MA-036 - DGA 900 MultiTank-family Operator Guide - Rev 1.2
MA-036 - DGA 900 MultiTank-family Operator Guide - Rev 1.2
Grid Solutions
Kelman™
DGA 900 MultiTank-family
Operator Guide
Transformer Oil
Dissolved Gas and Moisture Monitor
MA-036 – DGA 900 MultiTank-family Operator Guide – Rev 1.2 9-Dec-21 Page 2 of 121
6.11.2 Communications............................................................................................................................................... 50
6.11.3 Date & Time ........................................................................................................................................................ 51
6.11.4 SMS Alerting ....................................................................................................................................................... 52
6.11.5 Firewall ................................................................................................................................................................. 52
6.11.6 Communication Services ............................................................................................................................... 53
6.12 Service ................................................................................................................................................... 54
6.12.1 Measurement ..................................................................................................................................................... 54
6.12.2 Controller Reprogramming ........................................................................................................................... 55
6.12.3 Analysis Box Reprogramming ...................................................................................................................... 56
6.12.4 I/O Board Reprogramming ............................................................................................................................ 60
6.12.5 Gas Normalization ........................................................................................................................................... 61
6.12.6 Factory .................................................................................................................................................................. 62
6.12.7 User Administration ........................................................................................................................................ 66
6.12.8 Configuration Import ...................................................................................................................................... 67
6.13 TransOpto............................................................................................................................................ 68
6.13.1 Measurements ................................................................................................................................................... 68
6.13.2 Rate of Change .................................................................................................................................................. 68
6.13.3 Alarms ................................................................................................................................................................... 69
6.13.4 Rate of Change Alarms ................................................................................................................................... 70
6.13.5 Channels .............................................................................................................................................................. 71
6.13.6 Settings ................................................................................................................................................................. 71
6.14 BMT ......................................................................................................................................................... 72
6.14.1 General Settings ............................................................................................................................................... 72
6.14.2 Calibration ........................................................................................................................................................... 74
6.14.3 Configuration ..................................................................................................................................................... 75
6.14.4 Live Measurement............................................................................................................................................ 79
6.14.5 BMT Reprogramming ...................................................................................................................................... 81
6.15 Logout ................................................................................................................................................... 82
6.16 Shutdown Procedure ...................................................................................................................... 83
6.17 Error Notifications ........................................................................................................................... 84
6.17.1 Error Codes ......................................................................................................................................................... 86
6.17.2 Other Notifications .......................................................................................................................................... 87
7 Manual Oil Sampling .....................................................................................88
7.1 Sampling Arrangement.................................................................................................................. 88
7.2 Local HMI for manual sampling.................................................................................................. 89
7.3 Sampling Process ............................................................................................................................. 93
8 Communications............................................................................................95
8.1 DNP3 ...................................................................................................................................................... 95
8.2 IEC 61850 ............................................................................................................................................. 95
8.3 Modbus Protocol .............................................................................................................................. 95
8.4 HTTP / HTTPS Protocol................................................................................................................... 95
9 Technical Support .........................................................................................95
Appendix A Security Configuration ................................................................96
Appendix B Transportation PGA Lock ........................................................ 104
Appendix C Maintenance Activities ............................................................ 108
Appendix D Time Sync Implementation ..................................................... 114
Appendix E Alarm Settings: General Advice ............................................. 116
Contact & Copyright Details ............................................................................ 121
MA-036 – DGA 900 MultiTank-family Operator Guide – Rev 1.2 9-Dec-21 Page 3 of 121
List of Tables and Figures
Page
Figure 1-1: Inside MultiTank – Analysis module (left) & Hub module (right) .......................................... 8
Figure 1-2: TapTrans Analysis module (left) & MultiTrans Analysis module (right) ............................... 9
Table 1-1: Hub front panel LED lights ..................................................................................................... 11
Table 3-1: Measurements ....................................................................................................................... 15
Table 4-1: Type tests ............................................................................................................................... 17
Figure 5-1: Fuse holder ........................................................................................................................... 18
Table 5-1: External LED status indicators .............................................................................................. 18
Figure 6-1: Inside the Hub module – LCD top left .................................................................................. 19
Figure 6-2: Ethernet / USB HMI connection ........................................................................................... 20
Figure 6-3: Log-in page............................................................................................................................ 21
Table 6-1: User access rights .................................................................................................................. 21
Table 6-2: Oil sources .............................................................................................................................. 22
Figure 6-4: MultiTrans local HMI home page ......................................................................................... 22
Figure 6-5: TapTrans local HMI home page ............................................................................................ 23
Figure 6-6: MultiTrans remote HMI dashboard page ............................................................................. 24
Figure 6-7: MultiTrans oil sources .......................................................................................................... 25
Figure 6-8: TapTrans remote HMI dashboard page ............................................................................... 25
Figure 6-9: TapTrans oil tanks ................................................................................................................ 26
Figure 6-10: Last DGA Measurement ..................................................................................................... 26
Figure 6-11: Quick Access ....................................................................................................................... 27
Figure 6-12: Quick Access – Rapid Mode ............................................................................................... 28
Figure 6-13: Active Alarms...................................................................................................................... 30
Figure 6-14: Measurements.................................................................................................................... 31
Figure 6-15: Duval Diagnostic – MultiTrans (OS1) ................................................................................. 32
Figure 6-16: Duval Diagnostic – TapTrans (Div) ..................................................................................... 32
Figure 6-17: Gas Ratio ............................................................................................................................. 33
Figure 6-18: DGA Scheduler (MultiTrans) .............................................................................................. 34
Figure 6-19: DGA Scheduler (TapTrans) ................................................................................................. 34
Figure 6-20: Gas Ratio Settings .............................................................................................................. 35
Figure 6-21: Gas Ratio Settings – Ratio 1 definition .............................................................................. 35
Figure 6-22: Relative Saturation Settings .............................................................................................. 35
Figure 6-23: Gas RoC Configuration ....................................................................................................... 36
Figure 6-24: Analog Inputs RoC Configuration....................................................................................... 36
Figure 6-25: Gas Alarms Configuration .................................................................................................. 38
Figure 6-26: Hydrogen alerts .................................................................................................................. 39
Figure 6-27: Gas Ratio Alarms Configuration ........................................................................................ 40
Figure 6-28: Gas Ratio Alarms Configuration – Ratio 1 definition ........................................................ 41
Figure 6-29: Gas RoC Alarms Configuration .......................................................................................... 42
Figure 6-30: Relative Saturation Alarms Configuration ........................................................................ 43
Figure 6-31: Analog Inputs Alarms Configuration ................................................................................. 44
Figure 6-32: Analog Inputs RoC Alarms Configuration .......................................................................... 45
Figure 6-33: Digital Inputs Alarms Configuration .................................................................................. 46
Figure 6-34: Digital Inputs Transition Total Alarms Configuration ....................................................... 46
Figure 6-35: Peripheral Scheduler .......................................................................................................... 47
Figure 6-36: Analog Inputs Configuration .............................................................................................. 47
Figure 6-37: Analog Input 4 (4-20 mA Temperature Sensor) ................................................................ 47
Figure 6-38: Digital Input Configuration ................................................................................................. 48
Figure 6-39: Input Measurements .......................................................................................................... 48
Figure 6-40: Communications Settings .................................................................................................. 49
MA-036 – DGA 900 MultiTank-family Operator Guide – Rev 1.2 9-Dec-21 Page 4 of 121
Figure 6-41: Communications Settings .................................................................................................. 50
Figure 6-42: Date & Time ........................................................................................................................ 51
Figure 6-43: Date & Time Settings.......................................................................................................... 51
Figure 6-44: NTP Settings ....................................................................................................................... 51
Figure 6-45: SMS Alerting ....................................................................................................................... 52
Figure 6-46: Firewall configuration ........................................................................................................ 52
Figure 6-47: Communication Services ................................................................................................... 53
Figure 6-48: Measurement Settings ....................................................................................................... 54
Figure 6-49: Controller Reprogramming ................................................................................................ 55
Figure 6-50: Upgrade in progress ........................................................................................................... 55
Figure 6-51: Analysis Box Reprogramming ............................................................................................ 56
Figure 6-52: Drag and drop firmware file ............................................................................................... 57
Figure 6-53: Upload to host confirmation .............................................................................................. 57
Figure 6-54: Firmware package uploaded to host ................................................................................. 57
Figure 6-55: Upload to Analysis box confirmation................................................................................. 58
Figure 6-56: Ready to upgrade the Analysis box ................................................................................... 58
Figure 6-57: Analysis box firmware upgrade in progress ...................................................................... 59
Figure 6-58: Analysis box firmware upgrade complete ......................................................................... 59
Figure 6-59: I/O Board Reprogramming ................................................................................................. 60
Figure 6-60: Upgrade in progress ........................................................................................................... 60
Figure 6-61: Gas Normalization Settings ............................................................................................... 61
Figure 6-62: Factory Settings.................................................................................................................. 62
Figure 6-63: TapTrans HMI banner bar showing Safe Mode activated ................................................. 63
Figure 6-64: DGA Scheduler > Selector Scheduler Disabled (left) and Enabled (right) ....................... 63
Figure 6-65: TapTrans HMI banner bar showing Safe Mode cleared .................................................... 63
Table 6-3: Factory Settings: Data and configuration cleardown ........................................................... 64
Figure 6-66: Simulation mode ................................................................................................................ 65
Figure 6-67: Restart the device .............................................................................................................. 65
Figure 6-68: User Administration ........................................................................................................... 66
Figure 6-69: Change Password ............................................................................................................... 66
Table 6-4: Password Strength ................................................................................................................ 66
Figure 6-70: Configuration Import .......................................................................................................... 67
Figure 6-71: Configuration Import in progress ...................................................................................... 67
Figure 6-72: TransOpto Measurements ................................................................................................. 68
Figure 6-73: TransOpto RoC Configuration ............................................................................................ 68
Figure 6-74: TransOpto Alarms Configuration ....................................................................................... 69
Figure 6-75: Channel 1 High alerts ......................................................................................................... 69
Figure 6-76: TransOpto RoC Alarms Configuration ............................................................................... 70
Figure 6-77: Channel 2 High-High alerts ................................................................................................ 70
Figure 6-78: TransOpto Channels Settings ............................................................................................ 71
Figure 6-79: TransOpto Settings ............................................................................................................ 71
Figure 6-80: General Settings ................................................................................................................. 72
Figure 6-81: Primary and Secondary bushing settings & CT and temperature sensor sliders ............ 73
Figure 6-82: Temperature sensor configuration .................................................................................... 74
