0% found this document useful (0 votes)
28 views108 pages

Acson AC Repair Manual

The document provides detailed specifications and features for the A5LCY series air conditioning units, including various models and their nomenclature. It includes information on the indoor and outdoor units, application information, operating ranges, and energy efficiency features. Additionally, it covers installation guidelines, troubleshooting, and maintenance procedures for optimal performance.

Uploaded by

saadspace86
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
28 views108 pages

Acson AC Repair Manual

The document provides detailed specifications and features for the A5LCY series air conditioning units, including various models and their nomenclature. It includes information on the indoor and outdoor units, application information, operating ranges, and energy efficiency features. Additionally, it covers installation guidelines, troubleshooting, and maintenance procedures for optimal performance.

Uploaded by

saadspace86
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 108

Models:

A5LCY 10DR
A5LCY 15DR
A5LCY 20CR
A5LCY 25CR

A5LCY - I - 2010
Inverter-Y Single Split
Table of Contents A5LCY-I-2010

Contents
Nomenclature......................................................................................................................1
Indoor Unit .....................................................................................................................1
Outdoor Unit ..................................................................................................................3
Product Line-Up.............................................................................................................4
Features.............................................................................................................................10
Application Information ................................................................................................... 11
Operating Range ......................................................................................................... 11
Refrigerant Circuit Diagram .........................................................................................12
Controller ....................................................................................................................13
Installation Guideline ...................................................................................................16
Engineering & Physical Data ...........................................................................................40
General Data - Heat pump ..........................................................................................40
Component Data - Heat Pump ....................................................................................49
Safety Devices Data ....................................................................................................58
Outline and Dimension ....................................................................................................61
Electrical Data ...................................................................................................................65
Wiring Diagram .................................................................................................................70
Service and Maintenance.................................................................................................79
Troubleshooting ...............................................................................................................81
Exploded View and Part List ...........................................................................................92
Nomenclature A5LCY-I-2010

Nomenclature
Indoor Unit

A 5 WM Y 10 J R

Brand
A : Acson

Refrigerant
5 : R410A

Model Name
WM : Wall Mounted

Inverter System Type


Y : Y series

Capacity Index
10 : 10,000 Btu/h
15 : 15,000 Btu/h
20 : 20,000 Btu/h
25 : 25,000 Btu/h

Chassis
J : J Series

Model Type
“ “ : Omitted if cooling only
R : Heatpump

1
A5LCY-I-2010 Nomenclature

Indoor Unit

A 5 CK Y 10 C R

Brand
A : Acson

Refrigerant
5 : R410A

Model Name
CK : Ceiling Cassette
CC : Ceiling Concealed
CM : Ceiling Mounted

Inverter System Type


Y : Y series

Capacity Index
10 : 10,000 Btu/h
15 : 15,000 Btu/h
20 : 20,000 Btu/h
25 : 25,000 Btu/h

Chassis
C : C Series
E : E Series

Model Type
“ “ : Omitted if cooling only
R : Heatpump

2
Nomenclature A5LCY-I-2010

Outdoor Unit

A 5 LC Y 10 D R

Brand
A : Acson

Refrigerant
5 : R410A

Model Name
LC : Single Split Condensing Unit

Inverter System Type


Y : Y series

Capacity Index
10 : 10,000 Btu/h
15 : 15,000 Btu/h
20 : 20,000 Btu/h
25 : 25,000 Btu/h

Chassis
C : C Series
D : D Series

Model Type
“ “ : Omitted if cooling only
R : Heatpump

3
HEATPUMP
A5LCY-I-2010

Indoor Unit

25JR
20JR
15JR
10JR
A5WMY
A5WMY-J Series

ACLTA
ACLTA
ACLTC
ACLTC
Nomenclature
Product Line-Up

X
X
X
X
GS02
Handset

X
X
X
X
W_2_03A
PCB

X
X
X
X
Saranet Filter

Negative Ionizer Air Purification


Classification

Nano Technology Air Filtration

X
X
X
X

CE
X Marking
X
X
X

Auto Restart
Others
Product Line-Up

4
5
HEATPUMP
Product Line-Up

Indoor Unit

20CR
15CR
10CR
A5CKY

PLCKYCR
A5CKY-C Series

ACOA
ACOA
ACOA

NGS02
Nomenclature

X
GS02
Handset

X
X
X
C_2_01A_M
PCB

X
Saranet Filter

Negative Ionizer Air Purification


Classification

Nano Technology Air Filtration

X
X
X
X

CE
Marking
X
X
X

Auto Restart Others


A5LCY-I-2010
HEATPUMP
A5LCY-I-2010

Indoor Unit

25ER
20ER
A5CKY

PLCKYER
A5CKY-E Series

ACOA
ACOA

NGS02
Nomenclature

X
GS02
Handset

X
X
C_2_01A_M
PCB

X
Saranet Filter

Negative Ionizer Air Purification


Classification

Nano Technology Air Filtration

X
X
X

CE
Marking
X
X

Auto Restart
Others
Product Line-Up

6
7
HEATPUMP
Product Line-Up

Indoor Unit

25CR
20CR
15CR
10CR
A5CCY
A5CCY-C Series

ACPA
ACPA
ACPA
ACPA
Nomenclature

X
X
X
X
Netware 3C
Handset

X
X
X
C_2_01A_M
PCB

X
X
X
Saranet Filter

Negative Ionizer Air Purification


Classification

Nano Technology Air Filtration


X
X
X

CE
Marking
X
X
X

Auto Restart
Others
A5LCY-I-2010
HEATPUMP
A5LCY-I-2010

Indoor Unit

25ER
20ER
15ER
A5CMY
A5CMY-E Series

ACAA
ACAA
ACAA
Nomenclature

X
X
X
GS02
Handset

X
X
X
C_2_01A_M
PCB

X
X
X
Saranet Filter

Negative Ionizer Air Purification


Classification

Nano Technology Air Filtration


X
X
X

CE
Marking
X
X
X

Auto Restart
Others
Product Line-Up

8
9
HEATPUMP

A5LCY
Product Line-Up

25CR
20CR
15DR
10DR
Outdoor Unit
A5LCY-D Series

Nomenclature

ACDOA
ACDOA
ACOUB
ACOUA

X
X
X
X
OYL Controller
PCB

Cap Tube
Refrigerant
Control

X
X
X
X
EXV

Gold Coated

Blue Coated FIN

X
X
X
X
Bare Fin

Contactor
Classification

HP Safety Devices

LP
X
X

DC Inverter Single Rotary


Compressor
X
X

DC Inverter Swing Compressor


X
X
X
X

CE
Marking
A5LCY-I-2010
A5LCY-I-2010 Features

Features
Self Diagnosis

The microprocessor provides the possibility to detect and diagnose any fault or malfunction that occurs in
the system. The error will be reflected by the blinking of the LED lights and by wireless or wired* handset 7-
segment display. On top of that, in order to improve serviceability, outdoor unit is also equipped with built in
7-segment display for error code and operating parameters.

Technology

Incorporate Fuzzy Logic control to achieve more precise temperature control, faster and smoother response.
Enhanced design using
• Electronic Expansion Valve to achieve optimum refrigerant control as compared to capillary tube.
• Discharge pipe temperature control, high pressure limit control, input current control and heat sink
temperature control to improve reliability.

On / Off Button on Indoor Unit

On/Off button is provided on the unit. It can be used when the remote controller is missing or if its battery has
run out. (Note: This button can also be used for forced operation mode)

Auto Random Restart

Auto random restart function allows the unit to automatic restart as the last setting condition when the power
supply is resumed after power failure. However, the compressor will restart randomly if more than one unit is
installed and sharing the same phase of power.

Wireless Remote Controller

• The compact LCD transmitter is able to operate the air conditioner unit within the distance of 8 meters.
• Fan speed can be set at high / medium / low / super low or automatic.
• Sleep mode auto control will gradually increase or decrease the setting temperature to provide a
comfortable surrounding for sleeping.
• Air flow direction can be controlled automatically.
• Room temperature is controlled by electronic thermostat.
• The real time timer allows the air conditioner to be switched On and Off automatically based on user
settings.

Energy Efficiency

Using a more efficient compressor and superior R410A refrigerant, AWM-J series achieves the highest
European Energy Rating of A/A. This ensures higher energy savings is accomplished especially during daily
usage. A5WM-J series participates in the Eurovent Certification Programme under category of Comfort Air
Conditioners rated below 12kW cooling capacity (AC1). The certified data for the certified models are listed in
the Eurovent Directory.

Low Ambient Application

Variable speed outdoor fan allows cooling operation down to minus 10 degree Celsius. This is achieved by
modulating fan speed according to ON/OFF duty cycles in respond to the current system load and ambient
conditions.

* Currently available for all indoor models except for wall mounted series.

10
Application Information A5LCY-I-2010

Application Information
Operating Range

Ensure the operating temperature is in allowable range.

Heatpump
Heating Standard Cooling
point

18
46
Outdoor temp. (°CWB)

43

Outdoor temp. (°CDB)


10 STD
35

STD
6

-15 -10

15 20 21 27 14 19 23
Indoor temp. (°CDB) Indoor temp. (°CWB)

Caution :
The use of your air conditioner
outside the range of working
temperature and humidity can result
in serious failure.

11
A5LCY-I-2010 Application Information

Refrigerant Circuit Diagram

Model: A5LCY 10DR - A5WMY 10JR / A5CKY 10CR / A5CCY 10CR


A5LCY 15DR - A5WMY 15JR / A5CKY 15CR / A5CCY 15CR / A5CMY 15ER
A5LCY 20CR - A5WMY 20JR / A5CKY 20C/ER / A5CCY 20CR / A5CMY 20ER
A5LCY 25CR - A5WMY 25JR / A5CKY 25ER / A5CCY 25CR / A5CMY 25ER

70034106462

12
Application Information A5LCY-I-2010

Controller

GS02

3
6 4
SWING FAN
5
7
TURBO MODE 13
9
QUIET SLEEP
12
TIMER

11 ON OFF 8
CANCEL CLOCK CANCEL

10

13
A5LCY-I-2010 Application Information

Operation Guide
1 Transmission source 8 OFF timer setting
• The source where the signal will be transmitted. • Press the TIMER OFF button will activate the off timer
function.
2 Signal transmission indication • Set the desired off time by pressing the TIMER OFF button
• Blink to confirm that the last setting has been transmitted continuously.
to the unit. • Press the CANCEL button to cancel the off timer setting.
3 “ON/OFF” Button 9 Quiet function (model dependant)
• Press once to start the air conditioner unit. • Press for quiet operation.
• Press again to stop the unit. • Fan speed turn to minimum speed.
4 Fan Speed Selection • Press again to deactivate the function.
• Any change of fan speed will deactivate this function.
• Press the button continuously will toggle the fan speed
• The Silent function ( ) is unavailable for chiller water
in the following order:
system.
Low p Med p High p Auto
• Stop pressing when the desired fan speed appears on the 10 Clock time setting
display screen. • Press and hold button to set the clock time.
5 Operation mode
11 ON timer setting
• Press the MODE button to select the type of operating
mode. • Press the TIMER ON button will activate the on timer
• For cooling only unit, the available modes are: COOL (7), function.
DRY (6) and FAN ( ). • Set the desired on time by pressing the TIMER ON
• For heat pump unit, the available modes are: AUTO (U), button continuously. If the timer is set to 7.30am, the air
COOL (7), DRY (6), FAN ( ) and HEAT ( ). conditioner will turn on at 7.30am sharp.
• The AUTO (U) mode is unavailable for chilled water • Press the CANCEL button to cancel the on timer setting.
system. 12 Sleep mode setting
6 Automatic air swing • Press the  button will activate the sleep mode function.
• Press the SWING button to activate the automatic air • This is an energy
swing function. saving option. When +2 C
• To distribute the air to a specific direction, press the the unit is operating
SWING button and wait until the louver move to the under cooling mode, +1 C

desired direction and press the button once again. the set temperature is
Swing mode selection method (for CK-E model) increased by 0.5°C
• Press SWING ( ) button for 4 seconds to enter field after the first half an
setting mode. While in field setting mode, it will only show hour, another 0.5°C -1C

SWING MODE ( ). after the second half an


• Press temperature and button to select SWING MODE ( ) hour and 1°C after the - 2 C
rotation from Swing Mode 1 to Swing Mode 3. following 1 hour.
• There are 3 different SWING MODE, which are: • When the unit is -3C
operating under 0 0.5 1 1.5 2
heating mode, the set
Swing mode 1 Swing mode 2 Swing mode 3
temperature is decreased by 1°C after the first half an
• SWING MODE will not activate unless SWING is activated. hour, another 1°C after the second half an hour and 1°C
• Swing is indicated by the logo: after the following 1 hour.
• If no mode changes within 4 seconds, unit will operate • This function is available under COOL, HEAT and AUTO
according to the selected SWING MODE ( ). mode.

7 Turbo function (model dependent) 13 Temperature setting


• Press for fast cooling or heating operation. • To set the desired room temperature, press the * or *
• Fan speed turn to maximum speed. button to increase or decrease the set temperature.
• Press again to deactivate the function. • The temperature setting range is from 16°C to 30°C
• Available under HEAT, COOL and DRY modes only. (Optional setting 20°C to 30°C).
• Any change of fan speed will deactivate this function. • Press both buttons S and T simultaneously to toggle from
• The Turbo function ( ) is unavailable for chilled water °C to °F setting.
system and remote control with SWING MODE ( )
function.

14
Application Information A5LCY-I-2010

Controller

Netware 3C

1 ON/OFF Button 8 ON TIMER Button


• Starting Operation: • Enable/disable the Event 1, 2 and 3 ON TIMER setting
When the unit is turned off, press the ON/OFF button. mode
The operation LED lights and the unit is turned on.
• Stopping Operation: 9 OFF TIMER Button
When the unit is turned on, press the ON/OFF button. The • Enable/disable the Event 1, 2 and 3 OFF TIMER setting
operation LED is extinguished and control are turned off. mode

2 SLEEP Button 10 Timer Active Button


• Press SLEEP button to activate the sleep mode or energy • These timers will not triggered if the timer is not active.
saving mode. To activate the timers, press the TIMER ACTIVE key
unit “TIMER ACTIVE” appears on LCD. This symbol is to
3 FAN Button indicate Event 1, Event 2 and/or Event 3 timers are active.
• Press FAN button to select AUTO, HIGH, MEDIUM or LOW Pressing the same steps will deactivate the timers and
fan speed. “TIMER ACTIVE” symbol will disappear.
• Another method to cancel the timers setting is changed all
4 MODE Button the hour setting of the timers to null one by one. When the
• Press the MODE button to switch operation from COOL, setting is null, the LCD display --:--, then this respective
HEAT, DRY, FAN. timer will be disable.
• Check the display to see in which mode the control is set.
11 CLOCK Button
5,6 ‘▲’ or ‘▼’ Set Temperature Button • Enable/disable the Real Time Clock (RTC) setting mode
• Press the temperature button and set the temperature 12 DAY Button
of your choice. By pressing the ‘▲’ or ‘▼’ button once,
temperature changes by 1°C [or 1°F]. a) Select the day for RTC or timer setting
• Temperature can be set within the range 16°C~30°C b) Enable/disable FAN Key lock
(61°F~86°F) 13 HOUR Button
• During fan mode, temperature cannot be set. a) Select the hour for RTC or timer settings
• If pressing ‘▲’ and ‘▼’ together, the unit of temperature will b) Set Override function for 1, 2 or 4 hours
change from °C to °F and vice-versa.
14 MINUTE Button
7 SWING button a) Select the minute for RTC or timer settings
• Press SWING button to activate the air sweep function. b) Enable/disable key lock

15
A5LCY-I-2010 Application Information

Installation Guideline

Safety Precautions

WARNING CAUTION
• Installation and maintenance should be performed by qualified Please take note of the following important points
persons who are familiar with local code and regulation, and when installing.
experienced with this type of appliance. • Do not install the unit where leakage of flammable
• All field wiring must be installed in accordance with the national gas may occur.
wiring regulation. If gas leaks and accumulates around the unit, it
• Ensure that the rated voltage of the unit corresponds to that of the may cause fire ignition.
name plate before commencing wiring work according to the wiring • Ensure that drainage piping is connected properly.
diagram. If the drainage piping is not connected properly,
• The unit must be GROUNDED to prevent possible hazard due to it may cause water leakage which will dampen
insulation failure. the furniture.
• All electrical wiring must not touch the refrigerant piping or any • Do not overcharge the unit.
moving parts of the fan motors.
This unit is factory pre-charged. Overcharge will
• Confirm that the unit has been switched OFF before installing or
cause over-current or damage to the compressor.
servicing the unit.
• Ensure that the unit’s panel is closed after service
• Disconnect from the main power supply before servicing the air
or installation.
conditioner unit.
• DO NOT pull out the power cord when the power is ON. This may Unsecured panels will cause the unit to operate
cause serious electrical shocks which may result in fire hazards. noisily.
• Keep the indoor and outdoor units, power cable and transmission • Sharp edges and coil surfaces are potential
wiring, at least 1m from TVs and radios, to prevent distorted locations which may cause injury hazards. Avoid
pictures and static. {Depending on the type and source of the from being in contact with these places.
electrical waves, static may be heard even when more than 1m • Before turning off the power supply, set the remote
away}. controller’s ON/OFF switch to the “OFF” position
to prevent the nuisance tripping of the unit. If this is
not done, the unit’s fans will start turning automatically
when power resumes, posing a hazard to service
personnel or the user.
• Do not operate any heating apparatus too close to the
air conditioner unit. This may cause the plastic panel to
melt or deform as a result of the excessive heat.
• Ensure the color of wires of the outdoor unit and
the terminal markings are same to the indoors
respectively.
• IMPORTANT : DO NOT INSTALL OR USE THE
• AIR CONDITIONER UNIT IN A LAUNDRY ROOM.
• Do not use joined and twisted wires for incoming
power supply.

NOTICE
Disposal requirements
Your air conditioning product is marked with this symbol. This means that electrical and electronic products
shall not be mixed with unsorted household waste.
Do not try to dismantle the system yourself: the dismantling of the air conditioning system, treatment of
the refrigerant, of oil and of other parts must be done by a qualified installer in accordance with relevant
local and national legislation. Air conditioners must be treated at a specialized treatment facility for re-use,
recycling and recovery. By ensuring this product is disposed of correctly, you will help to prevent potential
negative consequences for the environment and human health. Please contact the installer or local authority
for more information.
Batteries must be removed from the remote controller and disposed of separately in accordance with relevant
local and national legislation.

16
Application Information A5LCY-I-2010

Installation Diagram

Cut thermal insulation


Wall Mounted 30mm or more from ceiling pipe to an appropriate
Caulk pipe length and wrap it with
hole gap tape, making sure that no
with putty. gap is left in the insulation
Front panel pipe’s cut line.

Wrap the insulation pipe with


the finishing tape from bottom
50mm or more from walls to top.
(on both sides)

M4 x 12L Service lid


Air filter • Opening service lid
Service lid is opening/closing
type.
• Opening method
1) Remove the service lid
screws.
2) Pull out the service lid
diagonally down in the
direction of the arrow.
3) Pull down.

250mm from wall

Caution
• Before installing the unit, ensure that the power supply matches the power requirement of the air conditioner.

