NI-DAQmx User Manual
Contents
NI-DAQmx User Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
New Features and Changes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
NI-DAQmx Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
LabVIEW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Creating an Application with LabWindows/CVI . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Measurement Studio with Visual C++, Visual C#, or Visual Basic .NET . . . . . . . . . . . . . . . 26
ANSI C Application without LabWindows/CVI . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Creating a .NET Application without Measurement Studio . . . . . . . . . . . . . . . . . . . . . . . . 27
SignalExpress . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Getting Started with NI-DAQmx . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Finding Examples . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Common Applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Measuring Acceleration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Measuring Acceleration Programming Flowchart. . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Measuring Analog Frequency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Measuring Analog Frequency Programming Flowchart . . . . . . . . . . . . . . . . . . . . . . 37
Hysteresis with Analog Frequency Measurements . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Measuring Angular Displacement. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Measuring Position with Encoders Programming Flowchart . . . . . . . . . . . . . . . . . . 39
Measuring Position with an RVDT or LVDT Programming Flowchart . . . . . . . . . . . 40
Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Event Response . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Control Loops . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Edge Counting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Edge Counting Programming Flowchart. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Measuring Charge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Measuring Charge Programming Flowchart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Measuring and Generating Current . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Measuring Current Programming Flowchart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Tips on Measuring AC Current . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Generating Current Programming Flowchart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
2 ni.com
NI-DAQmx User Manual
© National Instruments 3
NI-DAQmx User Manual
4 ni.com
NI-DAQmx User Manual
© National Instruments 5
NI-DAQmx User Manual
6 ni.com
NI-DAQmx User Manual
Skew . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 163
Methods of Synchronization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 163
Start Trigger Synchronization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 163
Sample Clock Synchronization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 164
Reference Clock Synchronization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 164
Master Timebase Synchronization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 166
Sample Clock Timebase Synchronization . . . . . . . . . . . . . . . . . . . . . . . 167
Mixed-Clock Synchronization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 168
Counter Synchronization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 169
Trigger Skew Correction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 169
Subsystem . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 170
Timing Engines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 170
Events . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 172
Exported Signal Behaviors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 173
Software Events . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 174
Reading and Writing Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 176
Selecting Read and Write Data Format and Organization . . . . . . . . . . . . . . . . . . . . 176
Data Formats in NI-DAQmx. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 176
Data Organization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 179
Digital Data (Integer Format) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 180
Interleaving . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 182
Raw Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 183
Unscaled Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 183
Waveform Timing Limitations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 184
Buffering. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 184
How Is Buffer Size Determined? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 185
Continuous Acquisition and Generation with Finite Buffer Size . . . . . . . . . 187
Reference Triggering Impact on Buffers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 188
Controlling Where in the Buffer to Read Samples. . . . . . . . . . . . . . . . . . . . . . 188
Read Status Attributes/Properties and Buffers . . . . . . . . . . . . . . . . . . . . . . . . 189
Controlling Where in the Buffer to Write Samples . . . . . . . . . . . . . . . . . . . . . 189
Write Status Attributes/Properties and Buffers . . . . . . . . . . . . . . . . . . . . . . . . 189
Glitching . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 190
Data Transfer Mechanisms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 191
Regeneration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 193
TDMS Logging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 193
© National Instruments 7
NI-DAQmx User Manual
8 ni.com
NI-DAQmx User Manual
© National Instruments 9
NI-DAQmx User Manual
10 ni.com
NI-DAQmx User Manual
© National Instruments 11
NI-DAQmx User Manual
12 ni.com
NI-DAQmx User Manual
© National Instruments 13
NI-DAQmx User Manual
14 ni.com
NI-DAQmx User Manual
© National Instruments 15
NI-DAQmx User Manual
16 ni.com
NI-DAQmx User Manual
© National Instruments 17
NI-DAQmx User Manual
18 ni.com
NI-DAQmx User Manual
TEDS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 627
Writing Data to TEDS Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 628
Control Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 628
Proportional-Integral-Derivative (PID) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 629
Real Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 630
Loop Cycle Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 630
Jitter Overview for Control Applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 630
Event Response . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 631
© National Instruments 19
NI-DAQmx User Manual
Related information:
• Download NI-DAQmx
• NI-DAQmx Release Notes
• License Setup and Activation
• Dimensional Drawings
• Product Certifications
• Letter of Volatility
• Discussion Forums
• NI Learning Center
• NI-DAQmx LabVIEW API Reference
• NI-DAQmx Properties Reference
20 ni.com
New Features and Changes
New Features
Added support for the following NI mioDAQ devices.
• USB-6421
• USB-6423
• USB-6451
• USB-6453
Behavior Changes
• Support for VB6 has been removed.
Behavior Changes
NI-DAQmx support for VB6 is expected to be removed in NI-DAQmx 2024 Q3. NI-DAQmx
2024 Q2 will be the last release to support VB6.
© National Instruments 21
New Features and Changes
New Features
Support has been added for the following devices:
• TS-15050 DIO P0
• TS-15100
• TS-15110
• TS-15120
• TS-15130
• TS-15200
22 ni.com
NI-DAQmx Overview
NI-DAQmx Overview
What is DAQmx?
NI-DAQmx is the driver software you use to communicate with and control your NI data
acquisition (DAQ) devices. It includes an extensive library of functions and VIs you can
call from your application software, such as LabVIEW or LabWindows/CVI, to program
your devices.
For information on getting started, refer to Getting Started with NI-DAQmx. Refer to
Device Support in NI-DAQmx in the NI-DAQmx Readme for a list of devices supported in
NI-DAQmx.
For more information, refer to the Measurement & Automation Explorer Help for NI-
DAQmx or Getting Started.
© National Instruments 23
NI-DAQmx Overview
For more information, refer to the DAQ Assistant Help or Getting Started.
• LabVIEW
• LabWindows/CVI
• Measurement Studio with Visual C++, Visual C#, or Visual Basic .NET
• ANSI C Application without LabWindows/CVI
• .NET Application without Measurement Studio
• SignalExpress
Related concepts:
Related information:
24 ni.com
NI-DAQmx Overview
LabVIEW
If you program your NI-DAQmx-supported device in LabVIEW, you can interactively
create virtual channels—both global and local—and tasks by launching the DAQ
Assistant from MAX or from within LabVIEW. You also can create local virtual channels
and tasks, and write your own applications using the NI-DAQmx API.
To learn about which NI-DAQmx VIs are most commonly used when creating a NI-
DAQmx data acquisition application, see Learn 10 Functions in NI-DAQmx and Handle
80% of your Data Acquisition Applications.
For help with NI-DAQmx VIs, refer to DAQmx - Data Acquisition VIs and Functions.
For help with using the DAQ Assistant with LabVIEW, refer to Using the DAQ Assistant to
Automatically Generate LabVIEW Code.
For help with NI-DAQmx functions, refer to NI-DAQmx C Function Reference Help. For
general help with programming in LabWindows/CVI, refer to LabWindows/CVI Help,
accessible through Start»All Programs»National Instruments»LabWindows
CVI»LabWindows CVI Help.
For help with using the DAQ Assistant with LabWindows/CVI, refer to Using the DAQ
Assistant in NI LabWindows/CVI.
© National Instruments 25
NI-DAQmx Overview
Related information:
For help with NI-DAQmx methods and properties, refer to the NI-DAQmx .NET Class
Library or the NI-DAQmx Visual C++ Class Library included in the NI Measurement
Studio Help. For general help with programming in Measurement Studio, refer to the
NI Measurement Studio Help, which is fully integrated with the Microsoft Visual Studio
.NET help. To view this help file in Visual Studio. NET, select Measurement Studio»NI
Measurement Studio Help.
For help with using the DAQ Assistant with Measurement Studio, refer to Using the DAQ
Assistant in Measurement Studio.
Related information:
26 ni.com
NI-DAQmx Overview
include the NI-DAQmx header file, nidaqmx.h, in your source code files. You can
find this header file at NI-DAQ\DAQmx ANSI C Dev\include.
3. Add the NI-DAQmx import library, nidaqmx.lib, to the project. The import
library files are located under NI-DAQ\DAQmx ANSI C Dev\lib\.
4. To view examples of NI-DAQmx applications, go to the NI-DAQ\Examples\
DAQmx ANSI C directory.
5. Build your application.
For help with NI-DAQmx functions, refer to the NI-DAQmx C Reference Help, which is
installed by default at Start»All Programs»National Instruments»NI-DAQ»Text-Based
Code Support»NI-DAQmx C Reference Help.
For help with using the DAQ Assistant with ANSI C, refer to Using NI-DAQmx in Text
Based Programming Environments.
The installed documentation contains the NI-DAQmx API overview, measurement tasks
and concepts, and function reference. This help is fully integrated into the Visual
Studio .NET documentation. To view the NI-DAQmx .NET documentation, go to
Start»All Programs»National Instruments»NI-DAQ»NI-DAQmx .NET Reference Help.
Expand NI Measurement Studio Help»Measurement Studio Support for NI-DAQmx
Overview» NI-DAQmx .NET class library to view the function reference. Expand NI
Measurement Studio Help»NI Measurement Studio .NET Class Library»Using the
Measurement Studio .NET Class Libraries to view conceptual topics for using NI-
DAQmx with Visual C# and Visual Basic .NET.
To get to the same help topics from within Visual Studio, go to Help»Contents. Select
Measurement Studio from the Filtered By drop-down list and follow the previous
instructions.
© National Instruments 27
NI-DAQmx Overview
For help with using the DAQ Assistant with Visual Studio .NET, refer to Using NI-DAQmx
in Text Based Programming Environments.
SignalExpress
If you use your NI-DAQmx-supported device in SignalExpress, you can create a project
that includes NI-DAQmx steps. With SignalExpress, you can log and analyze data. You
can also add global virtual channels that you created in MAX to your NI-DAQmx steps in
SignalExpress. Refer to the DAQ Assistant Help for additional information.
For help with using the DAQ Assistant with SignalExpress, refer to Taking an NI-DAQmx
Measurement in SignalExpress. For general help with programming in SignalExpress,
refer to SignalExpress Help.
Related information:
28 ni.com
Getting Started with NI-DAQmx
Related concepts:
• NI-DAQmx Overview
• Finding Examples
• Troubleshooting
Finding Examples
Each API includes a collection of programming examples to help you get started
developing an application. You can modify example code and save it in an application.
You can use examples to develop a new application or add example code to an existing
application.
To run examples without hardware installed, you can use an NI-DAQmx simulated
device. In MAX, refer to the Measurement & Automation Explorer Help for NI-DAQmx by
selecting Help»Help Topics» NI-DAQmx for information on NI-DAQmx simulated
devices.
© National Instruments 29
Getting Started with NI-DAQmx
To find the locations of examples for your software application, refer to the following
table.
Note Visual Studio 2003 and later do not require Measurement Studio.
Troubleshooting
Installation and Configuration
Refer to the DAQ Getting Started Guide for general installation and configuration
instructions.
Use the following resources if you have problems installing your DAQ hardware and/or
software:
30 ni.com
Getting Started with NI-DAQmx
• Refer to NI DAQ Setup and Support on ni.com for information on getting started
with NI DAQ, support, drivers and code, and other resources.
• Refer to ni.com/kb for documents on troubleshooting common installation and
programming problems and for answering frequently asked questions about NI
products.
• If you think you have damaged your device and need to return your NI hardware
for repair or calibration, refer to sending a NI board in for repair or calibration.
For LabWindows/CVI users, if the Data Acquisition function panel is disabled, you may
need to uninstall NI-DAQmx and reinstall it, making sure that you add support for
LabWindows/CVI. If you have installed LabWindows/CVI support and Data Acquisition
is still dimmed, select Library»Customize. In the Customize Library Menu dialog box,
check Data Acquisition, and restart LabWindows/CVI. You might also need to verify
that the dataacq.lib is in the bin directory.
Programming
To help you get started programming, you can use the shipping examples for your ADE.
You can also visit NI's extensive library of technical support resources at ni.com/
support.
You can interactively configure global virtual channels and tasks with the DAQ
Assistant. For NI application software such as LabVIEW, you can use the DAQ Assistant
to generate code.
You can use NI I/O Trace to analyze the functions you have called in the API with NI
application software. With NI I/O Trace, you can watch the order of execution of the
application and locate errors as they happen.