Figure 6-83: Failures detection ............................................................................................................... 74
Figure 6-84: Bushing Adaptor Failure Alarms ........................................................................................ 74
Figure 6-85: HF / LF multipliers and Input Impedance .......................................................................... 75
Figure 6-86: HF / LF multipliers and Input Impedance .......................................................................... 75
Figure 6-87: HF / LF multipliers and Input Impedance .......................................................................... 75
Figure 6-88: Live HF Noise ...................................................................................................................... 75
Figure 6-89: Exponential Moving Average Configuration ...................................................................... 76
Figure 6-90: Input signalling monitoring / configuration ....................................................................... 76
MA-036 – DGA 900 MultiTank-family Operator Guide – Rev 1.2 9-Dec-21 Page 5 of 121
Figure 6-91: HF Gain and Control ........................................................................................................... 76
Figure 6-92: Noise threshold .................................................................................................................. 77
Figure 6-93: PD Settings and Correlation PDi-RH .................................................................................. 77
Figure 6-94: Failures detection ............................................................................................................... 77
Figure 6-95: Failures detection ............................................................................................................... 78
Figure 6-96: Bushing profiles and mappings .......................................................................................... 78
Figure 6-97: Live Measurement .............................................................................................................. 79
Figure 6-98: Bushing readings ................................................................................................................ 79
Figure 6-99: PD & PDi-RH correlations ................................................................................................... 80
Figure 6-100: Chart ................................................................................................................................. 81
Figure 6-101: BMT Reprogramming........................................................................................................ 81
Figure 6-102: Upgrade in progress ......................................................................................................... 82
Figure 6-103: Logout ............................................................................................................................... 82
Figure 6-104: Log-in page ....................................................................................................................... 82
Figure 6-105: System Info – Standby ..................................................................................................... 83
Figure 6-106: Measurement started ...................................................................................................... 83
Figure 6-107: PGA and Oxygen Sensor Error States.............................................................................. 84
Figure 6-108: PGA Errors ........................................................................................................................ 85
Table 6-5: PGA Errors .............................................................................................................................. 86
Table 6-6: Oxygen sensor error codes.................................................................................................... 87
Figure 6-109: MicroSD card memory usage ........................................................................................... 87
Figure 7-1: Oil filter location (above) and manual sampling ports (below) (TapTrans Analysis module)
................................................................................................................................................................. 88
Figure 7-2: Manual sampling port with quick connect fitting................................................................ 89
Figure 7-3: Valve orientation .................................................................................................................. 89
Figure 7-4: Sampling assembly ............................................................................................................... 89
Figure 7-5: Luer fitting on assembly ....................................................................................................... 89
Figure 7-6: Local HMI: Quick Access ....................................................................................................... 90
Figure 7-7: Manual Sampling .................................................................................................................. 90
Figure 7-8: Purging Oil ............................................................................................................................. 91
Figure 7-9: Take manual oil sample ........................................................................................................ 91
Figure 7-10: Manual Sampling cannot be started.................................................................................. 92
Figure 7-11: Dashboard: Stop Measurement ......................................................................................... 92
Figure 7-12: Manual oil sampling flowchart ........................................................................................... 93
Table A-1: External Interfaces ................................................................................................................ 97
Table A-2: Protocols ................................................................................................................................ 98
Figure A-1: Settings > Communication Services.................................................................................... 98
Figure A-2: Communication Services ..................................................................................................... 99
Figure A-3: Firewall Settings ................................................................................................................. 101
Figure A-4: Default policy options ........................................................................................................ 101
Figure A-5: Specific policy options........................................................................................................ 102
Figure A-6: LAN interface ...................................................................................................................... 102
Figure A-7: LAN interface ...................................................................................................................... 102
Figure A-8: Accept HTTPS ..................................................................................................................... 102
Figure B-1: PGA lock – engaged ............................................................................................................ 104
Figure B-2: PGA lock – pins and locking bracket secured with cable ties ........................................... 104
Figure B-3: PGA lock – remove pins...................................................................................................... 105
Figure B-4: PGA lock – remove plastic nuts ......................................................................................... 105
Figure B-5: PGA lock – remove metal bracket ..................................................................................... 105
Figure B-6: PGA lock – insert metal bracket ........................................................................................ 106
Figure B-7: PGA lock – attach plastic nuts ........................................................................................... 106
Figure B-8: PGA lock – insert pins......................................................................................................... 106
MA-036 – DGA 900 MultiTank-family Operator Guide – Rev 1.2 9-Dec-21 Page 6 of 121
Figure B-9: PGA lock – pin to enclosure hole ....................................................................................... 107
Figure B-10: PGA lock – pins and locking bracket secured with cable ties......................................... 107
Figure C-1: Controller PCB coin cell battery......................................................................................... 108
Figure C-2: GMCU PCB coin cell battery ............................................................................................... 108
Figure C-3: Hub fan air inlet .................................................................................................................. 109
Figure C-4: Detached inlet cover with filter – facedown ..................................................................... 109
Figure C-5: Detached inlet cover with filter removed ......................................................................... 109
Figure C-6: Filter mesh cartridge – face up .......................................................................................... 109
Figure C-7: Louvre catchment tray – attached .................................................................................... 110
Figure C-8: Louvre gasket – tray removed ........................................................................................... 110
Figure C-9: Louvre catchment tray – detached & filter removed........................................................ 110
Figure C-10: Louvre air filter ................................................................................................................. 110
Figure C-11: Oil connections – TapTrans (left) & MultiTrans (right) ................................................... 111
Figure C-12: Oil filter ............................................................................................................................. 111
Figure C-13: Internal push-fit cover removal ....................................................................................... 111
Figure C-14: Peltier cooler .................................................................................................................... 113
Figure C-15: Fan group electrical connection ...................................................................................... 113
Figure C-16: Peltier cooling fins ............................................................................................................ 113
Figure C-17: Fan group detached from cooler ..................................................................................... 113
Table D-1: Timing................................................................................................................................... 114
Table D-2: UNIX time registers ............................................................................................................. 114
Table D-3: Access flags ......................................................................................................................... 115
Table D-4: Modifier flags ....................................................................................................................... 115
Table E-1: Main Tank: Gas Level Alarms ............................................................................................... 117
Table E-2: ROC alarms (key gas values) ............................................................................................... 117
Table E-3: ROC alarms (for ROC in ml/day) .......................................................................................... 119
Table E-4: Measurement intervals........................................................................................................ 119
Related Documents
Ref# Title
MA-035 DGA 900 MultiTank-family Installation Manual
MA-036 – DGA 900 MultiTank-family Operator Guide – Rev 1.2 9-Dec-21 Page 7 of 121
1 INTRODUCTION
1.1 MultiTank-family Overview
The MultiTank-family is an overarching term for the following products — Kelman™ DGA
900 MultiTrans and Kelman™ DGA 900 TapTrans (herein referred to as the products
MultiTrans and TapTrans respectively). The products are multigas online DGA (Dissolved
Gas Analysis) and moisture monitoring systems for implementing Asset Performance
Management (APM) across electrical generation, transmission, distribution and
industrial applications.
The products can detect and diagnose incipient faults and trend asset health via the
monitoring of critical gases including moisture in the transformer oil. This includes any
mineral oil or ester-based fluid (natural or synthetic). The products measure nine
certified fault gases on three oil sources: hydrogen, methane, ethane, ethylene, carbon
monoxide, carbon dioxide, acetylene, oxygen, nitrogen as well as water content and the
transformer load current. Such data provides insight on transformer condition criteria,
such as developing faults, paper degradation and electrical arcing.
Once installed, operation is intuitive and programmable. The products can be managed
remotely over a network via a web-based interface or locally via a touchscreen interface.
All results are stored within the product, but online management is recommended.
Results and the full product database can also be downloaded to a PC for analysis,
aggregation and trending with the Perception software suite.
As part of the DGA 900 family, both products comprise of an Analysis module (with
internal cover) where the oil samples are analysed, and a Hub module where all other
hardware and functionality is located, as shown for example, in Figure 1-1.
Figure 1-1: Inside MultiTank – Analysis module (left) & Hub module (right)
The Hub module runs the relevant product firmware and communications options, but
the Analysis module is where the hardware differs as shown in Figure 1-2. The TapTrans
has two oil manifolds to measure oil from the transformer main tank and on-load tap
MA-036 – DGA 900 MultiTank-family Operator Guide – Rev 1.2 9-Dec-21 Page 8 of 121
changer (OLTC), including the selector and diverter tanks where they exist. The
MultiTrans has one oil manifold to measure oil from three separate oil tanks, for
example, three transformer tanks operating in a single-phase bank.
Figure 1-2: TapTrans Analysis module (left) & MultiTrans Analysis module (right)
MA-036 – DGA 900 MultiTank-family Operator Guide – Rev 1.2 9-Dec-21 Page 9 of 121
▪ Compatible with AC or DC power.
▪ Four sunlight-visible LED arrays on the exterior of the Hub module — red for alarm,
yellow for caution (both user-configurable) — and green for power, blue for service.
▪ A fully embedded microprocessor with 4 GB non-volatile internal memory storage,
highly scalable analogue and digital I/Os, an embedded webserver, 8 GB SD card to
hold measurement data and an integrated 7 in. colour LCD screen with resistive
touch for simplified local user interaction and visualization of data.
▪ The infrastructure provides a platform for expansion and future feature
enhancements complemented by an extensive range of secure communications
options. These include Ethernet, RS-485, cellular modem (SMS Text Alerts /GPRS), and
fibre optic options (IEC61850 or DNP3). Internal USB connection is provided for
commissioning and service, or local data download. Other options may be available
on request.
▪ Compatibility with GE’s advanced fleet management software, such as Perception
and APM solutions, providing data download, trending, analysis and configuration of
assets. Supports industry standard protocols for communication with other non-GE
supervisory, data analysis and historian systems.
*1 Note: The only recommended equipment care is periodic cleaning of the air filters, in-
line oil filter and battery replacement.
MA-036 – DGA 900 MultiTank-family Operator Guide – Rev 1.2 9-Dec-21 Page 10 of 121
1.2 Scope
This guide outlines the use of the HMI, manual sampling function and general equipment
care activities for a MultiTank product.
MA-036 – DGA 900 MultiTank-family Operator Guide – Rev 1.2 9-Dec-21 Page 11 of 121
2 SAFETY
2.1 Symbols
The meaning of symbols used on MultiTank-family products:
The customer and installer are responsible for ensuring that all local
regulations and site policies are complied with concerning safe working
practices.
MA-036 – DGA 900 MultiTank-family Operator Guide – Rev 1.2 9-Dec-21 Page 12 of 121
responsibility of the installer to ensure that planned work complies with
those requirements.
The installer shall also ensure that any third-party equipment, such as an
approved platform, scaffold or lift is suitable and safe before commencing
work. Ladders or improvised platforms do not meet GE service engineer
requirements.
Hot surfaces present on oil pipes and risk of contact with mineral oil. Use
suitable PPE.
Hazardous voltages are accessible when the doors are open. The Analysis
module door shall only be opened for service access by suitably qualified
and authorised service personnel. Under normal use, the Hub module door
can be opened to access the HMI. The doors shall be kept shut and locked
at all other times.
The product provides IP56 water spray protection. It is possible for a water
deluge system to exceed IP56 thresholds depending on the location,
pressure and direction of the water jets. Should customers require testing a
water deluge system in the area in which the product is installed, GE
recommends powering down the product and draping it with a suitable
waterproof covering.
MA-036 – DGA 900 MultiTank-family Operator Guide – Rev 1.2 9-Dec-21 Page 13 of 121
2.3 Hazardous Substances
The gases measured in the product are extracted from the oil and expelled to the
atmosphere via the exhaust vent on the external base of the Analysis module. The area
around the exhaust vent should be kept clear and unobstructed. All expelled gases are at
concentrations that are nonflammable, nontoxic and quickly diluted in the surrounding
atmosphere. The expelled gases are not hazardous to health or life.
MA-036 – DGA 900 MultiTank-family Operator Guide – Rev 1.2 9-Dec-21 Page 14 of 121
3 TECHNICAL SPECIFICATIONS
The product meets the following technical specification as outlined in Table 3-1.
Table 3-1: Measurements
PARAMETER VALUE/MEETS
GAS MEASURED *1 & 10
RANGE ACCURACY *2 & 3 REPEATABILITY
*2
MA-036 – DGA 900 MultiTank-family Operator Guide – Rev 1.2 9-Dec-21 Page 15 of 121
*1
Note: Parameters specified in application with mineral oil.
*2
Note: Accuracy and repeatability are quoted for the detectors under factory
calibration and test levels. Gas-in-oil measurements may be affected by
sampling and/or oil type.
*3
Note: Whichever is greater.
*4
Note: Available on free-breathing transformers only.
*5
Note: Given in ppm.
*6
Note: Based on testing carried out using VOLTESSO™ 35 mineral oil over a ¼ in. pipe
run of 10 metres or less from oil supply or return valve to product connection
point, and on transformer oil supply valve volumes of 200 ml or less. For oil
temperatures colder than −20 ºC, GE recommends the use of heat trace cabling
on piping. Low oil viscosity reduces oil flow.
*7
Note: The weight depends on the order specification. The stated weight is for a base
product without packaging and excludes options such as a mounting stand.
Check the shipping document for the exact packaged weight.
*8
Note: Maximum DC breaking capacity for a resistive load.
*9
Note: Use only the approved and recommended fuse to ensure continued fire
protection and compliance.
*10
Note: Laboratory results can vary greatly worldwide as has been established through
many round-robin tests. Any comparison of product measurement results
against laboratory results need to be considered in this context.
*11
Note: It is possible for a small amount of condensation to form on the inner surface of
the Analysis enclosure. This occurs under certain environmental conditions and
does not affect the performance or reliability of the product.
MA-036 – DGA 900 MultiTank-family Operator Guide – Rev 1.2 9-Dec-21 Page 16 of 121
4 COMPLIANCE
The product is designed to meet the following type tests as listed in Table 4-1.