Service Space
Install the indoor unit at a location with the following requirements
• Location is suitable for wiring, piping and drainage.
• No obstruction of air flow into and out of unit where cooler air can be evenly distributed.
• Ensure that air discharge is not short circuited with air intake.
• Ensure that wall is sufficiently strong, rigid, flat, perpendicular and vibration free.
• Where air filter cassette can be slided in or out easily.
• Where there is no danger of flammable gases.
• Where there is no direct sunlight on unit.

Air flow
performance)

(Indoor)
(Space for
min. 30

min. 50 min. 50
(Space for
Required space (Space for
maintenance) maintenance)

17
A5LCY-I-2010 Application Information

Routing of Piping
• The refrigerant piping can be routed to the unit in a number of ways (left or right from the back of the unit),
by using the cut-out holes on the casing of the unit . Bend the pipes carefully to the required position in
order to align it with the holes. For the side and bottom out, hold the bottom of the piping and then position
it to the required direction. The condensation drain hose can be taped to the pipes.

Right-side, right-back or right-bottom piping Left-side, left-back or left-bottom piping


Remove pipe port
cover here for
left-side piping

Right-side
Left-side
piping
piping
Right-back piping
Remove pipe port cover Remove pipe port cover here for
here for right-side piping Left-back
Right-bottom left-bottom piping piping
piping Bind coolant pipe Left-bottom piping
Remove pipe port cover and drain hose
here for right-bottom piping together with
insulating tape.

Mounting Installation Plate


• Paste the installation plan provided on the desired location on the wall and marks the holes location
accordingly.
• Ensure the wall is strong enough to withstand the weight of the unit. Otherwise, it is necessary to reinforce
the wall with plates, beams or pillars.
• Ensure the levelness of the installation plate, and fix with 5 suitable screws.

Mounting plate

Mounting plate
fixing screw

18
Application Information A5LCY-I-2010

• Fix the installation plate firmly to the wall, without tilting to left or right. Use a plumb line, if available.

Use tape measure as shown.


Recommended mounting plate
Position the end of a tape measure
retention spots (5 spots in all)
166 at 184

42.2
42.2

42.2
Through

288
the wall
hole
Ø 65mm

45.9
45.9
54.5 153.8 181.7 555
263 51.9
800
Drain
hose
Liquid pipe end Gas pipe end position

All dimensions are in mm

• In case of rear piping drawings out, drill a hole 65mm in diameter with a cone drill, slightly lower on the
outside wall.

Hole with cone drill Inside Outside


Wall embedded pipe
(Field supply) Caulking

Ø 65
Wall hole cover
(Field supply)
Wall embedded pipe
(Field supply)

Mounting Unit onto the Installation Plate


• Hook the indoor unit onto the upper portion of the installation plate (engage the two hooks at the rear top of
the indoor unit with the upper edge of the installation plate). Ensure the hooks are properly seated onto the
installation plate by moving it to the left and right.
• To attach the indoor unit, hook the claws of the bottom frame to the mounting plate. If the claws are difficult
to hook, remove the front grille.
• To remove the indoor unit, push the marked area (at the lower part of the front grille) to release the claws.
If it is difficult to release, remove the front grille.

Mounting Hang indoor unit's hook here.


plate

Mounting plate
When stripping the
Clip ends of interconnecting
wires in advance, bind
right ends of wires with Interconnecting
insulating tape. wires

Bottom frame Wire guide


Mark (rear side)
Front grille

19
A5LCY-I-2010 Application Information

Water Drainage Piping


• The indoor drain pipe must be downward gradient for smooth drainage. Avoid situation as shown in figure
below.

Water Drainage

Water
Retention
End
Water Water dipped
Water
leaking leaking into
leaking
water

Drain

Correct Wrong Wrong Wrong

Drain work. (Heat Pump Unit Only)


1) Use drain plug for drainage.
2) If the drain port is covered by a mounting base or floor surface, place additional foot bases of at least 30mm
in height under the outdoor unit’s feet.
3) In cold areas, do not use a drain hose with the outdoor unit. (Otherwise, drain water may freeze, impairing
heating performance.)

Drain-water hole

Bottom frame

Drain plug
Hose (available commercially,
inner dia. 16mm)

20
Application Information A5LCY-I-2010

Ceiling Cassette
Drain Piping Thermal Insulation

Wrap the insulated pipe with the


finishing tape from bottom to top

Front Panel

Air Filter
(behind the grille)

Air Intake Grille


Air Discharge Louver

Preliminary Site Survey


• Electrical supply and installation is to confirm to local authority’s (e.g. National Electrical Board) codes and
regulations.
• Voltage supply fluctuation must not exceed ± 10% of rated voltage. Electricity supply lines must be
independent of welding transformers which can cause high supply fluctuation.
• Ensure that the location is convenient for wiring, piping and drainage.
• The indoor unit must be installed in such that free from any obstacles in path of cool air discharge and
warm air return, and must allow spreading or air throughout the room (near the centre of the room).
• Clearance must be provided for the indoor unit from the wall and obstacles as shown in the figure.
Beam

Max 3.0 m
Min 1.0 m

Max 3.0 m

Min 0.5 m Min 0.5 m Min 0.5 m

Obstacles
Floor

• The installation place must be strong enough to support a load of 4 times the indoor unit weight to avoid
amplifying noise and vibration.
• The installation place (handling ceiling surface) must be level and the height in the ceiling is 350mm or
more.

21
A5LCY-I-2010 Application Information

Unit Installation
770.0 mm (Hanging rod)
15.0 538.0 18.0

38.0

580.0 ~ 610mm (CEILING OPENING MEASUREMENT)


88.0

622.0 mm (Hanging rod)


505.0

448.0
32.0 529.0 19.0

580.0 ~ 610mm (CEILING OPENING MEASUREMENT) Piping Direction

A5CKY-C A5CKY-E

• The indoor unit must be away from heat and steam sources (avoid installing it near an entrance).
• Measure and mark the position for the hanging rod. Drill the hole for the angle nut on the ceiling and fix the
hanging rod.
• The installation template is extended according to temperature and humidity. Check on dimensions in
using.
• The dimensions of the installation template are same as those of the ceiling opening dimensions.
• Before ceiling laminating work is completed, be sure to fit the installation template to the indoor unit.

Note: Be sure to discuss the ceiling drilling work with the installers concerned.

Unit Hanging

Indo or U nit
Ceiling
Board

30.0mm

A5CKY-C/E
• Confirm the pitch of the hanging rod is 770mm x 622mm sharp (A5CKY-E)
• Hold the unit and hand it on the hanging rod with the nut and washer.
• Adjust the unit height to 35.0mm between the indoor unit bottom surface and the ceiling surface.
• Confirm with a level gauge that the unit is installed horizontally and tighten the nut and bol to prevent unit
falling and vibration.
• Open the ceiling board along the outer edge of the paper installation template.

22
Application Information A5LCY-I-2010

Drain Piping Work


• Drain pipe must be downward gradient for smooth
drainage.
• Avoid the drain pipe from up and down slope to prevent
INDOOR UNIT
reversal flow.
• During the drain pipe connection, be careful not to exert
extra force on the drain connector at the indoor unit.
Pipe clamp • The outside diameter of the drain connection at the
flexible drain hose is 20mm.
Bad • Be sure to provide heat insulation (polyethylene foam
Good
with thickness more than 8.0mm) on the drain piping to
avoid the condensed water dripping inside the room.

Drain Test
FEED WATER MAIN DRAIN PIPE • Connect the main drain pipe to the flexible drain hose.
• Feed water from flexible drain hose and check the
piping for leakage.
• When the test is completed, connect the flexible drain
FLEXIBLE hose to the drain connector on the indoor unit.
DRAIN HOSE

Note: This indoor unit use drain pump for condensed water drainage. Install the unit horizontally to prevent
water leakage or condensation around the air outlet.

Panel Installation
• The front panel can only be fitted in one direction, follow the piping direction. (Follow piping arrow sticker
on the front panel).
• Be sure to remove the installation template before installing the front panel.

• Open the air intake grille by pulling back the catchers and remove it together with filter from panel.
• Install the front frame panel onto the indoor unit by using 4 screws and tighten it completely to prevent cool
air leakage.
• Connect the LED wire and air swing wire to the indoor unit (Optional).

23
A5LCY-I-2010 Application Information

Note: Install the front frame panel firmly to prevent cool air leakage which will
cause condensation and water dripping.

Fresh Air Intake For A5CKY-E Unit

Take off the panel from the indoor unit

Remove the PE foam from the drain pan and another one on the unit.
Remove the pre-punched panel on the CKC unit with a screwdriver.
The diameter of the air intake knock out hole is 65mm.
Then, fix the fresh air kit (refer to parts list) to the hole. Finally, a flexible duct is connected to let the fresh air
moving in.

24
Application Information A5LCY-I-2010

Fig. 2

The direction of the fresh air intake is shown as fig. 2.

Sealing Material
• It is possible to seal one of the four air discharge outlet (sealing two or more air discharge outlet could
cause a malfunction).
• Remove the front panel and inserting the seal material into the air discharge outlet at the indoor unit to
sealthe air outlet.
• The sealing material is the same length as the length air discharge outlet. If it is desired to seal the shorter
air discharge outlet, cut the sealing material to shorten it.
• Push the sealing material in about 10mm beyond the bottom surface of the indoor unit so that it does not
touch the air louver. Be sure not to push the sealing material in any farther than about 10mm.

Short Duct Specification For A5CKY-E Unit

• The indoor unit is provided with air discharge and air intake “knock-out” hole for duct connection. However
the connection of the short duct for air discharge is possible on only one side.
• The use of short duct for air discharge will improve air flow distribution if there is an obstruction (such as
alighting fixture) or in a long, narrow room or an L-shaped room. It is also used for air-conditioning of two
rooms simultaneously.

Possible Direction For Air Discharge and Air Intake

Air Discharge Air Discharge

Air Intake
Air Discharge Air Discharge

25
A5LCY-I-2010 Application Information

Possible Opening Dimension for Duct Connection

Note: 1. Avoid to use the short duct on which the air discharge grille can be completely closed, to
prevent evaporator freezing.
2. In order to prevent condensation forming, be sure that there is sufficient thermal insulation
and no leakage of cool air when installing the short duct.
3. Keep the introduction of fresh air intake within 20% of total air flow. Also provide a chamber
and use a booster fan.

Ceiling Concealed

Hanger

Return duct

Supply duct

Wrap the insulated pipe with the


finishing tape from bottom to top

Drain Thermal insulation


Ceiling piping

26
Application Information A5LCY-I-2010

Preliminary Survey
• Electrical supply and installation is to confirm to local authority’s (e.g. National Electrical Board) codes and
regulations.
• Voltage supply fluctuation must not exceed ± 10% of rated voltage. Electricity supply lines must be
independent of welding transformers which can cause high supply fluctuation.
• Ensure that the location is convenient for wiring, piping and drainage.
• The indoor unit must be installed in such that free from any obstacles in path of cool air discharge and
warm air return, and must allow spreading or air throughout the room (near the centre of the room).
• Clearance must be provided for the indoor unit from the wall and obstacles as shown in the figure.
• Use the hanger supplied with the unit.
• Ensure the support is strong enough to withstand the weight of the unit.
• Use the supplied drain socket to connect the drain pipe (the drain socket is only available for 10˚C to 25˚C)

Install the unit in such a way that


the condensate water can flow
out smoothly.

The diagrams below show the screws position for duct work connection.

27
A5LCY-I-2010 Application Information

Ceiling Convertible

Preliminary Site Survey


• Electrical supply and installation is to confirm to local authority’s (e.g. National Electrical Board) codes and
regulations.
• Voltage supply fluctuation must not exceed ± 10% of rated voltage. Electricity supply lines must be
independent of welding transformers which can cause high supply fluctuation.
• Ensure that the location is convenient for wiring, piping and drainage.

Standard Mounting
Ensure that the overhead supports are strong enough to hold the weight of the unit. Position the hanger
rods (wall mounting bracket for floor standing), and check for its alignment with the unit as shown in Fig. 3.
Also,check that the hangers are secured and the base of the fan coil unit is leveled in both horizontal
directions, taking into account the gradient for drainage flow as recommended under section Piping and Drain
Hose Installation.

Fig. 3

28
Application Information A5LCY-I-2010

Please ensure that the following steps are taken:


• Check the gradient for drainage flow as recommended in Figure 4.
• Provide clearance for easy servicing and optimal air flow as shown in Figure 5.
• The indoor unit must be installed such that there is no short circuit of the cool discharge air with the warm
return air.
• Don not install the indoor unit where there is direct sunlight shining on the unit. The location should be
suitable for piping and drainage installation. The unit must be a large distance away from the door.

Fig.4

Under ceiling type

Floor standing type

Fig.5

29
A5LCY-I-2010 Application Information

Under Ceiling Installation

Install the Suspension Bolts


1. Install the suspension bolts so that it can support the indoor unit.
2. Adjust the distance to ceiling before installation.
3. Refer to the dimension given (Fig. 5) to install the unit.

Install the Indoor Unit


1. Insert the suspension bolts into the fittings of the hanger bracket.
2. Set the nuts and washer on the both side of the metal fittings.
3. Secure it with nuts.
4. Attach the hanger cover (4 pcs) to the units.

30
Application Information A5LCY-I-2010

Floor Standing Installation

1. Refer to the dimension as illustrated when installing the mounting bracket.


2. Determine the pipe hose position using the rear piping hole. Drill the pipe hole at the slight downward slant
to the outdoor side.

MOUNTING BRACKET

HOCK THE UNIT ON THE


MOUNTING BRACKET WALL

31
A5LCY-I-2010 Application Information

Piping and Drain Hose Installation

Under Ceiling Type


1. The piping direction can be 2 ways as illustrated.
2. The drain hose is only 1 way.

OR

Floor Standing Type

OR

How to Install the Drain Hose


1. Remove the 2 screws and the drain pipe holder.
2. Cut a slit for the drain hose hole.
3. Place the drain hose on the v-shape area and secure it with drain pipe holder and 2 screws.

32
Application Information A5LCY-I-2010

How to Remove the Air Inlet Grille


1. Remove the air inlet grille by both hands as the direction shown.
2. Loosen the screws for fixing the panel arm (3 screws – Left, Right and Center). Do not remove the screws
at this time.
3. Move the air inlet grille upward, and then turn it backwards. (Do not use too much force).
4. Remove the grille holder (both left and right side). After that, remove the air intake grille.
5. Remove the grille holder (center) from the panel.

33
A5LCY-I-2010 Application Information

How to Install the Air Filter

To Adjust the Vane Direction


Adjust the vane linkage as the direction shown to get the required vane direction.

Dimension of the Fresh Air Intake Hole


70.0

64.0 70.0 3.0

34
Application Information A5LCY-I-2010

Outdoor Unit Installation


• Where a wall or other obstacle is in the path of outdoor unit’s intake or exhaust airflow, follow the
installation guidelines below.

Wall facing one side Walls facing two sides

More than 50 More than 100


More than 100
More
than 150

More than 50 More than 50


Top view

Side view

Walls facing three sides

More than 150

More than 300

More
than 50
Top view Unit: mm

Electrical Wiring Connection


IMPORTANT : * The figures shown in the table are for information purpose only. They should be checked
and selected to comply with the local/national codes of regulations. This is also subject to
the type of installation and conductors used.
** The appropriate voltage range should be checked with label data on the unit.

Indoor Unit Outdoor Unit Model 10/15


Terminal Block Terminal Block Voltage range 220V-240V/ 1Ph/ 50Hz +
1 1
Power supply cable size* mm2 1.5
2 2 Number of core 3
SIG SIG
Power supply cable size* mm2 1.5
N Number of core 4
L Recommended time delay fuse A 15
Power Supply
Cable * If the length of the cable is more than 2m, use cable with bigger
size.

There must be a double pole


! switch with a minimum 3mm
contact gap and fuse/circuit
breaker as recommended in
the fixed installation circuit.

• All wires must be firmly connected.


• All wires must not touch the refrigerant piping, compressor or any moving parts of the fan motor.
• The connecting wires between the indoor unit and the outdoor unit must be clamped on the wire clamps.
• The power supply cord must be equivalent to H07RN-F (245IEC57) which is the minimum requirement.

35
A5LCY-I-2010 Application Information

Refrigerant Piping
Piping Length and Elevation
If the pipe is too long, both the capacity and reliability of the unit will drop. As the number of bends increases,
resistance to the flow of refrigerant system increases, thus lowering cooling capacity. As a result, the
compressor may become defective. Always choose the shortest path and follow the recommendations as
tabulated below:
Outdoor A5LCY10DR A5LCY15DR A5LCY20CR A5LCY25CR
Indoor A5WMY10JR A5WMY15JR A5WMY20JR A5WMY25JR
Max. allowable length, m 15 15 30 30
Max. allowable elevation, m 10 10 10 10
Liquid pipe, mm O.D. 6.4 O.D. 6.4 O.D. 6.4 O.D. 6.4
Gas pipe, mm O.D. 9.5 O.D. 12.7 O.D. 12.7 O.D. 15.9
Additional charge of refrigerant, g/m
20 20 20 20
(for piping length above 7.5m)

Outdoor A5LCY10DR A5LCY15DR A5LCY20CR


Indoor A5CKY10CR A5CKY15CR A5CKY20CR
Max. allowable length, m 15 15 30
Max. allowable elevation, m 10 10 10
Liquid pipe, mm O.D. 6.4 O.D. 6.4 O.D. 6.4
Gas pipe, mm O.D. 9.5 O.D. 12.7 O.D. 12.7
Additional charge of refrigerant, g/m
20 20 20
(for piping length above 7.5m)

Outdoor A5LCY20CR A5LCY25CR


Indoor A5CKY20ER A5CKY25ER
Max. allowable length, m 30 30
Max. allowable elevation, m 10 10
Liquid pipe, mm O.D. 6.4 O.D. 6.4
Gas pipe, mm O.D. 12.7 O.D. 15.9
Additional charge of refrigerant, g/m
20 20
(for piping length above 7.5m)

Outdoor A5LCY10DR A5LCY15DR A5LCY20CR A5LCY25CR


Indoor A5CCY10CR A5CCY15CR A5CCY20CR A5CCY25CR
Max. allowable length, m 15 15 30 30
Max. allowable elevation, m 10 10 10 10
Liquid pipe, mm O.D. 6.4 O.D. 6.4 O.D. 6.4 O.D. 6.4
Gas pipe, mm O.D. 9.5 O.D. 12.7 O.D. 12.7 O.D. 15.9
Additional charge of refrigerant, g/m
20 20 20 20
(for piping length above 7.5m)

Outdoor A5LCY15DR A5LCY20CR A5LCY25CR


Indoor A5CMY15ER A5CMY20ER A5CMY25ER
Max. allowable length, m 15 30 30
Max. allowable elevation, m 10 10 10
Liquid pipe, mm O.D. 6.4 O.D. 6.4 O.D. 6.4
Gas pipe, mm O.D. 12.7 O.D. 12.7 O.D. 15.9
Additional charge of refrigerant, g/m
20 20 20
(for piping length above 7.5m)

* Be sure to add the proper amount of additional refrigerant. Failure to do so may result in reduced performance.
Remark: The refrigerant pre-charged in the outdoor unit is for piping length up to 7.5m.

