Abuja Project Output Hap

The document provides an air system sizing summary for the DATA HALL of the INTERKEL project located in Abuja, Nigeria, detailing various air system specifications and calculations. It includes central cooling coil and heating coil sizing data, supply fan sizing, outdoor ventilation air data, and zone peak sensible loads. The analysis covers design cooling and heating loads, system psychrometrics, and airflow rates necessary for effective climate control within the data hall.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
17 views

Abuja Project Output Hap

The document provides an air system sizing summary for the DATA HALL of the INTERKEL project located in Abuja, Nigeria, detailing various air system specifications and calculations. It includes central cooling coil and heating coil sizing data, supply fan sizing, outdoor ventilation air data, and zone peak sensible loads. The analysis covers design cooling and heating loads, system psychrometrics, and airflow rates necessary for effective climate control within the data hall.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 8

Air System Sizing Summary for DATA HALL

Project Name: INTERKEL 01-22-2025


Prepared by: Sterling And Wilson 06:55PM

Air System Information


Air System Name DATA HALL Number of zones 1
Equipment Class PKG VERT Floor Area 2241.6 ft²
Air System Type SZCAV Location ABUJA, Nigeria

Sizing Calculation Information


Calculation Months Jan to Dec Zone CFM Sizing Sum of space airflow rates
Sizing Data Calculated Space CFM Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 166.0 Tons Load occurs at Jun 1500
Total coil load 1992.0 MBH OA DB / WB 105.3 / 85.1 °F
Sensible coil load 1979.3 MBH Entering DB / WB 76.2 / 63.3 °F
Coil CFM at Jun 1500 106679 CFM Leaving DB / WB 58.2 / 56.9 °F
Max block CFM 106679 CFM Coil ADP 56.2 °F
Sum of peak zone CFM 106679 CFM Bypass Factor 0.100
Sensible heat ratio 0.994 Resulting RH 50 %
CFM/Ton 642.7 Design supply temp. 58.0 °F
ft²/Ton 13.5 Zone T-stat Check 1 of 1 OK
BTU/(hr·ft²) 888.6 Max zone temperature deviation 0.0 °F
Water flow @ 15.0 °F rise N/A

Central Heating Coil Sizing Data


No central heating coil loads occurred during this calculation.

Supply Fan Sizing Data


Actual max CFM 106679 CFM Fan motor BHP 39.44 BHP
Standard CFM 101803 CFM Fan motor kW 31.29 kW
Actual max CFM/ft² 47.59 CFM/ft² Fan static 2.00 in wg

Outdoor Ventilation Air Data


Design airflow CFM 199 CFM CFM/person 39.87 CFM/person
CFM/ft² 0.09 CFM/ft²

Hourly Analysis Program 5.11 Page 1 of 8


Zone Sizing Summary for DATA HALL
Project Name: INTERKEL 01-22-2025
Prepared by: Sterling And Wilson 06:55PM

Air System Information


Air System Name DATA HALL Number of zones 1
Equipment Class PKG VERT Floor Area 2241.6 ft²
Air System Type SZCAV Location ABUJA, Nigeria

Sizing Calculation Information


Calculation Months Jan to Dec Zone CFM Sizing Sum of space airflow rates
Sizing Data Calculated Space CFM Sizing Individual peak space loads

Zone Terminal Sizing Data

Reheat Zone Zone


Design Minimum Reheat Coil Htg Unit Htg Unit Mixing
Supply Supply Coil Water Coil Water Box Fan
Airflow Airflow Zone Load gpm Load gpm Airflow
Zone Name (CFM) (CFM) CFM/ft² (MBH) @ 20.0 °F (MBH) @ 20.0 °F (CFM)
Zone 1 106679 106679 47.59 0.0 - 0.0 - 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (MBH) Cooling Load (MBH) (ft²)
Zone 1 1869.1 Aug 1500 10.0 2241.6

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (MBH) Load (CFM) (MBH) (ft²) CFM/ft²
Zone 1
DATA HALL 1 1869.1 Aug 1500 106679 10.0 2241.6 47.59

Hourly Analysis Program 5.11 Page 2 of 8


Air System Design Load Summary for DATA HALL
Project Name: INTERKEL 01-22-2025
Prepared by: Sterling And Wilson 06:55PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jun 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 105.3 °F / 85.1 °F HEATING OA DB / WB 58.5 °F / 43.9 °F
Sensible Latent Sensible Latent
ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 0 ft² 0 - 0 ft² - -
Wall Transmission 2486 ft² 14704 - 2486 ft² 6445 -
Roof Transmission 2242 ft² 14635 - 2242 ft² 3108 -
Window Transmission 0 ft² 0 - 0 ft² 0 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 2242 ft² 0 - 2242 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 4483 W 15296 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 508000 W 1733288 - 0 0 -
People 5 1225 1025 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 5% / 5% 88957 51 5% 478 0
>> Total Zone Loads - 1868105 1076 - 10031 0
Zone Conditioning - 1866504 1076 - 8571 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 106679 CFM 0 - 106679 CFM 0 -
Ventilation Load 199 CFM 5999 11565 199 CFM 2487 2336
Supply Fan Load 106679 CFM 106762 - 106679 CFM -106762 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 1979265 12641 - -95704 2336
Central Cooling Coil - 1979266 12705 - -95704 0
Central Heating Coil - 0 - - 0 -
>> Total Conditioning - 1979266 12705 - -95704 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program 5.11 Page 3 of 8