© National Instruments 31
Getting Started with NI-DAQmx
External Connections
In addition to the information on making signal connections in this help file, the
Connection Diagram tab in the DAQ Assistant within MAX shows you how to connect
signals.
Calibration
CPU Usage
NI-DAQmx tasks use 100% of the CPU if no other processes are running. However, as
soon as another process requires the CPU, the NI-DAQmx task yields to that process.
Related concepts:
• Finding Examples
32 ni.com
Common Applications
Common Applications
Measuring Acceleration
Acceleration is a change in velocity with respect to time. An accelerometer is a
transducer that represents acceleration as a voltage. Accelerometers also can measure
vibration and shock. Accelerometers typically convert acceleration measured in g's to
voltage. For example, a sensor with a rated output of 10 mV/g should produce 50 mV
when subjected to 5 g of acceleration.
Related concepts:
© National Instruments 33
Common Applications
Related concepts:
Devices that measure analog frequency, such as DSA devices and the SCXI-1126, have
34 ni.com
Common Applications
circuitry that produces triggers of the same frequency as the measured signal. Every
time the signal passes from threshold level minus hysteresis to threshold level, a
trigger occurs. A pulse generator uses these triggers and produces a pulse once every
frequency cycle. The input frequency range sets the width of this pulse. As the input
frequency range increases, the pulse width grows smaller. This pulse train is then
converted to a DC signal that has a level proportional to the duty cycle of the pulse
train. The duty cycle is the fraction of a period of the pulse train when the pulse is
occurring. The DC signal has a voltage that is proportional to the input frequency and
can therefore be scaled to that frequency value.
For devices that cannot measure frequency directly, you need to use software
algorithms, such as the Fast Fourier Transform (FFT), to convert voltage to frequency.
LabVIEW Full and Professional Development Systems contains advanced analysis VIs
that handle these transformations. The LabWindows™/CVI™ full development system
also contains advanced analysis functions to help you measure analog frequency.
Regardless of whether you use existing VIs or functions or create your own, you need to
sample at least twice as fast as the highest frequency component in the signal you are
acquiring.
The Nyquist Theorem states that the highest frequency you can accurately represent is
half the sampling rate. For instance, to measure the frequency of a 100 Hz signal, you
need a sampling rate of at least 200 S/s. In practice, you should use sampling rates of 5
to 10 times the expected frequencies to improve accuracy of measurements.
In addition to sample rate, you need to determine the number of samples to acquire.
You must sample a minimum of three cycles of the analog signal. For example, you
need to collect at least 15 samples, or points, if you use a sampling rate of 500 S/s to
measure the frequency of a 100 Hz signal. Because you sample about five times faster
than the signal frequency, you sample about five points per cycle of the signal. You
need data from three cycles, so 5 points x 3 cycles = 15 points. In practice, however,
you should acquire 10 or more cycles to improve accuracy of measurements, so you
should acquire 50 or more samples.
The number of points you collect determines the number of frequency bins that the
samples fall into. The size of each bin is the sampling rate divided by the number of
points you collect. For example, if you sample at 500 S/s and collect 100 points, you
© National Instruments 35
Common Applications
The Nyquist frequency is the bandwidth of the sampled signal and is equal to half the
sampling frequency. Frequency components below the Nyquist frequency appear
normally. Frequency components above the Nyquist frequency appear aliased
between 0 and the Nyquist frequency. The aliased component is the absolute value of
the difference between the actual component and the closest integer multiple of the
sampling rate. For example, if you have a signal with a component at 800 Hz and you
sample at 500 S/s, that component appears aliased at 200 Hz because |800–(2 x 500)| =
200(Hz).
One way to eliminate aliased components is to use an analog hardware filter before
you digitize and analyze the frequency information. If you want to perform all the
filtering in software, you must first sample at a rate fast enough to correctly represent
the highest frequency component the signal contains. For example, with the highest
component at 800 Hz, the minimum sampling rate is 1,600 Hz, but you should sample
5 to 10 times faster than 800 Hz. If the frequency you want to measure is around 100
Hz, you can use a lowpass Butterworth filter with a cutoff frequency (fc) of 250 Hz to
filter out frequencies above 250 Hz and pass frequencies below 250 Hz.
Note LabVIEW includes Butterworth filters with the LabVIEW Full and
Professional Development Systems.
Lowpass Filter
The Ideal Filter in the figure is optimal. All frequencies above the Nyquist frequency are
36 ni.com
Common Applications
rejected. The Real Filter in the figure is what you might actually be able to accomplish
with a Butterworth filter. The passband is where Vout/Vin is close to 1. The stopband
occurs where Vout/Vin is close to 0. The frequencies gradually attenuate on the
transition region between 1 and 0.
Related concepts:
© National Instruments 37
Common Applications
Input Programming Flowcharts for additional flowcharts that can help you create an
application.
Related concepts:
On M Series devices, C Series devices, and NI-TIO-based devices, you can use the
counters to perform displacement measurements with quadrature encoders, or
angular encoders. You can measure angular position with X1, X2, and X4 angular
encoders. You can choose to do either a single-point or a buffered sample clock
displacement measurement.
You also can measure velocity with angular encoders, but you need to use a sample
clock with a fixed frequency. To measure velocity, use the following formula:
38 ni.com
Common Applications
V = D/T
The counter measures the position of the encoder using the A and B signals, which are
offset by 90°. The counter also supports the Z index, which provides a precise reference
point and is available on some encoders.
Related concepts:
© National Instruments 39
Common Applications
Related concepts:
40 ni.com
Common Applications
Related concepts:
© National Instruments 41
Common Applications
Control
You can create an event response or control loop application in any operating system
supported by NI-DAQmx. However, your application can only be deterministic if you
have the LabVIEW Real-Time module and use your application on a real-time
controller. This section assumes that you are using LabVIEW with NI-DAQmx to create a
control application. It does not assume that you have the LabVIEW Real-Time module
or the real-time controller.
Related concepts:
• Control Loops
Event Response
In a control application, an event is the same as an occurrence. This occurrence leads
to an action, or a response. An example is monitoring the temperature of an engine.
When the temperature rises too high, the engine slows down. The event, in this case,
would be the temperature rising above a predetermined level, and the response would
be the engine slowing down. Another example comes from manufacturing. In a
manufacturing line, a system senses when a part is in front of a station (the event) and
takes a reading or manipulates the part (the response). If the system does not sense
and respond to the presence of that part in a set amount of time, the manufacturing
line creates defective parts.
When creating an event response application, make sure you consider the amount of
time needed to respond to the event. For example, if the device controls the
temperature of your home, the time to react to events (changes in temperature) is less
critical than if the device controls a nuclear reactor. If the application is not time
critical, the application does not need to be deterministic, meaning that you do not
need the LabVIEW Real-Time Module or a real-time controller.
The relative priority of the task is important as well. Because LabVIEW is multi-
threaded, you can separate the application into tasks, each with its own priority. By
setting priorities, time-critical tasks can take precedence over non-time-critical tasks.
The time-critical task must periodically yield processor resources to the lower-priority
tasks so they can execute. By properly separating the time-critical task from lower
42 ni.com
Common Applications
priority tasks, you can reduce application jitter. Refer to the LabVIEW Real-Time
Module Concepts book in the LabVIEW Help for more information about assigning
priorities to tasks.
Related concepts:
• Finding Examples
Control Loops
A control application monitors and controls a system. The application continuously
loops by reading samples, processing data, and adjusting the output. You can use NI-
DAQmx and DAQ devices to create a control application. With the LabVIEW Real-Time
Module, you can create deterministic control applications.
The following block diagram shows a typical deterministic control loop application.
First, an analog value is read. This value corresponds to the process variable. This
value is compared to the set point, which is specified in the Ctrl Algrthm VI in the
diagram, and adjusted as necessary within the while loop, possibly using a PID
algorithm. The adjusted value is then written. This value corresponds to the actuator
output.
In the block diagram, the sampling rates are the same for analog input and output.
Because the example shown assumes a single DAQ device, the Start Trigger
synchronizes the analog input and analog output tasks. For multiple devices,
synchronization works differently. Refer to Synchronization for more information.
Notice also that the slave task—the analog output task—starts before the analog input
task. Finally, within the loop, the Wait for Next Sample Clock VI checks to make sure
that the loop executes within the specified sampling rate. If it does not, this VI returns
an error.
© National Instruments 43
Common Applications
Related concepts:
• Finding Examples
Edge Counting
Edge counting is when a device counts rising or falling edges using a counter channel.
You can choose to do either single point or buffered sample clock edge counting.
The following figure shows an example of edge counting in which the counter in a
device counts five edges on the input terminal.
With buffered edge counting, the device latches the number of edges counted onto
each active edge of the sample clock and stores the number in the buffer. There is no
built-in clock for buffered edge counting, so you must supply an external sample clock.
44 ni.com
Common Applications
In NI-DAQmx, when doing on-demand edge counting, you first arm the counter by
calling the Start function/VI. Each subsequent read returns the number of edges
counted since the counter was started. If you perform multiple reads without first
starting the counter, the counter implicitly starts and stops with each Read function/VI
call, and the number of counted edges is not cumulative between read calls.
On devices that support gate configuration along with timing engine pause triggering,
use the CI.CountEdges.Gate.Enable attribute/property to enable gate functionality.
With the exception of the NI 9361, you also can pause counting with on-demand edge
counting in NI-DAQmx by configuring a pause trigger. To configure a pause trigger, use
the trigger attributes/properties to set the source terminal of the digital trigger as well
as the level on which to pause.
Related concepts:
© National Instruments 45
Common Applications
Related concepts:
Measuring Charge
Electrical charge is a fundamental property of matter. Charge is a measurement of the
net effect of protons and electrons being unequally distributed. Piezoelectric
transducers produce a charge from physical stress, deformation, acceleration, or force.
Charge is measured in coulombs.
Related concepts:
46 ni.com
Common Applications
You can use charge sensors to measure physical phenomenon such as acceleration
and sound pressure with charge mode accelerometers and microphones. These
measurements can be converted from coulombs to the appropriate engineering units
using custom scales.
Related concepts:
© National Instruments 47
Common Applications
4 to 20 mA Loops
4 to 20 milliamp (4-20 mA) loops are commonly used in measurement systems. 4-20
mA loops couple a dynamic range with a live zero of 4 mA for open circuit detection in
a system that does not produce sparks. Other advantages include a variety of
compatible hardware, a long operating range, and low cost. 4-20 mA loops have a
variety of uses, including digital communications, control applications, and reading
remote sensors.
The purpose of the 4-20 mA current loop is for the sensor to transmit a signal in the
form of a current. In the following figure, the Level Sensor and Remote Sensor
Electronics are typically built into a single unit. An external 24 VDC supply powers the
sensor. The sensor regulates the current, which represents the value of what the
sensor measures, in this case, the fluid level in a tank.
The DAQ device reads the voltage drop across the 249 Ω resistor Rp, using Ohm's Law.
48 ni.com
Common Applications
Because the current is 4-20 mA and Rp is 249 Ω, V ranges from 0.996 V to 4.98 V, which
is within the range that DAQ devices can read. Although the equation is useful for
calculating the current, the current typically represents a physical quantity you want
to measure. In the following figure, the tank level measures 0 to 50 feet. 4 mA
represents 0 feet, and 20 mA represents 50 feet. L is the tank level, and I is the current.
Using the Ohm's Law equation and substituting 0.249 for the value of Rp, you can
derive L in terms of measured voltage:
Related concepts:
© National Instruments 49
Common Applications
Related concepts:
50 ni.com
Common Applications
Related concepts:
© National Instruments 51
Common Applications
Related concepts:
52 ni.com
Common Applications
The duty cycle of a pulse is between 0 and 1 and is often expressed as a percentage.
Refer to the following figure for examples of duty cycles. A pulse with a high time equal
to the low time has a duty cycle of 0.5, or 50%. A duty cycle less than 50% indicates
that the low time is greater than the high time, and a duty cycle greater than 50%
indicates that the high time is greater than the low time.
© National Instruments 53
Common Applications
Creating a Program
Related concepts:
54 ni.com
Common Applications
Digital frequency and period are examples of counter measurements. Refer to Counter
Programming Flowcharts for additional flowcharts that can help you create an
application.
Related concepts:
Measuring Force
Force is an influence that changes the motion, size, or shape of an object. Many types
of sensors exist for measuring force. Some are piezoelectric sensors, typically used for
dynamic force measurements, such as impact testing. Others are bridge-based
sensors, typically used for measuring static or slow-changing loads.