36
Application Information A5LCY-I-2010

Piping Works
• Do not use contaminated or damaged copper tubing. Do not remove plastic, rubber plugs and brass nuts
from the valves, fittings, tubings and coils until you are ready to connect suction or liquid line into valves or
fittings.
• If any brazing work is required, ensure that the nitrogen gas is passed through coil and joints while the
brazing work is being done. This will eliminate soot formation on the inside walls of the copper tubings.
• Cut the connection pipe with a pipe cutter.
Cutting copper tube

1/4t

• Remove burrs from cut edges of the pipes with remover. Hold the end of the pipe downwards to prevent
metal chips from entering the pipe.

Remove burr

• Insert the flare nuts, mounted on the connection parts of both the indoor unit and outdoor unit onto the
copper pipes.
• Flare the pipe with extra length above the flaring tool as shown in the table.
• The flared edge must be even and not cracked or scratched.
Ø Tube, A (mm) Copper tube
Inch mm Imperial Die Rigid Die Swaging block
1/4 6.35 1.3 0.7
3/8 9.52 1.6 1.0
1/2 12.70 1.9 1.3
5/8 15.88 2.2 1.7
3/4 19.05 2.5 2.0

Piping Connection to the Units


• Align the center of the piping and tighten the flare nut sufficiently with fingers.
• Finally tighten the flare nut with torque wrench unit the wrench clicks.
• When tightening the flare nut with torque wrench, ensure the direction for tightening follows the arrow on
the wrench.
Pipe Size (mm/in) Torque (Nm)/(ft - lb)
6.35 (1/4) 18 (13.3)
9.52 (3/8) 42 (31.0)
12.70 (1/2) 55 (40.6)
15.88 (5/8) 65 (48.0)
19.05 (3/4) 78 (57.6)

Flare joint Flared tube

Indoor piping Flare nut

Torque wrench
Spanar

37
A5LCY-I-2010 Application Information

Vacuuming and Charging

Purging The Piping And The Indoor Unit


Except for the outdoor unit which is pre-charged with refrigerant, the indoor unit and the refrigerant connection
pipes must be air-purged because the air containing moisture that remains in the refrigerant cycle may cause
malfunction of the compressor.
• Remove the caps from the valve and the service port.
• Connect the center of the charging gauge to the vacuum pump.
• Connect the charging gauge to the service port of the 3-way valve.
• Start the vacuum pump. Evacuate for approximately 30 minutes. The evacuation time varies with different
vacuum pump capacity. Confirm that the charging gauge needle has moved towards -760mmHg.

Refrigerant piping
Allen key Indoor Unit Liquid side Outdoor Unit
Flare nut Discharge
valve
Close

Gas side
Service port Outdoor unit 3 ways valve Suction
valve
Open
Vacuum Close
pump Hi
Low
Close

Caution
• If the gauge needle does not move to -760mmHg, be sure to check for gas leaks (using the refrigerant detector) at
flare type connection of the indoor and outdoor unit and repair the leak before proceeding to the next step.
• Close the valve of the charging gauge and stop the vacuum pump.
• On the outdoor unit, open the suction valve (3 way) and liquid valve (2 way) (in anti-clockwise direction) with 4mm key
for hexagon sacked screw.

Charge Operation
This operation must be done by using a gas cylinder and a precise weighing machine. The additional charge
is topped-up into the outdoor unit using the suction valve via the service port.
• Remove the service port cap.
• Connect the low pressure side of the charging gauge to the suction service port center of the cylinder tank
and close the high pressure side of the gauge. Purge the air from the service hose.
• Start the air conditioner unit.
• Open the gas cylinder and low pressure charging valve.
• When the required refrigerant quantity is pumped into the unit, close the low pressure side and the gas
cylinder valve.
• Disconnect the service hose from service port. Put back the service port cap.

Indoor Unit Liquid side Outdoor Unit


Discharge valve
Open

Gas side

Check Suction
valve
valve
Open
Hi
Low
Close

38
Application Information A5LCY-I-2010

Special Precautions when Dealing with R410A Unit


R410A is a new HFC refrigerant which does not damage the ozone layer. The working pressure of this
new refrigerant is 1.6 times higher than conventional refrigerant (R22), thus proper installation / servicing is
essential.
• Never use refrigerant other than R410A in an air conditioner which designed to operate with R410A.
• POE oil is used as lubricant for R410A compressor, which is different from the mineral oil used for R22
compressor.During installation or servicing, extra precaution must be taken not to expose the R410A
system too long to moist air. Residual POE oil in the piping and components can absorb moisture from the
air.
• To prevent mischarging, the diameter of the service port on the flare valve is different from that of R22.
• Use tools and materials exclusively for refrigerant R410A. Tools exclusively for R410A are manifold valve,
charging hose, pressure gauge, gas leak detector, flare tools, torque wrench, vacuum pump and refrigerant
cylinder.
• As an R410A air conditioner incurs higher pressure than R22 units, it is essential to choose the copper
pipes correctly. Never use copper pipes thinner than 0.8mm even though they are available in the market.
• If the refrigerant gas leakage occurs during installation / servicing, be sure to ventilate fully. If the
refrigerant gas comes into contact with fire, a poisonous gas may occur.
• When installing or removing an air conditioner, do not allow air or moisture to remain in the refrigerant
cycle.

39
A5LCY-I-2010 Engineering & Physical Data

Engineering & Physical Data


General Data - Heat pump
OUTDOOR UNIT A5LCY 10DR A5LCY 15DR
MODEL
INDOOR UNIT A5WMY 10JR A5WMY 15JR

Btu/h 8872 (3754 - 11260) 11942 (4436 - 13307)


NOMINAL COOLING CAPACITY
W 2600 (1100 - 3300) 3500 (1300 - 3900)

Btu/h 10236 (3412 - 13990) 12966 (3412 - 15696)


NOMINAL HEATING CAPACITY
W 3000 (1000 - 4100) 3800 (1000 - 4600)

NOMINAL TOTAL INPUT POWER (COOLING) W 760 1050

NOMINAL RUNNING CURRENT (COOLING) A 4.10 5.00

NOMINAL TOTAL INPUT POWER (HEATING) W 828 1050

NOMINAL RUNNING CURRENT (HEATING) A 4.00 4.90

POWER SOURCE V/Ph/Hz 220 - 240 / 1 / 50 220 - 240 / 1 / 50

EER W/W 3.42 3.33

COP W/W 3.62 3.62

REFRIGERANT TYPE R410A R410A

REFRIGERANT CONTROL (EXPANSION DEVICE) OUTDOOR EXV OUTDOOR EXV


AUTO LOUVER (UP & DOWN) & AUTO LOUVER (UP & DOWN) &
AIR DISCHARGE
CONTROL GRILLE (LEFT & RIGHT) GRILLE (LEFT & RIGHT)
OPERATION WIRELESS REMOTE CONTROL WIRELESS REMOTE CONTROL

HIGH l/s / CFM 153 / 324 160 / 337

AIR FLOW MEDIUM l/s / CFM 119 / 252 124 / 262

LOW l/s / CFM 93 / 197 101 / 213


INDOOR UNIT

SOUND PRESSURE LEVEL (H/M/L/SL) dBA 40 / 34 / 29 / 25 41 / 34 / 30 / 28

HEIGHT mm/in 288 / 11.3 288 / 11.3

UNIT DIMENSION WIDTH mm/in 800 / 31.5 800 / 31.5

DEPTH mm/in 204 / 8.0 204 / 8.0

HEIGHT mm/in 350 / 13.8 350 / 13.8

PACKING DIMENSION WIDTH mm/in 894 / 35.2 894 / 35.2

DEPTH mm/in 280 / 11.0 280 / 11.0

UNIT WEIGHT kg/lb 9 / 19.9 9 / 19.9

CONDENSATE DRAIN SIZE mm/in 16 / 0.63 16 / 0.63

AIR FLOW l/s / CFM 521 / 1100 473 / 1000

SOUND PRESSURE LEVEL dBA 48 49

HEIGHT mm/in 550 / 21.7 550 / 21.7

UNIT DIMENSION WIDTH mm/in 765 / 30.1 765 / 30.1


OUTDOOR UNIT

DEPTH mm/in 285 / 11.2 285 / 11.2

HEIGHT mm/in 610 / 24.0 610 / 24.0

PACKING DIMENSION WIDTH mm/in 895 / 35.2 895 / 35.2

DEPTH mm/in 360 / 14.2 360 / 14.2

UNIT WEIGHT kg/lb 31 / 68.4 33 / 72.8

TYPE FLARE VALVE FLARE VALVE

PIPE CONNECTION LIQUID mm/in 6.4 / 1/4 6.4 / 1/4


SIZE
GAS mm/in 9.5 / 3/8 12.7 / 1/2

REFRIGERANT CHARGE kg/lb 0.75 / 1.65 1.10 / 2.43

1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151.
3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW :
a) COOLING - 27°C DB / 19°C WB INDOOR AND 35°C DB / 24°C WB OUTDOOR
b) HEATING - 20°C DB INDOOR AND 7°C DB / 6°C WB OUTDOOR
4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS B 8615 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND 1m
BELOW THE UNIT.

40
Engineering & Physical Data A5LCY-I-2010

General Data - Heat pump


OUTDOOR UNIT A5LCY 20CR A5LCY 25CR
MODEL
INDOOR UNIT A5WMY 20JR A5WMY 25JR

Btu/h 18600 (6415 - 21155) 21200 (6824 - 22178)


NOMINAL COOLING CAPACITY
W 5450 (1880 - 6200) 6210 (2000 - 6500)

Btu/h 19176 (4504 - 22520) 21837 (5323 - 24226)


NOMINAL HEATING CAPACITY
W 5620 (1320 - 6600) 6400 (1560 - 7100)

NOMINAL TOTAL INPUT POWER (COOLING) W 1460 1880

NOMINAL RUNNING CURRENT (COOLING) A 6.53 8.45

NOMINAL TOTAL INPUT POWER (HEATING) W 1500 1710

NOMINAL RUNNING CURRENT (HEATING) A 6.72 7.63

POWER SOURCE V/Ph/Hz 220 - 240 / 1 / 50 220 - 240 / 1 / 50

EER W/W 3.73 3.30

COP W/W 3.75 3.74

REFRIGERANT TYPE R410A R410A

REFRIGERANT CONTROL (EXPANSION DEVICE) OUTDOOR EXV OUTDOOR EXV


4 WAY AUTOMATIC LOUVER 4 WAY AUTOMATIC LOUVER
AIR DISCHARGE
CONTROL (UP & DOWN) (UP & DOWN)
OPERATION WIRELESS REMOTE CONTROL WIRELESS REMOTE CONTROL

HIGH l/s / CFM 250 / 529 309 / 654

AIR FLOW MEDIUM l/s / CFM 222 / 471 276 / 585

LOW l/s / CFM 197 / 418 239 / 507


INDOOR UNIT

SOUND PRESSURE LEVEL (H/M/L) dBA 41 / 39 / 35 44 / 41 / 37

HEIGHT mm/in 310 / 12.2 310 / 12.2

UNIT DIMENSION WIDTH mm/in 1065 / 42.0 1065 / 42.0

DEPTH mm/in 224 / 8.8 224 / 8.8

HEIGHT mm/in 386 / 15.2 386 / 15.2

PACKING DIMENSION WIDTH mm/in 1136 / 44.7 1136 / 44.7

DEPTH mm/in 285 / 11.2 285 / 11.2

UNIT WEIGHT kg/lb 6.3 / 14 6.3 / 14

CONDENSATE DRAIN SIZE mm/in 19.1 / 0.75 19.1 / 0.75

AIR FLOW l/s / CFM 869 / 1842 869 / 1842

SOUND PRESSURE LEVEL dBA 51 51

HEIGHT mm/in 753 / 29.7 753 / 29.7

UNIT DIMENSION WIDTH mm/in 922 / 36.3 922 / 36.3


OUTDOOR UNIT

DEPTH mm/in 392 / 15.4 392 / 15.4

HEIGHT mm/in 793 / 31.2 793 / 31.2

PACKING DIMENSION WIDTH mm/in 990 / 39.0 990 / 39.0

DEPTH mm/in 415 / 16.3 415 / 16.3

UNIT WEIGHT kg/lb 49 / 107.8 49 / 107.8

TYPE FLARE VALVE FLARE VALVE

PIPE CONNECTION LIQUID mm/in 6.4 / 1/4 6.4 / 1/4


SIZE
GAS mm/in 12.7 / 1/2 15.9 / 5/8

REFRIGERANT CHARGE kg/lb 1.45 / 3.20 1.50 / 3.30

1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151.
3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW :
a) COOLING - 27°C DB / 19°C WB INDOOR AND 35°C DB / 24°C WB OUTDOOR
b) HEATING - 20°C DB INDOOR AND 7°C DB / 6°C WB OUTDOOR
4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS B 8615 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND 1m
BELOW THE UNIT.

41
A5LCY-I-2010 Engineering & Physical Data

General Data - Heat pump


OUTDOOR UNIT A5LCY 10DR A5LCY 15DR
MODEL
INDOOR UNIT A5CKY 10CR A5CKY 15CR

Btu/h 9792 (4026 - 11942) 12385 (5254 - 13306)


NOMINAL COOLING CAPACITY
W 2870 (1180 - 3500) 3630 (1540 - 3900)

Btu/h 10884 (3753 - 13989) 13239 (3650 - 15865)


NOMINAL HEATING CAPACITY
W 3190 (1100 - 4100) 3880 (1070 - 4650)

NOMINAL TOTAL INPUT POWER (COOLING) W 780 1006

NOMINAL RUNNING CURRENT (COOLING) A 4.26 4.70

NOMINAL TOTAL INPUT POWER (HEATING) W 792 1024

NOMINAL RUNNING CURRENT (HEATING) A 4.01 4.90

POWER SOURCE V/Ph/Hz 220 - 240 / 1 / 50 220 - 240 / 1 / 50

EER W/W 3.68 3.61

COP W/W 4.03 3.79

REFRIGERANT TYPE R410A R410A

REFRIGERANT CONTROL (EXPANSION DEVICE) OUTDOOR EXV OUTDOOR EXV


4 WAY AUTOMATIC LOUVER 4 WAY AUTOMATIC LOUVER
AIR DISCHARGE
(UP & DOWN) (UP & DOWN)
CONTROL
WIRELESS OR WIRED REMOTE WIRELESS OR WIRED REMOTE
OPERATION
CONTROL CONTROL
HIGH l/s / CFM 193 / 400 193 / 410

AIR FLOW MEDIUM l/s / CFM 184 / 390 184 / 390

LOW l/s / CFM 170 / 360 170 / 360


INDOOR UNIT

SOUND PRESSURE LEVEL (H/M/L) dBA 44 / 43 / 42 44 / 42 / 41

HEIGHT mm/in 250 (295) / 9.8 (11.6) 250 (295) / 9.8 (11.6)
UNIT DIMENSION
WIDTH mm/in 570 (640) / 22.4 (25.2) 570 (640) / 22.4 (25.2)
(WITH PANEL)
DEPTH mm/in 570 (640) / 22.4 (25.2) 570 (640) / 22.4 (25.2)

HEIGHT mm/in 317 (127) / 12.5 (5.0) 317 (127) / 12.5 (5.0)
PACKING DIMENSION
WIDTH mm/in 630 (700) / 24.8 (27.6) 630 (700) / 24.8 (27.6)
(WITH PANEL)
DEPTH mm/in 630 (700) / 24.8 (27.6) 630 (700) / 24.8 (27.6)

UNIT WEIGHT (UNIT + PANEL) kg/lb 22 + 2.0 / 49 + 4.0 23 + 2.0 / 51 + 4.0

CONDENSATE DRAIN SIZE mm/in 19.1 / 0.75 19.1 / 0.75

AIR FLOW l/s / CFM 521 / 1100 473 / 1000

SOUND PRESSURE LEVEL dBA 46 49

HEIGHT mm/in 550 / 21.7 550 / 21.7

UNIT DIMENSION WIDTH mm/in 765 / 30.1 765 / 30.1


OUTDOOR UNIT

DEPTH mm/in 285 / 11.2 285 / 11.2

HEIGHT mm/in 610 / 24.0 610 / 24.0

PACKING DIMENSION WIDTH mm/in 895 / 35.2 895 / 35.2

DEPTH mm/in 360 / 14.2 360 / 14.2

UNIT WEIGHT kg/lb 31 / 68.4 33 / 72.8

TYPE FLARE VALVE FLARE VALVE

PIPE CONNECTION LIQUID mm/in 6.4 / 1/4 6.4 / 1/4


SIZE
GAS mm/in 9.5 / 3/8 12.7 / 1/2

REFRIGERANT CHARGE kg/lb 0.75 / 1.65 1.10 / 2.43

1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151.
3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW :
a) COOLING - 27°C DB / 19°C WB INDOOR AND 35°C DB / 24°C WB OUTDOOR
b) HEATING - 20°C DB INDOOR AND 7°C DB / 6°C WB OUTDOOR
4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS B 8615 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND 1m
BELOW THE UNIT.

42
Engineering & Physical Data A5LCY-I-2010

General Data - Heat pump


OUTDOOR UNIT A5LCY 20CR
MODEL
INDOOR UNIT A5CKY 20CR

Btu/h 18118 (6346 - 20643)


NOMINAL COOLING CAPACITY
W 5310 (1860 - 6050)

Btu/h 19039 (5050 - 19517)


NOMINAL HEATING CAPACITY
W 5580 (1480 - 5720)

NOMINAL TOTAL INPUT POWER (COOLING) W 1654

NOMINAL RUNNING CURRENT (COOLING) A 7.26

NOMINAL TOTAL INPUT POWER (HEATING) W 1701

NOMINAL RUNNING CURRENT (HEATING) A 7.78

POWER SOURCE V/Ph/Hz 220 - 240 / 1 / 50

EER W/W 3.21

COP W/W 3.28

REFRIGERANT TYPE R410A

REFRIGERANT CONTROL (EXPANSION DEVICE) OUTDOOR EXV


4 WAY AUTOMATIC LOUVER
AIR DISCHARGE
(UP & DOWN)
CONTROL
WIRELESS OR WIRED REMOTE
OPERATION
CONTROL
HIGH l/s / CFM 212 / 450

AIR FLOW MEDIUM l/s / CFM 203 / 430

LOW l/s / CFM 193 / 410


INDOOR UNIT

SOUND PRESSURE LEVEL (H/M/L) dBA 47 / 46 / 44

HEIGHT mm/in 250 (295) / 9.8 (11.6)


UNIT DIMENSION
WIDTH mm/in 570 (640) / 22.4 (25.2)
(WITH PANEL)
DEPTH mm/in 570 (640) / 22.4 (25.2)

HEIGHT mm/in 317 (127) / 12.5 (5.0)


PACKING DIMENSION
WIDTH mm/in 630 (700) / 24.8 (27.6)
(WITH PANEL)
DEPTH mm/in 630 (700) / 24.8 (27.6)

UNIT WEIGHT (UNIT + PANEL) kg/lb 23 + 2.0 / 51 + 4.0

CONDENSATE DRAIN SIZE mm/in 19.1 / 0.75

AIR FLOW l/s / CFM 869 / 1842

SOUND PRESSURE LEVEL dBA 51

HEIGHT mm/in 753 / 29.7

UNIT DIMENSION WIDTH mm/in 922 / 36.3


OUTDOOR UNIT

DEPTH mm/in 392 / 15.4

HEIGHT mm/in 793 / 31.2

PACKING DIMENSION WIDTH mm/in 990 / 39.0

DEPTH mm/in 415 / 16.3

UNIT WEIGHT kg/lb 49 / 107.8

TYPE FLARE VALVE

PIPE CONNECTION LIQUID mm/in 6.4 / 1/4


SIZE
GAS mm/in 12.7 / 1/2

REFRIGERANT CHARGE kg/lb 1.45 / 3.20

1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151.
3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW :
a) COOLING - 27°C DB / 19°C WB INDOOR AND 35°C DB / 24°C WB OUTDOOR
b) HEATING - 20°C DB INDOOR AND 7°C DB / 6°C WB OUTDOOR
4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS B 8615 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND 1m
BELOW THE UNIT.