Zone Design Load Summary for DATA HALL
Project Name: INTERKEL 01-22-2025
Prepared by: Sterling And Wilson 06:55PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Aug 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 106.3 °F / 85.1 °F HEATING OA DB / WB 58.5 °F / 43.9 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 0 ft² 0 - 0 ft² - -
Wall Transmission 2486 ft² 15003 - 2486 ft² 6445 -
Roof Transmission 2242 ft² 15285 - 2242 ft² 3108 -
Window Transmission 0 ft² 0 - 0 ft² 0 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 2242 ft² 0 - 2242 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 4483 W 15296 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 508000 W 1733288 - 0 0 -
People 5 1225 1025 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 5% / 5% 89005 51 5% 478 0
>> Total Zone Loads - 1869102 1076 - 10031 0

Hourly Analysis Program 5.11 Page 4 of 8


System Psychrometrics for DATA HALL
Project Name: INTERKEL 01-22-2025
Prepared by: Sterling And Wilson 06:55PM

June DESIGN COOLING DAY, 1500

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)
Ventilation Air Inlet 105.3 0.02287 199 400 5999 11565
Vent - Return Mixing Outlet 76.2 0.01009 106679 800 - -
Central Cooling Coil Outlet 58.2 0.01006 106679 800 1979266 12705
Central Heating Coil Outlet 58.2 0.01006 106679 800 0 -
Supply Fan Outlet 59.1 0.01006 106679 800 106762 -
Cold Supply Duct Outlet 59.1 0.01006 106679 800 - -
Zone Air - 76.1 0.01006 106679 801 1866504 1076
Return Plenum Outlet 76.1 0.01006 106679 801 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.031 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4529.6 BTU/(hr-CFM)
Site Altitude = 1289.0 ft

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (BTU/hr) Mode (BTU/hr) (°F) (CFM) (ppm) (BTU/hr) (BTU/hr)
Zone 1 1868105 Cooling 1866504 76.1 106679 801 0 0

Hourly Analysis Program 5.11 Page 5 of 8


System Psychrometrics for DATA HALL
Project Name: INTERKEL 01-22-2025
Prepared by: Sterling And Wilson 06:55PM

WINTER DESIGN HEATING

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)
Ventilation Air Inlet 58.5 0.00304 199 400 -2487 -2336
Vent - Return Mixing Outlet 70.6 0.00562 106679 799 - -
Central Cooling Coil Outlet 69.7 0.00562 106679 799 95704 0
Central Heating Coil Outlet 69.7 0.00562 106679 799 0 -
Supply Fan Outlet 70.7 0.00562 106679 799 106762 -
Cold Supply Duct Outlet 70.7 0.00562 106679 799 - -
Zone Air - 70.6 0.00562 106679 800 -8571 0
Return Plenum Outlet 70.6 0.00562 106679 800 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.031 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4529.6 BTU/(hr-CFM)
Site Altitude = 1289.0 ft

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (BTU/hr) Mode (BTU/hr) (°F) (CFM) (ppm) (BTU/hr) (BTU/hr)
Zone 1 -10031 Deadband -8571 70.6 106679 800 0 0

Hourly Analysis Program 5.11 Page 6 of 8


System Psychrometrics for DATA HALL
Project Name: INTERKEL 01-22-2025
Prepared by: Sterling And Wilson 06:55PM

Location: ABUJA, Nigeria


Altitude: 1289.0 ft.
Data for: June DESIGN COOLING DAY, 1500

1. Outdoor Air
2. Mixed Air
3. Central Cooling Coil Outlet 1 0.024
4. Supply Fan Outlet
5. Room Air
0.022
0.020

Specific Humidity ( lb/lb )


0.018
0.016
0.014
0.012
34 2
5 0.010
0.008
0.006
0.004
0.002
0.000
30 40 50 60 70 80 90 100 110
Temperature ( °F )

Hourly Analysis Program 5.11 Page 7 of 8


System Psychrometrics for DATA HALL
Project Name: INTERKEL 01-22-2025
Prepared by: Sterling And Wilson 06:55PM

Location: ABUJA, Nigeria


Altitude: 1289.0 ft.
Data for: WINTER DESIGN HEATING
0.020
1. Outdoor Air
2. Mixed Air
3. Central Cooling Coil Outlet
4. Supply Fan Outlet 0.018
5. Room Air

0.016

Specific Humidity ( lb/lb )


0.014

0.012

0.010

0.008
324 0.006
5
1 0.004

0.002

0.000
30 40 50 60 70 80 90 100
Temperature ( °F )

Hourly Analysis Program 5.11 Page 8 of 8