Experiment no 6 Electrical machine lab
Experiment no 6 Electrical machine lab
➢ Submitted By ➢ Submitted To
Schematic Diagram:
Loading Test(c)
Procedure:
1) Open Circuit Test: Complete connections as shown in the experimental setup.
Apply rated voltage to Low Tension side of the transformer. Note the readings of
the ammeter, voltmeter & wattmeter.
2) Short Circuit Test: Complete connections as shown in the experimental setup.
Gradually apply voltage across the Low Tension side of the transformer until rated
primary current flows through the ammeter. Quickly take the readings of the
ammeter, voltmeter & wattmeter.
3) Loading Test: Load the secondary with an RL load and complete connections as
shown in the figure. Apply rated voltage across the LT side. Measure the currents,
voltages and readings of the both: wattmeters. Set L = 1.3 H & vary R from
infinity to 403 2
DATA:
Name plate data of the transformer:
VA rating:15KVA Voltage rating: VIF= 2300 V V2F= 230V Current rating:
I1F= I2F= a=10:1
Data for open circuit test (referred to LT side):
Input power (Woc), watts =50W Input current (loc), amps= 0.21 A Input
power (Voc), volts= 2300 V
Data for short circuit test (referred to LT side):
Input power (Wsc), watts =160W Input current (Isc), amps=6A (rated) Input
power (Vsc), volts = 47 V
CALCULATIONS:
Referred to primary side,
𝑋𝑀
Rc=105 kΩ , XM=11 kΩ→LM= =29 H
2𝜋60
OC Test→
|𝐼𝑂𝐶 |
|𝑌𝑂𝐶 |=
|𝑉𝑂𝐶 |
=9.186*10-5 Ω
cosϴ=0.104→ϴ=84.030
YOC=|𝑌𝑂𝐶 |∟-ϴ
=9.186*10-5∟-84.030
=9.55*10-6-j9.136*10-5
1 1
= -𝑗
𝑅𝐶 𝑋𝑀
1
= 9.55*10-6 → RC=105k Ω
𝑅𝐶
1 𝑋𝑀
=9.136*10-5 → XM=11K Ω → LM=29H ( )
𝑋𝑀 2𝜋60
SC Test→
|𝑉𝑆𝐶 |
|𝑍𝑠𝑐 |= =7.8
|𝐼𝑆𝐶 |
cosϴ=0.5736→ϴ=550
𝑍𝑠𝑐 =|𝑍𝑠𝑐 |∟ϴ
= 7.8∟550
=4.474+j6.389
REQ= 4.474 Ω / 4.45 Ω
XEQ= 6.389 Ω / 6.45 Ω
Loading Test→
R=403 Ω→ WIN=103.5
WOUT=52.95
𝑊𝑂𝑈𝑇
η= 𝑊𝐼𝑁
= 51.15%
=0.2633 w
Core loss in RL load , Wcore=WOC=50.86 W
WIN(calculate)= 52.95+0.2933+50.86
=104.1033
Report:
1. Show all the data in schematic diagram form
Loading Test