43
A5LCY-I-2010 Engineering & Physical Data

General Data - Heat pump


OUTDOOR UNIT A5LCY 20CR A5LCY 25CR
MODEL
INDOOR UNIT A5CKY 20ER A5CKY 25ER

Btu/h 18459 (5220 - 20608) 21564 (2081 - 21564)


NOMINAL COOLING CAPACITY
W 5410 (1530 - 6040) 6320 (610 - 6320)

Btu/h 18868 (5323 - 20574) 22212 (5357 - 24873)


NOMINAL HEATING CAPACITY
W 5530 (1560 - 6030) 6510 (1570 - 7290)

NOMINAL TOTAL INPUT POWER (COOLING) W 1587 1945

NOMINAL RUNNING CURRENT (COOLING) A 7.37 8.89

NOMINAL TOTAL INPUT POWER (HEATING) W 1495 1632

NOMINAL RUNNING CURRENT (HEATING) A 6.96 7.53

POWER SOURCE V/Ph/Hz 220 - 240 / 1 / 50 220 - 240 / 1 / 50

EER W/W 3.41 3.25

COP W/W 3.70 3.99

REFRIGERANT TYPE R410A R410A

REFRIGERANT CONTROL (EXPANSION DEVICE) OUTDOOR EXV OUTDOOR EXV


4 WAY AUTOMATIC LOUVER 4 WAY AUTOMATIC LOUVER
AIR DISCHARGE
(UP & DOWN) (UP & DOWN)
CONTROL
WIRELESS OR WIRED REMOTE WIRELESS OR WIRED REMOTE
OPERATION
CONTROL CONTROL
HIGH l/s / CFM 283 / 600 321 / 680

AIR FLOW MEDIUM l/s / CFM 250 / 530 283 / 600

LOW l/s / CFM 203 / 430 250 / 530


INDOOR UNIT

SOUND PRESSURE LEVEL (H/M/L) dBA 34 / 31 / 28 37 / 34 / 31

HEIGHT mm/in 265 (340) / 10.4 (13.4) 265 (340) / 10.4 (13.4)
UNIT DIMENSION
WIDTH mm/in 820 (990) / 32.3 (39.0) 820 (990) / 32.3 (39.0)
(WITH PANEL)
DEPTH mm/in 820 (990) / 32.3 (39.0) 820 (990) / 32.3 (39.0)

HEIGHT mm/in 335 (410) / 13.2 (16.1) 335 (410) / 13.2 (16.1)
PACKING DIMENSION
WIDTH mm/in 900 (1070) / 35.4 (42.1) 900 (1070) / 35.4 (42.1)
(WITH PANEL)
DEPTH mm/in 900 (1070) / 35.4 (42.1) 900 (1070) / 35.4 (42.1)

UNIT WEIGHT (UNIT + PANEL) kg/lb 29 + 6.0 / 64 + 13.2 29 + 6.0 / 64 + 13.2

CONDENSATE DRAIN SIZE mm/in 19.1 / 0.75 19.1 / 0.75

AIR FLOW l/s / CFM 869 / 1842 869 / 1842

SOUND PRESSURE LEVEL dBA 51 51

HEIGHT mm/in 753 / 29.7 753 / 29.7

UNIT DIMENSION WIDTH mm/in 922 / 36.3 922 / 36.3


OUTDOOR UNIT

DEPTH mm/in 392 / 15.4 392 / 15.4

HEIGHT mm/in 793 / 31.2 793 / 31.2

PACKING DIMENSION WIDTH mm/in 990 / 39.0 990 / 39.0

DEPTH mm/in 415 / 16.3 415 / 16.3

UNIT WEIGHT kg/lb 49 / 107.8 49 / 107.8

TYPE FLARE VALVE FLARE VALVE

PIPE CONNECTION LIQUID mm/in 6.4 / 1/4 6.4 / 1/4


SIZE
GAS mm/in 12.7 / 1/2 15.9 / 5/8

REFRIGERANT CHARGE kg/lb 1.45 / 3.20 1.50 / 3.30

1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151.
3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW :
a) COOLING - 27°C DB / 19°C WB INDOOR AND 35°C DB / 24°C WB OUTDOOR
b) HEATING - 20°C DB INDOOR AND 7°C DB / 6°C WB OUTDOOR
4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS B 8615 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND 1m
BELOW THE UNIT.

44
Engineering & Physical Data A5LCY-I-2010

General Data - Heat pump


OUTDOOR UNIT A5LCY 10DR A5LCY 15DR
MODEL
INDOOR UNIT A5CCY 10CR A5CCY 15CR

Btu/h 8769 (4504 - 11361) 12522 (5050 - 12829)


NOMINAL COOLING CAPACITY
W 2570 (1320 - 3330) 3670 (1480 - 3760)

Btu/h 9451 (2389 - 12897) 12624 (3719 - 14671)


NOMINAL HEATING CAPACITY
W 2770 (700 - 3780) 3700 (1090 - 4300)

NOMINAL TOTAL INPUT POWER (COOLING) W 791 1089

NOMINAL RUNNING CURRENT (COOLING) A 4.43 4.91

NOMINAL TOTAL INPUT POWER (HEATING) W 812 1066

NOMINAL RUNNING CURRENT (HEATING) A 4.29 4.80

POWER SOURCE V/Ph/Hz 220 - 240 / 1 / 50 220 - 240 / 1 / 50

EER W/W 3.25 3.37

COP W/W 3.41 3.47

REFRIGERANT TYPE R410A R410A

REFRIGERANT CONTROL (EXPANSION DEVICE) OUTDOOR EXV OUTDOOR EXV

AIR DISCHARGE DUCTED DUCTED


CONTROL WIRELESS OR WIRED REMOTE WIRELESS OR WIRED REMOTE
OPERATION
CONTROL CONTROL
HIGH l/s / CFM 172 / 365 194 / 410

AIR FLOW MEDIUM l/s / CFM 160 / 340 175 / 370

LOW l/s / CFM 137 / 290 118 / 250

EXTERNAL STATIC PRESSURE (H/M/L) Pa / mmAq 29 / 25 / 19 (0.12 / 0.10 / 0.08) 29 / 20 / 10 (0.12 / 0.08 / 0.04)
INDOOR UNIT

SOUND PRESSURE LEVEL (H/M/L) dBA 35 / 32 / 26 37 / 34 / 29

HEIGHT mm/in 261 / 10.3 261 / 10.3

UNIT DIMENSION WIDTH mm/in 765 / 30.1 765 / 30.1

DEPTH mm/in 411 / 16.2 411 / 16.2

HEIGHT mm/in 376 / 14.8 376 / 14.8

PACKING DIMENSION WIDTH mm/in 1091 / 43.0 1091 / 43.0

DEPTH mm/in 541 / 21.3 541 / 21.3

UNIT WEIGHT kg/lb 21 / 9.5 21 / 9.5

CONDENSATE DRAIN SIZE mm/in 19.1 / 0.75 19.1 / 0.75

AIR FLOW l/s / CFM 521 / 1100 473 / 1000

SOUND PRESSURE LEVEL dBA 48 49

HEIGHT mm/in 550 / 21.7 550 / 21.7

UNIT DIMENSION WIDTH mm/in 765 / 30.1 765 / 30.1


OUTDOOR UNIT

DEPTH mm/in 285 / 11.2 285 / 11.2

HEIGHT mm/in 610 / 24.0 610 / 24.0

PACKING DIMENSION WIDTH mm/in 895 / 35.2 895 / 35.2

DEPTH mm/in 360 / 14.2 360 / 14.2

UNIT WEIGHT kg/lb 31 / 68.4 33 / 72.8

TYPE FLARE VALVE FLARE VALVE

PIPE CONNECTION LIQUID mm/in 6.4 / 1/4 6.4 / 1/4


SIZE
GAS mm/in 9.5 / 3/8 12.7 / 1/2

REFRIGERANT CHARGE kg/lb 0.75 / 1.65 1.10 / 2.43

1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151.
3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW :
a) COOLING - 27°C DB / 19°C WB INDOOR AND 35°C DB / 24°C WB OUTDOOR
b) HEATING - 20°C DB INDOOR AND 7°C DB / 6°C WB OUTDOOR
4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS B 8615 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND 1m
BELOW THE UNIT.

45
A5LCY-I-2010 Engineering & Physical Data

General Data - Heat pump


OUTDOOR UNIT A5LCY 20CR A5LCY 25CR
MODEL
INDOOR UNIT A5CCY 20CR A5CCY 25CR

Btu/h 17742 (6892 - 20472) 20643 (6346 - 20643)


NOMINAL COOLING CAPACITY
W 5200 (2020 - 6000) 6050 (1860 - 6050)

Btu/h 19687 (5391 - 22895) 21873 (5357 - 22758)


NOMINAL HEATING CAPACITY
W 5770 (1580 - 6710) 6400 (1570 - 6670)

NOMINAL TOTAL INPUT POWER (COOLING) W 1604 1917

NOMINAL RUNNING CURRENT (COOLING) A 7.34 8.90

NOMINAL TOTAL INPUT POWER (HEATING) W 1694 1775

NOMINAL RUNNING CURRENT (HEATING) A 7.74 8.11

POWER SOURCE V/Ph/Hz 220 - 240 / 1 / 50 220 - 240 / 1 / 50

EER W/W 3.24 3.21

COP W/W 3.41 3.66

REFRIGERANT TYPE R410A R410A

REFRIGERANT CONTROL (EXPANSION DEVICE) OUTDOOR EXV OUTDOOR EXV

AIR DISCHARGE DUCTED DUCTED


CONTROL WIRELESS OR WIRED REMOTE WIRELESS OR WIRED REMOTE
OPERATION
CONTROL CONTROL
HIGH l/s / CFM 269 / 570 326 / 690

AIR FLOW MEDIUM l/s / CFM 255 / 540 302 / 640

LOW l/s / CFM 213 / 450 245 / 520

EXTERNAL STATIC PRESSURE (H/M/L) Pa / (in.wq) 29 / 20 / 10 (0.12 / 0.08 / 0.04) 29 / 20 / 10 (0.12 / 0.08 / 0.04)
INDOOR UNIT

SOUND PRESSURE LEVEL (H/M/L) dBA 38 / 36 / 34 40 / 39 / 36

HEIGHT mm/in 261 / 10.3 261 / 10.3

UNIT DIMENSION WIDTH mm/in 1065 / 41.9 1200 / 47.2

DEPTH mm/in 411 / 16.2 411 / 16.2

HEIGHT mm/in 376 / 14.8 376 / 14.8

PACKING DIMENSION WIDTH mm/in 1251 / 49.3 1386 / 54.6

DEPTH mm/in 541 / 21.3 541 / 21.3

UNIT WEIGHT kg/lb 9.5 / 21 11.3 / 25

CONDENSATE DRAIN SIZE mm/in 19.1 / 0.75 19.1 / 0.75

AIR FLOW l/s / CFM 869 / 1842 869 / 1842

SOUND PRESSURE LEVEL dBA 51 51

HEIGHT mm/in 753 / 29.7 753 / 29.7

UNIT DIMENSION WIDTH mm/in 922 / 36.3 922 / 36.3


OUTDOOR UNIT

DEPTH mm/in 392 / 15.4 392 / 15.4

HEIGHT mm/in 793 / 31.2 793 / 31.2

PACKING DIMENSION WIDTH mm/in 990 / 39.0 990 / 39.0

DEPTH mm/in 415 / 16.3 415 / 16.3

UNIT WEIGHT kg/lb 49 / 107.8 49 / 107.8

TYPE FLARE VALVE FLARE VALVE

PIPE CONNECTION LIQUID mm/in 6.4 / 1/4 6.4 / 1/4


SIZE
GAS mm/in 12.7 / 1/2 15.9 / 5/8

REFRIGERANT CHARGE kg/lb 1.45 / 3.20 1.50 / 3.30

1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151.
3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW :
a) COOLING - 27°C DB / 19°C WB INDOOR AND 35°C DB / 24°C WB OUTDOOR
b) HEATING - 20°C DB INDOOR AND 7°C DB / 6°C WB OUTDOOR
4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS B 8615 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND 1m
BELOW THE UNIT.

46
Engineering & Physical Data A5LCY-I-2010

General Data - Heat pump


OUTDOOR UNIT A5LCY 15DR A5LCY 20CR
MODEL
INDOOR UNIT A5CMY 15ER A5CMY 20ER

Btu/h 12249 (5936 - 14671) 18322 (5527 - 20199)


NOMINAL COOLING CAPACITY
W 3590 (1740 - 4300) 5370 (1620 - 5920)

Btu/h 13170 (3650 - 16991) 19039 (5220 - 20199)


NOMINAL HEATING CAPACITY
W 3860 (1070 - 4980) 5580 (1530 - 5920)

NOMINAL TOTAL INPUT POWER (COOLING) W 928 1683

NOMINAL RUNNING CURRENT (COOLING) A 4.55 7.75

NOMINAL TOTAL INPUT POWER (HEATING) W 972 1617

NOMINAL RUNNING CURRENT (HEATING) A 4.68 7.45

POWER SOURCE V/Ph/Hz 220 - 240 / 1 / 50 220 - 240 / 1 / 50

EER W/W 3.87 3.19

COP W/W 3.97 3.45

REFRIGERANT TYPE R410A R410A

REFRIGERANT CONTROL (EXPANSION DEVICE) OUTDOOR EXV OUTDOOR EXV


AUTOMATIC LOUVER AUTOMATIC LOUVER
AIR DISCHARGE
(UP & DOWN) (UP & DOWN)
CONTROL
WIRELESS OR WIRED REMOTE WIRELESS OR WIRED REMOTE
OPERATION
CONTROL CONTROL
HIGH l/s / CFM 240 / 508 245 / 520

AIR FLOW MEDIUM l/s / CFM 182 / 386 217 / 460

LOW l/s / CFM 165 / 350 192 / 406


INDOOR UNIT

SOUND PRESSURE LEVEL (H/M/L) dBA 48 / 43 / 41 50 / 43 / 41

HEIGHT mm/in 218 / 8.6 218 / 8.6

UNIT DIMENSION WIDTH mm/in 1080 / 42.5 1080 / 42.5

DEPTH mm/in 630 / 24.8 630 / 24.8

HEIGHT mm/in 297 / 11.7 297 / 11.7

PACKING DIMENSION WIDTH mm/in 1197 / 47.1 1197 / 47.1

DEPTH mm/in 740 / 29.1 740 / 29.1

UNIT WEIGHT kg/lb 25 / 55.1 27 / 59.5

CONDENSATE DRAIN SIZE mm/in 19.1 / 0.75 19.1 / 0.75

AIR FLOW l/s / CFM 473 / 1000 869 / 1842

SOUND PRESSURE LEVEL dBA 49 51

HEIGHT mm/in 550 / 21.7 753 / 29.7

UNIT DIMENSION WIDTH mm/in 765 / 30.1 922 / 36.3


OUTDOOR UNIT

DEPTH mm/in 285 / 11.2 392 / 15.4

HEIGHT mm/in 610 / 24.0 793 / 31.2

PACKING DIMENSION WIDTH mm/in 895 / 35.2 990 / 39.0

DEPTH mm/in 360 / 14.2 415 / 16.3

UNIT WEIGHT kg/lb 33 / 72.8 49 / 107.8

TYPE FLARE VALVE FLARE VALVE

PIPE CONNECTION LIQUID mm/in 6.4 / 1/4 6.4 / 1/4


SIZE
GAS mm/in 12.7 / 1/2 12.7 / 1/2

REFRIGERANT CHARGE kg/lb 1.10 / 2.43 1.45 / 3.20

1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151.
3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW :
a) COOLING - 27°C DB / 19°C WB INDOOR AND 35°C DB / 24°C WB OUTDOOR
b) HEATING - 20°C DB INDOOR AND 7°C DB / 6°C WB OUTDOOR
4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS B 8615 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND 1m
BELOW THE UNIT.

47
A5LCY-I-2010 Engineering & Physical Data

General Data - Heat pump


OUTDOOR UNIT A5LCY 25DR
MODEL
INDOOR UNIT A5CMY 25ER

Btu/h 20608 (5323 - 21291)


NOMINAL COOLING CAPACITY
W 6040 (1560 - 6240)

Btu/h 21086 (5596 - 21700)


NOMINAL HEATING CAPACITY
W 6180 (164 - 6360)

NOMINAL TOTAL INPUT POWER (COOLING) W 2007

NOMINAL RUNNING CURRENT (COOLING) A 9.23

NOMINAL TOTAL INPUT POWER (HEATING) W 1873

NOMINAL RUNNING CURRENT (HEATING) A 8.52

POWER SOURCE V/Ph/Hz 220 - 240 / 1 / 50

EER W/W 3.01

COP W/W 3.30

REFRIGERANT TYPE R410A

REFRIGERANT CONTROL (EXPANSION DEVICE) OUTDOOR EXV


AUTOMATIC LOUVER
AIR DISCHARGE
(UP & DOWN)
CONTROL
WIRELESS OR WIRED REMOTE
OPERATION
CONTROL
HIGH l/s / CFM 274 / 580

AIR FLOW MEDIUM l/s / CFM 250 / 530

LOW l/s / CFM 231 / 490


INDOOR UNIT

SOUND PRESSURE LEVEL (H/M/L) dBA 53 / 51 / 49

HEIGHT mm/in 218 / 8.6

UNIT DIMENSION WIDTH mm/in 1080 / 42.5

DEPTH mm/in 630 / 24.8

HEIGHT mm/in 297 / 11.7

PACKING DIMENSION WIDTH mm/in 1197 / 47.1

DEPTH mm/in 740 / 29.1

UNIT WEIGHT kg/lb 27 / 59.5

CONDENSATE DRAIN SIZE mm/in 19.1 / 0.75

AIR FLOW l/s / CFM 869 / 1842

SOUND PRESSURE LEVEL dBA 51

HEIGHT mm/in 753 / 29.7

UNIT DIMENSION WIDTH mm/in 922 / 36.3


OUTDOOR UNIT

DEPTH mm/in 392 / 15.4

HEIGHT mm/in 793 / 31.2

PACKING DIMENSION WIDTH mm/in 990 / 39.0

DEPTH mm/in 415 / 16.3

UNIT WEIGHT kg/lb 49 / 107.8

TYPE FLARE VALVE

PIPE CONNECTION LIQUID mm/in 6.4 / 1/4


SIZE
GAS mm/in 15.9 / 5/8

REFRIGERANT CHARGE kg/lb 1.50 / 3.30

1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151.
3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW :
a) COOLING - 27°C DB / 19°C WB INDOOR AND 35°C DB / 24°C WB OUTDOOR
b) HEATING - 20°C DB INDOOR AND 7°C DB / 6°C WB OUTDOOR
4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS B 8615 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND 1m
BELOW THE UNIT.