Table 4-1: Type tests
CATEGORY STANDARD CLASS/LEVEL TEST
EMC Emissions CISPR 11 A Radiated & Conducted Emissions
EN 61326- FCC Part 15 Meets the Radiated & Conducted Emissions
1:2006 requirements of A
EN 61000-3-2 A Harmonic Current Emissions
Limits
EMC Immunity EN 61000-4-2 IV Electrostatic Discharge
EN 61326- EN 61000-4-3 III Electromagnetic Field Immunity
1:2006
EN 61000-4-4 III Electrical Fast Transients
IEC 61000-6-5:
2015 EN 61000-4-5 III Surge Immunity
EN 61000-4-6 III Conducted RF Immunity
EN 61000-4-8 IV & V Magnetic Field Immunity
EN 61000-4-11 III Voltage Dips & Interruptions
IEC 61000-4-12 2.5 kV & 1 kV Oscillatory Wave
IEC 61000-4-16 A Mains frequency voltage
EN 60255-5 5 kV, 2 kV & Impulse, Dielectric & Insulation
500 V DC resistance testing
Environmental IEC 60068-2-1 −40 °C Cold
Tests IEC 60068-2-2 55 °C Dry Heat
IEC 60068-2-6 10 – 500 Hz, Vibration
0.5 g operation
10 – 500 Hz,
1 g endurance
IEC 60068-2-30 55 °C, 95% RH Damp Heat
EN 60529 IP56 Degree of Protection
Safety IEC 61010-1 2010
EN 61010-1 2010
MA-036 – DGA 900 MultiTank-family Operator Guide – Rev 1.2 9-Dec-21 Page 17 of 121
5 POWER
The product is wired directly to the mains so is continually powered on. The mains fuse
holder for the product is shown in Figure 5-1 and is located towards the bottom right-
hand side of the Hub module. Note: This is not a point of electrical isolation.
Live
Neutral
Earth
Fuse holder
The product uses four external sunlight-visible LEDs on the front door. Each LED has two
states – ‘Off’ (-) or ‘On’ as outlined in Table 5-1.
Table 5-1: External LED status indicators
Mode Alarm Caution Power Service
red LED amber LED green LED blue LED
Power Off - - - -
Normal - - On -
Alarm On - On -
Caution - On On -
Service - - On On
MA-036 – DGA 900 MultiTank-family Operator Guide – Rev 1.2 9-Dec-21 Page 18 of 121
6 HMI
6.1 Introduction
The local HMI features an integrated 7 in. colour LCD panel with resistive touch screen
and embedded webserver. The remote HMI is via a wireless comms option (or direct USB
connection) to a web browser. The latter being the preferred means of interaction with
the product since it offers the convenience of accessing the product from anywhere
using a full screen web browser. The remote HMI is optimised for Chrome, but has also
been tested in Firefox and Edge. The local HMI allows operators to interact directly with
the product onsite without additional equipment. However, the local HMI facility is
intended as an alternative or secondary access method in situations where network
connectivity is unavailable.
The LCD panel is in the Hub module and is visible when the door is open as shown in
Figure 6-1.
The LCD and web server are powered on by default as soon as power is supplied to the
product. Access to the HMI can be gained locally via the resistive touch screen (using a
finger or stylus) or remotely through the Web from any computer. Both HMI experiences
are comparable with a similar look and feel.
Note: This guide primarily uses screenshots from the remote Web access HMI. The
images rendered on the local HMI are similar, but some have a different layout
due to the smaller screen.
Note: This guide displays screens from an Administrator login. All user logins have a
similar look and feel, but some features are dependent on the type of user.
MA-036 – DGA 900 MultiTank-family Operator Guide – Rev 1.2 9-Dec-21 Page 19 of 121
Note: If there are any rendering issues on the remote HMI, press Ctrl + F5 to
refresh.
Note: If using Internet Explorer 11, ensure that the option for ‘Compatibility View’ is
disabled.
6.2 Connections
The remote HMI can also be accessed from a laptop via a direct physical connection to
the product. The product ships with the default IP address as shown in Figure 6-2. Use
either an Ethernet or USB cable to make the connection as shown in Figure 6-2.
MA-036 – DGA 900 MultiTank-family Operator Guide – Rev 1.2 9-Dec-21 Page 20 of 121
6.3 Start-Up Procedure
When the product is powered on or rebooted, the PGA takes several minutes to
initialise. If using the remote access HMI, the icon denotes that the initialization
process is not yet complete.
6.4 Login
The log-in page prompts for a username and password as shown in Figure 6-3. The
product ships with a default username and password that can be changed after initial
login.
The system supports three roles with different levels of access as outlined in Table 6-1.
Table 6-1: User access rights
Role Access
Observer View information only (includes downloading if using the remote HMI)
Operator View information and make configuration changes.
Administrator View information, make configuration changes and perform user
administration e.g. change passwords.
MA-036 – DGA 900 MultiTank-family Operator Guide – Rev 1.2 9-Dec-21 Page 21 of 121
Table 6-2: Oil sources
Tanks / Oil sources # TapTrans (label) MultiTrans (label)
1 Main (Main) Oil Source 1 (OS1)
The banner bar on each page shows the product name, signal strength, oil source or
tank, language, username and menu bar as shown in Figure 6-4 to Figure 6-9.
Note: All data shown relates to the chosen oil source or tank. All HMI elements and
data are clearly demarcated with the appropriate blue source labels as
appropriate for the chosen oil source or tank (as listed in brackets on Table
6-2).
MA-036 – DGA 900 MultiTank-family Operator Guide – Rev 1.2 9-Dec-21 Page 22 of 121
The TapTrans local HMI home page on the default Main tank is shown in Figure 6-5. To
choose a different oil tank, press the blue oil tank button on the banner bar.
Note: For all manual sampling HMI functionality, see Section 7.2.
MA-036 – DGA 900 MultiTank-family Operator Guide – Rev 1.2 9-Dec-21 Page 23 of 121
Figure 6-6: MultiTrans remote HMI dashboard page
Click the blue dropdown list button on the banner bar to choose between showing data
for Oil Source 1, Oil Source 2 or Oil Source 3 as shown in Figure 6-7.
MA-036 – DGA 900 MultiTank-family Operator Guide – Rev 1.2 9-Dec-21 Page 24 of 121
Figure 6-7: MultiTrans oil sources
TapTrans remote access HMI with home page data for the default Main tank is shown in
Figure 6-8.
MA-036 – DGA 900 MultiTank-family Operator Guide – Rev 1.2 9-Dec-21 Page 25 of 121
Click the blue dropdown list button on the banner bar to choose between showing data
for the Main, Diverter or Selector tanks as shown in Figure 6-9.
6.6 Dashboard
Let’s examine the dashboard of the remote web-based HMI section by section.
The ‘Last DGA Measurement’ panel as shown in Figure 6-10 lists the measurement date
and time stamp, gas levels (with measurements in PPM) displayed numerically and
represented graphically on a bar chart marked with the configured Caution (H for High)
and Alarm (HH for High High) levels.
Blue signifies a reading within the normal limits, yellow a caution — the reading has
exceeded the High (H) level, and red an alarm – the reading has exceeded the High-High
level.
Rest the pointer on any gas to obtain the full name in a tooltip. After the next
measurement completes, the details automatically update.
The ‘System Info’ panel (top right of Figure 6-8) gives the current date, time, product
state, scheduler mode (Normal, Alarm, Caution) and next scheduled measurement.
Indicators show the status of the alarm, caution and service LEDs as well as the six
relays. There is also a free text ID field to assign a meaningful name to the product. The
default is the product’s serial number. Note: Only Operator or Administrator changes will
be saved. The product’s serial and firmware version numbers are also listed.
MA-036 – DGA 900 MultiTank-family Operator Guide – Rev 1.2 9-Dec-21 Page 26 of 121
The trend chart panel (bottom of Figure 6-8) provides a variety of trend charts —
Historical, Thermal, Humidity, and RTD Sensor. The default trend chart is an Historical
Chart that plots selected gas readings over time. Use the gas legend to identify the gas
and the date selector control to change the timeframe. Rest the pointer on any data
point on a plot line to obtain a tooltip with a timestamped gas value. Click a gas label on
the legend to toggle the display of the plotted gas on or off.
Note: This manual illustrates common functionality using a MultiTrans on Oil Source 1
(typically). HMI functionality is the same irrespective of the product or oil
source. Blue labels next to the relevant item of information denote the oil
source or tank to which it relates.
6.6.1.1 Diagnostics
Click Download Log to access the available log files. Choose from a System Log, TFD
Log, CFR Log and PGA Advanced Techlog. These service files contain product
MA-036 – DGA 900 MultiTank-family Operator Guide – Rev 1.2 9-Dec-21 Page 27 of 121
performance data that is used to check product functionality. If requested, download and
send the relevant log files to the GE M&D Service Support team for analysis. Note: Logs
are saved in the PC Downloads folder.
Rapid mode is a means of on demand sampling and uses a smaller quantity of oil to
deliver a result in around 30 minutes. Rapid mode measures four critical gases —
hydrogen, acetylene, carbon monoxide, carbon dioxide — and water, and charts the
measurements below. The ability to invoke successive quick measurement cycles over a
short period can indicate the speed at which a fault is progressing.
Note: Rapid mode measurements are performed independently of all other
measurements and do not affect alarms, relays or calculations.
Click Enter Rapid Mode to access the rapid mode options. The Quick Access panel
displays the available options as shown in Figure 6-12.
To start four rapid mode measurements in succession, click Start 4x Rapid Mode.
To exit Rapid Mode and return to the main dashboard, click Exit Rapid Mode.
MA-036 – DGA 900 MultiTank-family Operator Guide – Rev 1.2 9-Dec-21 Page 28 of 121
6.6.1.5 Start / Stop Measurement
MA-036 – DGA 900 MultiTank-family Operator Guide – Rev 1.2 9-Dec-21 Page 29 of 121
6.7 GAS / Diagnostics
6.7.1 Active Alarms
Select GAS / Diagnostics > Active Alarms to open the Active Alarms page as shown in
Figure 6-13.
Note: Deadbands are specified in the units relating to what is measured. E.g. PPM for
gas, degrees Celsius (°C) for temperature. See Section 6.9 for a definition of
deadbands.
6.7.2 Measurements
Select GAS / Diagnostics > Measurements to open the Measurements page as shown
in Figure 6-14. The Measurements page reports the values of all variables from a
measurement cycle. The most recent measurement cycle is listed first. Use the scroll
buttons to navigate to previous measurements.
MA-036 – DGA 900 MultiTank-family Operator Guide – Rev 1.2 9-Dec-21 Page 30 of 121
Figure 6-14: Measurements
MA-036 – DGA 900 MultiTank-family Operator Guide – Rev 1.2 9-Dec-21 Page 31 of 121
Figure 6-15: Duval Diagnostic – MultiTrans (OS1)
Use the ‘Select Diagnostic’ dropdown menu to apply other Duval diagnostic options.
Figure 6-16 shows a TapTrans product with the Duval Diagnostic applied to the on-load
tap changer.
MA-036 – DGA 900 MultiTank-family Operator Guide – Rev 1.2 9-Dec-21 Page 32 of 121
6.7.4 Gas Ratio
Select GAS / Diagnostics > Gas Ratio to open the Gas Ratio page as shown in Figure
6-17.
6.7.5 Scheduler
MultiTank products manage up to three oil sources / tanks and these are enabled by
default as outlined in Section 6.11.1. It is recommended to use the scheduling capability
described here to enable / disable DGA measurements rather than the oil sources /
tanks.
To schedule a DGA measurement cycle, select GAS / Diagnostics > Scheduler to open
the DGA Scheduler page as shown in Figure 6-18.
Use the ‘tank / oil source’ dropdown (blue label top right of screen) to choose the
relevant oil source or tank to schedule a DGA measurement on. In this example Figure
6-18 shows a MultiTrans on Oil Source 1.
Use the Scheduler Enabled slider control to enable the master scheduler.
Set the required date and time, for example, as shown in Figure 6-18.
Note: Each oil source / tank can be independently enabled and scheduled.
Use the [oil source # / tank] Scheduler Enabled slider control to enable the scheduler
on the chosen oil source / tank.
Note: It is conceivable that one or more oil sources / tanks may be inactive or run
with differing measurement schedules. While each oil source / tank can be
independently controlled, it is recommended to keep each oil source / tank
enabled and to use the source / tank scheduler to control the scheduling of
MA-036 – DGA 900 MultiTank-family Operator Guide – Rev 1.2 9-Dec-21 Page 33 of 121
measurements to avoid any scheduling conflicts, such as where an oil source is
disabled with a measurement scheduled.
Set the required measurement intervals for the Normal, Caution and Alarm modes.
The default intervals are 12 hours, 6 hours, and 3 hours respectively.
Note: When deciding interval periods, consider the number of oil sources / tanks to
be measured. If two or more active oil sources / tanks have an interval set to 1
hour, measurements may be skipped due to the scheduling conflict.
Repeat these steps as indicated on Figure 6-18 as appropriate for each oil source / tank.
Figure 6-19 shows the DGA Scheduler page for TapTrans on the Diverter tank configured
similarly.
MA-036 – DGA 900 MultiTank-family Operator Guide – Rev 1.2 9-Dec-21 Page 34 of 121
6.8 Calculations
6.8.1 Gas Ratios
Select Calculations > Gas Ratios to open the Gas Ratio Settings page as shown in
Figure 6-20. Note: Ratios can be set for each tank.