© National Instruments 55
Common Applications
When selecting the scaling type, choose the one that best matches the specifications
for your sensor.
Related concepts:
56 ni.com
Common Applications
Related concepts:
© National Instruments 57
Common Applications
The Counter Timebase Rate is a known frequency and is usually a built-in time source.
If the counter timebase rate is unknown, you only can make measurements only in
terms of ticks of the counter timebase. This may be the case if you are using an
external signal for the counter timebase, and the frequency of the external signal is
unknown or aperiodic.
Related concepts:
58 ni.com
Common Applications
Digital frequency and period are examples of counter measurements. Refer to Counter
Programming Flowcharts for additional flowcharts that can help you create an
application.
Related concepts:
© National Instruments 59
Common Applications
Digital frequency and period are examples of counter measurements. Refer to Counter
Programming Flowcharts for additional flowcharts that can help you create an
application.
Related concepts:
Functions and VIs produce the core functionality of the NI-DAQmx API. For instance, NI-
DAQmx includes functions for timing, triggering, reading, and writing samples.
60 ni.com
Common Applications
However, for advanced functionality, Visual C++, Visual C#, Visual Basic .NET, and
LabVIEW require properties. ANSI C and LabWindows/CVI employ the Get and Set
Attribute functions. For more information, refer to the programming reference help for
your ADE.
Functions and VIs provide the core functionality of the NI-DAQmx API. For instance, NI-
DAQmx includes functions for timing, triggering, reading, and writing samples.
However, for advanced functionality, Visual C++, Visual C#, Visual Basic .NET, and
LabVIEW require properties. ANSI C and LabWindows/CVI employ the Get and Set
Attribute functions. For more information, refer to the programming reference help for
your ADE.
Related concepts:
With NI-DAQmx, you also can gather data from multiple channels. For instance, you
© National Instruments 61
Common Applications
might want to monitor the fluid level in the tank as well as the temperature. In this
case, you need two transducers connected to two channels on your device. The
following flowchart depicts the steps to programmatically create a single sample
analog input application. If you prefer, you can configure a task for acquiring a single
sample using the DAQ Assistant.
One way to acquire multiple samples for one or more channels is to acquire single
samples in a repetitive manner. However, acquiring a single sample on one or more
channels over and over is inefficient and time consuming. Moreover, you do not have
accurate control over the time between each sample or channel. Instead, you can use
hardware timing, which uses a buffer in computer memory to acquire data more
efficiently. Programmatically, you need to include the timing function, specifying the
sample rate and the sample mode (finite). As with other functions, you can acquire
multiple samples for a single channel or multiple channels. You can configure a task
for finite analog input using the DAQ Assistant.
62 ni.com
Common Applications
If you want to view, process, or log a subset of the samples as they are being acquired,
you need to continually acquire samples. For these types of applications, set the
sample mode to continuous. The following flowchart depicts the main steps required
in an NI-DAQmx application for measuring voltage. Instead, you can configure a task
for continuous analog input using the DAQ Assistant.
© National Instruments 63
Common Applications
Functions and VIs provide the core functionality of the NI-DAQmx API. For instance, NI-
DAQmx includes functions for timing, triggering, reading, and writing samples.
However, for advanced functionality, Visual C++, Visual C#, Visual Basic .NET, and
64 ni.com
Common Applications
LabVIEW require properties. ANSI C and LabWindows/CVI employ the Get and Set
Attribute functions. For more information, refer to the programming reference help for
your ADE.
Related concepts:
• Generating Voltage
• Measuring and Generating Current
With NI-DAQmx, you also can generate samples from multiple channels. If you prefer,
you can configure a task for generating a single sample using the DAQ Assistant.
The following flowchart depicts the main steps required in an NI-DAQmx application to
© National Instruments 65
Common Applications
generate a finite number of voltage samples in a buffered generation. If you prefer, you
can configure this task using the DAQ Assistant.
The following flowchart depicts the main steps required in an NI-DAQmx application to
continuously generate voltage samples. If you prefer, you can configure this task using
the DAQ Assistant.
66 ni.com
Common Applications
Functions and VIs provide the core functionality of the NI-DAQmx API. For instance, NI-
DAQmx includes functions for timing, triggering, reading, and writing samples.
© National Instruments 67
Common Applications
However, for advanced functionality, Visual C++, Visual C#, Visual Basic .NET, and
LabVIEW require properties. ANSI C and LabWindows/CVI employ the Get and Set
Attribute functions. For more information, refer to the programming reference help for
your ADE.
Related concepts:
• Edge Counting
• Generating Pulses
The following flowchart depicts the main steps you must complete for an on-demand
counting application. If you prefer, you can configure this task using the DAQ Assistant.
The following flowchart depicts the main steps you must complete for finite counter
input in an NI-DAQmx application. If you prefer, you can configure this task using the
DAQ Assistant.
68 ni.com
Common Applications
1
Time-based measurements include period, semi-period, pulse width, two-edge
separation, and digital frequency.
2
Edge counting-based measurements include edge counting, encoder-based position
measurements, and GPS timestamp measurements.
The following flowchart depicts the main steps you must complete for continuous
counting in an NI-DAQmx application. If you prefer, you can configure this task using
the DAQ Assistant.
© National Instruments 69
Common Applications
1
Time-based measurements include period, semi-period, pulse width, two-edge
separation, and digital frequency.
2
Edge counting-based measurements include edge counting, encoder-based position
measurements, and GPS timestamp measurements.
Functions and VIs provide the core functionality of the NI-DAQmx API. For instance, NI-
70 ni.com
Common Applications
DAQmx includes functions for timing, triggering, reading, and writing samples.
However, for advanced functionality, Visual C++, Visual C#, Visual Basic .NET, and
LabVIEW require properties. ANSI C and LabWindows/CVI employ the Get and Set
Attribute functions. For more information, refer to the programming reference help for
your ADE.
Related concepts:
With NI-DAQmx, you also can gather data from multiple channels. For instance, you
might want to monitor the fluid level in the tank as well as the temperature. In this
case, you need two transducers connected to two channels on your device. The
following flowchart depicts the steps to programmatically create an application to
measure digital values. If you prefer, you can configure a task for acquiring a single
sample using the DAQ Assistant.
© National Instruments 71
Common Applications
One way to acquire multiple samples for one or more channels is to acquire single
samples in a repetitive manner. However, acquiring a single data sample on one or
more channels over and over is inefficient and time consuming. Moreover, you do not
have accurate control over the time between each sample or channel. Instead, you can
use hardware timing, which uses a buffer in computer memory to acquire data more
efficiently. Programmatically, you need to include the timing function, specifying the
sample rate and the sample mode (finite). As with other functions, you can acquire
multiple samples for a single channel or multiple channels. You can configure a task
for measuring digital values using the DAQ Assistant.
72 ni.com
Common Applications
Note Triggering and Sample Clock timing for Digital I/O are not supported
on all devices.
Related concepts:
If you want to view, process, or log a subset of the samples as they are being acquired,
you need to continually acquire samples. For these types of applications, set the
sample mode to continuous. The following flowchart depicts the main steps required
in an NI-DAQmx application for acquiring digital signals. You can configure a task for
continuously acquiring digital values using the DAQ Assistant.
© National Instruments 73
Common Applications
Note Sample clock timing for Digital I/O is not supported on all devices.
74 ni.com
Common Applications
Functions and VIs provide the core functionality of the NI-DAQmx API. For instance, NI-
DAQmx includes functions for timing, triggering, reading, and writing samples.
However, for advanced functionality, Visual C++, Visual C#, Visual Basic .NET, and
LabVIEW require properties. ANSI C and LabWindows/CVI employ the Get and Set
Attribute functions. For more information, refer to the programming reference help for
your ADE.
With NI-DAQmx, you also can generate samples from multiple channels. If you prefer,
you can configure a task for generating a single sample using the DAQ Assistant.
The following flowchart depicts the main steps required in an NI-DAQmx application to
generate a finite number of digital values in a buffered generation. If you prefer, you
can configure a task for generating digital values using the DAQ Assistant.
© National Instruments 75
Common Applications
Note Sample clock timing for Digital I/O is not supported on all devices.
The following flowchart depicts the main steps required in an NI-DAQmx application to
continuously generate digital values. If you prefer, you can configure a task for
generating digital values using the DAQ Assistant.
76 ni.com
Common Applications
Note Sample clock timing for Digital I/O is not supported on all devices.
© National Instruments 77
Common Applications
You can synchronize the GPS timestamp counter to a GPS receiver signal by using a
78 ni.com
Common Applications
pulse per second (PPS) or an IRIG-B (timecode TTL) synchronization signal from the
GPS receiver. PPS does not include any timing information; rather, the PPS accurately
reports when the beginning of a second occurs. IRIG-B, on the other hand, has the time
encoded in the signal from the beginning of the current year. The GPS counter can
latch on the current time upon receiving a hardware gate signal. GPS does not provide
year information; however, the time is stored in a 64-bit floating-point number that
can be converted to seconds since January 1 of the current year.
When doing an on-demand GPS timestamp measurement, you must first arm the
counter by calling the Start function/VI. Each subsequent read returns the number of
seconds counted.
When doing a buffered GPS timestamp measurement, the current time is latched on
each active edge of the sample clock and stored in the buffer. There is no built-in clock
for buffered GPS timestamp measurements, so you must supply an external sample
clock.
Related concepts:
© National Instruments 79
Common Applications
Related concepts:
On M Series devices, C Series devices, and NI-TIO-based devices, you can use the
counters to perform displacement measurements with two-pulse encoders. Linear
position can be measured with two-pulse encoders. You can choose to do either a
single point or a buffered sample clock displacement measurement.
You also can measure velocity with two-pulse encoders, but you need to use a sample
clock with a fixed frequency. To measure velocity, use the following formula:
V = D/T
80 ni.com
Common Applications
The counter measures the position of the encoder using the A and B signals, which are
offset by 90°. The counter also supports the Z index, which provides a precise reference
point and is available on some encoders.
Related concepts:
© National Instruments 81
Common Applications
Related concepts:
82 ni.com
Common Applications
Related concepts:
© National Instruments 83
Common Applications
Period measurements measure the time between consecutive rising or falling edges of
a pulse. Semi-period measurements measure the time between consecutive edges.
Pulse width measurements measure the time between either a rising and falling edge,
or a falling and rising edge. Two-edge separation measurements measure the time
between the rising or falling edge of one digital signal and the rising or falling edge of
another digital signal.
The formula for period, semi-period, pulse width, and two-edge separation is as
follows:
where Count is the number of counter timebase ticks that elapse during one period,
semi-period, pulse width, or two-edge separation of the measured input signal or
signals.
The Counter Timebase Rate is a known frequency and is usually a built-in time source.
If the counter timebase rate is unknown, you only can make measurements only in
terms of ticks of the counter timebase. This may be the case if you are using an
external signal for the counter timebase, and the frequency of the external signal is
84 ni.com
Common Applications
unknown or aperiodic.
Period, semi-period, pulse width, and two-edge separation are examples of time
measurements. Refer to Configuring a Time Measurement in NI-DAQmx and Two
Counter Measurement Method for more information about measuring time.
Related concepts:
• Generating Pulses
• Measuring Semi-Period, Two-Edge Separation, and Pulse Width Programming
Flowchart
• Measuring Digital Frequency and Period Programming Flowchart
• Measuring Pulses Programming Flowchart
• Finding Examples
Digital frequency and period are examples of counter measurements. Refer to Counter
Programming Flowcharts for additional flowcharts that can help you create an
application.
© National Instruments 85
Common Applications
Related concepts:
Digital frequency and period are examples of counter measurements. Refer to Counter
Programming Flowcharts for additional flowcharts that can help you create an
application.
Related concepts:
86 ni.com
Common Applications
Related concepts:
Measuring Pressure
Pressure is a measure of force per unit area. You can use bridge-based sensors to
measure pressure.
© National Instruments 87
Common Applications
Related concepts:
When selecting the scaling type, choose the one that best matches the specifications
for your sensor.
88 ni.com
Common Applications
Related concepts:
Measuring Proximity
Proximity is the distance between two objects. An eddy current proximity probe is a
transducer that uses changes in voltage to measure proximity. Eddy current proximity
probes use a high-frequency radio signal to convert voltage to a proximity
measurement. Measurements are recorded as milimeters, microns, mVolts/mil and
Volts/mil where a mil is 1/1000 of an inch.