48
Engineering & Physical Data A5LCY-I-2010

Component Data - Heat Pump


OUTDOOR UNIT A5LCY 10DR A5LCY 15DR
MODEL
INDOOR UNIT A5WMY 10JR A5WMY 15JR
TYPE CROSS FLOW FAN CROSS FLOW FAN
QUANTITY 1 1

GLASS REINFORCED ACRYL GLASS REINFORCED ACRYL


MATERIAL
INDOOR FAN STYRENE RESIN STYRENE RESIN

DRIVE DIRECT DIRECT


DIAMETER mm/in 92 / 3.6 92 / 3.6
LENGTH mm/in 607 / 23.9 607 / 23.9
TYPE INDUCTION INDUCTION
INDOOR FAN MOTOR QUANTITY 1 1
INDEX OF PROTECTION (IP) IP44 IP44
TYPE PROPELLER PROPELLER
QUANTITY 1 1

GLASS REINFORCED GLASS REINFORCED


OUTDOOR FAN MATERIAL
POLYPROPYLENE RESIN POLYPROPYLENE RESIN

DRIVE DIRECT DIRECT


DIAMETER mm/in 400 / 15.7 400 / 15.7
TYPE INDUCTION INDUCTION
OUTDOOR FAN
QUANTITY 1 1
MOTOR
INDEX OF PROTECTION (IP) IP24 IP24
TYPE ROTARY ROTARY
COMPRESSOR OIL TYPE RB68A or FREOL ALPHA68M RB68A or FREOL ALPHA68M
OIL AMOUNT cm3 / fl.oz. 320 / 11.3 320 / 11.3

SEAMLESS INNER GROOVE SEAMLESS INNER GROOVE


MATERIAL
COPPER COPPER
TUBE
DIAMETER mm/in 7.00 / 0.276 7.00 / 0.276
THICKNESS mm/in 0.28 / 0.011 0.28 / 0.011

INDOOR COIL MATERIAL ALUMINIUM (HYDROPHILIC FIN) ALUMINIUM (HYDROPHILIC FIN)


THICKNESS mm/in 0.10 / 0.004 0.10 / 0.004
FIN FACE AREA m2/ft2 0.18 / 1.937 0.18 / 1.937
ROW 2 2
FIN PER INCH 18 18

SEAMLESS INNER GROOVE SEAMLESS INNER GROOVE


MATERIAL
COPPER COPPER
TUBE
DIAMETER mm/in 7.00 / 0.276 7.00 / 0.276
THICKNESS mm/in 0.24 / 0.009 0.24 / 0.009

OUTDOOR COIL MATERIAL ALUMINIUM (CORR.) ALUMINIUM (CORR.)


THICKNESS mm/in 0.10 / 0.004 0.10 / 0.004
FIN FACE AREA m2/ft2 0.42 / 4.520 0.40 / 4.304
ROW 1 2
FIN PER INCH 18 18
TYPE WASHABLE SARANET FILTER WASHABLE SARANET FILTER
AIR QUALITY FILTER
QUANTITY pc 2 2
MATERIAL HIGH IMPACT POLYSTYRENE HIGH IMPACT POLYSTYRENE
INDOOR UNIT FINISHING MAT MAT
COLOUR WHITE WHITE
CASING
MATERIAL GALVANISED MILD STEEL GALVANISED MILD STEEL
OUTDOOR UNIT FINISHING POLYESTER POWDER POLYESTER POWDER
COLOUR LIGHT GREY LIGHT GREY

1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.

49
A5LCY-I-2010 Engineering & Physical Data

Component Data - Heat Pump


OUTDOOR UNIT A5LCY 20CR A5LCY 25CR
MODEL
INDOOR UNIT A5WMY 20JR A5WMY 25JR
TYPE CROSS FLOW FAN CROSS FLOW FAN
QUANTITY 1 1
MATERIAL RESIN ASG RESIN ASG
INDOOR FAN
DRIVE DIRECT DIRECT
DIAMETER mm/in 102 / 4.0 102 / 4.0
LENGTH mm/in 867 / 34.1 867 / 34.1
TYPE INDUCTION INDUCTION
INDOOR FAN MOTOR QUANTITY 1 1
INDEX OF PROTECTION (IP) IP20 IP20
TYPE PROPELLER PROPELLER
QUANTITY 1 1
OUTDOOR FAN MATERIAL MRP421L2BC MRP421L2BC
DRIVE DIRECT DIRECT
DIAMETER mm/in 455 / 17.9 455 / 17.9
TYPE INDUCTION INDUCTION
OUTDOOR FAN
QUANTITY 1 1
MOTOR
INDEX OF PROTECTION (IP) IP34 IP34
TYPE ROTARY SWING ROTARY SWING
COMPRESSOR OIL TYPE ETHER ETHER
OIL AMOUNT cm3 / fl.oz. N/A N/A

SEAMLESS INNER GROOVE SEAMLESS INNER GROOVE


MATERIAL
COPPER COPPER
TUBE
DIAMETER mm/in 7.00 / 0.276 7.00 / 0.276
THICKNESS mm/in 0.24 / 0.009 0.24 / 0.009

INDOOR COIL MATERIAL ALUMINIUM (HYDROPHILIC FIN) ALUMINIUM (HYDROPHILIC FIN)


THICKNESS mm/in 0.11 / 0.004 0.11 / 0.004
FIN FACE AREA m /ft
2 2
0.29 / 3.10 0.29 / 3.10
ROW 2 2
FIN PER INCH 18 18

SEAMLESS INNER GROOVE SEAMLESS INNER GROOVE


MATERIAL
COPPER COPPER
TUBE
DIAMETER mm/in 7.00 / 0.276 7.00 / 0.276
THICKNESS mm/in 0.24 / 0.009 0.24 / 0.009

OUTDOOR COIL MATERIAL ALUMINIUM (CORR.) ALUMINIUM (CORR.)


THICKNESS mm/in 0.10 / 0.004 0.10 / 0.004
FIN FACE AREA m2/ft2 0.62 / 6.64 0.62 / 6.64
ROW 2 2
FIN PER INCH 20 20
TYPE WASHABLE SARANET FILTER WASHABLE SARANET FILTER
AIR QUALITY FILTER
QUANTITY pc 2 2
MATERIAL HIGH IMPACT POLYSTYRENE HIGH IMPACT POLYSTYRENE
INDOOR UNIT FINISHING ETCHING ETCHING
COLOUR WHITE WHITE
CASING
MATERIAL GALVANISED MILD STEEL GALVANISED MILD STEEL
OUTDOOR UNIT FINISHING POLYESTER POWDER POLYESTER POWDER
COLOUR LIGHT GREY LIGHT GREY

1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.

50
Engineering & Physical Data A5LCY-I-2010

Component Data - Heat Pump


OUTDOOR UNIT A5LCY 10DR A5LCY 15DR
MODEL
INDOOR UNIT A5CKY 10CR A5CKY 15CR
TYPE TURBO TURBO
QUANTITY 1 1
MATERIAL ABSG20 ABSG20
INDOOR FAN
DRIVE DIRECT DIRECT
DIAMETER mm/in 315 / 12.4 315 / 12.4
LENGTH mm/in 163 / 6.4 163 / 6.4
TYPE INDUCTION INDUCTION
INDOOR FAN MOTOR QUANTITY 1 1
INDEX OF PROTECTION (IP) IP20 IP20
TYPE PROPELLER PROPELLER
QUANTITY 1 1

GLASS REINFORCED POLYPRO- GLASS REINFORCED POLYPRO-


OUTDOOR FAN MATERIAL
PYLENE RESIN PYLENE RESIN

DRIVE DIRECT DIRECT


DIAMETER mm/in 400 / 15.7 400 / 15.7
TYPE INDUCTION INDUCTION
OUTDOOR FAN
QUANTITY 1 1
MOTOR
INDEX OF PROTECTION (IP) IP24 IP24
TYPE ROTARY ROTARY
COMPRESSOR OIL TYPE RB68A or FREOL ALPHA68M RB68A or FREOL ALPHA68M
OIL AMOUNT cm3 / fl.oz. 320 / 11.3 320 / 11.3

SEAMLESS INNER GROOVE SEAMLESS INNER GROOVE


MATERIAL
COPPER COPPER
TUBE
DIAMETER mm/in 7.00 / 0.28 7.00 / 0.276
THICKNESS mm/in 0.24 / 0.009 0.24 / 0.009

INDOOR COIL MATERIAL ALUMINIUM (HYDROPHILIC FIN) ALUMINIUM (HYDROPHILIC FIN)


THICKNESS mm/in 0.105 / 0.004 0.105 / 0.004
FIN FACE AREA m2/ft2 0.25 / 2.73 0.25 / 2.73
ROW 2 2
FIN PER INCH 20 20

SEAMLESS INNER GROOVE SEAMLESS INNER GROOVE


MATERIAL
COPPER COPPER
TUBE
DIAMETER mm/in 7.00 / 0.276 7.00 / 0.276
THICKNESS mm/in 0.24 / 0.009 0.24 / 0.009

OUTDOOR COIL MATERIAL ALUMINIUM (CORR.) ALUMINIUM (CORR.)


THICKNESS mm/in 0.10 / 0.004 0.10 / 0.004
FIN FACE AREA m /ft
2 2
0.42 / 4.520 0.40 / 4.304
ROW 1 2
FIN PER INCH 18 18
TYPE WASHABLE SARANET FILTER WASHABLE SARANET FILTER
AIR QUALITY FILTER
QUANTITY pc 1 1
MATERIAL GALVANISED IRON GALVANISED IRON
INDOOR UNIT FINISHING WITH PE INSULATION WITH PE INSULATION
COLOUR GREY GREY
CASING
MATERIAL GALVANISED MILD STEEL GALVANISED MILD STEEL
OUTDOOR UNIT FINISHING POLYESTER POWDER POLYESTER POWDER
COLOUR LIGHT GREY LIGHT GREY

1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.

51
A5LCY-I-2010 Engineering & Physical Data

Component Data - Heat Pump


OUTDOOR UNIT A5LCY 20CR
MODEL
INDOOR UNIT A5CKY 20CR
TYPE TURBO
QUANTITY 1
MATERIAL ABSG20
INDOOR FAN
DRIVE DIRECT
DIAMETER mm/in 315 / 12.4
LENGTH mm/in 163 / 6.4
TYPE INDUCTION
INDOOR FAN MOTOR QUANTITY 1
INDEX OF PROTECTION (IP) IP20
TYPE PROPELLER
QUANTITY 1
OUTDOOR FAN MATERIAL MRP421L2BC
DRIVE DIRECT
DIAMETER mm/in 455 / 17.9
TYPE INDUCTION
OUTDOOR FAN
QUANTITY 1
MOTOR
INDEX OF PROTECTION (IP) IP34
TYPE ROTARY SWING
COMPRESSOR OIL TYPE ETHER
OIL AMOUNT cm3 / fl.oz. N/A

SEAMLESS INNER GROOVE


MATERIAL
COPPER
TUBE
DIAMETER mm/in 7.00 / 0.276
THICKNESS mm/in 0.24 / 0.009

INDOOR COIL MATERIAL ALUMINIUM (HYDROPHILIC FIN)


THICKNESS mm/in 0.11 / 0.004
FIN FACE AREA m /ft
2 2
0.25 / 2.73
ROW 2
FIN PER INCH 20

SEAMLESS INNER GROOVE


MATERIAL
COPPER
TUBE
DIAMETER mm/in 7.00 / 0.276
THICKNESS mm/in 0.24 / 0.009

OUTDOOR COIL MATERIAL ALUMINIUM (CORR.)


THICKNESS mm/in 0.10 / 0.004
FIN FACE AREA m2/ft2 0.62 / 6.64
ROW 2
FIN PER INCH 20
TYPE WASHABLE SARANET FILTER
AIR QUALITY FILTER
QUANTITY pc 1
MATERIAL GALVANISED IRON
INDOOR UNIT FINISHING WITH PE INSULATION
COLOUR GREY
CASING
MATERIAL GALVANISED MILD STEEL
OUTDOOR UNIT FINISHING POLYESTER POWDER
COLOUR LIGHT GREY

1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.

52
Engineering & Physical Data A5LCY-I-2010

Component Data - Heat Pump


OUTDOOR UNIT A5LCY 20CR A5LCY 25CR
MODEL
INDOOR UNIT A5CKY 20ER A5CKY 25ER
TYPE TURBO TURBO
QUANTITY 1 1
MATERIAL ASG 10% ASG 10%
INDOOR FAN
DRIVE DIRECT DIRECT
DIAMETER mm/in 486 / 19.1 486 / 19.1
LENGTH mm/in 172 / 6.8 172 / 6.8
TYPE INDUCTION INDUCTION
INDOOR FAN MOTOR QUANTITY 1 1
INDEX OF PROTECTION (IP) IP20 IP20
TYPE PROPELLER PROPELLER
QUANTITY 1 1
OUTDOOR FAN MATERIAL MRP421L2BC MRP421L2BC
DRIVE DIRECT DIRECT
DIAMETER mm/in 455 / 17.9 455 / 17.9
TYPE INDUCTION INDUCTION
OUTDOOR FAN
QUANTITY 1 1
MOTOR
INDEX OF PROTECTION (IP) IP34 IP34
TYPE ROTARY SWING ROTARY SWING
COMPRESSOR OIL TYPE ETHER ETHER
OIL AMOUNT cm3 / fl.oz. N/A N/A

SEAMLESS INNER GROOVE SEAMLESS INNER GROOVE


MATERIAL
COPPER COPPER
TUBE
DIAMETER mm/in 7.00 / 0.28 7.00 / 0.276
THICKNESS mm/in 0.24 / 0.009 0.24 / 0.009

INDOOR COIL MATERIAL ALUMINIUM (HYDROPHILIC FIN) ALUMINIUM (HYDROPHILIC FIN)


THICKNESS mm/in 0.10 / 0.004 0.10 / 0.004
FIN FACE AREA m /ft
2 2
0.39 / 4.15 0.39 / 4.15
ROW 2 2
FIN PER INCH 18 18

SEAMLESS INNER GROOVE SEAMLESS INNER GROOVE


MATERIAL
COPPER COPPER
TUBE
DIAMETER mm/in 7.00 / 0.276 7.00 / 0.276
THICKNESS mm/in 0.24 / 0.009 0.24 / 0.009

OUTDOOR COIL MATERIAL ALUMINIUM (CORR.) ALUMINIUM (CORR.)


THICKNESS mm/in 0.10 / 0.004 0.10 / 0.004
FIN FACE AREA m2/ft2 0.62 / 6.64 0.62 / 6.64
ROW 2 2
FIN PER INCH 20 20
TYPE WASHABLE SARANET FILTER WASHABLE SARANET FILTER
AIR QUALITY FILTER
QUANTITY pc 1 1
MATERIAL GALVANISED IRON GALVANISED IRON
INDOOR UNIT FINISHING WITH PE INSULATION WITH PE INSULATION
COLOUR GREY GREY
CASING
MATERIAL GALVANISED MILD STEEL GALVANISED MILD STEEL
OUTDOOR UNIT FINISHING POLYESTER POWDER POLYESTER POWDER
COLOUR LIGHT GREY LIGHT GREY

1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.

53
A5LCY-I-2010 Engineering & Physical Data

Component Data - Heat Pump


OUTDOOR UNIT A5LCY 10DR A5LCY 15DR
MODEL
INDOOR UNIT A5CCY 10CR A5CCY 15CR
TYPE SIROCCO SIROCCO
QUANTITY 2 2
MATERIAL GALVANISED STEEL GALVANISED STEEL
INDOOR FAN
DRIVE DIRECT DIRECT
DIAMETER mm/in 164 / 6.5 164 / 6.5
LENGTH mm/in 202 / 8.0 202 / 8.0
TYPE INDUCTION INDUCTION
INDOOR FAN MOTOR QUANTITY 1 1
INDEX OF PROTECTION (IP) - -
TYPE PROPELLER PROPELLER
QUANTITY 1 1

GLASS REINFORCED POLYPRO- GLASS REINFORCED POLYPRO-


OUTDOOR FAN MATERIAL
PYLENE RESIN PYLENE RESIN

DRIVE DIRECT DIRECT


DIAMETER mm/in 400 / 15.7 400 / 15.7
TYPE INDUCTION INDUCTION
OUTDOOR FAN
QUANTITY 1 1
MOTOR
INDEX OF PROTECTION (IP) IP24 IP24
TYPE ROTARY ROTARY
COMPRESSOR OIL TYPE RB68A or FREOL ALPHA68M RB68A or FREOL ALPHA68M
OIL AMOUNT cm3 / fl.oz. 320 / 11.3 320 / 11.3

SEAMLESS INNER GROOVE SEAMLESS INNER GROOVE


MATERIAL
COPPER COPPER
TUBE
DIAMETER mm/in 7.00 / 0.276 7.00 / 0.276
THICKNESS mm/in 0.24 / 0.009 0.24 / 0.009

INDOOR COIL MATERIAL ALUMINIUM (HYDROPHILIC FIN) ALUMINIUM (HYDROPHILIC FIN)


THICKNESS mm/in 0.11 / 0.004 0.11 / 0.004
FIN FACE AREA m2/ft2 0.13 / 1.43 0.13 / 1.43
ROW 3 3
FIN PER INCH 18 18

SEAMLESS INNER GROOVE SEAMLESS INNER GROOVE


MATERIAL
COPPER COPPER
TUBE
DIAMETER mm/in 7.00 / 0.276 7.00 / 0.276
THICKNESS mm/in 0.24 / 0.009 0.24 / 0.009

OUTDOOR COIL MATERIAL ALUMINIUM (CORR.) ALUMINIUM (CORR.)


THICKNESS mm/in 0.10 / 0.004 0.10 / 0.004
FIN FACE AREA m /ft
2 2
0.42 / 4.520 0.40 / 4.304
ROW 1 2
FIN PER INCH 18 18
TYPE WASHABLE SARANET FILTER WASHABLE SARANET FILTER
AIR QUALITY FILTER
QUANTITY pc 1 1
MATERIAL GALVANISED STEEL GALVANISED STEEL
INDOOR UNIT FINISHING WITH PE INSULATION WITH PE INSULATION
COLOUR WITHOUT POWDER PAINT WITHOUT POWDER PAINT
CASING
MATERIAL GALVANISED MILD STEEL GALVANISED MILD STEEL
OUTDOOR UNIT FINISHING POLYESTER POWDER POLYESTER POWDER
COLOUR LIGHT GREY LIGHT GREY

1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.