Choose the relevant > icon to expand the ratio definition as shown in Figure 6-21.
MA-036 – DGA 900 MultiTank-family Operator Guide – Rev 1.2 9-Dec-21 Page 35 of 121
6.8.3 Gas Rate of Change
Select Calculations > Gas Rate of Change to open the Gas RoC Configuration page as
shown in Figure 6-23. See Appendix E for more details on settings.
MA-036 – DGA 900 MultiTank-family Operator Guide – Rev 1.2 9-Dec-21 Page 36 of 121
6.9 Alarms
Perception allows deadbands to be defined for each alarm. A deadband establishes
another limit for clearing the alarm and prevents an alarm returning to normal until the
alarm condition is cleared by the deadband. This reduces the number of false alarms and
the amount of chattering. For example, an alarm triggered at 200 ppm with a deadband
of 3 will remain in the alarm state until the value falls below 197 ppm.
Note: Deadbands are specified in the units being measured. Gases are specified in
PPM, temperature in degrees Celsius.
The host network must have the capability to transmit alarms and critical
messages during times of heavy use, including but not limited to network
storm conditions. If this requirement is not met or has not been tested, the
notification of hazardous gas levels could be delayed by a network
slowdown.
MA-036 – DGA 900 MultiTank-family Operator Guide – Rev 1.2 9-Dec-21 Page 37 of 121
6.9.1 Gases
Select Alarms > Gases to open the Gas Alarms Configuration page as shown in Figure
6-25.
MA-036 – DGA 900 MultiTank-family Operator Guide – Rev 1.2 9-Dec-21 Page 38 of 121
Click on a gas alarm icon > e.g. Hydrogen to configure the type of alerts as shown in
Figure 6-26.
MA-036 – DGA 900 MultiTank-family Operator Guide – Rev 1.2 9-Dec-21 Page 39 of 121
6.9.2 Gas Ratios
Select Alarms > Gas Ratios to open the Gas Ratio Alarms Configuration page as shown
in Figure 6-27.
MA-036 – DGA 900 MultiTank-family Operator Guide – Rev 1.2 9-Dec-21 Page 40 of 121
Choose the relevant > icon to expand the ratio definition and configure the alerts as
shown in Figure 6-28.
Refer to the IEEE® C57.104 and IEC® 60599 standards for alarm settings or Appendix E.
MA-036 – DGA 900 MultiTank-family Operator Guide – Rev 1.2 9-Dec-21 Page 41 of 121
6.9.3 Gas Rate of Change
Select Alarms > Gas Rate of Change to open the Gas RoC Alarms Configuration page as
shown in Figure 6-29. See Appendix E for more details on settings.
MA-036 – DGA 900 MultiTank-family Operator Guide – Rev 1.2 9-Dec-21 Page 42 of 121
6.9.4 Relative Saturation
Select Alarms > Relative Saturation to open the Relative Saturation Alarms
Configuration page as shown in Figure 6-30.
MA-036 – DGA 900 MultiTank-family Operator Guide – Rev 1.2 9-Dec-21 Page 43 of 121
6.9.5 Analog Inputs
Select Alarms > Analog Inputs to open the Analog Inputs Alarms Configuration page as
shown in Figure 6-31.
MA-036 – DGA 900 MultiTank-family Operator Guide – Rev 1.2 9-Dec-21 Page 44 of 121
6.9.6 Analog Inputs Rate of Change
Select Alarms > Analog Inputs Rate of Change to open the Analog Inputs RoC Alarms
Configuration page as shown in Figure 6-32.
MA-036 – DGA 900 MultiTank-family Operator Guide – Rev 1.2 9-Dec-21 Page 45 of 121
6.9.7 Digital Inputs
Select Alarms > Digital Inputs to open the Digital Inputs Alarms Configuration page.
Choose the relevant > icon to expand the digital input and configure the alerts. For
example, DIN1, as shown in Figure 6-33.
MA-036 – DGA 900 MultiTank-family Operator Guide – Rev 1.2 9-Dec-21 Page 46 of 121
6.10 Peripherals
6.10.1 Peripheral Scheduler
Select Peripherals > Peripheral Scheduler to open the Peripheral Scheduler page as
shown in Figure 6-35.
The Peripheral Scheduler allows the Measurement Time Interval to be set to 5, 10, 15 or
20 minutes.
If there are analogue cards fitted to the I/O PCB, these will auto populate with default
values as shown in Figure 6-37. The next step is to configure each card to the required
sensor.
MA-036 – DGA 900 MultiTank-family Operator Guide – Rev 1.2 9-Dec-21 Page 47 of 121
6.10.3 Digital Inputs
Select Peripherals > Digital Inputs to open the Digital Input Configuration page as
shown in Figure 6-38. Note: Name field is editable to allow custom name fields.
Use the controls (top right) to move back and forward through the Input Measurement
data and Export to CSV (if required).
MA-036 – DGA 900 MultiTank-family Operator Guide – Rev 1.2 9-Dec-21 Page 48 of 121
6.11 Settings
6.11.1 Oil Source Settings
Select Settings > Oil Source Settings to open the Oil Source Settings page as shown in
Figure 6-41.
By default, all oil sources are enabled and use the default field name, which can be
amended using the adjacent text box. The toggle switches are used to enable/disable the
respective oil sources. Disabling an Oil Source means the ‘Next Measurement’ of the Oil
Source shows as ‘Never’ on the dashboard.
Note: It is recommended to keep each oil source / tank enabled. This prevents
conflicts when scheduling DGA measurements. Instead use the scheduler as
outlined in Section 6.7.5 to enable / disable DGA measurements.
MA-036 – DGA 900 MultiTank-family Operator Guide – Rev 1.2 9-Dec-21 Page 49 of 121
6.11.2 Communications
Select Settings > Communications to open the Communications Settings page as
shown in Figure 6-41.
If a GPRS modem is fitted and the appropriate carrier sim is installed, the IP address also
displays.
Note: APN sim and login credentials are required before the IP address displays.
See Appendix A.2 for more details on the external interfaces and supported protocols.
MA-036 – DGA 900 MultiTank-family Operator Guide – Rev 1.2 9-Dec-21 Page 50 of 121
6.11.3 Date & Time
Select Settings > Date & Time to open the Date & Time page as shown in Figure 6-42.
To change the system time, click Edit System Time.
The Date & Time Settings section becomes editable as shown in Figure 6-43. Use the
controls to update the date and time.
PC time lists the current time on the PC hosting the connection. To synchronise the
product’s system time with that of the PC, click Synchronize Time.
Note: Power up Time records when the product was last powered on or rebooted.
Support for the Network Time Protocol (NTP) allows for accurate clock synchronisation.
The NTP Settings section lists the IP address of all NTP servers as shown in Figure 6-44.
Use this section to enable the NTP protocol and add or remove NTP servers as required.
MA-036 – DGA 900 MultiTank-family Operator Guide – Rev 1.2 9-Dec-21 Page 51 of 121
6.11.4 SMS Alerting
Select Settings > SMS Alerting to open the SMS Alerting page as shown in Figure 6-45.
The system can be configured to send SMS messages to designated person(s) on restart,
measurement error or whenever a system error is raised.
6.11.5 Firewall
To create a custom security policy, select Settings > Firewall to open the Firewall
Settings page as shown in Figure 6-46. Rules can be added, edited or deleted to create a
suitable access policy for each type of interface. These rules are used to block unused
ports and specify distinct firewall actions (accept, reject or drop) based on the IP or port.
MA-036 – DGA 900 MultiTank-family Operator Guide – Rev 1.2 9-Dec-21 Page 52 of 121
6.11.6 Communication Services
Select Settings > Communication Services to open the Communication Services page
as shown in Figure 6-47.
Note: This functionality is available only to ‘Operator’ and ‘Administrator’ users.
All configuration settings specified on this page apply to all interfaces (Ethernet, USB and
GSM-GPRS modem).
Select the relevant slider button to enable/disable the relevant communication service.
E.g. Modbus-TCP, SSH (Secure Shell) and HTTPS — but do not rely on the firewall settings.
To implement a custom security policy, upload a new certificate and enable HTTPS
requests. Note: If HTTPS is enabled, all requests via HTTP are blocked.
In the Upload certificate field, click the Select file button, select the new certificate (PEM
file), and click Open. Click the ‘Save’ button in the application header to apply the
changes and then restart the MultiTank product.
Note: SSL certificates are small data files that digitally bind a cryptographic key to an
organization's details. When installed on a web server, it activates the padlock
and the HTTPS protocol and allows secure connections from a web server to a
browser.
Note: If HTTPS is disabled, the certificate will be applied when HTTPS is enabled.
Note: The HMI has no automatic redirection between HTTP and HTTPS (or vice versa).
This results in the following browser message “Site cannot be reached over
HTTP”.
MA-036 – DGA 900 MultiTank-family Operator Guide – Rev 1.2 9-Dec-21 Page 53 of 121
6.12 Service
6.12.1 Measurement
Select Service > Measurement to open the Measurement Settings page as shown in
Figure 6-48. The Normalization Temperature is a thermostatically controlled internal
target temperature for the Analysis module. Depending on the region, one of two
temperatures can be set 0 °C or 20 °C.
MA-036 – DGA 900 MultiTank-family Operator Guide – Rev 1.2 9-Dec-21 Page 54 of 121
6.12.2 Controller Reprogramming
Consult with Technical Support to confirm the availability of new firmware for the
Controller PCB. Upgrade to the latest version of the firmware via an Ethernet connection
to avail of new features.
Note: A firmware upgrade resets passwords back to their default values.
To upgrade the Controller PCB firmware, select Service > Controller Reprogramming
to open the Controller Reprogramming page as shown in Figure 6-49.
Drag and drop the firmware file into the circle or click in the circle to select the file. After
the file loads into the software cache, click Upgrade and the status information and a
progress bar display as shown in Figure 6-50.
Once complete, the firmware image is applied and the system restarts. On initial power
up, the product’s LCD screen remains blank, but the ‘On’ heartbeat LED and ‘Boot’ LED
illuminate (solid blue and red respectively). After a moment, the Boot LED switches off
and the ‘On’ heartbeat LED flashes blue to indicate normal operation. The restart
sequence takes approximately 3 minutes after which the onboard HMI loads up.
MA-036 – DGA 900 MultiTank-family Operator Guide – Rev 1.2 9-Dec-21 Page 55 of 121
6.12.3 Analysis Box Reprogramming
Consult with Technical Support to confirm the availability of new firmware for the
Analysis box. Upgrade to the latest version of the firmware via an Ethernet connection to
avail of new features.
The Analysis box firmware package comprises of three firmware components – the Gas
Manifold Control Unit (GMCU), Oil Manifold Control Unit (OMCU) and the PGA. These
components are upgraded using a single firmware upgrade package, which is initially
uploaded to the Controller (host) and then automatically rolled out to the respective
component parts of the Analysis box as outlined below.
To start, select Service > Analysis Box Reprogramming to open the Analysis Box
Reprogramming page as shown in Figure 6-51.
Note: The product must be in Standby to complete the Analysis firmware
reprogramming. Either, wait until the product finishes the current
measurement cycle and the status returns to Standby, or ‘Stop’ the current
measurement and wait for the status to return to Standby.
Drag and drop the firmware file (*.pkg) into the circle or click in the circle to select the file
as shown in Figure 6-52.
MA-036 – DGA 900 MultiTank-family Operator Guide – Rev 1.2 9-Dec-21 Page 56 of 121
Figure 6-52: Drag and drop firmware file
Once the firmware upload to the host completes, a confirmation dialog displays as
shown in Figure 6-53. Click OK.
And the screen updates to reflect the latest firmware as shown in Figure 6-54. The next
phase is to upload the firmware to the Analysis box. Click Upload. Note: If necessary,
scroll down to see the button.
MA-036 – DGA 900 MultiTank-family Operator Guide – Rev 1.2 9-Dec-21 Page 57 of 121
Once the upload to the Analysis box is complete, a confirmation dialog displays as shown
in Figure 6-55. Click OK.
To upgrade the Analysis box as shown in Figure 6-56, click Upgrade. Note: If necessary,
scroll down to see the button.
This upgrades the the Analysis box firmware on the respective PCBs in turn. Individual
progress counters display status information and a progress percentage, and a progress
dial displays overall upgrade progress, for example, as shown in Figure 6-57.
MA-036 – DGA 900 MultiTank-family Operator Guide – Rev 1.2 9-Dec-21 Page 58 of 121
Figure 6-57: Analysis box firmware upgrade in progress
If the upgrade completes successfully, each PCB is listed with the new version of
firmware followed by the status label ‘Upgraded’, for example, as shown in Figure 6-58.