Related concepts:
© National Instruments 89
Common Applications
Related concepts:
Generating Pulses
A pulse is a rapid change in the amplitude of a signal from its idle value to an active
value for a short period of time. Pulses can have high or low idle states. A pulse with a
low idle state starts at the low value (typically zero), pulses high, and returns to low. A
pulse with a high idle state starts high, pulses to low, and returns to high.
A pulse train is more than one pulse. You can use a pulse or pulse train as a clock
signal, a gate, or a trigger for a measurement or a pulse generation. You can use a
single pulse of known duration to determine an unknown signal frequency or to trigger
an analog acquisition. You can use a pulse train of known frequency to determine an
unknown pulse width.
90 ni.com
Common Applications
The pairing of high time and low time pair is a pulse specification.
The period of the pulse is the sum of the high time and the low time. The frequency is
the reciprocal of the period, 1/period.
Before you generate a pulse, you need to determine if you want to output the pulse or
pulse train in terms of frequency, time, or number of ticks of the counter timebase. For
frequency, you need to determine the duty cycle. For time, you specify the high time
and the low time. Use the number of ticks if you are using a counter timebase with an
unknown rate. When you configure a pulse generation, the output appears at the
counter output terminal.
Related concepts:
© National Instruments 91
Common Applications
92 ni.com
Common Applications
© National Instruments 93
Common Applications
Measuring Resistance
Resistance is the opposition to passage of an electric current. One Ohm (Ω) is the
resistance through which one volt (V) of electric force causes one ampere (A) to flow.
Two common methods for measuring resistance are the 2-wire method and the 4-wire
method. Both methods send a current through a resistor with a measurement device
measuring the voltage drop from the signal before and after it crosses the resistor. The
2-wire method is easier to implement, but this method is less accurate than the 4-wire
method for resistances below 100 Ω. For 3-wire resistors, there is also a 3-wire method.
To calculate resistance, use the following equation.
Related concepts:
94 ni.com
Common Applications
• Finding Examples
Related concepts:
© National Instruments 95
Common Applications
The Sound Pressure Level (SPL or LP) in decibels is defined by the following equation.
Related concepts:
96 ni.com
Common Applications
Related concepts:
Measuring Strain
Strain (ε) is the amount of deformation of a body due to an applied force. Specifically,
strain is the fractional change in length, as shown in the following figure.
© National Instruments 97
Common Applications
When a uniaxial force strains a bar, as in the preceding figure, a phenomenon known as
Poisson Strain causes the girth of the bar, D, to contract in the transverse direction,
which is perpendicular to the force. The magnitude of this transverse contraction is a
material property indicated by its Poisson's Ratio. The Poisson's Ratio of a material is
the negative ratio of the strain in the transverse direction to the strain in the axial
direction, which is parallel to the force. Poisson's Ratio for steel, for example, ranges
from 0.25 to 0.3.
To measure strain, you can use one or more strain gages in a Wheatstone bridge in one
of several bridge configurations. Refer to Signal Conditioning Requirements for Bridge-
Based Sensors for more information about strain gages and bridge configurations.
Related concepts:
98 ni.com
Common Applications
Related concepts:
© National Instruments 99
Common Applications
Measuring Torque
Torque is a measure of the tendency of a force to rotate an object. Torque is the cross
product of a force and the distance of the force from the fulcrum. You can use bridge-
based sensors to measure torque.
Related concepts:
100 ni.com
Common Applications
When selecting the scaling type, choose the one that best matches the specifications
for your sensor.
Related concepts:
Measuring Temperature
Note Temperature measurements may require you to condition the signal.
The conditioning requirements depend on your sensor. Refer to the Overview
of Temperature Sensor Types for an explanation of sensor types and
conditioning requirements.
The typical wiring for a thermocouple, as shown in the following figure, uses a resistor,
R, only if the thermocouple is not grounded at any other point. If, for example, the
thermocouple tip were already grounded, using a resistor would cause a ground loop
and result in erroneous readings.
You also can measure temperature using Resistance Temperature Detectors (RTD) and
Thermistors.
Related concepts:
102 ni.com
Common Applications
Related concepts:
104 ni.com
Common Applications
Related concepts:
Related concepts:
Measuring Velocity
Velocity is the rate of change in position with respect to time.
Related concepts:
The following flowchart depicts the main steps required in an NI-DAQmx application to
measure velocity with a piezoelectric sensor. Alternatively, you can configure a task for
measuring velocity using the DAQ Assistant.
106 ni.com
Common Applications
Related concepts:
The counter measures the velocity of the encoder using the A and B signals, which are
offset by 90°. The velocity is calculated using the A and B input signal transitions and
the amount of time that elapses between the changes in the encoder count value.
The decoding type attribute/property specifies how to count and interpret the pulses
the encoder generates on signal A and signal B.
The counter measures the velocity of the encoder using the A and B signals, which are
offset by 90°. The velocity is calculated using the A and B input signal transitions and
the amount of time that elapses between the changes in the encoder count value.
The pulse in the distance per pulse attribute/property is one full period of both signal A
and signal B in the units specified by the length portion of the Units input. The
decoding type attribute/property specifies how to count and interpret the pulses the
encoder generates on signal A and signal B.
Generating Voltage
You can generate single sample DC signals or time-varying multiple sample signals.
Use single samples if the signal level is more important than the generation rate. For
instance, generate one sample at a time if you need to generate a constant, or DC,
signal. You can use software or hardware timing if the device supports hardware
timing to control when the device generates a signal.
108 ni.com
Common Applications
Use multiple samples if the generation rate is just as important as the signal level, as in
an AC sine wave. Function generators are a common type of device that you can
program to produce certain types of waveforms, such as sine, triangle, and square
waves. You also can use a DAQ device as a function generator. You do this by
generating one cycle of a sine wave, such as with the Sine Generation VI in LabVIEW,
storing one cycle of sine wave data in a waveform, and programming the device to
generate the values continuously from the waveform one point at a time at a specified
rate.
Also called buffered analog output, generating multiple samples involves the following
steps:
Related concepts:
Related concepts:
Measuring Voltage
Most measurement devices can measure, or read, voltage. Two common voltage
measurements are direct current (DC) and alternating current (AC).
110 ni.com
Common Applications
Measuring DC Voltage
DC voltage is useful for measuring phenomena that change slowly with time, such as
temperature, pressure, or strain. With DC signals, you want to accurately measure the
amplitude of a signal at a given point in time.
The following figure shows a typical wiring diagram for an anemometer with an output
range of 0 to 10 V, which corresponds to wind speed of 0 to 200 mph. Use the following
equation to scale the data:
Notice that the wiring diagram in the following figure uses a resistor, R, because an
anemometer is usually not a grounded signal source. If the anemometer transducer
were already grounded, using a resistor would cause a ground loop and result in
erroneous readings.
Averaging
Averaging can improve measurement accuracy for noisy and rapidly changing signals.
The following figure shows what an actual wind speed might look like over time. Due
to gusting winds, the speed values look noisy. Notice that the wind speed reading of 29
mph is a peak speed that might give the impression that the wind is holding at 29 mph.
A better representation might be to take the average speed over a short period of time.
One common reason for averaging is to eliminate 50 or 60 Hz power line noise. The
oscillating magnetic field around power lines can introduce noise voltages on
unshielded transducer wiring. Because power line noise is sinusoidal, or shaped like a
sine wave, the average over one period is zero. If you use a scan rate that is an integer
multiple of the noise and average data for an integer multiple of periods, you can
eliminate the line noise. One example that works for both 50 and 60 Hz is to sample at
300 samples per second and average 30 points. Notice that 300 is an integer multiple
of both 50 and 60. One period of the 50 Hz noise is 300/50 = 6 points. One period of the
60 Hz noise is 300/60 = 5 points. Averaging 30 points is an integer multiple of both
periods, so you can ensure that you average whole periods.
Measuring AC Voltage
Voltage, current, and power are not constant values because AC signals alternate.
However, you can use Vrms (root mean square) to measure voltage, current, and power
such that a load connected to a 120 volts AC (VAC) source develops the same amount
of power as that same load connected to a 120 volts DC (VDC) source. With RMS, the
power formula for DC also works for AC. For sinusoidal waveforms, Vrms = Vpeak/
square root of 2. Because voltmeters read Vrms, the 120 VAC of a typical U.S. wall outlet
actually has a peak value of about 170 V.
Related concepts:
112 ni.com
Common Applications
To measure AC voltages, you generally use a hardware timed acquisition, such as the
ones shown in Finite Voltage Measurements and Continuous Voltage Measurements.
To measure DC voltages, you often do not need a buffer or hardware timing, so you can
use a simple application such as the one shown in Acquiring a Single Sample.
Related concepts:
114 ni.com
NI-DAQmx Key Concepts
Related concepts:
Virtual channels are software entities that encapsulate the physical channel along with
other channel specific information—range, terminal configuration, and custom
scaling—that formats the data. To create virtual channels, use the DAQmx Create
Virtual Channel function/VI or the DAQ Assistant.
Virtual channels created with the DAQmx Create Virtual Channel function/VI are called
local virtual channels and can only be used within the task. With this function/VI, you
choose the name to assign for the virtual channel, which is used in the rest of the NI-
DAQmx software framework to refer to the physical channel.
If you create virtual channels with the DAQ Assistant, you can use them in other tasks
and reference them outside the context of a task. Because these channels can apply to
multiple tasks, they are called global virtual channels. You can select global virtual
channels with the NI-DAQmx API or DAQ Assistant and add them to a task. If you add a
global virtual channel to several tasks and modify that global virtual channel with the
DAQ Assistant, the change applies to all tasks that use that global virtual channel. You
must save the changes before they become globally available.
Related concepts:
Related tasks:
The following example illustrates the difference between physical and virtual channels
and demonstrates how to create virtual channels with the API.
Problem
Create an NI-DAQmx virtual channel to measure temperature in the range 50° C to 200°
C using a J-type thermocouple wired to channel 0 on an M Series device configured as
Device 1. Use LabVIEW or LabWindows™/CVI™ to write your application.
Solution
1. Call the AI Temp TC instance of the DAQmx Create Virtual Channel VI in LabVIEW
116 ni.com
NI-DAQmx Key Concepts
You can create a number of different types of virtual channels, depending on the signal
type—analog, digital, or counter—and direction (input or output). These channels can
be either global virtual channels or local virtual channels. For information on specific
functions/VIs, refer to the NI reference help for your ADE.
based channel does not affect other lines on the hardware. You can split lines in a
particular port among multiple channels and use those channels simultaneously
within one or multiple tasks, but the lines in a given channel must all be input lines
or all be output lines. Additionally, all channels in a task must be either input
channels or output channels. Some devices also require that the lines of a given
port all be input lines or output lines. Check your device documentation for the
capabilities of your device.
• Power Channels—Power channels source voltage and current and also provide
measurements of those sources. You can change the voltage and current setpoints
dynamically at runtime. You can use a power channel to control (enable or disable)
the power output as well as to detect various error states that impact power
output.
Related concepts:
Use this syntax to refer to physical channels and groups of physical channels in NI-
DAQmx.
Related concepts:
• Physical Channels
• Internal Channels
• Multidevice Tasks
118 ni.com
NI-DAQmx Key Concepts
Physical channel names consist of a device identifier and a slash (/) followed by a
channel identifier. For example, if the physical channel is Dev1/ai1, the device
identifier is Dev1, and the channel identifier is ai1. MAX assigns device identifiers to
devices in the order they are installed in the system, such as Dev0 and Dev1. You also
can assign arbitrary device identifiers with MAX.
For analog I/O and counter I/O, channel identifiers combine the type of the channel,
such as analog input (ai), analog output (ao), and counter (ctr), with a channel number
such as the following:
ai1
ctr0
For digital I/O, channel identifiers specify a port, which includes all lines within a port:
port0
port0/line1
All lines have a unique identifier. Therefore, you can use lines without specifying which
port they belong to. For example, line31 is equivalent to port3/line7 on a
device with four 8-bit ports.