54
Engineering & Physical Data A5LCY-I-2010

Component Data - Heat Pump


OUTDOOR UNIT A5LCY 20CR A5LCY 25CR
MODEL
INDOOR UNIT A5CCY 20CR A5CCY 25CR
TYPE SIROCCO SIROCCO
QUANTITY 2 2
MATERIAL GALVANISED STEEL GALVANISED STEEL
INDOOR FAN
DRIVE DIRECT DIRECT
DIAMETER mm/in 160 / 6.3 160 / 6.3
LENGTH mm/in 200 / 7.9 200 / 7.9
TYPE INDUCTION INDUCTION
INDOOR FAN MOTOR QUANTITY 1 1
INDEX OF PROTECTION (IP) IP20 IP21
TYPE PROPELLER PROPELLER
QUANTITY 1 1
OUTDOOR FAN MATERIAL MRP421L2BC MRP421L2BC
DRIVE DIRECT DIRECT
DIAMETER mm/in 455 / 17.9 455 / 17.9
TYPE INDUCTION INDUCTION
OUTDOOR FAN
QUANTITY 1 1
MOTOR
INDEX OF PROTECTION (IP) IP34 IP34
TYPE ROTARY SWING ROTARY SWING
COMPRESSOR OIL TYPE ETHER ETHER
OIL AMOUNT cm3 / fl.oz. N/A N/A

SEAMLESS INNER GROOVE SEAMLESS INNER GROOVE


MATERIAL
COPPER COPPER
TUBE
DIAMETER mm/in 7.00 / 0.276 7.00 / 0.276
THICKNESS mm/in 0.24 / 0.009 0.24 / 0.009

INDOOR COIL MATERIAL ALUMINIUM (HYDROPHILIC FIN) ALUMINIUM (HYDROPHILIC FIN)


THICKNESS mm/in 0.11 / 0.004 0.11 / 0.004
FIN FACE AREA m /ft
2 2
0.16 / 1.76 0.19 / 2.03
ROW 3 3
FIN PER INCH 18 18

SEAMLESS INNER GROOVE SEAMLESS INNER GROOVE


MATERIAL
COPPER COPPER
TUBE
DIAMETER mm/in 7.00 / 0.276 7.00 / 0.276
THICKNESS mm/in 0.24 / 0.009 0.24 / 0.009

OUTDOOR COIL MATERIAL ALUMINIUM (CORR.) ALUMINIUM (CORR.)


THICKNESS mm/in 0.10 / 0.004 0.10 / 0.004
FIN FACE AREA m2/ft2 0.62 / 6.64 0.62 / 6.64
ROW 2 2
FIN PER INCH 20 20
TYPE WASHABLE SARANET FILTER WASHABLE SARANET FILTER
AIR QUALITY FILTER
QUANTITY pc 1 1
MATERIAL GALVANISED STEEL GALVANISED STEEL
INDOOR UNIT FINISHING WITH PE INSULATION WITH PE INSULATION
COLOUR WITHOUT POWDER PAINT WITHOUT POWDER PAINT
CASING
MATERIAL GALVANISED MILD STEEL GALVANISED MILD STEEL
OUTDOOR UNIT FINISHING POLYESTER POWDER POLYESTER POWDER
COLOUR LIGHT GREY LIGHT GREY

1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.

55
A5LCY-I-2010 Engineering & Physical Data

Component Data - Heat Pump


OUTDOOR UNIT A5LCY 15DR A5LCY 20CR
MODEL
INDOOR UNIT A5CMY 15ER A5CMY 20ER
TYPE SIROCCO SIROCCO
QUANTITY 2 2
MATERIAL ABS ABS
INDOOR FAN
DRIVE DIRECT DIRECT
DIAMETER mm/in 145 / 5.7 145 / 5.7
LENGTH mm/in 200 / 8.9 200 / 8.9
TYPE INDUCTION INDUCTION
INDOOR FAN MOTOR QUANTITY 1 1
INDEX OF PROTECTION (IP) - IP20
TYPE PROPELLER PROPELLER
QUANTITY 1 1

GLASS REINFORCED POLYPRO-


OUTDOOR FAN MATERIAL MRP421L2BC
PYLENE RESIN

DRIVE DIRECT DIRECT


DIAMETER mm/in 400 / 15.7 455 / 17.9
TYPE INDUCTION INDUCTION
OUTDOOR FAN
QUANTITY 1 1
MOTOR
INDEX OF PROTECTION (IP) IP24 IP34
TYPE ROTARY ROTARY SWING
COMPRESSOR OIL TYPE RB68A or FREOL ALPHA68M ETHER
OIL AMOUNT cm / fl.oz.
3
320 / 11.3 N/A

SEAMLESS INNER GROOVE SEAMLESS INNER GROOVE


MATERIAL
COPPER COPPER
TUBE
DIAMETER mm/in 7.00 / 0.276 7.00 / 0.276
THICKNESS mm/in 0.24 / 0.009 0.24 / 0.009

INDOOR COIL MATERIAL ALUMINIUM (HYDROPHILIC FIN) ALUMINIUM (HYDROPHILIC FIN)


THICKNESS mm/in 0.11 / 0.004 0.11 / 0.004
FIN FACE AREA m2/ft2 0.27 / 2.89 0.27 / 2.89
ROW 2 3
FIN PER INCH 18 18

SEAMLESS INNER GROOVE SEAMLESS INNER GROOVE


MATERIAL
COPPER COPPER
TUBE
DIAMETER mm/in 7.00 / 0.276 7.00 / 0.276
THICKNESS mm/in 0.24 / 0.009 0.24 / 0.009

OUTDOOR COIL MATERIAL ALUMINIUM (CORR.) ALUMINIUM (CORR.)


THICKNESS mm/in 0.10 / 0.004 0.10 / 0.004
FIN FACE AREA m /ft2 2
0.40 / 4.304 0.62 / 6.64
ROW 2 2
FIN PER INCH 18 20
TYPE WASHABLE SARANET FILTER WASHABLE SARANET FILTER
AIR QUALITY FILTER
QUANTITY pc 2 2
MATERIAL PS PS
INDOOR UNIT FINISHING ETCHING SURFACE ETCHING SURFACE
COLOUR LIGHT GREY LIGHT GREY
CASING
MATERIAL GALVANISED MILD STEEL GALVANISED MILD STEEL
OUTDOOR UNIT FINISHING POLYESTER POWDER POLYESTER POWDER
COLOUR LIGHT GREY LIGHT GREY

1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.

56
Engineering & Physical Data A5LCY-I-2010

Component Data - Heat Pump


OUTDOOR UNIT A5LCY 25CR
MODEL
INDOOR UNIT A5CMY 25ER
TYPE SIROCCO
QUANTITY 2
MATERIAL ABS
INDOOR FAN
DRIVE DIRECT
DIAMETER mm/in 145 / 5.7
LENGTH mm/in 200 / 8.9
TYPE INDUCTION
INDOOR FAN MOTOR QUANTITY 1
INDEX OF PROTECTION (IP) IP20
TYPE PROPELLER
QUANTITY 1
OUTDOOR FAN MATERIAL MRP421L2BC
DRIVE DIRECT
DIAMETER mm/in 455 / 17.9
TYPE INDUCTION
OUTDOOR FAN
QUANTITY 1
MOTOR
INDEX OF PROTECTION (IP) IP34
TYPE ROTARY SWING
COMPRESSOR OIL TYPE ETHER
OIL AMOUNT cm3 / fl.oz. N/A

SEAMLESS INNER GROOVE


MATERIAL
COPPER
TUBE
DIAMETER mm/in 7.00 / 0.276
THICKNESS mm/in 0.24 / 0.009

INDOOR COIL MATERIAL ALUMINIUM (HYDROPHILIC FIN)


THICKNESS mm/in 0.11 / 0.004
FIN FACE AREA m /ft
2 2
0.27 / 2.89
ROW 3
FIN PER INCH 18

SEAMLESS INNER GROOVE


MATERIAL
COPPER
TUBE
DIAMETER mm/in 7.00 / 0.276
THICKNESS mm/in 0.24 / 0.009

OUTDOOR COIL MATERIAL ALUMINIUM (CORR.)


THICKNESS mm/in 0.10 / 0.004
FIN FACE AREA m2/ft2 0.62 / 6.64
ROW 2
FIN PER INCH 20
TYPE WASHABLE SARANET FILTER
AIR QUALITY FILTER
QUANTITY pc 2
MATERIAL PS
INDOOR UNIT FINISHING ETCHING SURFACE
COLOUR LIGHT GREY
CASING
MATERIAL GALVANISED MILD STEEL
OUTDOOR UNIT FINISHING POLYESTER POWDER
COLOUR LIGHT GREY

1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.

57
A5LCY-I-2010 Engineering & Physical Data

Safety Devices Data


OUTDOOR UNIT A5LCY 10DR A5LCY 15DR
MODEL
INDOOR UNIT A5WMY 10JR A5WMY 15JR

TYPE N/A N/A

HIGH PRESSURE SWITCH OPEN kPa / psi N/A N/A

CLOSE kPa / psi N/A N/A

TYPE N/A N/A


SAFETY
DEVICE LOW PRESSURE SWITCH OPEN kPa / psi N/A N/A

CLOSE kPa / psi N/A N/A

PHASE SEQUENCER N/A N/A

DISCHARGE THERMOSTAT
°C / °F N/A N/A
SETTING

OUTDOOR UNIT A5LCY 20CR A5LCY 25CR


MODEL
INDOOR UNIT A5WMY 20JR A5WMY 25JR

TYPE N/A N/A

HIGH PRESSURE SWITCH OPEN kPa / psi N/A N/A

CLOSE kPa / psi N/A N/A

TYPE N/A N/A


SAFETY
DEVICE LOW PRESSURE SWITCH OPEN kPa / psi N/A N/A

CLOSE kPa / psi N/A N/A

PHASE SEQUENCER N/A N/A


DISCHARGE THERMOSTAT
°C / °F N/A N/A
SETTING

OUTDOOR UNIT A5LCY 10DR A5LCY 15DR


MODEL
INDOOR UNIT A5CKY 10CR A5CKY 15CR

TYPE N/A N/A

HIGH PRESSURE SWITCH OPEN kPa / psi N/A N/A

CLOSE kPa / psi N/A N/A

TYPE N/A N/A


SAFETY
DEVICE LOW PRESSURE SWITCH OPEN kPa / psi N/A N/A

CLOSE kPa / psi N/A N/A

PHASE SEQUENCER N/A N/A


DISCHARGE THERMOSTAT
°C / °F N/A N/A
SETTING

OUTDOOR UNIT A5LCY 20CR


MODEL
INDOOR UNIT A5CKY 20CR

TYPE N/A

HIGH PRESSURE SWITCH OPEN kPa / psi N/A

CLOSE kPa / psi N/A

TYPE N/A
SAFETY
DEVICE LOW PRESSURE SWITCH OPEN kPa / psi N/A

CLOSE kPa / psi N/A

PHASE SEQUENCER N/A


DISCHARGE THERMOSTAT
°C / °F N/A
SETTING

1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.

58
Engineering & Physical Data A5LCY-I-2010

Safety Devices Data


OUTDOOR UNIT A5LCY 20CR A5LCY 25CR
MODEL
INDOOR UNIT A5CKY 20ER A5CKY 25ER

TYPE N/A N/A

HIGH PRESSURE SWITCH OPEN kPa / psi N/A N/A

CLOSE kPa / psi N/A N/A

TYPE N/A N/A


SAFETY
DEVICE LOW PRESSURE SWITCH OPEN kPa / psi N/A N/A

CLOSE kPa / psi N/A N/A

PHASE SEQUENCER N/A N/A


DISCHARGE THERMOSTAT
°C / °F N/A N/A
SETTING

OUTDOOR UNIT A5LCY 10DR A5LCY 15DR


MODEL
INDOOR UNIT A5CCY 10CR A5CCY 15CR

TYPE N/A N/A

HIGH PRESSURE SWITCH OPEN kPa / psi N/A N/A

CLOSE kPa / psi N/A N/A

TYPE N/A N/A


SAFETY
DEVICE LOW PRESSURE SWITCH OPEN kPa / psi N/A N/A

CLOSE kPa / psi N/A N/A

PHASE SEQUENCER N/A N/A


DISCHARGE THERMOSTAT
°C / °F N/A N/A
SETTING

OUTDOOR UNIT A5LCY 20CR A5LCY 25CR


MODEL
INDOOR UNIT A5CCY 20CR A5CCY 25CR

TYPE N/A N/A

HIGH PRESSURE SWITCH OPEN kPa / psi N/A N/A

CLOSE kPa / psi N/A N/A

TYPE N/A N/A


SAFETY
DEVICE LOW PRESSURE SWITCH OPEN kPa / psi N/A N/A

CLOSE kPa / psi N/A N/A

PHASE SEQUENCER N/A N/A


DISCHARGE THERMOSTAT
°C / °F N/A N/A
SETTING

OUTDOOR UNIT A5LCY 15DR A5LCY 20CR


MODEL
INDOOR UNIT A5CMY 15ER A5CMY 20ER

TYPE N/A N/A

HIGH PRESSURE SWITCH OPEN kPa / psi N/A N/A

CLOSE kPa / psi N/A N/A

TYPE N/A N/A


SAFETY
DEVICE LOW PRESSURE SWITCH OPEN kPa / psi N/A N/A

CLOSE kPa / psi N/A N/A

PHASE SEQUENCER N/A N/A


DISCHARGE THERMOSTAT
°C / °F N/A N/A
SETTING

1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.

59
A5LCY-I-2010 Engineering & Physical Data

Safety Devices Data


OUTDOOR UNIT A5LCY 25CR
MODEL
INDOOR UNIT A5CMY 25ER

TYPE N/A

HIGH PRESSURE SWITCH OPEN kPa / psi N/A

CLOSE kPa / psi N/A

TYPE N/A
SAFETY
DEVICE LOW PRESSURE SWITCH OPEN kPa / psi N/A

CLOSE kPa / psi N/A

PHASE SEQUENCER N/A


DISCHARGE THERMOSTAT
°C / °F N/A
SETTING

1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.

60
Outline and Dimension A5LCY-I-2010

Outline and Dimension


Outdoor Unit
Model: A5LCY 10/15DR

490

574 105.5 All dimensions are in mm

13

29.5
311

285 8 12 765 63
550

Note: Dimension in mm

Outdoor Unit
Model: A5LCY 20/25CR

Note: Dimension in mm

61
A5LCY-I-2010 Outline and Dimension

Indoor Unit
Model: A5WMY 10/15JR

800

206

288
288

Note: Dimension in mm

Indoor Unit
Model: A5WMY 20/25JR

1065

224
310
310

Note: Dimension in mm

62
Outline and Dimension A5LCY-I-2010

Indoor Unit
Model: A5CKY 10/15/20CR

MODEL A B C D E F G H I J K
A5CKY 10/15/20CR 570 570 295 275 20 640 640 408 408 364 364

Note: Dimension in mm

Indoor Unit
Model: A5CKY 20/25ER

B F
C
D E
H
A

G
I
J

MODEL A B C D E F G H I J K
A5CKY 20/25ER 820 820 350 290 60 990 990 627 627 607 607

Note: Dimension in mm

63
A5LCY-I-2010 Outline and Dimension

Indoor Unit
Model: A5CCY 10/15/20/25CR

MODEL A B C D E F G H I J K L M N O
A5CCY 10/15CR 31 881 842 802 10 905 72 261 411 351 225 211 232 212,8 114
A5CCY 20CR 31 1041 1002 962 10 1065 72 261 411 351 225 211 232 212,8 114
A5CCY 25CR 31 1176 1137 1097 10 1200 72 261 411 351 225 211 232 212,8 114

Note: Dimension in mm

Indoor Unit
Model: A5CMY 15/20/25ER

Note: Dimension in mm

64
Electrical Data A5LCY-I-2010

Electrical Data
OUTDOOR UNIT A5LCY 10DR A5LCY 15DR
MODEL
INDOOR UNIT A5WMY 10JR A5WMY 15JR
INSULATION GRADE E E
POWER SOURCE V/Ph/Hz 220 - 240 / 1 / 50 220 - 240 / 1 / 50
RATED INPUT POWER W 34 42
INDOOR MOTOR
RATED RUNNING CURRENT A 0.19 0.21
MOTOR OUTPUT W 18 18
POLES 4 4
INSULATION GRADE E E
POWER SOURCE V/Ph/Hz 220 - 240 / 1 / 50 220 - 240 / 1 / 50
RATED INPUT POWER W 66 67
OUTDOOR MOTOR
RATED RUNNING CURRENT A 0.31 0.31
MOTOR OUTPUT W 26 26
POLES 6 6
INSULATION GRADE E E
POWER SOURCE V/Ph/Hz 220 - 240 / 1 / 50 220 - 240 / 1 / 50
CAPACITOR μF - -
RATED INPUT POWER (COOLING) W 660 941
COMPRESSOR
RATED INPUT POWER (HEATING) W 728 941
RATED RUNNING CURRENT (COOLING) A 3.60 4.48
RATED RUNNING CURRENT (HEATING) A 3.50 4.38
LOCKED ROTOR AMP. A - -

OUTDOOR UNIT A5LCY 20CR A5LCY 25CR


MODEL
INDOOR UNIT A5WMY 20JR A5WMY 25JR

INSULATION GRADE E E

POWER SOURCE V/Ph/Hz 220 - 240 / 1 / 50 220 - 240 / 1 / 50

RATED INPUT POWER W 37 63


INDOOR MOTOR
RATED RUNNING CURRENT A 0.32 0.56

MOTOR OUTPUT W 40 40

POLES 8 8

INSULATION GRADE F F

POWER SOURCE V/Ph/Hz 220 - 240 / 1 / 50 220 - 240 / 1 / 50

RATED INPUT POWER W 120 120


OUTDOOR MOTOR
RATED RUNNING CURRENT A 0.52 0.52

MOTOR OUTPUT W 66 66

POLES 6 6

INSULATION GRADE E E

POWER SOURCE V/Ph/Hz 220 - 240 / 1 / 50 220 - 240 / 1 / 50

CAPACITOR μF - -

RATED INPUT POWER (COOLING) W 1296 1690


COMPRESSOR
RATED INPUT POWER (HEATING) W 1334 1518

RATED RUNNING CURRENT (COOLING) A 5.66 7.25

RATED RUNNING CURRENT (HEATING) A 5.84 6.52

LOCKED ROTOR AMP. A - -

1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151.