Click Restart Analysis Box to finalise the upgrade and resume measurements.
Note: If the upgrade fails at any point, reattempt the steps as outlined above.
Once complete, the firmware image is applied and the system restarts. On initial power
up, the product’s LCD screen remains blank, but the ‘On’ heartbeat LED and ‘Boot’ LED
illuminate (solid blue and red respectively). After a moment, the Boot LED switches off
and the ‘On’ heartbeat LED flashes blue to indicate normal operation. The restart
sequence takes approximately 3 minutes after which the onboard HMI loads up.
MA-036 – DGA 900 MultiTank-family Operator Guide – Rev 1.2 9-Dec-21 Page 59 of 121
6.12.4 I/O Board Reprogramming
Consult with Technical Support to confirm the availability of new firmware for the I/O
Board. Upgrade to the latest version of the firmware via an Ethernet connection to avail
of new features.
To upgrade the I/O Board firmware using an Ethernet connection, select Service > I/O
Board Reprogramming to open the I/O Board Reprogramming page as shown in Figure
6-59.
Drag and drop the firmware file into the circle or click in the circle to select the file. Click
Upgrade and the status information and a progress bar displays as shown in Figure
6-60.
Once complete, the firmware image is applied and the system restarts. On initial power
up, the product’s LCD screen remains blank, but the ‘On’ heartbeat LED and ‘Boot’ LED
illuminate (solid blue and red respectively). After a moment, the Boot LED switches off
and the ‘On’ heartbeat LED flashes blue to indicate normal operation. The restart
sequence takes approximately 3 minutes after which the onboard HMI loads up.
MA-036 – DGA 900 MultiTank-family Operator Guide – Rev 1.2 9-Dec-21 Page 60 of 121
6.12.5 Gas Normalization
Select Service > Gas Normalization to open the Gas Normalization Settings page as
shown in Figure 6-61. Note: Each oil source has its own Gas Normalization Settings.
MA-036 – DGA 900 MultiTank-family Operator Guide – Rev 1.2 9-Dec-21 Page 61 of 121
6.12.6 Factory
Select Service > Factory to open the Factory Settings page. Product details are as
shown in Figure 6-62
Note: Once the Device Class has been set as either Taptrans or Multitrans, it is not
recommended to change the number of oil sources. If an oil source is not
required, disable this oil source using GAS / Diagnostics > Scheduler and
disable the scheduler for the relevant oil source – see Section 6.7.5).
The Alarm Reflash option ensures that a relay’s digital output reflashes (if already
activated) when another source triggers the same relay. An alarm reflash applies only to
relays 1-6 and is achieved by deactivating the relevant digital output for a duration of 1
second before reactivating it to achieve a flashing effect. This signifies to an operator or
control room in real time that multiple sources have triggered the same relay.
Note: This ensures that further alarms raised by the same source have no further
effect.
The Oil Source Safe Mode control is enabled by default and allows the product to detect
if certain errors are being repeated on measurements. When such errors are detected,
safe mode is activated on the identified oil source and flagged by a red label on the HMI
banner bar. In this example, using TapTrans, Safe Mode is activated on the Selector oil
source as shown in Figure 6-63.
MA-036 – DGA 900 MultiTank-family Operator Guide – Rev 1.2 9-Dec-21 Page 62 of 121
Figure 6-63: TapTrans HMI banner bar showing Safe Mode activated
When Safe Mode is activated, the DGA Scheduler cancels any further scheduled
measurements on the affected oil source as shown in Figure 6-64 (left) until an Operator
logs in and manually reactivates the Scheduler as shown in Figure 6-64 (right).
Figure 6-64: DGA Scheduler > Selector Scheduler Disabled (left) and Enabled (right)
Once the issue that triggered Safe Mode has been identified and resolved, scheduled
measurements on that oil source can resume. In this example, using a TapTrans product,
the Safe Mode label clears from the HMI banner bar as shown in Figure 6-65.
Figure 6-65: TapTrans HMI banner bar showing Safe Mode cleared
Note: Safe Mode should not be cleared from an oil source until the product has been
assessed by a qualified field service engineer or qualified independent third-
party engineer.
Clears all historical data — DGA measurements, alarm data and TransOpto
measurements. Table 6-3 outlines the type of data items that get erased.
Clears all historical data described previously and resets configuration settings (except
Communications) to the default state. Table 6-3 outlines the type of data items that get
erased.
MA-036 – DGA 900 MultiTank-family Operator Guide – Rev 1.2 9-Dec-21 Page 63 of 121
Table 6-3: Factory Settings: Data and configuration cleardown
Clear Reset of
Full Factory
Historical Configuration
Reset
Data Only Settings
Measurements
DGA Scheduler
Gas ratios
Relative Saturation
Calculations Gas RoC
Transopto RoC
Analog Input RoC
Alarms Alarms
Transopto Channels
Transopto
Peripherals Measurements
Analog Inputs
Digital Inputs
Settings Communications
Measurement
Oxygen Sensor
Service Transopto
Gas Normalization
Factory
The Rapid Test Cycle is used by the factory to test operational aspects of the
measurement cycle.
Note: Usage not applicable outside of factory testing.
MA-036 – DGA 900 MultiTank-family Operator Guide – Rev 1.2 9-Dec-21 Page 64 of 121
To differentiate between real and simulation data, the colour scheme for the bar chart
simulation data uses grey scales and the DGA 900 state changes to ‘PGA simulation
mode’ as shown in Figure 6-66.
This allows the HMI to display realistic sample data for showcasing e.g. training and
testing purposes without affecting real-time data, but has no validity since it does not
relate to any underlying measurement cycles.
Some configuration changes require a device restart. Click Restart Device to restart the
device and then click Restart to confirm as shown in Figure 6-67.
The local HMI (LHMI) can be recalibrated to adjust the sensitivity of the touchscreen.
Recalibration must be performed using the local screen, but it is not recommended to
change the default settings for the touchscreen unless there is an issue.
To initiate calibration mode, press and hold the touchscreen for 20 seconds or click
Recalibrate LHMI.
Follow the onscreen instructions until the new calibration settings have been measured.
Once measured, ensure to tap the screen to store the new calibration data to the
product.
Note: Tap the screen within the time limit otherwise the settings are not stored, and
a reminder prompts for screen calibration.
MA-036 – DGA 900 MultiTank-family Operator Guide – Rev 1.2 9-Dec-21 Page 65 of 121
6.12.7 User Administration
Select Service > User Administration to open the User Administration page as shown
in Figure 6-68.
Select the user or root password. Click Change Password to enter a new password. On
typing, the strength of the password is assessed as shown in Figure 6-69.
Other security options relating to all accounts include implementing the Secure Shell
Protocol (SSH) to increase login security over the Internet and a means to enable all
Observer accounts to perform the manual sampling process (by default, it’s disabled for
Observer accounts).
MA-036 – DGA 900 MultiTank-family Operator Guide – Rev 1.2 9-Dec-21 Page 66 of 121
6.12.8 Configuration Import
To upgrade the product configuration, select Service > Configuration Import to open
the Configuration Import page as shown in Figure 6-70. Product configuration details
(including alarm settings) can be uploaded to a replacement product eliminating the
need to re-input the original settings.
Drag and drop the configuration file into the circle or click in the circle to select the file.
The status information and a progress bar display as shown Figure 6-71. Click Apply to
proceed.
Once complete, the system restarts. On initial power up, the product’s LCD screen
remains blank, but the ‘On’ heartbeat LED and ‘Boot’ LED illuminate (solid blue and red
respectively). After a moment, the Boot LED switches off and the ‘On’ heartbeat LED
flashes blue to indicate normal operation. The restart sequence takes approximately 3
minutes after which the onboard HMI loads up.
MA-036 – DGA 900 MultiTank-family Operator Guide – Rev 1.2 9-Dec-21 Page 67 of 121
6.13 TransOpto
6.13.1 Measurements
Select TransOpto > Measurements to open the TransOpto Measurements page as
shown in Figure 6-72.
MA-036 – DGA 900 MultiTank-family Operator Guide – Rev 1.2 9-Dec-21 Page 68 of 121
6.13.3 Alarms
Select TransOpto > Alarms to open the TransOpto Alarms Configuration page as shown
in Figure 6-74.
Click on a channel alarm icon > e.g. ‘Channel 1 High’ to configure the type of alerts as
shown in Figure 6-75.
MA-036 – DGA 900 MultiTank-family Operator Guide – Rev 1.2 9-Dec-21 Page 69 of 121
6.13.4 Rate of Change Alarms
Select TransOpto > Rate of Change Alarms to open the TransOpto RoC Alarms
Configuration page as shown in Figure 6-76.
Click on a channel alarm icon > e.g. ‘Channel 2 High-High’ to configure the type of alerts
as shown in Figure 6-77.
MA-036 – DGA 900 MultiTank-family Operator Guide – Rev 1.2 9-Dec-21 Page 70 of 121
6.13.5 Channels
Select TransOpto > Channels to open the TransOpto Channels Settings page as shown
in Figure 6-78.
6.13.6 Settings
Select TransOpto > Settings to open the TransOpto Settings page as shown in Figure
6-79.
MA-036 – DGA 900 MultiTank-family Operator Guide – Rev 1.2 9-Dec-21 Page 71 of 121
6.14 BMT
Note: Bushing monitoring is currently only available on the TapTrans product. This
functionality will be released on the MultiTrans product in the future.
The Enable Service Mode allows full access to all BMT calibration and configuration
settings (see Section 6.14.2). Service mode is reserved for commissioning and service
activities but should not be required for standard operations.
Note: The correct factory Password Of The Month (POTM) must be specified to allow
Service Mode.
All relevant settings are pre-configured in the factory, but the Import from PC and
Export to PC buttons allow the operator to import new settings or export existing
settings if requested by the GE Technical Support Team.
Scroll down the page to see further sections with more settings. Let’s examine each
section in turn. Figure 6-81 shows details for the Primary and Secondary bushings,
including slider controls to toggle On or Off the Neutral CT and multiple temperature
sensors.
MA-036 – DGA 900 MultiTank-family Operator Guide – Rev 1.2 9-Dec-21 Page 72 of 121
Figure 6-81: Primary and Secondary bushing settings & CT and temperature sensor sliders
The Primary section defines the label for the HV bushings and respective phase names.
The Secondary section defines the label for the LV bushing and respective phase names.
The default convention is to use ‘Primary’ and ‘Secondary’ as the labels. However, it is
recommended to change the default labels to match the naming convention in use on
the site, particularly if the site has multiple transformers or monitoring devices. For
example, HV1 for Primary and LV1 for Secondary. Otherwise, it is fine to retain the
default names. Phase names may also be changed, for example A, B, C might be R, Y, B or
U, V, W.
Note: The Input Labels are free text.
The operational voltages and nominal phase angles are preconfigured in the factory as
per the customer-specific workflow or as otherwise requested. However, at the time of
commissioning it is advised to review the General Settings page to verify that the
operational voltage values reflect the actual operational values of the transformer.
Phase angles A-B and A-C are preconfigured in the factory as per the customer-specific
workflow or as otherwise requested. However, at the time of commissioning it is advised
to review the ‘Live Measurement’ page to verify that the phase angles measured are
within two degrees of the nominal phase angles. Refer to the ‘MA-041 - DGA 900
Plus - Installation & Commissioning Manual’ for precise commissioning instructions.
The measurement Log interval is specified in minutes and the default value is 240.
Customers may want to review the log interval depending on the criticality/age of the
equipment.
MA-036 – DGA 900 MultiTank-family Operator Guide – Rev 1.2 9-Dec-21 Page 73 of 121
In this example, there is one Neutral CT and one Top Oil sensor installed. The site-
specific details of the customer are pre-configured in the factory. If the sensors cannot
be fitted, they can be disabled by toggling the relevant HMI control to the ‘Off’ position.
The Temperature sensor configuration is shown in Figure 6-82. In this section, the Top
Oil Sensor is assigned to the relevant phase. The default allocation is as shown. Use the
dropdown menu to assign the temperature sensor to the correct phase.
In addition to core bushing settings, a list of operational attributes can be polled for
issues and the detection of a failure fault can be flagged. These distinct attributes are
required and are as listed in Figure 6-83. The ability to detect failure can be individually
toggled On or Off under the Administrator account using the corresponding slider
control as shown in Figure 6-83.
The Bushing Adaptor Failure Alarms are listed as shown in Figure 6-84. If any alarms are
activated, the Service LED will illuminate. Click Clear to clear the respective alarm for the
relevant bushing. In this example, no alarms are activated.