To specify a range of physical channels, use a colon between two channel numbers or
two physical channel names:
Dev1/ai0:4
Dev1/ai0:Dev1/ai4
For digital I/O, you can specify a range of ports with a colon between two port
numbers:
Dev1/port0:1
Dev1/port0/line0:4
Dev1/line0:31
Dev1/ai4:0
Dev1/ai4:Dev1/ai0
Dev1/port1/line3:0
Use commas to separate physical channel names and ranges in a list as follows:
Dev1/ai0, Dev1/ai3:6
Dev1/port0, Dev1/port1/line0:2
Digital lines and ports are important parts of a digital input/output system.
• Line—A line is an individual signal. It refers to a physical terminal. The data that
the line carries are called bits, binary values that are either 1 or 0. The terms line
and bit are fairly interchangeable. For example, an 8-bit port is the same as a port
with eight lines.
• Port—A port is a collection of digital lines. Usually, the lines are grouped into an
8-bit or 32-bit port.
• Port Width—The port width refers to the number of lines in a port. For example, a
device with one port with eight lines has a port width of eight.
120 ni.com
NI-DAQmx Key Concepts
Output Lines
Output Port
Data Latches
and Drivers
NI-DAQmx assigns names to local virtual channels that you create programmatically
with the NI-DAQmx API when you do not provide a name for each local virtual channel.
On devices with built-in cold-junction compensation (CJC) channels, the CJC channel
is read once per sample clock edge.
Related concepts:
• Sample Clock
Tasks in NI-DAQmx
A task is a collection of one or more virtual channels with timing, triggering, and other
properties. Conceptually, a task represents a measurement or generation you want to
perform. All channels in a task must be of the same I/O type, such as analog input or
counter output. However, a task can include channels of different measurement types,
such as an analog input temperature channel and an analog input voltage channel. For
most devices, only one task per subsystem can run at once, but some devices can run
multiple tasks simultaneously. With some devices, you can include channels from
multiple devices in a task. To perform a measurement or a generation with a task,
follow these steps:
1. Create or load a task. You can create tasks interactively with the DAQ Assistant or
programmatically in your ADE such as LabVIEW or LabWindows/CVI.
2. Configure the channel, timing, and triggering properties as necessary.
3. Optionally, perform various task state transitions to prepare the task to perform
the specified operation.
4. Read or write samples.
5. Clear the task.
If appropriate for your application, repeat steps 2 through 4. For instance, after reading
or writing samples, you can reconfigure the virtual channel, timing, or triggering
properties and then read or write additional samples based on this new configuration.
If properties need to be set to values other than their defaults for your task to be
successful, your program must set these properties every time it executes. For
example, if you run a program that sets property A to a nondefault value and follow
that with a second program that does not set property A, the second program uses the
122 ni.com
NI-DAQmx Key Concepts
default value of property A. The only way to avoid setting properties programmatically
each time a program runs is to use virtual channels and/or tasks created in the DAQ
Assistant.
Related concepts:
• Simultaneous Tasks
• Multidevice Tasks
• Task State Model
• Creating Channels and Tasks with the DAQ Assistant
Related tasks:
The following example illustrates how to create a task with the API:
Problem
Create an NI-DAQmx task to measure temperature in the range 50°C to 200°C using a J-
type thermocouple that is wired to channel 0 on an M Series device configured as
Device 1. Sample the temperature 10 times per second, and acquire 10,000 samples.
Use LabVIEW or LabWindows/CVI to write your application.
Solution
1. Call the AI Temp TC instance of the DAQmx Create Virtual Channel VI in LabVIEW
(DAQmxCreateAIThrmcplChan function in LabWindows/CVI).
2. Specify Dev1/ai0 as the physical channel for the device connected to the
thermocouple signal.
3. Specify myThermocoupleChannel as the name to assign to your virtual
channel.
4. Select the appropriate values for the thermocouple type and range inputs. NI-
DAQmx applies these attributes to the virtual channel.
5. Call the Sample Clock instance of DAQmx Timing VI in LabVIEW (or
DAQmxCfgSampClkTiming function in LabWindows/CVI), specifying a rate of 10
You have now created a task called myTemperatureTask that uses a local virtual
channel called myThermocoupleChannel.
Note You also can use the DAQ Assistant to create the same task and
generate the code to run the task.
Related concepts:
To explicitly start a task, call the Start Task function/VI. You auto-start a task when you
perform some other operation that implicitly starts the task. For instance, calling a
Read function/VI or a Write function/VI might implicitly start the task if one is not
already started. How to specify this behavior depends on the operation that your task
performs. By default, the Read function/VI and the Write function/VI for a single
sample automatically starts a task.
Related concepts:
• Committed State
• Running State
• Task State Model
• Verified State
124 ni.com
NI-DAQmx Key Concepts
If you have specified a task to perform a finite measurement, you do not need to call
the Start Task function/VI, nor do you need to change the default behavior of the
DAQmx Read function/VI. Calling the Read function/VI starts your task, performs the
finite measurement, and stops the task after the last sample is read. The task returns
to its state before you called the read operation. However, if you need to perform
additional read operations after the task has been stopped (in other words, if you want
to read earlier locations in the buffer), the default behavior is insufficient for two
reasons:
1. The task is returned to the Verified state and the samples are no longer accessible.
2. Future calls of the Read function/VI start new read operations rather than reading
from the completed operation.
For this situation, explicitly commit the task by calling the Control Task function/VI
with the Action parameter set to Commit. Then, after performing the initial read
operation and before performing the subsequent read operations, set the Auto-Start
Read attribute/property to False.
For a continuous measurement, explicitly call the Start Task function/VI, perform the
desired read operations, and call the Stop Task function/VI to stop the continuous
measurement. When you perform a read operation in a loop—regardless if the read
operation performs a single-sample, on-demand read, or a multiple-sample,
hardware-timed read—call the Start Task function/VI before entering the loop and call
the Stop Task function/VI after leaving the loop.
The behavior of the Write function/VI is more complicated. Calling the Write function/
VI always results in the task transitioning to at least the Committed state. Whether the
task transitions to the Running state depends on the value of the Auto-Start
parameter.
For single-sample write operation, call a single-sample version of the Write function/
VI. This call implicitly starts the task, writes the single sample, and stops the task. For a
multiple-sample, on-demand write operation, call the Write function/VI, but also set
the Auto-Start parameter to True, which by default is set to False. This call
implicitly starts the task, writes the multiple samples, and stops the task.
For a multiple-sample, hardware-timed write operation, first call the Write function/VI
to write the samples to generate, explicitly call the Start Task function/VI, wait for the
samples to be generated by calling the Wait Until Done function/VI, and then explicitly
call the Stop Task function/VI.
There are other situations in which you should explicitly call the DAQmx Start Task
function/VI and the DAQmx Stop Task function/VI, even though you are not required to
do so. When you call the Read function/VI or the Write function/VI in a loop, you can
significantly improve performance if you explicitly call the Start Task function/VI
before entering the loop and call the Stop Task function/VI after exiting the loop.
Without explicitly calling the Start Task function/VI before entering the loop, the task
must implicitly transition from its current state to the Running state before performing
the read or write operation. After the read or write operation is complete, the task must
implicitly transition from the Running state back to its previous state. These implicit
state transitions occur for every iteration of the loop, which is inefficient.
Aborting a Task
Several conditions cause a task to abort:
• To explicitly abort a task, call the DAQmx Control Task function/VI with the
Action parameter set to Abort. In general, aborting a task is not a normal
operation. It is intended for exceptional situations.
• In LabVIEW, you also can abort a task by clicking the Abort Execution button.
Doing so results in all tasks created in that VI hierarchy to be aborted and then
126 ni.com
NI-DAQmx Key Concepts
cleared.
• If you remove a device from the system, all tasks currently using the resources of
that device are aborted.
• If you call the DAQmx Reset Device function/VI to restore a device to its initial
configuration, all tasks currently utilizing the resources of that device are aborted.
When a task is aborted, it is returned to the Verified state. If the task is running, it is
stopped as soon as possible and is then unreserved. After a task has been aborted, you
can continue to use the task. However, you might need to transition the task back to its
previous state before continuing the specified operation.
Related concepts:
• Verified State
You can use the Is Task Done function/VI for applications in which you need to monitor
the progress of a task running in one section of your application from another section
of your application.
In general, use the Is Task Done function/VI with continuous measurements and
generations when you are not actively reading or writing samples but want to monitor
for errors.
Related concepts:
You might need to call the Wait Until Done function/VI to ensure that the specified
operation is complete before you stop the task.
The most common example is a finite generation. If you start a task that performs a
finite generation and then immediately stop the task, the generation probably has not
completed when you stop the task. As a result, the generation does not complete as
expected. To ensure that the finite generation completes as expected, call the Wait
Until Done function/VI before stopping the task. After the Wait Until Done function/VI
executes, the finite generation has been completed, and you can stop the task.
In general, use the Wait Until Task Done function/VI with finite measurements and
generations.
Related concepts:
If the measurement or generation is finite, the task is done when you acquire or
generate the final sample or when you call the Stop Task function/VI. If the
measurement or generation is continuous (including on-demand timing), or if
retriggering is enabled, the task is not done until you call the Stop Task function/VI. In
addition, the task is done if a fatal error is generated while performing the
measurement or generation, or you abort the measurement or generation. Check for
errors and warnings to verify the task completed successfully.
NI-DAQmx uses a task state model to improve ease of use and speed up driver
performance.
If you explicitly invoke a state transition that has already occurred, it is not repeated
128 ni.com
NI-DAQmx Key Concepts
and an error is not returned. For example, if the task has already reserved its resources
and, therefore, is in the Reserved state, calling the Control Task function/VI with the
Action parameter set to Reserve does not reserve the resources again.
Sometimes, calling a function/VI may require multiple state transitions, such as calling
the Start Task function/VI while in the Verified state. In these cases, the task will
implicitly transition between each of the necessary states to get to the final desired
state, as shown in the following diagram.
Create Verify or Get Reserve Commit Start
Unverified Verified Reserved Committed Running
Set Unreserve Stop
Clear
Abort
Abort
Abort
Transitioning backwards in the Task State Model will undo any implicit forwards
transitions in addition to the requested explicit transition. Continuing with the
example above, calling the Stop Task function/VI after implicitly transitioning to the
Running State from the Verified State will cause the task to return to the Verified State,
as shown in the following diagram.
Create Verify or Get Reserve Commit Start
Unverified Verified Reserved Committed Running
Set Unreserve Stop
Clear
Abort
Abort
Abort
Unverified State
Verified State
devices being used. NI-DAQmx checks the value of these attributes/properties during
the verify transition and reports any invalid values at that time. If NI-DAQmx finds no
invalid values, the task is successfully verified and transitions to the Verified state.
Otherwise, it remains in the Unverified state.
Related concepts:
• Coercion
Reserved State
The resources a task uses to perform the specified operation are acquired exclusively
when the task transitions from the Verified state to the Reserved state. These resources
can be clocks or channels on a device, trigger lines on a PXI chassis, or buffer memory
in the computer. Reserving these resources prevents other tasks from using these
resources, which interferes with this task performing the specified operation. You can
explicitly perform this transition by calling the Control Task function/VI with Action
set to Reserve. This transition fails if some task resources are currently reserved by
another task. If the task can gain access to all the resources it uses, the task is
successfully reserved and transitions to the Reserved state. Otherwise, it remains in
the Verified state.
Committed State
NI-DAQmx programs some of the settings for the resources when the task is
committed. These settings might be the rate of a clock or the input limits of a channel
on a device, the direction of a trigger line on a PXI chassis, or the size of the buffer
memory in the computer. Other settings, such as the sample counter, cannot be
programmed when the task is committed because they need to be programmed every
time the task is started. When a task is committed, it transitions from the Reserved
state to the Committed state. You can explicitly perform this transition by invoking the
Control Task function/VI with Action set to Commit. In general, the commit
transition should not fail. If it does, it is an exceptional condition and the task remains
130 ni.com
NI-DAQmx Key Concepts
in the Reserved state. If the settings for the resources used by the task are
programmed, the task is successfully committed and transitions to the Committed
state.
Running State
When the task begins to perform the specified operation, the task transitions from the
Committed state to the Running state. You can explicitly perform this transition by
invoking the Start Task function/VI. Notice that starting a task does not necessarily
start acquiring samples or generating a waveform. You might have specified the timing
and triggering attributes/properties such that a sample is not acquired until you call
the Read function/VI or a waveform is not generated until a trigger is detected. In
general, the start transition does not fail. If it does, it is an exceptional condition, and
the task remains in the Committed state. If the task begins to perform the specified
operation, the task is successfully started and transitions to the Running state.