65
A5LCY-I-2010 Electrical Data

OUTDOOR UNIT A5LCY 10DR A5LCY 15DR


MODEL
INDOOR UNIT A5CKY 10CR A5CKY 15CR

INSULATION GRADE B B

POWER SOURCE V/Ph/Hz 220 - 240 / 1 / 50 220 - 240 / 1 / 50

RATED INPUT POWER W 62 62


INDOOR MOTOR
RATED RUNNING CURRENT A 0.28 0.28

MOTOR OUTPUT W 16 16

POLES 6 6

INSULATION GRADE E E

POWER SOURCE V/Ph/Hz 220 - 240 / 1 / 50 220 - 240 / 1 / 50

RATED INPUT POWER W 66 67


OUTDOOR MOTOR
RATED RUNNING CURRENT A 0.31 0.31

MOTOR OUTPUT W 26 26

POLES 6 6

INSULATION GRADE E E

POWER SOURCE V/Ph/Hz 220 - 240 / 1 / 50 220 - 240 / 1 / 50

CAPACITOR μF - -

RATED INPUT POWER (COOLING) W 660 941


COMPRESSOR
RATED INPUT POWER (HEATING) W 728 941

RATED RUNNING CURRENT (COOLING) A 3.60 4.48

RATED RUNNING CURRENT (HEATING) A 3.50 4.38

LOCKED ROTOR AMP. A - -

OUTDOOR UNIT A5LCY 20CR


MODEL
INDOOR UNIT A5CKY 20CR

INSULATION GRADE B

POWER SOURCE V/Ph/Hz 220 - 240 / 1 / 50

RATED INPUT POWER W 74


INDOOR MOTOR
RATED RUNNING CURRENT A 0.31

MOTOR OUTPUT W 22

POLES 6

INSULATION GRADE F

POWER SOURCE V/Ph/Hz 220 - 240 / 1 / 50

RATED INPUT POWER W 120


OUTDOOR MOTOR
RATED RUNNING CURRENT A 0.52

MOTOR OUTPUT W 66

POLES 6

INSULATION GRADE E

POWER SOURCE V/Ph/Hz 220 - 240 / 1 / 50

CAPACITOR μF -

RATED INPUT POWER (COOLING) W 1296


COMPRESSOR
RATED INPUT POWER (HEATING) W 1334

RATED RUNNING CURRENT (COOLING) A 5.66

RATED RUNNING CURRENT (HEATING) A 5.84

LOCKED ROTOR AMP. A -

1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151.

66
Electrical Data A5LCY-I-2010

OUTDOOR UNIT A5LCY 20CR A5LCY 25CR


MODEL
INDOOR UNIT A5CKY 20ER A5CKY 25ER

INSULATION GRADE B B

POWER SOURCE V/Ph/Hz 220 - 240 / 1 / 50 220 - 240 / 1 / 50

RATED INPUT POWER W 89 103


INDOOR MOTOR
RATED RUNNING CURRENT A 0.40 0.45

MOTOR OUTPUT W 20 30

POLES 6 6

INSULATION GRADE F F

POWER SOURCE V/Ph/Hz 220 - 240 / 1 / 50 220 - 240 / 1 / 50

RATED INPUT POWER W 120 120


OUTDOOR MOTOR
RATED RUNNING CURRENT A 0.52 0.52

MOTOR OUTPUT W 66 66

POLES 6 6

INSULATION GRADE E E

POWER SOURCE V/Ph/Hz 220 - 240 / 1 / 50 220 - 240 / 1 / 50

CAPACITOR μF - -

RATED INPUT POWER (COOLING) W 1296 1690


COMPRESSOR
RATED INPUT POWER (HEATING) W 1334 1518

RATED RUNNING CURRENT (COOLING) A 5.66 7.25

RATED RUNNING CURRENT (HEATING) A 5.84 6.52

LOCKED ROTOR AMP. A - -

OUTDOOR UNIT A5LCY 10DR A5LCY 15DR


MODEL
INDOOR UNIT A5CCY 10CR A5CCY 15CR

INSULATION GRADE B E

POWER SOURCE V/Ph/Hz 220 - 240 / 1 / 50 220 - 240 / 1 / 50

RATED INPUT POWER W 89 100


INDOOR MOTOR
RATED RUNNING CURRENT A 0.39 0.42

MOTOR OUTPUT W 40 50

POLES 4 4

INSULATION GRADE E E

POWER SOURCE V/Ph/Hz 220 - 240 / 1 / 50 220 - 240 / 1 / 50

RATED INPUT POWER W 66 67


OUTDOOR MOTOR
RATED RUNNING CURRENT A 0.31 0.31

MOTOR OUTPUT W 26 26

POLES 6 6

INSULATION GRADE E E

POWER SOURCE V/Ph/Hz 220 - 240 / 1 / 50 220 - 240 / 1 / 50

CAPACITOR μF - -

RATED INPUT POWER (COOLING) W 660 941


COMPRESSOR
RATED INPUT POWER (HEATING) W 728 941

RATED RUNNING CURRENT (COOLING) A 3.60 4.48

RATED RUNNING CURRENT (HEATING) A 3.50 4.38

LOCKED ROTOR AMP. A - -

1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151.

67
A5LCY-I-2010 Electrical Data

OUTDOOR UNIT A5LCY 20CR A5LCY 25CR


MODEL
INDOOR UNIT A5CCY 20CR A5CCY 25CR

INSULATION GRADE B B

POWER SOURCE V/Ph/Hz 220 - 240 / 1 / 50 220 - 240 / 1 / 50

RATED INPUT POWER W 133 164


INDOOR MOTOR
RATED RUNNING CURRENT A 0.61 0.74

MOTOR OUTPUT W 80 100

POLES 4 4

INSULATION GRADE F F

POWER SOURCE V/Ph/Hz 220 - 240 / 1 / 50 220 - 240 / 1 / 50

RATED INPUT POWER W 120 120


OUTDOOR MOTOR
RATED RUNNING CURRENT A 0.52 0.52

MOTOR OUTPUT W 66 66

POLES 6 6

INSULATION GRADE E E

POWER SOURCE V/Ph/Hz 220 - 240 / 1 / 50 220 - 240 / 1 / 50

CAPACITOR μF - -

RATED INPUT POWER (COOLING) W 1296 1690


COMPRESSOR
RATED INPUT POWER (HEATING) W 1334 1518

RATED RUNNING CURRENT (COOLING) A 5.66 7.25

RATED RUNNING CURRENT (HEATING) A 5.84 6.52

LOCKED ROTOR AMP. A - -

OUTDOOR UNIT A5LCY 15DR A5LCY 20CR


MODEL
INDOOR UNIT A5CMY 15ER A5CMY 20ER

INSULATION GRADE B B

POWER SOURCE V/Ph/Hz 220 - 240 / 1 / 50 220 - 240 / 1 / 50

RATED INPUT POWER W 83.6 101


INDOOR MOTOR
RATED RUNNING CURRENT A 0.37 0.46

MOTOR OUTPUT W 40 50

POLES 4 4

INSULATION GRADE E F

POWER SOURCE V/Ph/Hz 220 - 240 / 1 / 50 220 - 240 / 1 / 50

RATED INPUT POWER W 67 120


OUTDOOR MOTOR
RATED RUNNING CURRENT A 0.31 0.52

MOTOR OUTPUT W 26 66

POLES 6 6

INSULATION GRADE E E

POWER SOURCE V/Ph/Hz 220 - 240 / 1 / 50 220 - 240 / 1 / 50

CAPACITOR μF - -

RATED INPUT POWER (COOLING) W 941 1296


COMPRESSOR
RATED INPUT POWER (HEATING) W 941 1334

RATED RUNNING CURRENT (COOLING) A 4.48 5.66

RATED RUNNING CURRENT (HEATING) A 4.38 5.84

LOCKED ROTOR AMP. A - -

1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151.

68
Electrical Data A5LCY-I-2010

OUTDOOR UNIT A5LCY 25CR


MODEL
INDOOR UNIT A5CMY 25ER

INSULATION GRADE B

POWER SOURCE V/Ph/Hz 220 - 240 / 1 / 50

RATED INPUT POWER W 109


INDOOR MOTOR
RATED RUNNING CURRENT A 0.49

MOTOR OUTPUT W 65

POLES 4

INSULATION GRADE F

POWER SOURCE V/Ph/Hz 220 - 240 / 1 / 50

RATED INPUT POWER W 120


OUTDOOR MOTOR
RATED RUNNING CURRENT A 0.52

MOTOR OUTPUT W 66

POLES 6

INSULATION GRADE E

POWER SOURCE V/Ph/Hz 220 - 240 / 1 / 50

CAPACITOR μF -

RATED INPUT POWER (COOLING) W 1690


COMPRESSOR
RATED INPUT POWER (HEATING) W 1518

RATED RUNNING CURRENT (COOLING) A 7.25

RATED RUNNING CURRENT (HEATING) A 6.52

LOCKED ROTOR AMP. A -

1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151.

69
A5LCY-I-2010 Wiring Diagram

Wiring Diagram
Heat Pump

Outdoor Unit Indoor Unit


Model: A5LCY 10/15DR Model: A5WMY 10/15JR

70034106463

70
Wiring Diagram A5LCY-I-2010

Outdoor Unit Indoor Unit


Model: A5LCY 20/25CR Model: A5WMY 20/25JR

71
A5LCY-I-2010 Wiring Diagram

Heat Pump

Outdoor Unit Indoor Unit


Model: A5LCY 10/15DR Model: A5CKY 10/15CR

70034108590

72
Wiring Diagram A5LCY-I-2010

Heat Pump

Outdoor Unit Indoor Unit


Model: A5LCY 20CR Model: A5CKY 20CR

73
A5LCY-I-2010 Wiring Diagram

Heat Pump

Outdoor Unit Indoor Unit


Model: A5LCY 20/25CR Model: A5CKY 20/25ER

70034110364

74
Wiring Diagram A5LCY-I-2010

Heat Pump

Outdoor Unit Indoor Unit


Model: A5LCY 10/15DR Model: A5CCY 10/15CR

70034108589

75
A5LCY-I-2010 Wiring Diagram

Heat Pump

Outdoor Unit Indoor Unit


Model: A5LCY 20/25CR Model: A5CCY 20/25CR

70034110366

76
Wiring Diagram A5LCY-I-2010

Heat Pump

Outdoor Unit Indoor Unit


Model: A5LCY 15DR Model: A5CMY 15ER

70034108591

77
A5LCY-I-2010 Wiring Diagram

Heat Pump

Outdoor Unit Indoor Unit


Model: A5LCY 20/25CR Model: A5CMY 20/25ER

70034110365

78
Service and Maintenance A5LCY-I-2010

Service and Maintenance


Warning
• Disconnect from main supply before servicing the air conditioner.
• The unit is designed to give long life operation with minimum maintenance required. However, it should be regularly
checked and the following items should be given due attention.

Components Maintenance Procedures Period


Air Filter 1. Remove any dust adhering to the filter by using a vacuum cleaner At least once every 2
(Indoor Unit) or wash in lukewarm water (below 40˚C) with a neutral cleaning weeks.
detergent. More frequently if
2. Rinse the filter well and dry before placing it back onto the unit. necessary.
3. Note: Never use gasoline, volatile substances or chemicals to
clean the filter.
Indoor Unit 1. Clean any dirt or dust on the grille or panel by wiping it with a At least once every 2
soft cloth soaked in lukewarm water (below 40˚C) and a neutral weeks.
detergent solution. More frequently if
2. Note: Never use gasoline, volatile substances or chemicals to necessary.
clean the indoor unit.
Condense Drain 1. Check the cleanliness and clean it if necessary. Every 3 months.
Pan & Pipe 2. Check the condensate water flow.
Indoor Fan Check if there is any abnormal noise. If necessary.
Indoor / Outdoor 1. Check and remove the dirt between the fins. Every month.
Coil 2. Check and remove any obstacles which hinder air flow through
the indoor or outdoor.
3. Note: Avoid direct contact of any coil treatment material on the
plastic part. This may cause plastic part to deform as a result of
chemical reaction.
Power Supply 1. Check the running current and voltage for indoor and outdoor Every 2 months.
unit.
2. Check the electrical wiring and tighten the wire onto the terminal Every year.
block if necessary.
Compressor No maintenance needed if refrigerant circuit remains sealed. How- Every 6 months.
ever, check for refrigerant leak at joint and fitting.

Indoor Models Recess on


main unit
1. Open the front panel
• Hold the panel at the recesses on the main unit
(2 recesses on right and left sides) and lift it until
it stops.
2. Remove the front panel
• While lifting the front panel further, slide it to the
right and pull it to the front side. The left rotating
shaft is detached. Slide the right rotating shaft to
Rotating
the left and pull it to the front side to remove it. shaft
3. Attach the front panel
• Align the right and left rotating shafts of the front
panel with the grooves and push them all the
way in.
• Gently close the front panel. (Push both ends
and the center on the front panel.)

79
A5LCY-I-2010 Service and Maintenance

Air Filter
1. Open the front panel.
• Hold the panel at the recesses on the main unit (2 recesses on right and left sides) and lift it until it
stops.

Recess on
main unit

2. Pull out the air filters.


• Push a little upwards the tab at the center of each air filter, then pull it down.
3. Clean or replace each filter.
• When shaking off remaining water, do not wring the filter.
4. Set the air filter and close the front panel.
• Insert claws of the filters into slots of the front panel. Close the front panel slowly and push the panel at
the 3 points. (1 on each side and 1 in the middle.)
• The air filter have a symmetrical form in the horizontal direction.

FRONT

Caution
• Don’t touch the metal parts of the indoor unit. It may cause an injury.
• When removing or attaching the front panel, use a robust and stable stool and watch your steps carefully.
• When removing or attaching the front panel, support the panel securely with hand to prevent from it falling.
• For cleansing, do no use hot water above 40°C, benzene, gasoline, thinner, nor other volatile oils, polishing
compound, scrubbing brushes, nor other hand stuff.
• After cleaning, make sure that the front panel is securely fixed.

Pre Start Up Maintenance


(After Extended Shutdown)
• Inspect thoroughly and clean indoor and outdoor units.
• Clean or replace air filters.
• Clean condensates drain line.
• Clean clogged indoor and outdoor coils.
• Check fan imbalance before operation.
• Tighten all wiring connections and panels.
• Check for refrigerant leakage.

Outdoor Models
The design of the A5LCY outdoor series allows servicing to be carried out easily. The removal of the top, front
and side panels makes almost every part accessible.
Under normal circumstances, these outdoor units only require a check and cleaning of air intake coil surface
once every 3 months. However, if a unit is installed in areas subjected to much oil mist and dust, the coils must
be regularly cleaned by qualified Air Conditioner Service Technicians to ensure sufficient heat exchange and
proper operation. Otherwise, the systems life span may be shortened.

Caution
• Do not charge OXYGEN, ACETYLENE OR OTHER FLAMMABLE and poisonous gases into the unit when
performing a leakage test or an airtight test. These gases could cause severe explosion and damage if exposed to
high temperature and pressure.
• It is recommended that only nitrogen or refrigerant be charged when performing the leakage or airtight test.

80
Troubleshooting A5LCY-I-2010

Troubleshooting
Fault Condition
When a malfunction of the air conditioner unit is detected, immediately switch off the main power supply before
proceeding with the following troubleshooting procedures.
The following are common fault conditions and simple troubleshooting tips. If any other fault conditions which
are not listed occur, contact your nearest local dealer. DO NOT attempt to troubleshoot the unit by yourself.

No Fault conditions Possible causes / corrective actions


1 The air conditioner unit will not resume after • The auto restart function is not functioning.
power failure. Please turn on the unit with the wireless /
wired controller.
2 The airflow is too slow or room cannot be • The air filter is dirty.
cooled sufficiently. • The doors and windows are opened.
• The air suction and discharge of both indoor
and outdoor units are clogged or blocked.
• The regulated temperature or temperature
setting is not low enough.
3 Discharge airflow has bad odor. • Cigarettes, smoke particles, perfume and
others, which might have adhered onto the
coil, may cause odor.
• Contact your nearest dealer.
4 Condensation on the front air grille of the indoor • This is caused by air humidity after an
unit. extended period of operation.
• The set temperature is too low. Increase the
temperature setting and operate the unit at
high fan speed.
5 Water flowing out from the air conditioner. • Switch off the unit and contact your nearest
dealer. This might be due to tilted installation.
6 Hissing airflow sound from the air conditioner • Liquid refrigerant flowing into the evaporator
unit during operation. coil.
7 The wireless controller display is dim. • The batteries are discharged.
• The batteries are not correctly inserted.
• The assembly is not good.
8 Compressor operates continuously. • Dirty air filter. Clean the air filter.
• Temperature setting too low (cooling). Use
higher temperature setting.
• Temperature setting too high (heating), Use
lower temperature setting.
9 No cool air comes out during cooling cycle, or • Temperature setting too high (cooling). Use
no hot air comes out during heating cycle. lower temperature setting.
• Temperature setting too low (heating). Use
higher temperature setting.
10 On heating cycle, warm air does not come out. • Unit is in defrost mode. Heating operation will
resume after defrost cycle ends.

81
A5LCY-I-2010 Troubleshooting

By means of diagnostic flow chart:

Generally, there are two kinds of problems, i.e. starting failure and insufficient cooling / heating. “Starting failure”
is caused by electrical defect while improper application or defects in refrigerant circuit causes “Insufficient
cooling / heating”.
i ) Diagnosis of Electric circuit

: Faulty : Check : Cause : Remedy

No cooling/heating (Unit fails to start)

Evaporator Stop
fan motor

No voltage or low voltage Get the right voltage


Faulty
Unit power
supply Wrong phase/missing
phase (applicable to 3 Repair the power line
phase model)

Fuse for Blown Components shorted Repair or replace the components


operation
circuit Connections loose Tighten the connections

Running

Over current High or low voltage Get the right voltage


Tripped
relay for
evaporator Wrong phase/missing
Check the power supply to the
fan phase (applicable to 3
motor: repair when necessary
phase model)

Faulty Coil burned Change the contactor


Evaporator
fan contactor
Contact faulty Repair the contacts

Faulty fan motor Repair or change the motor

Defective operation switch Repair or change the switch

Condenser Stop
fan motor

Over current No voltage or low voltage Get the right voltage


Tripped
relay for
condenser Wrong phase/missing
fan Check the power supply to the
phase (applicable to 3 motor: repair when necessary
Running phase model)

1 2

82
Troubleshooting A5LCY-I-2010

1 2

Coil burnt Change the contactor


Faulty
Condenser
fan contactor
Contact faulty Change the contacts

Blown Fan motor faulty Repair or replace the motor contactor

Other electrical Repair or change if necessary


component faulty

Faulty Coil burnt Change the contactor


Evaporator
contactor
Contact faulty Change the contacts

Open compressor
Change the compressor
windings

Incorrect wiring Correct the wiring

The most common causes of air conditioner failure to “start” are :


a) Voltage not within ±10% of rated voltage.
b) Power supply interrupted.
c) Improper control settings.
d) Air conditioner is disconnected from main power source.
e) Fuse blown or circuit breaker off.

83
A5LCY-I-2010 Troubleshooting

ii ) Diagnosis of Refrigerant Circuit / Application

There might be some causes where the unit starts running but does not perform satisfactorily, i.e. insufficient
cooling. Judgement could be made by measuring temperature difference of indoor unit’s intake and discharge
air as well as running current.

: Faulty : Check : Cause : Remedy

Insufficient cooling

Indoor/outdoor coil dirty


(clogged) Clean the coil
Air Restricted
circulation
Indoor air filter dirty Clean the filter

Fan motor malfunction Change or repair the motor

Obstruction at air inlet


/outlet of indoor / outdoor Remove the obstruction
unit

Excessive heat source.


e.g. electric kettle Remove or reduce heat source
High cooling
load
Room overcrowded with
people Reduce number of people in the room

Windows / doors wide


open Close the windows / doors

Refrigerant short charge


Add refrigerant. Repair leakage if detected
or refrigerant leakage
Refrigerant
circuit
Restriction e.g. at strainer, Repair clogging or replace faulty components
capillary, filter dryer, etc.

