Lecture 8
Lecture 8
Power System II
1
Useful mathematical expressions
Single Line-to-Ground Fault
Sequence current
Fault current
2
Useful mathematical expressions
Line–to–Line Fault
Sequence current
Phase current
Sequence voltage
3
Useful mathematical expressions
Double Line-to-Ground Fault
Sequence current
Sequence voltage
4
Problems
5
Problems
The fault is assumed to occur on the red phase. Taking red phase as the reference,
(i) The total impedance to any sequence current is the sum of generator and feeder impedances to
that sequence current
6
Problems
7
Problems
8
Problems
The fault is assumed to occur on the red phase. Taking red phase as the reference,
9
Problems
10
Problems
For each system parameter, per-unit value is equal to the actual value divided by
a rated or base value
𝑨𝒄𝒕𝒖𝒂𝒍 𝒗𝒂𝒍𝒖𝒆
𝒑. 𝒖 𝒗𝒂𝒍𝒖𝒆 =
𝑹𝒂𝒕𝒆𝒅 𝒐𝒓 𝒃𝒂𝒔𝒆 𝒗𝒂𝒍𝒖𝒆
11
Problems
12
Problems
13
Problems
14
Problems
15