The task ceases to perform the specified operation when the task transitions from the
Running state to the Committed state. To explicitly perform this transition, call the
Stop Task function/VI. Notice that you might have specified the timing and triggering
attributes/properties such that all the samples are acquired before this transition
occurs. For output operations, the last value written will typically continue to be
generated after the task is stopped. In this situation, despite the fact that no additional
samples are acquired, the task is still in the Running state until this transition occurs.
In general, the stop transition does not fail. If it does, it is an exceptional condition, and
the task is returned to the Reserved state. If the task is stopped, the task successfully
transitions back to the Committed state.
When the task resources that perform the specified operation are released, the task
transitions from the Committed state to the Verified state. These resources may be
clocks or channels on a device, trigger lines on a PXI chassis, or buffer memory in the
computer. To explicitly perform this transition, call the Control Task function/VI with
Action set to Unreserve. After the task releases all of its resources, it successfully
transitions back to the Verified state.
When should you perform explicit state transitions, and when should you rely on the
task to perform implicit state transitions? The answer depends on your application.
The following list identifies instances in which you should use explicit state transitions:
132 ni.com
NI-DAQmx Key Concepts
Related concepts:
For example, if the task is in the Reserved state, the value of the DAQmx Read Auto
Start attribute/property is True, and you call the Read function/VI, the task is
implicitly committed and started. The task transitions from the Reserved state to the
Committed state and to the Running state before the read operation is performed.
In some applications, it is not necessary to explicitly transition the task to any state.
Instead, invoke the desired operation and the task implicitly handles everything else.
Related concepts:
134 ni.com
NI-DAQmx Key Concepts
As another example, suppose the task is in the Reserved state, and you call the Read
function/VI to perform a finite measurement. This results in the task implicitly
transitioning from the Reserved state to the Committed state and then to the Running
state before performing the read operation. When the read operation completes, the
task does not remain in the running state. If this were the case, the result is
unexpected behavior, because you need to stop the task and unreserve its resources
despite the fact you never explicitly reserved the resources or started the task. Instead,
after the finite read operation completes, the task is implicitly transitioned from the
Running state to the Committed state to the Reserved state. This results in the task
returning to the state before you performed the read operation.
Keep in mind that setting the value of a channel, timing, or triggering attribute/
property does not implicitly transition the task back to the Unverified state. Instead,
the task remains in its current state and is implicitly verified when the next state
transition occurs. For example, if the task is in the Reserved state and you set the value
of timing attribute/property, the task remains in the Reserved state. The next time the
task, either implicitly or explicitly, is committed, the task is verified. Because the task is
implicitly verified when the next state transition occurs, NI-DAQmx can return an error
specifying that the value of attribute/property is invalid.
After you launch the DAQ Assistant, follow the wizard instructions to create your new
task or channel. When the wizard is done, you can configure measurement-specific
settings, scaling, and, if necessary, timing and triggering.
Related concepts:
LabVIEW
In LabVIEW, there are several ways to open the DAQ Assistant. A couple of common
ones are the following:
• Drop the DAQ Assistant Express VI from the Express Input palette.
• Use the DAQmx Task Name control to open the DAQ Assistant.
• Open the DAQ Assistant from within a LabVIEW Project as described in Using NI-
DAQmx with LabVIEW Project in the LabVIEW Help.
LabWindows/CVI
In LabWindows/CVI, select Tools»Create/Edit DAQmx Tasks. You also can launch the
DAQ Assistant by clicking the Task Name control of the DAQmx LoadTask function
panel and selecting New Task.
Measurement Studio
In Measurement Studio, open Visual Studio .NET and select Project»Add New Item to
open the Add New Item dialog box. In the Categories pane, select Measurement
Studio»Assistants. In the Templates pane, select DAQmx Task Class.
136 ni.com
NI-DAQmx Key Concepts
MAX
In MAX, right-click Data Neighborhood, and select Create New from the shortcut
menu. Select NI-DAQmx Task or NI-DAQmx Global Virtual Channel in the Create New
window, and click Next.
Signal Express
• The DAQ Assistant requires no programming. You can configure channels, timing,
triggering, and scales interactively.
• The DAQ Assistant can decrease development time. You can create a complete
application in a matter of minutes.
• If you create your application using the DAQ Assistant and later need functionality
that it doesn't expose, you can easily generate the equivalent API code from your
DAQ Assistant task if you use an NI ADE such as LabVIEW, LabWindows/CVI, or
Measurement Studio.
• The API contains advanced features not exposed by the DAQ Assistant.
• The API provides additional flexibility, allowing you to customize your application
to suit your needs.
• The API gives you tighter control over the performance of your application.
Related concepts:
• Clocks
• Triggering
In NI-DAQmx, select hardware timing with the Sample Clock Timing function/VI or by
setting the Sample Timing Type attribute/property to Sample Clock. If you do neither
of these things, or you set the Sample Timing Type attribute/property to On Demand,
you are selecting software timing.
Note Some devices do not support hardware timing. Refer to your device
documentation if you are unsure whether your device supports hardware
timing.
Clocks
Periodic digital edges measure time and are called clocks. Clocks such as a sample
timebase clock and the 20 MHz timebase clock mark the passing of time or are used to
align other signals in time. Clocks usually do not cause actions in the sense that
triggers do. The names of clocks usually do not refer to actions. The sample clock is a
notable exception.
The following are some common clocks used by DAQ devices. Refer to your device
documentation for all the clocks on your device.
138 ni.com
NI-DAQmx Key Concepts
other timebases are derived, if the device does not support an 80 MHz Timebase.
Otherwise, the clock produced by dividing the 80 MHz Timebase by 4.
• 80 MHz Timebase—The onboard clock source for the master timebase from which
other timebases are derived.
• 100 MHz Timebase—The onboard clock source for the master timebase from
which other timebases are derived.
• 100 kHz Timebase —The clock produced by dividing the 20 MHz Timebase by 200.
Note M Series, C Series, and X Series devices do not have a master timebase
of an arbitrary frequency. These devices use the 20 MHz/80 MHz/100 kHz
timebase directly.
The following diagram illustrates the M Series clocks that comprise analog input and
analog output timing. The black circles in the diagram represent terminals.
Onbrd Clk
RTSI (via RTSI) 80
10 MHz 0 MHz 80 MHz
RefClk RTSI 0-7 Ref PLL Timebase
1 Clock
80 MHz 20 MHz
Oscillator 8 2
PXI_CLK10 PLL Timebase
7 4
PXI_STAR
AnlgCmpEvent
AnlgCmpEvent PXI_STAR
PXI_CLK10 AnalogCompEvent
PXI_STAR Ctr1InternalOutput
PFI 0 - 15 Ctr0InternalOutput
RTSI 0 - 7 PFI 0 - 15
ai/SampleClk RTSI 0 - 7
Onbrd Timebase Onbrd
Clk Clk ai/SampleClk
200 Divisor
Onbrd
Clk
ai/ConvertClk
Divisor
ai/ConvertClock PFI 0 - 15
Timebase RTSI 0 - 7
Ctr0InternalOutput
PXI_STAR
PXI_STAR
PXI_CLK10 AnalogCompEvent
PXI_STAR Ctr1InternalOutput
PFI 0 - 15 Ctr0InternalOutput
RTSI 0 - 7 PFI 0 - 15
ao/SampleClock RTSI 0 - 7
Onbrd Timebase Onbrd
Clk Clk ao/SampleClock
200 Divisor
The following diagram illustrates the C Series clocks that comprise analog input and
analog output timing.
140 ni.com
NI-DAQmx Key Concepts
80 MHz
80 MHz Timebase
Oscillator 20 MHz
Timebase
4 Ctr0 Internal Output
Ctr1 Internal Output
ModN/AnlgCmpEvent
ModN/AnlgCmpEvent ModN/PFI0
ModN/PFI0 Mod5/PFI0–7
Mod5/PFI0–7 Mod6/PFI0–6
Mod6/PFI0–7 ModN/ai/SampleClk
200 Divisor
Onbrd
Clk Mod1/ai/ConvertClk
Divisor
Mod1 Mod8
Onbrd
Clk Mod8/ai/ConvertClk
Divisor
Ctr0InternalOutput
Ctr1InternalOutput
ModN/AnlgCmpEvent ModN/AnlgCmpEvent
ModN/PFI0 ModN/PFI0
Mod5/PFI0–7 Mod5/PFI0–7
Mod6/PFI0–7 Mod6/PFI0–7
Onbrd ai/SampleClk Onbrd
Clk Timebase Clk ao/SampleClock
200 Divisor
The following diagram illustrates the X Series clocks that comprise analog input,
analog output, digital input, and digital output timing. The black circles in the diagram
represent terminals.
RTSI 0-7
PFI 0-15
(RefClk)
100 MHz ÷ 10
Oscillator
PXIe_CLK100
Star_Trigger 100 MHz
RTSI 0-7 (RefClk) PLL
PFI 0-15 (RefClk) 100 MHz Timebase
20 MHz Timebase
÷5
100 KHz Timebase
÷ 200
Analog_Trigger
Analog_Trigger ai/ao/di/do/ReferenceTrigger
Star_Trigger ai/ao/di/do/SampleClk
ai/ao/di/do/
RTSI 0-7 (RefClk) ai/ConvertClk
SampleClkTimbase
PFI 0-15 (RefClk) ctrN/InternalOutput
100 MHz Timebase di/ChangeDetectEvent ai/ao/di/do/SampleClk
20 MHz Timebase ai/AnalogCompEvent
100 KHz Timebase
Divisor
÷ ai/HoldCompleteEvent
Star_Trigger
RTSI 0-7 (RefClk)
PFI 0-15 (RefClk)
Onboard Clk
Analog_Trigger
ai/ao/di/do/SampleClk
ctrN/InternalOutput
100 MHz
Divisor
÷ di/ChangeDetectEvent ai/ConvertClk
Timebase RTSI 0-7 (RefClk)
PFI 0-15 (RefClk)
Convert Clk
The following diagram illustrates the E Series clocks that comprise analog input and
analog output timing. The black circles in the diagram represent terminals.
Onboard
Clock ai/Convert
÷ Clock
Divisor
Related concepts:
142 ni.com
NI-DAQmx Key Concepts
The distinction between triggers and clocks is blurred when the digital edges used as a
trigger are periodic. In such a case, a clock causes the device to perform an action. The
sample clock is the primary example. The stimulus for the action of producing a
sample is so often a clock that NI-DAQmx configures the sample clock instead of the
sample trigger. The distinction is made clear when you consider the sample clock is in
fact just one way of providing the source of a sample trigger.
NI-DAQmx introduces the concept of a sample timing type. Each sample timing
type is a different stimulus for triggering the action of producing a sample. When you
select a Timing function/VI, you select your sample timing type. There also is an
attribute/property for setting the following sample timing types:
• Sample Clock—A digital edge produces each sample. Nearly all devices have an
onboard clock that is dedicated to producing these edges periodically. Even when
the edges are not periodic, as they might be when the clock source is something
other than the dedicated onboard clock, you still use sample clock timing. Sample
clock timing is a type of hardware timing.
• On Demand—Every time the Read or Write function/VI executes, the device
produces the requested samples as fast as possible. In this mode, the Sample
Quantity attributes/properties are ignored. On-demand timing is a type of
software timing.
• Change Detection—Change detection timing captures samples from digital
physical channels when NI-DAQmx detects a change-a rising edge, a falling edge,
or both rising and falling edges-on one or more digital lines or ports. Change
detection timing reduces the digital data an application has to process. One issue
to be aware of with change detection on some devices is overflow. Overflow occurs
when NI-DAQmx cannot read a sample prior to the next change detection event.
The effect is that one or more samples can be missed.
changes. You can query for an overflow by using the Overflow attribute/property in
your application after the task starts.
There are separate Burst Handshake Timing functions/VIs based on whether you
import or export a sample clock. Using the appropriate function/VI is important
because there are timing restrictions (such as setup and hold times) when sharing
a clock between the two devices.
• Implicit—The implicit sample timing type is used for acquiring period or frequency
samples using counters. It is also used for generating pulses. This timing type is
called implicit because the signal being measured is itself the timing signal or the
timing is implicit in the rate of the generated pulse train.
