr(10)+chr(13)
Probe address: 03744
Probe status: (0 = OK) in case of error status=1
Temperature: +25,0 °C
Product level: 129,4 mm
Water level: 31,00 mm
Doc. No.: M2010 Rev.: 11
Page 130 of 170
Setting 3:
Inside the receiver, 10.000 is added to the wireless probe address, answers through the new protocol both
on RS485 and RS232.
Use this setting when two (2) receivers are installed for maximum signal coverage. The two receivers must
be connected in parallel on the RS485 line. To avoid conflicts on the transmission bus this setting should be
used on only one of the receivers.
Select and read the message from the receiver with the stronger signal. Configure the console with the probe
address or with the probe address +10.000 to receive the message.
EXAMPLE:
If the wireless probe has address 03744, it is necessary to add 10.000 to query the receiver.
D) M13744+chr(13)
R) 13744N0=+250=00129.37=00031.00=083+chr(10)+chr(13)
Probe address: 03744
Probe status: (0 = OK) in case of error status=1
Temperature: +25,0 °C
Product level: 129,37 mm
Water level: 31,00 mm
Setting 4:
Inside the receiver 10.000 is added to the wireless probe address, answers through the old protocol both on
RS485 and RS232.
Use this setting when two (2) receivers are installed for maximum signal coverage. The two receivers must
be connected in parallel on the RS485 line. To avoid conflicts on the transmission bus this setting should be
used on only one of the receivers.
Configure the console with the probe address or with the probe address +10.000 to receive the message.
EXAMPLE:
If the wireless probe has address 03744, it is necessary to add 10.000 to query the receiver.
D) M03744+chr(13)
R) 03744=0=+250=01294=0031=237+chr(10)+chr(13)
Probe address: 03744
Probe status: (0 = OK) in case of error status=1
Temperature: +25,0 °C
Product level: 129,4 mm
Water level: 31,00 mm
Doc. No.: M2010 Rev.: 11
Page 131 of 170
Setting 8:
Repeater mode: Everything received on the radio channel is always immediately retransmitted on the radio
channel.
Transmission always done with frame recognition: The receiver waits with a silence of at least 20 ms on the
radio channel. This is to specify the end of a transmission and then continue with the retransmission.
Answers with the new protocol both on RS485 and RS232.
Setting 15:
ByPass function: This can only be used during the system test. Everything received on the radio channel is
retransmitted on RS232 as a character. This will not reply to any command.
Doc. No.: M2010 Rev.: 11
Page 132 of 170
Available Commands
Speed 9600
Data bits: 8
Parity bit: none
Stop bit: 1
Command M
Asks for the measurement. See the examples above.
Command D
Asks for the diagnostics.
EXAMPLE:
D) D14832+chr(13)
R)
14832D105=00000118=00006721=00000118=001=005=200=015=048=113=078=045=100=07
1=197
Probe address: 14832
Window of the signal: 105
Packets transmitted by the probe: 118
Counter of packets of the probe: 6721 (shows how long the probe has been switched on)
Packets received by the receiver: 118
Number of floats: 1
Transmission channel: 5
Signal power: 200
Operating mode: 15
Level of the local signal: -48 dB
Level of the local noise: -113 dB
Tension of the receiver: 78/21.1=3,7V (value transmitted to be divided by 21,1)
Level of the probe signal:
n -45 dB to -80 dB (Good Signal)
n -80 dB to -90 dB (Poor Signal)
n More than -90 dB (Signal cannot be used)
Level of the probe noise: -100 dB
Tension of the receiver: 71/21.1=3,4V (value transmitted to be divided by 21,1)
Doc. No.: M2010 Rev.: 11
Page 133 of 170
Command V
Asks for the version.
Command C
Asks for the list of all the registered probes.