6.14.2 Calibration
Select BMT > Calibration to specify calibration settings as shown in Figure 6-85. The
Calibration menu option is only visible and accessible to users with Service mode
enabled. These settings are preconfigured in the factory as per the customer order
workflow and should not be modified.
MA-036 – DGA 900 MultiTank-family Operator Guide – Rev 1.2 9-Dec-21 Page 74 of 121
Figure 6-85: HF / LF multipliers and Input Impedance
The calibration data for each Bushing Adaptor is shown in Figure 6-87. Select an Adaptor
label to reveal the relevant data for that Adaptor.
6.14.3 Configuration
Select BMT > Configuration to specify configuration settings as shown in Figure 6-88.
The Live HF Noise section lists all channels and noise levels. These settings are
preconfigured in the factory and cannot be modified here. They are only visible to
Administrator/operator users or those with Service mode enabled. (edit)
Scroll down the page to see further configuration sections with more settings. Let’s
examine each section in turn. Figure 6-89 shows the exponential moving average
configuration. These settings are preconfigured in the factory and cannot be modified
here. They are only visible to Administrator users or those with Service mode enabled.
MA-036 – DGA 900 MultiTank-family Operator Guide – Rev 1.2 9-Dec-21 Page 75 of 121
Use the slider to calculate daily averages as well as the pre-set values. This is useful as a
trending metric to observe over time.
The Input signalling monitoring / configuration is shown in Figure 6-90. These are pre-set
in the factory.
The HF Gain and Control sections are shown in Figure 6-91. These are pre-set in the
factory.
The Noise threshold values are shown in Figure 6-92. These are pre-set in the factory.
MA-036 – DGA 900 MultiTank-family Operator Guide – Rev 1.2 9-Dec-21 Page 76 of 121
Figure 6-92: Noise threshold
The PD Settings and Correlation PDi-RH are listed as shown in Figure 6-93. In this
example, the factory defaults are shown. The recommended settings for internal and
external PD measurements are listed and should not be changed unless advised by GE.
The PDi-RH value specifies in hours the time window for the effect of Relative Humidity
on the PD Intensity measurement.
The Failures Detection section lists bushing attributes and corresponding values that can
be used to detect issues as shown in Figure 6-94. These settings are preconfigured in the
factory and should not be modified. They are only visible to Administrator users or those
with Service mode enabled.
The Transformer monitoring configuration section is shown in Figure 6-95. These setting
are preconfigured in the factory as per the customer-specific workflow or as otherwise
requested.
MA-036 – DGA 900 MultiTank-family Operator Guide – Rev 1.2 9-Dec-21 Page 77 of 121
The operational frequency is typically 50 or 60 Hz. The monitoring modes is either ‘Single
transformer’ or ‘Multiple transformers’. For example, a three-phase transformer or a
bank of single-phase transformers. The Phase rotation order is A, B, C or C, B, A. The
default Bushing Adaptor type value is ‘Resistive’ and the default Temperature sensor
source value is ‘Wire sensor’. During installation and commissioning, all these settings
must be checked against the customer-specific workflow.
The Bushing profiles and mappings are shown in Figure 6-96. The product supports one
or two sets of three bushings in a single three-phase transformer, or three single-phase
transformers. They can only be modified by Administrator users or those with Service
mode enabled.
Each bushing must be mapped to a profile. Typically, it is recommended to use the
bushing adaptor serial number as an identifying label for the bushing. The naming will be
configured during installation and commissioning.
The nominal C1 and PF values can be obtained from the bushing nameplate or customer-
specific workflow. During installation and commissioning, these values must be checked
to verify each bushing has been fitted with the correct bushing adaptor. If the nominal
values for C1 and PF are not correct, the Service Engineer should update the bushing
profiles using the POTM.
Note: The bushing adaptor labels shown in this guide are generic. Every installation
has its own predefined naming convention.
MA-036 – DGA 900 MultiTank-family Operator Guide – Rev 1.2 9-Dec-21 Page 78 of 121
6.14.4 Live Measurement
Select BMT > Live Measurement to view the live measurements as shown in Figure
6-97 to Figure 6-100.
The System Frequency measurement should show as either 50 or 60 Hz, along with the
ambient temperature (C) and humidity (%).
Note: Realtime values for system frequency and environmental parameters update
every five seconds.
The Export to CSV button exports the entire BMT measurement log to a CSV file for
offline reference or forwarding. The measurement log can also be cleared at any time by
clicking the Clear button.
Note: It is advised to clear the measurement log of any unwanted data points prior to
re-energising the transformer.
Scroll down the page to see specific bushing and PD readings. Let’s examine each section
in turn. The Bushing readings are shown in Figure 6-98 starting with Capacitance. In this
example, the default naming convention of ‘Primary’ and ‘Secondary’ is used. Select
Primary or Secondary (or whatever name is assigned) to see the respective readings.
Note: The actual names depend on the prescribed naming convention followed at the
site.
MA-036 – DGA 900 MultiTank-family Operator Guide – Rev 1.2 9-Dec-21 Page 79 of 121
The top rows lists the Nameplate C1 capacitance readings (pF) for the bushings, with the
Expected and Measured Current values (mA) below, and below that, the Estimated C1
capacitance readings (pF) for each phase.
The three phase values of A, B and C are used to calculate the amplitude of the polar plot
and this is referenced as an ‘Imbalance’ value in the last column for Estimated C1 and
Tan δ.
The Nameplate Tan δ row provides the power factor percentages, with the Expected and
Measured degrees of angle (as found on the nameplate), and below that, the Estimated
Tan δ percentage for each phase. The Estimated Tan δ is calculated based on the
arbitrary frame of reference to provide a power factor percentage.
The PD readings and PDi-RH correlations are shown in Figure 6-99. Select Primary,
Neutral PD or PD N-Less to see the respective readings.
Several plots are available for the primary and secondary bushings, phase angles and
temperature. The chart in Figure 6-100 shows percentage change over time for the
specified date range. Use the dropdown control to change the type of plot and the date
selectors to change the date range.
MA-036 – DGA 900 MultiTank-family Operator Guide – Rev 1.2 9-Dec-21 Page 80 of 121
Figure 6-100: Chart
Drag and drop the firmware file into the circle or click in the circle to select the file. Click
Upgrade and the status information and a progress bar display as shown in Figure 6-50.
MA-036 – DGA 900 MultiTank-family Operator Guide – Rev 1.2 9-Dec-21 Page 81 of 121
Figure 6-102: Upgrade in progress
Once complete, the firmware image is applied and the system restarts. On initial power
up, the product’s LCD screen remains blank, but the ‘On’ heartbeat LED and ‘Boot’ LED
illuminate (solid blue and red respectively). After a moment, the Boot LED switches off
and the ‘On’ heartbeat LED flashes blue to indicate normal operation. The restart
sequence takes approximately 3 minutes after which the onboard HMI loads up.
6.15 Logout
Select the Logout option below the username as shown in Figure 6-103.
MA-036 – DGA 900 MultiTank-family Operator Guide – Rev 1.2 9-Dec-21 Page 82 of 121
6.16 Shutdown Procedure
If the product is to be shut down, perform the following steps:
Log in to the product to observe the operating state on the dashboard as shown in
Figure 6-105.
If the product is in “Standby” state, then proceed to shut down the product as follows:
− Turn the external switch or circuit breaker to the ‘Off’ position.
− Turn the transformer oil valves that connect to the input and output of the product
to the ‘Closed’ position.
If the product is performing a measurement as shown in Figure 6-106, then
− Either wait for the product to finish the active measurement or manually stop the
measurement. For the latter, choose Stop Measurement as shown in Figure 7-11.
− The MultiTank state changes to “Oil Draining”. This process may take several
minutes after which the product state returns to “Standby” as shown in Figure
6-105.
− Turn the external switch or circuit breaker to the ‘Off’ position.
− Turn the transformer oil valves that connect to the input and output of the product
to the ‘Closed’ position.
When the product is to be powered up again, first turn the transformer oil valves that
connect to the input and output of the product to the ‘Open’ position. Then turn ‘On’ the
external switch or circuit breaker. The product will be ready to resume taking scheduled
readings.
MA-036 – DGA 900 MultiTank-family Operator Guide – Rev 1.2 9-Dec-21 Page 83 of 121
6.17 Error Notifications
The Measurements page reports all errors as shown in Figure 6-107: If there are no
errors in the current measurement cycle, the results are displayed as normal. Errors for
the most recent measurement cycle are listed first. Use the navigation buttons to move
through the various measurement cycles and examine any errors encountered in
previous measurement cycles.
Errors are reported using a sequence of double-digit codes for the PGA and the Oxygen
sensor (if enabled). The PGA Error State denotes the most recent state within the
measurement cycle where the error occurred. All errors are listed as error codes and the
associated hexadecimal in brackets allows the most recent state to be identified. See
Section 6.17.1 for a definition of the error codes.
Note: The Customer Service Centre requires both the state code(s) and error code(s)
to interpret any error.
For example, Figure 6-108 shows that the product has encountered two PGA errors. The
PGA Error code 04 denotes that there is an issue with the gas flow in the Main
Measurement state (23) and error code 13 denotes that the pump pressure is too low.
MA-036 – DGA 900 MultiTank-family Operator Guide – Rev 1.2 9-Dec-21 Page 84 of 121
Figure 6-108: PGA Errors
Note: If the Oxygen sensor is not enabled, no Oxygen sensor state or error codes
display.
MA-036 – DGA 900 MultiTank-family Operator Guide – Rev 1.2 9-Dec-21 Page 85 of 121
6.17.1 Error Codes
Table 6-5 lists the PGA error codes. All the service alarm error codes are accompanied by
illumination of the blue Service light that is visible on the front door of the product.
Note: Error codes are offset by 1 from the Modbus register bit numbers.
Note: This information relates to PGA firmware version 19.0.52.
Table 6-5: PGA Errors
Code Error Note
PGA Connection Error
00 Incorrect H2 calibration
01 PGA power supply voltage too low
02 PGA chopper frequency outside range
03 PGA IR-source outside range
04 Gas flow lower than limit
05 Background noise/vibration too high
06 Microphone test failed
07 Not level sensor 1 pulses (level)
08 Not level sensor 3 (drain)
09 Fill level shows Oil
10 Over Fill shows Oil
11 PGA Air temperature outside limits
12 Bad communication with control PCB
13 Gas leak test: Pump pressure too low
14 Gas leak test: Pressure decay too high
15 Unusual ambient gas measurements
16 Oil temperature too low
17 Oil temperature too high
18 Oil pressure too low Check that all oil supply valves are open.
19 Oil pressure too high Check that all oil return valves are open.
20 Oil pump tacho count too high
21 Oil pump pressure too low
22 Oil pump speed out of range
23 Manual oil sampling switch
24 Oil pump tacho count too low
25 Oil pump not turning
26 PreSens reading is not available
27 Temperature Sensor(s) 1 disconnected
28 Temperature Sensor(s) 2 disconnected
29 Drain level shows oil
30 Conditioned oil temp. outside limits
31 timeout
MA-036 – DGA 900 MultiTank-family Operator Guide – Rev 1.2 9-Dec-21 Page 86 of 121
Table 6-6 lists the Oxygen sensor error codes.
MA-036 – DGA 900 MultiTank-family Operator Guide – Rev 1.2 9-Dec-21 Page 87 of 121
7 MANUAL OIL SAMPLING
A manual oil sample can be taken via the following arrangement.
Figure 7-1: Oil filter location (above) and manual sampling ports (below) (TapTrans Analysis module)
MA-036 – DGA 900 MultiTank-family Operator Guide – Rev 1.2 9-Dec-21 Page 88 of 121
The sampling arrangement consists of a quick-connect body and a captive body-
protector fitting as shown in Figure 7-2.
A male quick-connect fitting and valve assembly is provided in the product installation
kit. GE also recommends the use of a 50-mL ground glass syringe.
OPEN
CLOSED
Quick-connect body protector Figure 7-4: Sampling assembly
with pull-down collar for
release
Perform the manual oil sampling according to the sampling process outlined in Figure
7-12. GE recommends the use of a 50-ml ground glass syringe. Manual oil sampling shall
be performed while the product is in Standby state — either wait until the product
returns to Standby state or force the product to stop the current measurement cycle
using the software. The optimum time to perform a manual sample is just after the
product has completed a measurement because fresh oil will be at the manual sampling
point.
The manual oil sampling arrangement and sampling port must not be
cleaned with any type of solvent as this could affect results for subsequent
oil samples.
MA-036 – DGA 900 MultiTank-family Operator Guide – Rev 1.2 9-Dec-21 Page 89 of 121
Note: Before proceeding, ensure that the sampling assembly is fitted as outlined in
Section 7.1.