Related concepts:
Sample Clock
Your device uses a sample clock to control the rate at which samples are acquired and
generated. This sample clock sets the time interval between samples. Each tick of this
clock initiates the acquisition or generation of one sample per channel. You also can
connect an outside source as your clock. In software, you can specify the interval (how
fast the clock acquires or generates signals) by specifying the sample rate. You can
limit the sample rate by the signal conditioning you apply to the signals or the number
144 ni.com
NI-DAQmx Key Concepts
Note Sample clock timing for digital I/O is not supported on all devices.
Related reference:
Handshaking
For example, you might want to acquire an image from a scanner. The process involves
the following steps:
1. The scanner sends a pulse to your measurement device after it scans the image
and is ready to transfer the data.
2. Your measurement device reads an 8-, 16-, or 32-bit digital sample.
3. Your measurement device then sends a pulse to the scanner to inform the scanner
that the digital sample has been read.
4. The scanner sends out another pulse when the scanner is ready to send another
digital sample.
5. After your measurement device receives this digital pulse, the device reads the
sample.
Related concepts:
For digital input tasks, when the Pause Trigger signal is logic low and the Ready for
Transfer Event is logic high, the samples are sent to the measurement device. For
digital output tasks, when the Pause Trigger signal is logic low and the Ready for
Transfer Event is logic high, the NI-DAQmx device sends the samples to a peripheral
device. The sample clock, either onboard or external, controls the timing. Data is
transferred or acquired on either the rising or falling edge of the sample clock.
The default terminals used for burst handshaking signals vary from device to device.
Related concepts:
• Handshake Trigger—Also called Strobe Input (STB) and Acknowledge Input (ACK)
• Handshake Event—Also called Input Buffer Full (IBF) and Output Buffer Full (OBF)
For input tasks, when the Handshake Trigger signal is low, the samples are sent to the
measurement device. After the samples have been sent, Handshake Event is high,
which tells the peripheral device that the data has been read. For digital output,
Handshake Event is low while the NI-DAQmx device sends the samples to a peripheral
146 ni.com
NI-DAQmx Key Concepts
device. After the peripheral device receives the samples, it sends a low pulse back on
the Handshake Trigger line. Refer to your device documentation to determine which
digital ports you can configure for handshaking signals.
The default terminals used for handshaking signals vary from device to device.
Related concepts:
Use the STB and IBF signals for digital input operations and the OBF and ACK signals
for digital output operations. When the STB line is low, the samples are sent to the
measurement device. After the samples have been sent, IBF is high, which tells the
peripheral device that the data has been read. For digital output, OBF is low while the
software sends the samples to a peripheral device. After the peripheral device receives
the samples, it sends a low pulse back on the ACK line. Refer to your device
documentation to determine which digital ports you can configure for handshaking
signals.
For 8255-based devices, the ports in the task affect which handshaking lines are used.
Always use the handshaking lines associated with the highest order port in the task.
For instance, if you want to group ports 1 and 2 into a single task, use the handshaking
lines associated with port 2.
Connect all the STB lines together if you are grouping ports for digital input, as shown
in the following figure. Connect only the IBF line of the highest order port in the task to
the other device. No connection is needed for the IBF signals for the other ports.
STB*
Port x 1
IBF
STB*
Port x 2
IBF
STB*
External
Port x n
Device
IBF
(Highest Order Port)
If you group ports for digital output on an 8255-based device, connect only the
handshaking signals of the last port in the port list, as shown in the following figure.
ACK*
Port x 1
OBF
ACK*
Port x 2
OBF
ACK*
External
Port x n
Device
OBF
(Highest Order Port)
When performing handshaking, some lines are automatically reserved for control
purposes and are unavailable for use. The control lines used depend on the ports you
are using and whether you are handshaking with input or output channels. The
remaining lines in the port not used for control are still available for use. If you are
transferring data across any line in a port in a handshaking task, the entire port is
reserved for handshaking data and the remaining lines in the port are unavailable for
use.
148 ni.com
NI-DAQmx Key Concepts
Use hardware-timed single-point sample mode if you need to know if a loop executes
in a given amount of time, such as in a control application.
Continuous Pulses (HW Timed Updates) is hardware-timed single point for counter
output.
Related concepts:
Sample Clock
Ch1 Ch1
Ch2 Ch2
Ch3 Ch3
Multiplexed sampling devices have a single ADC for all analog input channels. These
devices use both a sample clock and a convert clock. The sample clock initiates the
acquisition of a sample from all channels in the scan list. The convert clock causes the
ADC conversion for each individual channel. The following figure depicts a three-
channel analog input task on a device that uses multiplexed sampling. Notice that,
unlike S Series devices, the samples are not digitized simultaneously.
Sample Clock
Convert Clock
Ch1 Ch2 Ch3 Ch1 Ch2 Ch3
The convert clock must run faster than the sample clock to achieve the specified
sample rate. For instance, if you specify a sample rate of 10 S/s for 8 analog input
channels, the convert clock must run at least eight times the sample rate (80 Hz) to
ensure that each channel is sampled 10 times a second. At faster sampling rates, you
must also take settling time between channels into account.
Related concepts:
• Clocks
• Device-Specific Sampling Methods
When a DAQ device samples a digital signal, the signal must remain stable for a period
of time before and after the assertion of the clock edge used for timing. The amount of
time before the assertion of the clock is called the setup time. The amount of time
after the assertion of the clock edge is called the hold time. Refer to your device
documentation for minimum setup and hold times.
Typically, when you use software timing to output samples on multiple AO channels,
NI-DAQmx writes a sample to the first DAC, and the sample is generated. Then, NI-
DAQmx writes a sample to the second DAC, and that sample is generated, and so on.
However, with the simultaneous single-point on-demand timing, all of the data is
generated at the same time after NI-DAQmx writes to each DAC. You set this timing
with the Simultaneous Analog Output Enable attribute/property.
Digital I/O and DAQ devices typically use the single-cycle timing response mode,
meaning the device responds to an external signal by the next active sample clock
edge.
Devices that support the pipelined timing response mode, such as the PCIe-6536 and
PCIe-6537, can respond to an external signal a few sample clock edges later. This mode
uses a source-synchronous clock scheme, which simultaneously returns the clock and
data to the acquiring device. With a source-synchronous data transfer, you can acquire
and generate data at much higher rates than with single-cycle timing response mode.
150 ni.com
NI-DAQmx Key Concepts
With the pipelined timing response mode, you can configure external sample clocks,
but the sample clock must be free-running and started before the task commits. If you
export the sample clock, the export occurs during a task commit. As with other events,
when the task uncommits, the signal remains exported.
Triggering
When a device controlled by NI-DAQmx does something, it performs an action. Two
very common actions are producing a sample and starting a waveform acquisition.
Every NI-DAQmx action needs a stimulus or cause. When the stimulus occurs, the
action is performed. Causes for actions are called triggers. Triggers are named after the
actions they cause:
• Advance Trigger
• Expiration Trigger
• Handshake Trigger
• Pause Trigger
• Reference Trigger
• Start Trigger
• Arm Start Trigger
In addition to specifying the action you want a trigger to cause, you must select the
type of trigger to use, which determines how the trigger is produced.
Advance Trigger
An Advance Trigger causes a switch device to execute the next entry in its instruction
(scan) list. You can configure this trigger to occur on a digital edge or when the Send
Software Trigger function/VI runs.
When you configure an Arm Start Trigger, a counter task does not respond to any Start
Triggers until after the Arm Start Trigger occurs. You can configure this trigger to occur
on a digital edge or at a specified time (for devices that support time triggering). The
Arm Start Trigger is separate from a Start Trigger and is typically used in advanced
counter/timer applications. You might use an Arm Start Trigger to synchronize multiple
tasks, such as counting edges and pulse generation. The Start Trigger then would be
used to start the acquisition or generation.
Expiration Trigger
An Expiration Trigger expires a watchdog task. You can use this trigger instead of the
watchdog timer to signal an expiration. You can configure this trigger to occur on a
digital edge.
Related concepts:
• Watchdog Timers
Handshake Trigger
A Handshake Trigger is a control signal from a peripheral device. The peripheral device
asserts the Handshake Trigger to indicate to the DAQ device that it has acquired a
sample (for output tasks) or generated a sample (for input tasks). For input tasks, the
DAQ device latches data, by default, at the trigger position specified by the Sample
Input Data When attribute/property, or when the peripheral device asserts the
Handshake Trigger.
Pause Trigger
With sample clock timing or burst handshake timing, the Pause Trigger pauses an
ongoing acquisition or generation. Deasserting this trigger resumes an acquisition or
generation. Depending on your device, there are some additional issues you need to
remember.
Related concepts:
• Pause Triggering
Reference Trigger
A Reference Trigger establishes the reference point in a set of input samples. You can
configure this trigger to occur on a digital edge, a digital pattern, an analog edge, or
152 ni.com
NI-DAQmx Key Concepts
when an analog signal enters or leaves a window. Data acquired up to the reference
point is pretrigger data. Data acquired after this reference point is posttrigger data.
Pretrigger Posttrigger
Samples Samples
Start Trigger
A Start Trigger begins an acquisition or generation. You can configure this trigger to
occur on a digital edge, a digital pattern, an analog edge, when an analog signal enters
or leaves a window, or at a specified time (for devices that support time triggering).
Trigger Types
In addition to specifying the action you want a trigger to cause, you must select the
type of trigger to use, which determines how the trigger is produced. If you need to
trigger off an analog signal, use an analog edge trigger or an analog window trigger. If
the trigger signal is digital, choose a digital edge trigger with the source typically being
one of the PFI pins.
For analog edge triggering, you configure the measurement device to look for a certain
signal level and slope (either rising or falling). After the device identifies the trigger
condition, the device performs the specified action associated with the trigger, such as
starting the measurement or marking which sample was acquired when the trigger
occurred. You connect analog trigger signals to any analog input channel or terminal
capable of accepting analog signals. Refer to the device-specific analog triggering
considerations for your device for additional information.
In the following figure, the trigger is set to capture data for a rising edge signal when
the signal reaches 3.2.
3.2
Hysteresis adds a window above or below the trigger level and often is used to reduce
false triggering due to noise or jitter in the signal. When using hysteresis with a rising
slope, the trigger asserts when the signal starts below level (or threshold
level) minus hysteresis and then crosses above level. The trigger deasserts
when the signal crosses below level minus hysteresis.
For example, if you add a hysteresis of 1 to the previous example, which used a
level of 3.2, the signal must start at or drop below 2.2 for triggering to occur. The
trigger then asserts as the signal rises above 3.2 and deasserts when it falls below 2.2.
Level
Level–Hysteresis
Trigger
When using hysteresis with a falling slope, the trigger asserts when the signal starts or
rises above level (or threshold level) plus hysteresis and then crosses below
level. The trigger deasserts when the signal crosses above level plus
hysteresis. If you instead trigger on a falling edge at 3.2 with a hysteresis of 1, the
signal must start at or rise above 4.2 and then fall below 3.2 for triggering to occur. The
trigger will then assert as the signal falls below 3.2 and deassert when it rises above
4.2.
Hysteresis+Level
Level
Trigger
154 ni.com
NI-DAQmx Key Concepts
Related concepts:
• Analog Triggering
An analog level trigger is similar to an analog edge trigger. With both trigger types, you
specify the edge—rising or falling—and the trigger level. With an analog edge trigger,
you are interested in the point at which the trigger condition is met. With an analog
level trigger, on the other hand, you are interested in the duration that the signal
remains above or below the trigger level. An analog level trigger is typically used with a
Pause Trigger. The Pause Trigger asserts or deasserts when the trigger condition is met.
In the following illustration, a trigger asserts when the signal crosses above the trigger
level and deasserts when it drops below it. The deassertion of the trigger could
correspond to a Pause Trigger.
Trigger Level
Trigger
An analog multi edge trigger functions similar to an analog edge trigger. The analog
multi edge trigger differs in that you can configure multiple channel sources acquiring
in the same task to each have their own analog trigger condition. When any of the
multiple channel sources satisfy their respective condition, a trigger is generated and
the device will perform the specified action associated with the trigger.
A window trigger occurs when an analog signal either passes into (enters) or passes
out of (leaves) a window defined by two voltage levels. Specify the levels by setting the
window top value and the window bottom value. The following image demonstrates a
trigger that acquires data when the signal enters the window.