EXAMPLE:
D) C+chr(13)
R)
03746N0=+290=00105.68=00028.64=102
03967N0=+290=00092.30=00016.32=093
03745N0=+290=00090.78=00015.47=102
03962N0=+280=00090.57=00015.61=095
14832N0=+260=00254.01=00000.00=069
Order Code
When you place your order please use these order codes:
POWER SUPPLY 24V
RECEIVER WITH LOW GAIN ANTENNA: ....................................RIC-RF
RECEIVER WITH HIGH GAIN HARMATTAN ANTENNA: ........RIC-RF-HARM
POWER SUPPLY 220Vac
RECEIVER WITH LOW GAIN ANTENNA: ....................................RIC-RF-220
RECEIVER WITH HIGH GAIN HARMATTAN ANTENNA: .........RIC-RF-HARM-2
Doc. No.: M2010 Rev.: 11
Page 134 of 170
On both BRA-SIP and BRA-SI, connectors from CN2 to CN9 are used to connect up to eight (8) probes.
Doc. No.: M2010 Rev.: 11
Page 137 of 170
NOTE: On the BRA-SI Active Barrier these two modes are handled in parallel and cannot be
used simultaneously.
The case is equipped with eight (8) cable glands (PG11 color BLUE) for cable entry of eight (8) probes
maximum, and one (1) cable gland (PG9 color WHITE) to connect the interface to the system.
System Examples
Fuel POS
To configure the Magdirect to use with a Fuel POS (Point of Sale):
IMPORTANT: Keep a record of the probe serial numbers and the tanks where they are
installed as a reference for configuration in the console.
l Enter the Serial Number into the Probe ID field. If a bar code scanner is connected to your PC you can
scan the serial number bar code to enter the Serial Number.
Doc. No.: M2010 Rev.: 11
Page 140 of 170
Connections:
- Safety zone -
JH5 - positive power supply
JH4 - negative power supply
JH8 - RS485 “ B “
JH7 - RS485 “ A “
JH6 - common RS485 (earth)
EARTH WIRE - connection to earth bar
- Hazardous zone -
JH5 - positive power supply
JH4 - negative power supply
JH8 - RS485 “ B “
JH7 - RS485 “ A “
JH6 - common RS485 (earth)
EARTH WIRE - connection to earth bar
NOTE: The EARTH WIRE cable is internally connected to terminals JH4, JH6, JH10. It must
be connected to the earth bar that, on its side, must be connected to the earth of the system
with a separate cable. The earth connection must have a maximum resistance of 1 Ohm.
The transmitter (or transmitters) located in Hazardous Area must not be connected to the earth.
The terminal JH6 (common RS485 in Safety Zone) could be left not connected if the power
supply (terminals JH5 and JH4) integrates RS485 interface. In this case we will have:
MR 3 - SAFETY ZONE
TO PROBE
PIN 3: +12V OUT .....................(RED)
PIN10: -0V OUT .......................(WHITE)
PIN 2: CHANNEL DATA B .......(BLUE)
PIN 1: CHANNEL DATA A .......(BROWN)
MR 2 - HAZARDOUS ZONE
TO SYSTEM
PIN 8: CHANNEL DATA A .......(BROWN)
PIN 7: CHANNEL DATA B .......(BLUE)
Characteristics: BRA-SIP
Device: BRA-SIP
Ex Classification: II (1) G [Ex ia] IIB - FISCO Power Supply Um = 250 V [Ex ia] IIB
Certificate Number: CEC 10 ATEX 025 Rev. 3
BRA-SI
Description:
BRA-SI device is a barrier with galvanic isolation and intrinsically safe, used to connect/power devices
placed in a hazardous zone.
BRA-SI device has:
l One power channel.
l Two RS485 communication channels.
l One RS232 communication channel in the safe zone.
A typical device is a data transmitter, 12Vdc powered that uses the RS485 communication port.
Device Marking:
The data interface in Safe Area is both RS485 (CN6) and RS232 (CN2). The two modes are
managed in parallel and cannot be used simultaneously.
The terminal CN2-3 (commonly RS485 Safe Area) can be connected to the negative power
supply (terminal CN 1-2) if the power supply incorporates the RS485 interface.
If RS232 is used (CN2) it is recommended to keep the galvanic isolation between power
supply (CN1) and connect RS232 (CN2).