The Manual Sampling page displays. Press Start as shown in Figure 7-7 to start the
manual sampling process.
MA-036 – DGA 900 MultiTank-family Operator Guide – Rev 1.2 9-Dec-21 Page 90 of 121
The oil purging process starts as shown in Figure 7-8. Allow several minutes for the oil to
purge and then press Continue when done.
The system prompts the user to take the manual oil sample. See Section 7.3 for more
details on the sampling process.
Press Finish to return to the home page as shown in Figure 7-9.
MA-036 – DGA 900 MultiTank-family Operator Guide – Rev 1.2 9-Dec-21 Page 91 of 121
If the product is already performing a measurement, manual sampling is prevented as
shown in Figure 7-10. Press Exit to return to the Quick Access page.
Either wait for the current measurement cycle to finish or stop the current measurement
cycle. To stop the current measurement cycle, return to the Dashboard and press Stop
Measurement as shown in Figure 7-11.
MA-036 – DGA 900 MultiTank-family Operator Guide – Rev 1.2 9-Dec-21 Page 92 of 121
7.3 Sampling Process
Logon to the product using the local HMI and observe the product state on the
Dashboard. The product state must be in Standby to initiate manual sampling. Figure
7-12 and the accompanying steps detail the process to obtain a manual oil sample.
Press Stop
Measurement
Oil Drains
Standby state
Remove quick-
connect body
protector
Press Manual
Sampling, & Start
Press Continue
Press Finish
MA-036 – DGA 900 MultiTank-family Operator Guide – Rev 1.2 9-Dec-21 Page 93 of 121
Observe the product state on the HMI Dashboard page. Either wait for the product to
return to the Standby state or use the HMI to stop the current measurement cycle.
If the product is in “Standby” state, proceed to step 3. If the product is in a
measurement state, manual sampling is prevented.
Navigate to the Dashboard page and press Stop Measurement. The state changes to
“Oil draining”. If there is oil in the headspace, the draining process may take several
minutes. The product returns to “Standby” state.
On the local HMI Quick Access page, press Manual Sampling.
When the product is in “Standby” state, remove the quick-connect body protector by
pulling the collar down.
Fit the male quick-connect fitting and valve assembly to the correct quick-connect
body on the base of the product as shown in Section 7.1. Ensure that the valve is
closed to prevent oil leakage.
Press Start.
An oil line purging process starts. The product state reads “Oil purging”. To ensure
accurate results, oil must be adequately purged before sampling begins. This brings
fresh oil from the transformer to the manual oil sampling port. Typically, this means
waiting approximately 5–10 minutes, but the recommended wait time can vary
depending on the installation (longer tubing and lower temperatures can increase the
purge duration). Consult with Technical Support.
Press Continue when done. The product state reads “Oil sampling”. Note: This
indicates that the oil sampling process can begin.
Remove the Luer fitting cap, connect the oil sampling equipment e.g. syringe, and
perform the oil sampling as per standard process and procedures.
When finished sampling, close the valve and disconnect the oil sampling equipment.
Remove the male fitting and valve assembly and replace the body protector fitting on
the quick-connect body.
Press Finish when done. The product state returns to “Standby”. Note: If left in the “Oil
sampling” state, the product reverts to “Standby” after one hour. Measurement then
begins at the next scheduled measurement time.
To start a measurement immediately, press the Start button.
MA-036 – DGA 900 MultiTank-family Operator Guide – Rev 1.2 9-Dec-21 Page 94 of 121
8 COMMUNICATIONS
See the Communications section of ‘MA-024 - DGA 900 MultiTank Installation Manual’
for available communication options.
8.1 DNP3
Refer to the document CG-060 – DGA 900 DNP3 Objects & IO Points Index.
9 TECHNICAL SUPPORT
For technical support, please contact the GE Customer Service Centre (24 hours a day,
365 days a year):
T +44 1785-250-070 (United Kingdom)
T 1-800-361-3652 (United States and Canada)
T +1 514-420-7460 (worldwide)
[email protected]
MA-036 – DGA 900 MultiTank-family Operator Guide – Rev 1.2 9-Dec-21 Page 95 of 121
Appendix A Security Configuration
A.1 Introduction
This appendix addresses security configuration for remote operations and the software
firewall.
This section provides a sample checklist to help guide the process of securely deploying
GE products.
▪ Create or locate a network diagram.
▪ Identify and record the required communication paths between nodes.
▪ Identify and record the protocols required along each path, including the role of each
node.
▪ Revise the network as needed to ensure appropriate partitioning, adding firewalls or
other network security devices as appropriate. Update the network diagram.
▪ Configure firewalls and other network security devices.
MA-036 – DGA 900 MultiTank-family Operator Guide – Rev 1.2 9-Dec-21 Page 96 of 121
▪ Enable and/or configure the appropriate security features on each GE product.
▪ On each GE product, change every supported password to something other than its
default value.
▪ Harden the configuration of each GE product, disabling unneeded features, protocols
and ports.
▪ Test / qualify the system.
▪ Create an update/maintenance plan.
The product features the following external interfaces as shown in Table A-1.
Table A-1: External Interfaces
External Comment
interface
RS-485
Ethernet HMI/SSH access
Ethernet Multi-protocol module DNP3/IEC
61850
GSM-GPRS modem
microSD
USB host
USB device USB-Ethernet
MA-036 – DGA 900 MultiTank-family Operator Guide – Rev 1.2 9-Dec-21 Page 97 of 121
A.2.2 Supported Protocols
The Communication Services page displays as shown in Figure A-2. All configuration
settings specified on this page apply to all interfaces (Ethernet, USB and GSM-GPRS
modem).
MA-036 – DGA 900 MultiTank-family Operator Guide – Rev 1.2 9-Dec-21 Page 98 of 121
Figure A-2: Communication Services
Select the relevant slider button to enable/disable the relevant communication service.
E.g. Modbus-TCP, SSH (Secure Shell) and HTTPS — but do not rely on the firewall settings.
To implement a custom security policy, upload a new certificate and enable HTTPS
requests. Note: If HTTPS is enabled, all requests via HTTP are blocked.
In the Upload certificate field, click the Select file button, select the new certificate (PEM
file), and click Open. Click the ‘Save’ button in the application header to apply the
changes and then restart the MultiTank product.
Note: SSL certificates are small data files that digitally bind a cryptographic key to an
organization's details. When installed on a web server, it activates the padlock
and the HTTPS protocol and allows secure connections from a web server to a
browser.
Note: If HTTPS is disabled, the certificate will be applied when HTTPS is enabled.
Note: The HMI has no automatic redirection between HTTP and HTTPS (or vice versa).
This results in the following browser message “Site cannot be reached over
HTTP”.
▪ Click the ‘Save’ button in the application header to apply the changes.
▪ Restart the MultiTank product.
MA-036 – DGA 900 MultiTank-family Operator Guide – Rev 1.2 9-Dec-21 Page 99 of 121
▪ Select the SSH Enable slider button to enable/disable the Secure Socket Shell service.
▪ Click the ‘Save’ button in the application header to apply the changes.
▪ Restart the MultiTank product.
▪ Click the ‘Save’ button in the application header to apply the changes.
▪ Restart the MultiTank product.
Note: The HMI has no automatic redirection between HTTP and HTTPS (or vice versa).
This results in the following browser message “Site cannot be reached over
HTTP”.
▪ Click the ‘Save’ button in the application header to apply the changes.
▪ Restart the MultiTank product.
Note: If HTTPS is disabled, the certificate will be applied when HTTPS is enabled.
MA-036 – DGA 900 MultiTank-family Operator Guide – Rev 1.2 9-Dec-21 Page 100 of 121
Figure A-3: Firewall Settings
Rules can be added, edited or deleted to create a suitable access policy for each type of
interface. These rules are used to block unused ports and specify distinct firewall actions
(accept, reject or drop) based on the IP address or port.
The default policy is to accept all incoming requests and applies for all cases not covered
by specific policies. The default policy provides a dropdown list of three options as shown
in Figure A-4.
Click the ‘Create new rule’ button to create a new policy. The rule options are as
shown in Figure A-5.
MA-036 – DGA 900 MultiTank-family Operator Guide – Rev 1.2 9-Dec-21 Page 101 of 121
Figure A-5: Specific policy options
In the Firewall Settings page, select the interface type e.g. lan and in the Default policy
dropdown, select REJECT as shown in Figure A-6.
In the Firewall Settings page, select the interface type e.g. lan and in the Default policy
dropdown, select REJECT as shown in Figure A-7.
Click the ‘Create new rule’ button to create a new policy. The policy requires
completing several fields as shown in Figure A-8.
In the ‘Rule Name’ field, type a descriptive name e.g. Accept HTTPS.
In the ‘IP’ field, select the IP checkbox and specify/edit the IP address e.g.
192.168.0.124.
In the ‘Port’ field, select the Port checkbox and type 443.
In the ‘Firewall Action’ dropdown list, select ACCEPT.
MA-036 – DGA 900 MultiTank-family Operator Guide – Rev 1.2 9-Dec-21 Page 102 of 121
Repeat the above steps for each interface type to ensure that only HTTPS requests are
permitted on those interfaces e.g. ‘usb’ and ‘gsm’.
After all interfaces have been configured, click the ‘Save’ button in the application
header to save the security settings and then restart the MultiTank product.
MA-036 – DGA 900 MultiTank-family Operator Guide – Rev 1.2 9-Dec-21 Page 103 of 121
Appendix B Transportation PGA Lock
The Analysis module is equipped with a factory-fitted transportation PGA lock that
consists of a metal locking bracket, two metal securing pins, two plastic nuts and three
cable ties as shown in Figure B-1.
The lock is engaged prior to shipping, but must be disengaged prior to operation of the
product. The lock must be refitted if there is ever a requirement to transport the module
(or if the product is ever to be laid horizontally). If the product is to be relocated or
transported, it must be shutdown using the procedure outlined in Section 6.16.
Note: If the product is to be removed from the transformer, ensure that the
transformer inlet and outlet valves, and the pipework valves are closed before
removing the pipework.
To access the lock, open the Analysis module, remove the black push-fit insulating cover
as described in Section C.3 and follow the relevant procedure outlined below.
Figure B-2: PGA lock – pins and locking bracket secured with cable ties
MA-036 – DGA 900 MultiTank-family Operator Guide – Rev 1.2 9-Dec-21 Page 104 of 121
▪ Pull each pin forward and out to remove it from the vibration mount assembly as
shown in Figure B-3.
▪ Loosen and remove the two plastic nuts securing the metal bracket to the anti-
vibration mounts as shown in Figure B-4.
▪ Remove the metal bracket as shown in Figure B-5. Note: Retain the metal bracket,
pins and plastic nuts for future use of the lock.
The transportation PGA lock is now disengaged rendering the PGA anti-vibration mounts
active. If the product is transported and reconnected to a different substation asset, it
must be recommissioned by a GE-approved commissioning engineer.
MA-036 – DGA 900 MultiTank-family Operator Guide – Rev 1.2 9-Dec-21 Page 105 of 121
B.2 Fit the lock
To fit the PGA lock, reverse the procedure outlined in Appendix B.1:
▪ Insert the metal bracket into the vibration mount assembly as shown in Figure B-6.
▪ Secure the metal bracket to the anti-vibration mounts using the two plastic nuts as
shown in Figure B-9.
Note: Hold the base of the anti-vibration mount while tightening the plastic nuts to
prevent twisting of the soft silicone.
▪ Push each metal pin into the vibration mount assembly as shown in Figure B-9.
MA-036 – DGA 900 MultiTank-family Operator Guide – Rev 1.2 9-Dec-21 Page 106 of 121
▪ Ensure that each pin end is fully inserted into the hole in the back wall of the
enclosure as shown in Figure B-9.
▪ Use three cable ties to secure the pins to the metal bracket at the appropriate holes
as shown in Figure B-10.
Figure B-10: PGA lock – pins and locking bracket secured with cable ties
The transportation PGA lock is now engaged rendering the PGA anti-vibration mounts
inactive. After the product is removed, ensure that it is stored in an upright position.
Note: Any remaining oil in the pipework should be drained into a suitable container.
MA-036 – DGA 900 MultiTank-family Operator Guide – Rev 1.2 9-Dec-21 Page 107 of 121
Appendix C Maintenance Activities
C.1 Battery
The product uses non-rechargeable lithium coin cell batteries (Panasonic CR2450
3 V 620 mAh) — one in the Hub module on the Controller PCB as shown in Figure C-1,
and the other in the Analysis module on the Gas Manifold Control Unit (GMCU) PCB as
shown in Figure C-2. If either battery needs to be replaced, data from the product must
be backed up. Failure to do so may result in historical data loss.