Compressor Less or no compression Replace compressor


(Low running current)

Satisfactory operation with temperature difference of air


intake & discharge of indoor unit 8°C to 13°C. *
( * value is for reference only )

84
Troubleshooting A5LCY-I-2010

Insufficient heating

Indoor/outdoor coil dirty


(clogged) Clean the coil
Air Restricted
circulation
Indoor air filter dirty Clean the filter

Fan motor malfunction Change or repair the motor

Obstruction at air inlet


/outlet of indoor / outdoor Remove the obstruction
unit

High heating Windows / doors wide


open Close the windows / doors
load

Refrigerant short charge


Add refrigerant. Repair leakage if detected
or refrigerant leakage
Refrigerant
circuit
Restriction e.g. at strainer, Repair clogging or replace faulty components
capillary, filter dryer, etc.

Compressor Less or no compression Replace compressor


(Low running current)

Satisfactory operation with temperature difference of air


intake & discharge of indoor unit 14°C to 20°C. *
( * value is for reference only )

85
A5LCY-I-2010 Troubleshooting

Indicator Lights

IR Signal Receiver
When an infrared remote control operating signal has been transmitted, the signal receiver on the indoor unit
will respond as below to confirm acceptance of the signal transmission.

ON to OFF 1 Long Beep


OFF to ON
2 Short Beep
Pump down/Cool force on
Others 1 Short Beep

Heat Pump Unit


The table shows the LED indicator lights for the air conditioner unit under normal operation and fault conditions.
The LED indicator lights are located at the side of the air conditioner unit.The heat pump units are equipped
with an “auto” mode sensor whereby it will provide reasonable room temperature by switching automatically to
either “cool” or “heat” mode according to the temperature set by the user.

IR Receiver

Cool / Heat
Timer
Sleep
ON/OFF ON/OFF switch

IR Receiver

LED Indicator Lights: Normal Operation and Fault Conditions for Heat Pump Unit

1  Normal Operation / Fault Indication


COOL/HEAT
(GREEN/RED)

Green
Cool mode

Red
Heat mode

Red
Auto mode in Heating operation

Green
Auto mode in Cooling operation

Time off (when unit is on)

Time on (when unit is off)

Sleep mode on

Green
Fan mode on

Green
Dry mode on

Red
Defrost operation

Green
Error indication

ON Blinking

86
Troubleshooting A5LCY-I-2010

Error Code Diagnosis by Wireless Handset GS02

SWING FAN

TURBO MODE

QUIET SLEEP

TIMER ON ON
TIMER
OFF

CANCEL CLOCK CANCEL

TIMER OFF

Diagnosis Step
1. Hold down ON TIMER CANCEL button or OFF TIMER CANCEL button for 5 seconds, a “ ” indication
flashes on the temperature display section.
2. Press ON TIMER CANCEL or OFF TIMER CANCEL repeatedly until indoor buzzer produces a long beep.
This indicates the error code, refers to Error Codes table and is displayed on the temperature display
section.
3. A short beep or two consecutive beeps indicate non-corresponding error codes.
4. To cancel the error code display, hold down ON TIMER CANCEL or OFF TIMER CANCEL button for 5
seconds. Alternatively, the code display will cancel itself if the button is not pressed for 1 minute.

87
A5LCY-I-2010 Troubleshooting

Error Code Diagnosis by Wired Handset Netware 3C

Error code flashes e.g. A1

Error display using normal running

Error code flashes e.g. A1

&S

Error display using unit last state memory

88
Troubleshooting A5LCY-I-2010

Error Codes
ERROR
ERROR DESCRIPTION
CODE
00 NORMAL
A1 INDOOR PCB ERROR
A3 DRAIN PUMP ABNORMAL
A5 ANTIFREEZE (COOLING)/HEAT EXCHANGER OVERHEAT (HEATING)
A6 INDOOR FAN MOTOR ABNORMAL
AH ELECTRICAL AIR CLEANER ABNORMAL
C4 INDOOR HEAT EXCHANGER (1) THERMISTOR SHORT/OPEN
C5 INDOOR HEAT EXCHANGER (2) THERMISTOR SHORT/OPEN
C7 LOUVER LIMIT SWITCH ERROR
C9 INDOOR ROOM THERMISTOR SHORT/OPEN
E1 OUTDOOR PCB ERROR
E3 HIGH PRESSURE PROTECTION
E4 LOW PRESSURE PROTECTION
E5 COMPRESSOR MOTOR LOCK/COMPRESSOR OVERLOADED
E6 COMPRESSOR START-UP ERROR
E7 OUTDOOR DC FAN MOTOR LOCK
E8 AC INPUT OVER CURRENT
E9 EXV ERROR
EA 4 WAY VALVE ERROR
F3 DISCHARGE PIPE OVERHEAT
F6 HEAT EXCHANGER OVERHEAT
HO COMPRESSOR SENSOR SYSTEM ERROR
H3 HIGH PRESSURE SWITCH ERROR
H6 COMPRESSOR FEEDBACK DETECTION ERROR
H7 FAN MOTOR OVERLOADED/OVERCURRENT/SENSOR ABNORMAL
H8 AC CURRENT SENSOR ERROR
H9 OUTDOOR AIR THERMISTOR SHORT/OPEN
J1 PRESSURE SENSOR ERROR
J3 COMPRESSOR DISCHARGE PIPE THERMISTOR SHORT/OPEN/MISPLACED
J5 SUCTION PIPE THERMISTOR SHORT/OPEN
J6 OUTDOOR HEAT EXCHANGER THERMISTOR SHORT/OPEN
J7 SUBCOOLING HEAT EXCHANGER THERMISTOR SHORT/OPEN
J8 LIQUID PIPE THERMISTOR SHORT/OPEN
J9 GAS PIPE THERMISTOR SHORT/OPEN
L1 INVERTER OUTDOOR PCB ERROR
L3 OUTDOOR CONTROL BOX OVERHEAT
L4 HEAT SINK OVERHEAT
L5 IPM ERROR/IGBT ERROR
L8 INVERTER COMPRESSOR OVERCURRENT
L9 COMPRESSOR OVERCURRENT PREVENTION

89
A5LCY-I-2010 Troubleshooting

ERROR
ERROR DESCRIPTION
CODE
LC COMMUNICATION ERROR (OUTDOOR CONTROL PCB AND INVERTER PCB)
P1 OPEN PHASE OR VOLTAGE UNBALANCE
P4 HEAT SINK THERMISTOR SHORT/OPEN
PJ CAPACITY SETTING ERROR
U0 INSUFFICIENT GAS
U2 DC VOLTAGE OUT OF RANGE
U4 COMMUNICATION ERROR
U7 COMMUNICATION ERROR (OUTDOOR CONTROL PCB AND IPM PCB)
UA INSTALLATION ERROR
UF PIPING & WIRING INSTALLATION MISMATCH/WRONG WIRING/INSUFFICIENT GAS
UH ANTIFREEZE (OTHER ROOMS)

Unit Running Parameter


Parameter
Parameter Description Unit/ range
Number
00 Compressor Actual Rotation r/s
01 Compressor Target Rotation r/s
02 DC Bus Voltage VDC
03 Total Current (÷10) A
04 Outdoor Air Temperature °C
05 Outdoor Heat Exchanger Temperature °C
06 Compressor Discharge Temperature °C
07 Outdoor Heatsink Temperature °C
08 Indoor Air Temperature °C
09 Indoor Heat exchanger Temperature °C
10 EXV Opening Pulse
11 Outdoor fan speed W0 ~ W6
12 Horse power 15: 1.5hp
13 Software version (Production)
14 Software version (Development)
15 3 minutes count up stop timer
16 Communication stage 0~3
17 Indoor On/Off 0- Off, 1-ON
18 Delta D
19 Running mode 0-Fan, 1- Heat, 2-Cool
20 Startup up timer
21 Comp initial control flag ok
22 Fuzzy control Delta H
23 Comp freq set pointer
24 Comp stop pointer
25 Comp limit pointer
26 Comp limit speed Max r/s
27 Discharge high temp zone 0-Normal, Other-Active
28 High pressure zone 0-Normal, Other-Active

90
Troubleshooting A5LCY-I-2010

Parameter
Parameter Description Unit/ range
Number
29 Current control zone 0-Normal, Other-Active
30 Oil return status 0-Normal, Other-Active
31 De-ice setting 0-Normal, Other-Active
32 Dew drop setting 0-Normal, Other-Active
33 Heatsink protection zone 0-Normal, Other-Active
34 Turbo setting 0-Normal, Other-Active
35 Silent setting 0-Normal, Other-Active
36 Low ambient zone 0-Normal, Other-Active
37 Defrost status 0-Normal, Other-Active
38 Pump down status 0-Normal, Other-Active
39 O/D capacity flag 0- Comp off, 1- Comp On
40 O/D output capacity In %
41 Target discharge temp
42 EXV control status 0-Initial , 1- Feedback
43 Indoor fan tap
44 O/D error code
45 I/D error code
46 Low voltage control zone 0-Normal, Other-Active
47 Gas leak detection 0-Normal, Other-Active
48 Discharge sensor disconnected 0-Normal, Other-Active
49 Official test setting 0-Normal, Other-Active
50 Skip frequency flag 0-Normal, Other-Active
51 Last O/D error code
52 2nd last O/D error code
53 3rd last O/D error code

Error Code Diagnosis by Unit Last State Memory Using Wireless Handset
1. Remove battery from wireless handset.
2. Wait for the display to finally go off (as this handset uses very small amount of power, hence it takes
longer for the memory to reset).
3. Replace battery again and immediately (before display comes back on the LCD screen), press on Mode
and ON/OFF buttons together until you see “00” is being displayed.
4. Press Mode button to 5:00.
5. Press ON/OFF button once.
6. After that, remove battery from wireless handset and wait until the display has gone off. Then, replace
battery again into the handset.
7. Finally, repeat the fault diagnosis steps by wireless handset GS02 above.

Error Code Diagnosis by Unit Last State Memory Using Wired Handset
1. Press SLEEP and TIMER ACTIVE buttons together until error code starts flashing on the fan speed
indicator area.

91
A5LCY-I-2010 Exploded View and Part List

Exploded View and Part List


Outdoor Unit
Model: A5LCY 10/15DR

14 2

28 16

20
7
19

4
21

6
23

22 27

15 11

9
22
17
8
18

25

29 5 26 30 13 1 10 12 24

Note: All exploded view and part list are subjected to change by the manufacturer without prior notice

92
Exploded View and Part List A5LCY-I-2010

Outdoor Unit
Model: A5LCY 10/15DR
No Description No Description
1 Assy. Botttom Frame 16 Assy. Control Box
2 Top Plate 17 EXV Solenoid Coil
3 Right Side Plate 18 Assy. 4WV Coil
4 Left Side Plate 19 Reactor
5 Front Panel 20 Assy. Reactor Wire
6 Sealing Material 21 Thermistor Holder
7 Assy. Coil 22 Assy. Propeller Fan
8 Assy. 4WV 23 Assy. Panel Partition
9 Valve, Rev 4 Way 24 Stop Valve Mounting Plate
10 Valve, 3 Way 1/2” 25 Assy. Stop Valve Cover
11 Assy. EXV w/o Service Valve 26 Ins. Comp. Sound
12 Valve, 2 Way 1/4” 27 Releasable Tie
13 Compressor 28 Handle
14 Assy. Fan Motor 29 Front Grille
15 Motor 30 Drain Joint

Note: All exploded view and part list are subjected to change by the manufacturer without prior notice

93
A5LCY-I-2010 Exploded View and Part List

Outdoor Unit
Model: A5LCY 20/25CR

No Description No Description
1 Assy. Base Fan 11 Panel, Right Back
2 Panel, Service 12 Assy. Valve Bracket
3 Panel, Top 13 Assy. 4WV
4 Panel, Front/Left 14 Assy. EXV
5 Assy. Coil 15 Assy. Partition
6 Assy. Propeller Fan 16 Nut M8, with flange
7 Assy. Control Box 17 Bracket, Motor
8 Assy. Valve Cover 18 Plastic, Handle
9 Compressor 19 Motor
10 Plastic, Front Grille

Note: All exploded view and part list are subjected to change by the manufacturer without prior notice

94
Exploded View and Part List A5LCY-I-2010

Indoor Unit
Model: A5WMY 10/15JR

16

15
8
14

13

11

12

18 10
4 9
3
17
1

20

2
19

No Description No Description
1 Assy. Front Grille 11 Blower
2 Panel 12 Assy. Installation Plate
3 Disch. Grille Hor.Blade Assy. 13 Right Side Panel
4 Assy. Bottom Frame 14 Cover, Drip Proof
5 Assy. Control Box 15 Clip, Coil Sensor
6 Assy. Service Cover 16 Assy. Heat Exchanger
7 Assy. Piping Fixture 17 Assy. Drain Hose
8 Motor 18 Fan Bearing Vibration Absorber
9 Motor Mounting Plate (1) 19 Air Filter
10 Motor Mounting Plate (2) 20 Assy. Control Module

Note: All exploded view and part list are subjected to change by the manufacturer without prior notice

95
A5LCY-I-2010 Exploded View and Part List

Indoor Unit
Model: A5WMY 20/25JR

No Description No Description
1 Assy. Chasis 10 Assy. Control Box
2 Motor 11 Assy. Control Module
3 Blower 12 Cover, Control Box
4 Fan Bush 13 Cover, Service
5 Cover, Motor 14 Assy. Mounting Plate
6 Assy. Heat Exchanger 15 Assy. Front Cover
7 Assy. Air Discharge Housing 16 Cover, Front
8 Assy. Louver 17 Intake Grille
9 Hose 18 Filter

Note: All exploded view and part list are subjected to change by the manufacturer without prior notice

96
Exploded View and Part List A5LCY-I-2010

Indoor Unit
Model: PLCKY-CR

No Description No Description
1 Frame 11 Lingkage, Motor Cover
2 Assy. Intake Grille B 12 Assy. Bracket Receiver (LED/SLM)
3 Filter 13 Assy. Motor
4 Lock, Grille 14 Crank, Connector
5 Discharge, Foam 15 Louver, Holder
6 Discharge, Foam LED 16 Cross, Crank
7 Discharge, Foam Short 17 Ins. Long
8 Louver 18 Ins. Short
9 Louver, LED 19 Ins. Corner
10 Lingkage, Cover

Note: All exploded view and part list are subjected to change by the manufacturer without prior notice

97
A5LCY-I-2010 Exploded View and Part List

Indoor Unit
Model: A5CKY 10/15/20CR

Note: All exploded view and part list are subjected to change by the manufacturer without prior notice

98
Exploded View and Part List A5LCY-I-2010

Indoor Unit
Model: A5CKY 10/15/20CR
No Description No Description
1 Assy. Base 14 Bush, Pump
2 Assy. Casing 15 Assy. Drain Pump Support Bracket
3 Assy. Heat Exchanger 16 Assy. End Plate Support
4 Cover, Fan 17 Clip, Coil Sensor
5 Blower 18 Support, Heat Exchanger
6 Plate, Wire 19 Cover, Terminal
7 Motor 20 Assy. Cover Wire
8 Bush, Motor 21 Connector, Drain
9 Bush, Motor Ring 22 Hose, Drain
10 Assy. Control Box 23 Assy. Cover Valve
11 Pump, Water 24 Assy. Drain Pan
12 Switch, Water Level 25 Bush, Wire
13 Bush, Wire 26 Cover, Wire Bracket

Note: All exploded view and part list are subjected to change by the manufacturer without prior notice

99
A5LCY-I-2010 Exploded View and Part List

Indoor Unit
Model: PLCKY-ER

No Description No Description
1 Front, Frame 8 Crank Connector
2 Assy., Intake Grille 9 Assy., LED
3 Assy., Air Discharge Main 10 Wire, Guide
4 Assy., Air Discharge Main Right 11 Cover, Cross Connector
5 Assy., Air Discharge Main Left 12 Assy., Cover Corner A
6 Air Filter, CK-A/AR 13 Assy., Cover Corner B
7 Assy., Air Swing Motor 14 Mounting Plate

Note: All exploded view and part list are subjected to change by the manufacturer without prior notice

100
Exploded View and Part List A5LCY-I-2010

Indoor Unit
Model: A5CKY 20/25ER

No Description No Description
1 Assy. Base Pan 16 Cover, Wire B
2 Assy. Coil 17 Bracket, Hanger A
3 Assy. Coil Bracket 18 Bracket, Hanger B
4 Assy. Drain Pump Mounting 19 Bracket, Hanger C
5 Assy. Panel Side Back 20 Fresh Air Adaptor
6 Assy. Side Panel Front 21 Assembly, Valve Plate
7 Assy. Motor & Rubber 22 Assy. Air Guide
8 Blower, Turbo Fan DIA462 X 171.5 3P085496-1 23 Assy. Partition Holder
9 Assy. Drain Pan 24 Cover, Wire
10 Assy. Fan Cover 25 Switch Water Level 1A - CK Drain Pump
11 Assy. Cover Control Box 26 Pump, Water PC-04226-OYOB YCK
12 Assy. Control Box 27 Hose, Drain PE 18.3 X 0.5 X 315.0
13 Assy. Cover Terminal 28 Connector, Drain
14 Support, Coil 29 Ins., Drain Connector
15 Cover, Wire A

Note: All exploded view and part list are subjected to change by the manufacturer without prior notice

101
A5LCY-I-2010 Exploded View and Part List

Indoor Unit
Model: A5CCY 10/15/20/25CR

No Description No Description
1 Cabinet 9 Assy. Blower Left
2 Assy. Fan Deck 10 Motor
3 Assy. Heat Exchanger Parts Not in Diagram
4 Assy. Drain Pan Handset, Wired
5 Assy. Secondary Drain Pan Air Filter
6 Hanger Holder, Thermistor
7 Control Module Clip, Coil Sensor
8 Assy. Blower Right

Note: All exploded view and part list are subjected to change by the manufacturer without prior notice

102
Exploded View and Part List A5LCY-I-2010

Indoor Unit
Model: A5CMY 15/20/25ER

Note: All exploded view and part list are subjected to change by the manufacturer without prior notice

103
A5LCY-I-2010 Exploded View and Part List

Indoor Unit
Model: A5CMY 15/20/25ER
No Description No Description
1 Assy. Top Panel 12 Assy. Panel Bottom
2 Assy. Heat Exchanger 13 Cover, Hanger L1 (C)
3 Assy. Vane 14 Cover, Hanger L2 (D)
4 Assy. Drain Pan 15 Cover, Hanger R1 (A)
5 Assy. Control Box 16 Cover, Hanger R2 (B)
6 Terminal Box Cover 17 Bracket, Mounting
7 Motor 18 Control Box Cover
8 Bracket, Motor Parts Not in Diagram
9 Blower Handset, Wireless
10 Housing, Blower Control Module
11 Motor, Louver Intake Grille

Note: All exploded view and part list are subjected to change by the manufacturer without prior notice

104
While upmost care is taken in ensuring that all details in the publication are correct at time of going to press, we are constantly striving for
improvement and therefore reserve the rights to alter model specifications and equipment without prior notice. Details of speci fications
andequipment are also subject to change to suit local conditions and equirements and not all models are available in every market.

You might also like