Characteristics: BRA-SI
Device: BRA-SI
Ex Classification: II (1) G [Ex ia] IIB - FISCO Power Supply Um = 400 V [Ex ia] IIB
Certificate Number: CEC 10 ATEX 025 Rev. 3
Safety Instructions
0722 - Start Italiana Srl – Via Pola 6, 20813 Bovisio Masciago (MB)
BRA-SIP:
Addressed to qualified personnel in accordance with national laws, including relevant standards, and where
applicable in accordance with IEC 60079-17 referred to electrical device for potentially explosive
atmospheres.
l Technical data indicated on the label of the device level meter to be respected.
l Amendments on the product are not permitted.
l The barrier can be installed only if fully intact.
l Only START Italiana spare parts shall be used.
l Ordinary and extraordinary operations of maintenance must be carried out only by qualified personnel
with the approval of “expert technicians”.
l The following instructions must be observed scrupulously to get a perfect installation.
l The national standards of safety and accident prevention and the requirements indicated with in
this technical dossier must be strictly observed.
l Take probes to safety zone before barrier substitution.
Doc. No.: M2010 Rev.: 11
Page 152 of 170
BRA-SIP:
Warnings
l The employ of this equipment in hazardous areas requires special attention and special precautions
during use and maintenance. Avoid dust deposit.
l Clean only with damp cloth and / or anti-static and not aggressive products.
l The equipment has been approved for areas of use with specific characteristics: do not install and use
the unit in environments different from those provided.
l Installation, maintenance and repair of the equipment should be performed only by qualified, skilled,
instructed and authorized technicians.
l The equipment security is guaranteed only if device is installed, checked, maintained, used and
maintained according to the provisions outlined in the installation guide.
l Do not cover with coverage made of materials that can be loaded electrostatically.
l It is forbidden to modify or repair the equipment using components not conforming to the certification;
this operation undermines the intrinsic safety of the instrument (with consequent loss of Ex approval)
and causes the invalidation of the product warranty.
l All connections must be performed in accordance with regulations applicable in the area and
environment of installation, as per standard EN 60079-14. Please separate, protect and highlight with
appropriate color reference the intrinsically safe signals.
l The stockings of any shielded cables must be grounded in the external devices connected, so as not to
complicate the wiring in the box.
l Perform maintenance in accordance with the standard EN 60079-17 and EN 61241-17.
Safety Data
R=74,19
Power Data I/O Power Data I/O
Ohm x km
14 Vmax 6 Vmax 18,25 Vmax 12 Vmax R=18,55 Ohm x km
Um=250 V Um=6 V Um=400 V Uo=6 Vmax C/C<150 pF x m
Io=100 Ma Io=100 Ma Io=100 Ma Io=100 Ma C/S<200 Pf x m
Lo=1,5 Mh Lo=6 Mh [3] Lo=1,5 Mh [3] Lo=6 Mh [3] Lo<1 Nh x m
Po=0,153 W Po=0,126 W Po=0,153 W Po=0,126 W Riso>200 Mohm x km
Uo=14 Vmax Uo=6 Vmax Uo=14,05 Vmax Uo=6 Vmax
Co=3,55 Uf Co=40 Uf [2] Co=3,55 Uf Co=40 Uf [2]
Ree=15,3 Ree=12,6 - [1] - [1]
[3] ref. EN 60079-11, graph fig. A.4, for IIB, I=Io x 1.5
2. The voltage current of this associated apparatus is limited by a resistor such that the output voltage-
current plot is a straight line drawn between open-circuit voltage and short-circuit current.
3. Selected intrinsically safe equipment must be third party listed as intrinsically safe for the application
and have intrinsically safe entity parameters conforming with the following:
4. This associated apparatus may also be connected to simple apparatus as defined in Article 504.2 and
installed and temperature classified in accordance with Article 504.10(B) of the National Electrical
Code (ANSI/NFPA 70) or other local codes, as applicable.
5. Capacitance and inductance of the field wiring from the intrinsically safe equipment to the associated
apparatus shall be calculated and must be included in the system calculations as shown in Table 1.