Figure C-1: Controller PCB coin cell battery Figure C-2: GMCU PCB coin cell battery
MA-036 – DGA 900 MultiTank-family Operator Guide – Rev 1.2 9-Dec-21 Page 108 of 121
C.2 Air Filter Replacement
The Hub module draws air from the base and expels it via the air outlet on the front door.
The intake air is filtered to remove the largest particles, so depending on environmental
conditions, the air filter cartridge may need periodic replacement.
To replace the air intake filter:
First isolate the product through the external circuit breaker or external switch
and apply LOTO.
Remove the four M8 hex nuts from the four M2.5 hex bolts securing the filter
holder assembly as shown in Figure C-3 and then prise the holder off the base
plate as shown in Figure C-4.
Remove the used filter mesh cartridge from the holder and dispose of it as shown
in Figure C-5. Replace with a new filter mesh cartridge as shown in Figure C-6 in
the orientation shown in Figure C-4. Note: the metallic mesh cover must face
downwards and outwards in the holder.
Place the filter holder assembly back onto the module’s base plate and secure in
place using the four nuts and bolts previously removed as shown in Figure C-3.
Figure C-3: Hub fan air inlet Figure C-4: Detached inlet cover with filter –
facedown
Figure C-5: Detached inlet cover with filter Figure C-6: Filter mesh cartridge – face up
removed
The air outlet filter on the rear of the front door should also be periodically checked and
replaced if required.
To replace the air outlet filter:
First isolate the product through the external circuit breaker or external switch
and apply LOTO before opening the door.
MA-036 – DGA 900 MultiTank-family Operator Guide – Rev 1.2 9-Dec-21 Page 109 of 121
Remove the eight M5 aerotight nuts that secure the Louvre catchment tray to the
top rear of the front door as shown in Figure C-7, and then lift the tray away from
the neoprene 3 mm gasket as shown in Figure C-8.
Remove the used white filter from the tray (it’s disposable and can be pulled out)
as shown in Figure C-9. Insert a new Louvre air filter as shown in Figure C-10 into
the tray ensuring that the filter evenly fills the entire space.
Refit the tray to the gasket on the front door and secure in place using the eight
nuts previously removed as shown in Figure C-7.
Figure C-7: Louvre catchment tray – attached Figure C-8: Louvre gasket – tray removed
Figure C-9: Louvre catchment tray – detached & Figure C-10: Louvre air filter
filter removed
MA-036 – DGA 900 MultiTank-family Operator Guide – Rev 1.2 9-Dec-21 Page 110 of 121
Figure C-11: Oil connections – TapTrans (left) & MultiTrans (right)
Figure C-12 shows the oil filter location with the filter element removed.
Before removing the filter housing, first isolate the product through the
external switch or circuit breaker and ensure that the oil supply valve is
closed.
Remove the four M3 hex bolts holding the oil filter cover.
Remove the stainless steel filter element and clean it using a brush and compressed
air (or replace with a new filter, order FITT01029H). Then replace the filter back into its
housing and re-secure the oil filter cover using the four M3 hex bolts.
MA-036 – DGA 900 MultiTank-family Operator Guide – Rev 1.2 9-Dec-21 Page 111 of 121
Replace the black insulating push-fit cover by inserting the bottom end first. Note:
Take care to route the earthing cable through the groove in the insulation. And then
press fit the top of the cover home.
Close and lock the door.
Re-open the product’s supply and return valves.
Re-energise the product and it will automatically begin measuring at the next
scheduled time.
WARNING: Ensure the product is powered off and disconnect all supplies
at their source before continuing.
Remove the six M2.5 hex bolts holding the external fan group as highlighted in
Figure C-14 and separate the mating connectors of the electrical cable to free the
fan group from the unit as shown in Figure C-15 to Figure C-17.
Use dry compressed air to blow any dust, insect matter or other debris from the
fans, cooling fins and the top vent (if necessary, remove the hood held by two M2.5
hex bolts).
Use a clean dry cloth to remove any hardened deposits from the general area.
If necessary, protect the electrical connector and use a non-pressurised hose pipe
to direct deionised water through the top fins of the cooler and continue to flush
water through the fins until the water running out from the bottom of the cooler
turns clear.
Reconnect the electrical cable at the clip, replace the external fan group (and hood
if removed), and secure in place with the M2.5 hex bolts.
Power on the product.
MA-036 – DGA 900 MultiTank-family Operator Guide – Rev 1.2 9-Dec-21 Page 112 of 121
Hood
Hex bolts
(six
highlighted)
Electrical
clip
connector
Figure C-14: Peltier cooler Figure C-15: Fan group electrical connection
Figure C-16: Peltier cooling fins Figure C-17: Fan group detached from cooler
MA-036 – DGA 900 MultiTank-family Operator Guide – Rev 1.2 9-Dec-21 Page 113 of 121
Appendix D Time Sync Implementation
The product has a time-sync feature that allows users to synchronize the clock. This
Appendix explains the data format options for the “time sync” and its implementation.
This R/W (read/write) register is in BCD format (Binary Coded Decimal). Some systems
are not compatible with this data format. *The time registers can be written separately
in 5 second intervals in any order.
These registers are readable and writable, but should be written together as a single 32-
bit value.
The number of seconds from the UNIX epoch time of Jan 1st 1970 00:00:00.
For reference, the time on a device is reported in the UTC format on the HMI as
11/29/2017 00:00:00 BST and the corresponding value in the registers mentioned above
is 1511913600.
When testing, please check that you are reading registers 1197-1198 (assuming
addresses start at 999 +1) and decoding an unsigned 32-bit big endian number. The
MA-036 – DGA 900 MultiTank-family Operator Guide – Rev 1.2 9-Dec-21 Page 114 of 121
epoch time is in UTC. This matches the device time. An online converter e.g.
http://www.epochconverter.com/ can be used to verify.
The product registers are protected with access flags. The register map details the
relevant access flags for each register. Each register may have one or more access flags,
separated by commas. Table D-3 lists the supported access flags:
Table D-3: Access flags
Flag Access Description
R Read Read access to a single register
rgN Read group Read access to a group of length N (Nmax = 120)
W Write Write access to a single register
wgN Write group Write access to a group of length N (Nmax = 120)
Access flags may be modified with the addition of the modifier flags listed in Table D-4.
Table D-4: Modifier flags
Flag Access Description
u User Only accessible if the master is authorised with user access
c Config Only accessible if master is authorised as config (commissioning) user
f Factory Only accessible if master is authorised as factory (service) user
MA-036 – DGA 900 MultiTank-family Operator Guide – Rev 1.2 9-Dec-21 Page 115 of 121
Appendix E Alarm Settings: General Advice
E.1 Introduction
There are published standards for interpretation of DGA results. The main internationally
recognised standards are IEEE® C57.104 and IEC® 60599. It is recommended that the
customer refers to these or local standards for more information on DGA interpretation.
As every transformer is different due to design, manufacturing tolerances, operating
regime, etc., there are no rules that can be applied to every transformer. Therefore, alarm
settings should be individually set for each transformer.
IEEE C57.104 provides a 4-level criterion to classify risks to transformers. Condition 1
gives the average gas values below which a ‘normal transformer’ is operating
satisfactorily.
If there is DGA history available for the transformer, then the customer should also
consult this information when deciding on the alarm settings for the transformer.
MA-036 – DGA 900 MultiTank-family Operator Guide – Rev 1.2 9-Dec-21 Page 116 of 121
Table E-1: Main Tank: Gas Level Alarms
µL/L or Hydrogen Methane Acetylene Ethylene Ethane Carbon Carbon TDCG
ppm (H2) (CH4) (C2H2) (C2H4) (C2H6) monoxide dioxide
(CO) (CO2)
IEEE STD 100 120 1 50 65 350 2500 720
Condition
1
1) Set alarms to the following only if the measurements taken are LESS THAN the above values.
(C2H2 is set slightly higher to avoid spurious alarms)
2) Set alarms to the following only if the measurements taken are ABOVE the IEEE Condition 1
values.
Measured Value * yyy% = ppm caution/alarm value)
Caution Value *120% Value Value *120% Value Value Value *120% Value
*120% *120% *120% *120%
Alarm Value *150% Value Value *150% Value Value Value *150% Value
*150% *150% *150% *150%
Note: The values cited in this table assume that no previous tests on the transformer for
dissolved gas analysis have been made or that no recent history exists. If a previous analysis
exists, it should be reviewed to determine if the situation is stable or unstable.
Note: See the example in Section E.8 at the end of this Appendix.
If the oil volume is known, the severity of defects based on ROC depends on the volume
(or weight) of oil contained in the transformer. For instance, a 1 ppm/day gas increase in
a large transformer (80,000 l oil) means a ROC of 80 ml/day of such gas. In a smaller
transformer (4,000 l oil), the same 1 ppm/day gas increase means a ROC of 4 ml/day. In
MA-036 – DGA 900 MultiTank-family Operator Guide – Rev 1.2 9-Dec-21 Page 117 of 121
either case there is a defect, but in the larger transformer the defect is much more
severe.
It is strongly recommended to use ROC in ml/day. Convert the ppm/day figure to ml/day
based on the oil volume or weight:
1) ROC =
(ROC ) m ml / day
Transformer owner may calculate ROC in ml/day by using following formula (IEC 60599):
( y2 − y1 ) m ml / day
2) ROC =
(d 2 − d1 )
where:
▪ y1 is the last reading, in ppm;
▪ y2 is the previous reading, in ppm;
▪ m is the oil mass / weight, in kilograms;
▪ ρ is the oil density, in kilograms per cubic metre;
▪ d1 is the date of y1, and
▪ d2 is the date of y2.
Note: This is a very generic formula. As Kelman® equipment readings are taken every
day, then (d2 – d1) = 1
Should the transformer owner use oil mass instead of oil volume, then ρ = 1,000. Thus,
formula can be simplified to:
where:
▪ (y2 – y1) is the difference between two consecutive readings in 24 hours, in ppm
▪ M is the oil mass, in metric tons
Note: Pay attention to the units of measure.
▪ In formula 2), oil density is given in kilograms per cubic metre, thus typical oil density
is about 960 kg/m3.
▪ In formula 3), gas concentration is given in ppm and oil mass is given in metric tons).
If using ROC in ml/day, use Table E-3 to set ROC alarms:
MA-036 – DGA 900 MultiTank-family Operator Guide – Rev 1.2 9-Dec-21 Page 118 of 121
Table E-3: ROC alarms (for ROC in ml/day)
ml/day Hydrogen Methane Acetylene Ethylene Ethane Carbon Carbon TDCG
(H2) (CH4) (C2H2) (C2H4) (C2H6) monoxide dioxide
(CO) (CO2)
Caution 2.5 1 0.05 1 1 25 - 5
Alarm 5 2 0.1 2 2 50 - 10
E.8.1 Caution
There may be cases where the transformer suddenly fails (between measurements at
the normal measurement interval). The customer should be made aware that online
monitoring equipment is not capable of detecting such rapid (often catastrophic)
failures. DGA monitoring is designed for the detection of incipient slow-developing faults.
MA-036 – DGA 900 MultiTank-family Operator Guide – Rev 1.2 9-Dec-21 Page 119 of 121
Other protective devices (Buchholz relay, pressure relief device, over-current and
differential current protection, etc…) should be used in conjunction with DGA monitoring
equipment to provide complete protection for the transformer.
Some modern, unused oils are recognised as ‘stray gassing’. This means that the oil itself
can produce some hydrogen in the absence of defects. Should the online monitor be
installed before or within a few months after the commissioning of the transformer,
hydrogen concentration may rise to 250 ppm. This should be taken into consideration
when establishing the caution and alarm settings.
In stray gassing oils, hydrogen concentration increases very rapidly when the
transformer is energised, reaches a plateau at about 250 ppm and then decreases slowly
to normal values. The transformer owner should know this behaviour before setting up
caution and alarm values and adapt them during the first year or two of transformer
operation. If Kelman equipment is installed on a transformer already in service, this note
is not applicable unless a passivator or an additive has been recently added to the oil.
After any oil treatment (degassing, regeneration, drying, mixing, etc.), the alarm settings
should be reviewed and changed if necessary.
MA-036 – DGA 900 MultiTank-family Operator Guide – Rev 1.2 9-Dec-21 Page 120 of 121
Contact & Copyright Details
GE, the GE monogram and Kelman are trademarks of the General Electric Company.
Other company or product names mentioned in this document may be trademarks
or registered trademarks of their respective companies.
MA-036 – DGA 900 MultiTank-family Operator Guide – Rev 1.2 9-Dec-21 Page 121 of 121