Cable capacitance, Ccable, plus intrinsically safe equipment capacitance, Ci must be less than the
marked capacitance, Ca (or Co), shown on any associated apparatus used. The same applies for
inductance (Lcable, Li and La or Lo, respectively). Where the cable capacitance and inductance per
foot are not known, the following values shall be used: Ccable = 60pF/ft., Lcable = 0.2uH/ft.
6. The associated apparatus must be connected to a suitable ground electrode per the National Electrical
Code (ANSI/NFPA 70), the Canadian Electrical Code or other local installation codes, as applicable.
The resistance of the ground path must be less than 1 ohm.
7. Where multiple circuits extend from the same piece of associated apparatus, they must be installed in
separate cables or in one cable having suitable insulation. Refer to Article 504.30(B) of the National
Electrical Code (ANSI/NFPA 70) and Instrument Society of America Recommended Practice ISA
RP12.6 for installing Intrinsically safe equipment.
8. Intrinsically safe circuits must be wired and separated in accordance with Article 504.20 of the National
Electrical Code (ANSI/NFPA 70) or other local codes as applicable.
9. This associated apparatus has not been evaluated for use in combination with another associated
apparatus.
Doc. No.: M2010 Rev.: 11
Page 160 of 170
10. Control equipment must not use or generate more than 250V rms or dc with respect to earth
Doc. No.: M2010 Rev.: 11
Page 161 of 170
2. Associated Apparatus output current must be limited by a resistor such that the output voltage-current
plot is a straight line between open-circuit voltage and short-circuit current.
3. Selected Associated Apparatus must be third party listed as providing intrinsically safe circuits for the
application and have Voc or Vt not exceeding Vmax (or Uo not exceeding Ui), lsc or It not exceeding
Imax (or lo not exceeding Ii), and the Po of the associated apparatus must be less than or equal to the
Pmax or Pi of the intrinsically safe equipment as shown below.
4. Capacitance and inductance of the field wiring from the intrinsically safe equipment to the Associated
Apparatus shall be calculated and must be included in the system calculations as shown below. Cable
capacitance, Ccable, plus intrinsically safe equipment capacitance, Ci must be less than the marked
capacitance, Ca (or Co), shown on any associated apparatus used. The same applies for inductance
(Lcable, Li and La or Lo, respectively). Where the cable capacitance of inductance per foot are known,
the following values shall be used: Ccable = 60pF /ft., Lcable = 0.2uH/ft.
Use the following to determine the suitability of connections:
If Po of the associated apparatus is not known, it may be calculated using the following formula, Po=
(Uo*Io)/4
Example of a single 924B probe connected to a single position on the Associated Apparatus:
EXAMPLE:
Example Associated Apparatus 14.28V (Uo), 361mA (Io), 6.4uF (Co), 2,100uH (Lo)
Cable 1,000 feet, 60pF/ft, 0.2uH/ft = 0.060uF (60,000pf), 200uH
Doc. No.: M2010 Rev.: 11
Page 162 of 170
If the above statements are true (which they are) then it is safe to connect.
Example of 4 x 924B probes connected to a single position an the Associated Apparatus:
EXAMPLE:
Example Associated Apparatus 14.28V (Uo), 338mA (lo), 16.1 uF (Co), 2,240uH (Lo)
Cable 2,000 feet, 60pF/ft, 0.2uH/ft = 0.120uF (120,000pf), 400uH
If the above statements are true (which they are) then it is safe to connect.
5. Associated apparatus must be installed in accordance with its manufacturer's control drawing and
Article 504 of the National Electrical Code (ANSI/NFPA 70) for installation in the United States, or
Section 18 of the Canadian Electrical Code for installations in Canada. other local codes, as
applicable.
6. When required by the manufacturer's control drawing, the associated apparatus must be connected to
a suitable ground electrode per the National Electrical Code (ANSI/NFPA 70), the Canadian Electrical
Code, or other local installation codes as applicable. The resistance of the ground path must be less
than 1 ohm7
7. Associated apparatus must not be used in combination unless permitted by the associated apparatus
certification.
8. Control equipment must not use or generate more than 250Vrms or dc with respect to earth.
Doc. No.: M2010 Rev.: 11
Page 163 of 170
Doc. No.: M2010 Rev.: 11
Page 164 of 170
ISI standalone for attaching to a third party certified device Model 20-0349-ISI
3. Entity parameters
Entity input parameters of Intelligent Sensor Interface Module (ISI) when attached to sensor Includes a
maximum 15m cable between sensor and ISI.
Associated Apparatus must be third party listed (certified) as providing intrinsically safe circuits for the
application. Use the following to determine suitability of connections:
If Po of the associated apparatus is not known, it may be calculated using the following formula: Po=
(Uo*lo)/4
Associated Apparatus output current must be limited by resistor such that the output voltage current plot is
a straight line between open-circuit voltage and short-circuit current.
4. Calculating Capacitance
Doc. No.: M2010 Rev.: 11
Page 165 of 170
Capacitance of the field wiring from the intrinsically safe equipment to the Associated Apparatus shall be
calculated and must be included in the system calculations. Capacitance of the cable is Ccable. When
the cable capacitance per foot is not known, the following value shall be used: Ccable = 60pF/ft
The ISI, with or without sensor, has a Ci of OuF, so only the capacitance of the field wiring cable need to
be totaled and compared with the Associated Apparatus.
5. Calculating Inductance
Inductance of the field wiring from the intrinsically safe equipment to the Associated Apparatus shall be
calculated and must be included in the system calculations. Inductance of the cable is Lcable. When the
cable inductance per foot is not known, the following value shall be used: Lcable 0.2uH/Ft.
Add the Li Inductance of all the Sensors connected to the network and the cable inductance and compare
it to the Associated Apparatus.
EXAMPLE:
1,000 ft cable 0.0002 * 1000 = 0.2mH
8 sensors Li = 0.165mH 0.165 * 8 = 1.32mH
8 sensors Li = 50uH 0.00005 * 8 = 0.0004mH
Total inductance in network 0.2mH + 1.32mH + .0004mH = 1.5204mH
7. Installation
Associated apparatus must be installed in accordance with its manufacturers control drawing and Article
504 of the National Electrical Code (ANSI/NFPA 70) for installation in the United States, or Section 18 of
the Canadian Electrical Code for installations in Canada or other local codes as applicable.
When required by manufacturer's control drawing, the associated apparatus must be connected to a
suitable ground electrode per the National Electrical Code (ANSI/NFPA 70), the Canadian Electrical
Code or other local installation codes as applicable. The resistance of the ground path must be less than
1 ohm.
Associated Apparatus must not be used in combination unless permitted by the Associated Apparatus
Control drawing. Must not use or generate more than 250Vrrns or dc with respect to earth.
Doc. No.: M2010 Rev.: 11
Page 167 of 170
Doc. No.: M2010 Rev.: 11
Page 168 of 170
Warranty
OPW Fuel Management Systems warrants that all OPW Tank Gauge and Petro Vend Fuel Control systems supplied
by OPW Fuel Management Systems to the Original Purchaser will be free from defects in material and/or
workmanship under normal use and service for a period of 12 months from the date of installation or 15 months from
the date of shipment from OPW. Additionally, OPW Fuel Management Systems warrants that all upgrades and
replacement parts (new and remanufactured) supplied by OPW Fuel Management Systems will be free from defects in
material and workmanship under normal use and serviced for a period of 90 days from the date of installation or for the
remainder of the system’s original warranty, whichever is greater, as set forth in the first sentence of this statement.
The foregoing warranties will not extend to goods subjected to misuse, neglect, accident, or improper installation or
maintenance or which have been altered or repaired by anyone other than OPW Fuel Management Systems or its
authorized representative. The buyer’s acceptance of delivery of the goods constitutes acceptance of the foregoing
warranties and remedies, and all conditions and limitations thereof.
If a claim is made within the warranted time period that any equipment and/or remanufactured part is defective in
material or workmanship under normal use and service, such equipment and/or remanufactured part shall be returned
to OPW Fuel Management Systems, freight prepaid. If such equipment or remanufactured part is found by OPW Fuel
Management Systems in its sole judgment to be defective in material or workmanship under normal use and service,
OPW Fuel Management Systems shall, at its sole option, repair or replace such equipment and/or remanufactured part
(excluding, in all instances, fuses, ink cartridges, batteries, other consumable items, etc.) OPW Fuel Management
Systems shall not be held responsible for data loss or retrieval on returned products.
The warranties, as set forth above, are made expressly in lieu of all other warranties, either expressed or implied
(including, without limitation, warranties of merchantability and fitness for any particular purpose and of all other
obligations or liabilities on OPW Fuel Management Systems’ part.) Further, OPW Fuel Management Systems neither
assumes, nor authorizes any other person to assume for it, any other liability in connection with the sale of the
systems, or any new/replacement part that has been subject to any damage from any act of nature or any force
majeure. Any terms proposed by the Original Purchaser either orally or in writing are expressly rejected. The terms
and conditions expressed in this document may only be changed upon the express written consent of OPW Fuel
Management Systems.
The term “Original Purchaser” as used in these warranties shall be deemed to mean the authorized OPW Fuel
Management Systems’ distributor to which the system or any new/replacement part was originally sold. These
warranties may be assigned by the original purchaser to any of its customers who purchase any OPW Fuel
Management Systems’ systems or new/replacement parts. This document shall be governed by and construed in
accordance with the law of the State of Illinois. OPW Fuel Management Systems and Original Purchaser agree that
any legal action or proceeding under or with respect to this document may ONLY be brought in the courts of the State of
Illinois, or the United States District Court having jurisdiction in the City of Hodgkins, Illinois. Original Purchaser
expressly consents to personal jurisdiction in any of the above-mentioned forums and agrees to waive all defenses
based on improper venue or inconvenient form should an action be brought therein.
The sole liability of OPW Fuel Management Systems, for any breach of warranty, shall be as set forth above. OPW
Fuel Management Systems does not warrant against damage caused by accident, abuse, faulty or improper
installation or operation. In no event shall manufacturer’s liability on any claim for damages arising out of the
manufacture, sale, delivery or use of the goods exceed the original purchase price of the goods. In no event shall OPW
Fuel Management Systems be liable for any direct, indirect, incidental or consequential damage or loss of product.
TERMS
Ex-works our factory, Hodgkins, Illinois, USA
Installation not included.
All trade names are registered. Patents pending.
Subject to engineering improvement and/or other changes.
Doc. No.: M2010 Rev.: 11
Page 169 of 170
Revision History
Revision ECO Software
Effective Key Changes
# # Version*
0 624 7/18/14 Initial Release
Adds UL suggested battery warnings. Add probe/STP
graphic update. Add detailed instruction for sec. 5.1
1 696 3/3/15
Waterproof Elec Conn. Add density sensor/pressure
note
Sensor support...S07402 - Main Nano Application
2 834 11/6/15 3.42.38.3 Oracle Rev: 42 - Description: "Version: 3.42.38.3- Build
29"
Updated image for Nano Field Wiring Diagram (added
3 846 11/30/15
sensors)
Updated Declaration of Conformity for Nano Console
4 974 5/23/16
and added DOC for 924B Probes.
5 1041 9/21/16 Added Density Floats
Remove the sentence from page 37…"Sensors and
probes cannot be multi-dropped from the same I.S.
6 1088 12/22/16
channel. You must run sensors and probes to different
channels on the barrier." Update relevant images.
Add Precision spec for Density Floats
7 1105 01/11/17 Update 924B specs for Prod & Water Level Meas-
urements
In M4020: Applicable Warnings.htm - Add Integra con-
8 1109 01/30/2017 dition tag to NOTICE panel so that it does not appear on
Nano M2010 output.
9 1137 3/6/2017 Relabel the connection drawing to match 54-0525 label.
ProGauge support. Adds Control dwgs for Nano, 924B
10 1187 11/3/17
Probe and ISIM Sensors
Add M2018-PG-A&P in Site Wiring PG for EMEA
11 1350 4/13/18
(ProGauge/MagDirect)
NOTE: *It is possible that older software versions might not support all features.