Window Top
Window Bottom
Trigger Trigger
The following image demonstrates a trigger that acquires data when the signal leaves
the window.
Window Top
Window Bottom
Trigger Trigger
Related concepts:
A digital trigger is usually a TTL signal with two discrete levels: a high and a low level.
When the signal moves from high to low or from low to high, a digital edge is created.
There are two types of edges: rising and falling. You can produce Start or Reference
Triggers from the rising or falling edge of your digital signal.
In the following figure, the acquisition begins after the falling edge of the digital trigger
signal. Usually, digital trigger signals are connected to PFI pins on your measurement
device.
156 ni.com
NI-DAQmx Key Concepts
TTL Signal
For digital pattern triggering, you configure the device to detect a specific digital
pattern on specific physical channels. After detecting this condition, the device
performs the action associated with the trigger, such as starting the task or marking
which sample was acquired when the trigger occurred.
Requested
State Channel
x dev1/line0
1 dev1/line1
1 dev1/line2
1 dev1/line3
0 dev1/line4
0 dev1/line6
Pattern Matched
For pattern triggers on ports, the pattern match occurs in reverse order. For instance, if
you specify a pattern of "11000000" and a source of "dev1/port0," the pattern match
occurs when physical channels "dev1/line0" and "dev1/line1" are logic high and the
other six lines are logic low.
Software Triggers
Time Triggering
For devices that support it, a time trigger starts an acquisition or measurement at a
specific time. If the specified time has already elapsed, you will get an error message
indicating the time has already elapsed.
158 ni.com
NI-DAQmx Key Concepts
that way, the I/O Device Time provides the best precision and relative accuracy but
may reduce usability if it is not correlated to a recognizable global time. I/O Device
Time also has the advantage of being monotonically increasing, so time triggers
and timestamps spread across multiple devices or tasks accurately maintain their
offsets from each other.
• Host Time
The timescale your PC or NI Linux Real-Time controller uses. In cases where the NI
Linux Real-Time controller is the Grand Master of your 802.1AS subnet, Host Time
and I/O Device Time are the same. However, Host Time is typically synchronized to
a local Real Time Clock or a Network Time Protocol server, and it is usually
traceable to global time. Using Host Time is more intuitive because triggers and
timestamps on the chassis are specified in times that are easily correlated to your
local system time. However, this usability comes at the cost of reduced relative
accuracy between time triggers and timestamps that are spread across multiple
devices or tasks, because using the calculated offset between the two timescales is
not as accurate as using I/O Device Time directly. To help account for this loss of
accuracy in a specific and common use-case, NI-DAQmx guarantees that two
events that are scheduled for the same Host Time are guaranteed to start at the
same I/O Device Time, preserving precise synchronization between chassis.
Related concepts:
Synchronization
Synchronized operations are created by routing timing and control signals.
Synchronization can be within a single device—for instance, synchronizing analog
input and analog output on an M Series device—or on multiple devices. Timing and
control signals that synchronize operations fall into three categories: clocks, triggers,
and events.
These timing and control signals are routed by connecting two terminals together.
Selecting a terminal as the source of a clock or a trigger constructs a route. On PCI
devices, the RTSI bus provides the pathways for signal routing. On PXI devices, the PXI
trigger bus provides the same pathways. For NI-DAQmx to find a free PXI trigger line,
you must perform a PXI chassis identification in MAX. For NI-DAQmx to find a free RTSI
line, you must create a RTSI cable in MAX and populate it with the devices connected
by the cable. You can discover what routes are possible by referencing a table of
possible routes in MAX.
On some devices, you synchronize analog input, analog output, and digital input/
output channels from multiple modules by including those channels in the same task.
All channels within a task must be of the same channel type, such as analog input or
counter output.
Related concepts:
• Clocks
• Triggering
• Events
• Multidevice Tasks
Lockstep synchronization involves two or more similar devices sharing the same
timing and triggering and essentially acting as a single device. Sharing a sample clock
between analog input and analog output operations on a single device is also
considered lockstep synchronization. The goal of lockstep synchronization is to
eliminate skew as much as possible. In lockstep synchronization, clocks and triggers
are typically shared.
160 ni.com
NI-DAQmx Key Concepts
response to this pattern. At the same time or soon after, the digital device sends a
signal to a DMM causing the DMM to measure the voltage output by the DAC. When the
DMM has finished the measurement, it sends a signal back to the digital device causing
the digital device to send the next pattern to the DAC.
In lockstep synchronization, the operations involved all use a clock or trigger for the
same purpose. In handshaked synchronization, the roles of the trigger or event are
typically reversed between the operations (for example a Sample Complete Event from
a DMM is used as a Sample Clock by the digital device that receives it).
Related concepts:
• Skew
Most synchronization applications involve using a signal from another device. For
example, when performing Sample Clock synchronization, a device or set of devices
use the Sample Clock from another device. Even for Reference Clock synchronization,
where devices lock their onboard oscillators to a shared clock rather than use that
clock directly, the synchronized devices use the Start Trigger from one of the devices.
The device that provides the signal is called the master device, and all other devices in
the application that use that signal are called slave devices. Because the master device
provides all the signals, it begins acquiring or generating samples immediately when
the task starts. The slave devices, however, cannot acquire or generate data until
receiving the signals from the master. Therefore, you must start any tasks on slave
devices before starting the task on the master device. When you start the tasks on the
slave devices, they wait for the signals from the master device. Then, when the task
starts on the master device, that device emits the synchronized signals, ensuring all
devices start acquiring or generating samples simultaneously. If you start the task on
the master device before starting the tasks on slave devices, the master device will
acquire or generate data for a non-deterministic amount of time before the tasks start
on the slave devices. The application is not truly synchronized in such cases, and can
result in errors.
Related concepts:
Sources of Error
Jitter
Jitter is small variations in the period of the clock (from sample to sample). It shows up
as noise in the digitized signal and affects higher-frequency signals more. Each
component added to the clock's path adds additional jitter. You can control jitter but
not eliminate it by using an accurate clock source.
Stability
Stability describes how well the clock frequency resists fluctuations. Factors that can
cause the frequency to fluctuate include variations in temperature, time (aging),
supply voltage, shock, vibration, and capacitive load that the clock must drive.
Temperature is often the dominant factor that affects crystal oscillator stability.
Some oscillators are housed inside small ovens with controlled temperature to provide
stability that can be orders of magnitude better than with other techniques. These
oscillators are known as oven controlled crystal oscillators (OCXOs). For example, the
NI 6608 contains an OCXO.
Accuracy
Clock accuracy describes how well the actual frequency of the clock matches the
specified frequency. An oscillator generates a clock. However, an oscillator never
generates a perfect frequency. The accuracy of the oscillator-generated clock is
affected by the quality of the crystal and the oscillator's assembly.
You can describe timing errors in several different ways. Some common units of timing
error are parts per million (ppm) and parts per billion (ppb). Parts per million gives you
a fractional value of error. For example, to find the error in Hertz of an 80 MHz oscillator
with 5 ppm error, you multiply the frequency of the oscillator—80,000,000—by 5
divided by 1,000,000 or [80,000,000 Hz (5 Hz/1,000,000 Hz) = 400 Hz].
162 ni.com
NI-DAQmx Key Concepts
From this equation, you see that the oscillator can be off by as much as 400 Hz.
Therefore, the actual frequency of the oscillator can be anywhere between 79,999,600
Hz and 80,000,400 Hz. Parts per billion is similar to parts per million, and it is used to
describe more accurate clocks.
Skew
Skew is a propagation delay that is caused when a signal arrives at two places at
different times. For instance, a signal is sent by a controlling device at time T0. A
receiving device A acts upon the signal at time T1. A receiving device B acts upon the
signal at time T2. If T1 is not equal to T2, the difference between T1 and T2 is the skew.
The distance between devices and the cabling between your devices and signal paths
within the devices themselves all affect signal arrival times.
Methods of Synchronization
Several methods exist for synchronizing devices, depending on the devices involved
and the requirements of the application.
For synchronizing multiple tasks on a single device, even at different rates and on
different subsystems, you do not need to synchronize any clocks. Because the device
derives those clocks from the same internal oscillator, you need to share only the Start
Trigger among the tasks so the clocks start at the same time.
To perform Start Trigger synchronization, configure start triggering on all slave tasks,
setting the trigger source to the internal Start Trigger terminal from the master task,
such as ai/StartTrigger. You do not have to configure start triggering on the master
task. All tasks include an implicit Start Trigger, which occurs immediately when the
task starts.
Note You must start any tasks on slave devices before starting the task on
the master device.
Related concepts:
When using Sample Clock synchronization, slave devices replace the Sample Clock for
a given subsystem with the Sample Clock from another device.
To perform Sample Clock synchronization, configure all devices to use Sample Clock
timing. Set the source of the Sample Clock on all slave devices to the internal Sample
Clock terminal from the master device. For example, the name of the Sample Clock
terminal from the AI subsystem is ai/SampleClock.
Note You must start any tasks on slave devices before starting the task on
the master device.
Sample Clock synchronization results in skew due to the time required for the clock to
travel between devices. On multiplexed devices, Sample Clock synchronization results
in jitter because, even though you synchronized the Sample Clock, the devices do not
synchronize the AI Convert Clock.
Related concepts:
• Skew
• Jitter
• Master Timebase Synchronization
• Reference Clock Synchronization
• Master and Slave Devices
164 ni.com
NI-DAQmx Key Concepts
When using Reference Clock synchronization, a device does not directly use a clock
from another device in place of an onboard clock. Instead, all devices synchronize their
onboard oscillators to a common reference signal using a phase-locked loop. Each
device then derives other clocks from the synchronized oscillators. You must share a
Start Trigger for the derived clocks to start in phase.
For PXI devices, the reference signal is typically a 10 MHz clock on the chassis
backplane ( PXI_Clk10). For PXI Express devices, the reference signal is typically a 100
MHz clock on the chassis backplane ( PXIe_Clk100).
Note Always use one of the PXI or PXI Express chassis backplane clocks, if
possible. Using a clock from another device results in skew due to the time
required for the signal to travel from one device to the other.
PXI or PXI Express chassis backplane clocks might provide different accuracy than the
onboard oscillator of a device. For example, the PXIe-1062Q chassis has 25 ppm clock
accuracy, while the PXI-6259 has 50 ppm clock accuracy.
For PCI and PCI Express devices, that reference signal is a clock from another device
(typically 10MHzRefClk). Use the RefClk.Src attribute/property to specify the terminal
of the reference signal for a given task. Set RefClk.Src to OnboardClock on the
master device to lock to the onboard oscillator, rather than use it directly. Locking to
the onboard oscillator helps to equalize skew between the master and slave devices.
Some devices use a Master Timebase instead of a Reference Clock, thus they use
Related concepts:
• Synchronization
• Skew
• Accuracy
• Trigger Skew Correction
• Master Timebase Synchronization
• Sample Clock Synchronization
• Master and Slave Devices
When using Master Timebase synchronization, slave devices replace their onboard
oscillator (the Master Timebase) with the Master Timebase from a master device. Each
device then derives other clocks from the synchronized oscillators. You must share a
Start Trigger for the derived clocks to start in phase.
Note You must start any tasks on slave devices before starting the task on
the master device.
You must set two properties on the slave devices to synchronize the Master Timebase.
166 ni.com
NI-DAQmx Key Concepts
Master Timebase synchronization results in skew due to the time required for the clock
to travel between devices.
Most devices use a Reference Clock instead of a Master Timebase, thus they use
Reference Clock synchronization. Master Timebase synchronization also requires you
to share multiple signals and reserve multiple RTSI or PXI trigger lines for those
signals. For Sample Clock-timed applications where all devices run at the same rate,
you can use Sample Clock synchronization to eliminate the need for a shared Start
Trigger, thus the additional RTSI/PXI line. You can also use Sample Clock
synchronization to synchronize devices that use a Master Timebase with devices that
use a Reference Clock.
Related concepts:
• Synchronization
• Skew
• Reference Clock Synchronization
• Sample Clock Synchronization
• Master and Slave Devices
When using Sample Clock Timebase synchronization, slave devices replace the Sample
Clock Timebase for a given subsystem with the Sample Clock Timebase from another
device. Each device derives its Sample Clock from the synchronized Sample Clock
Timebase. You must share a Start Trigger for the derived clocks to start in phase.
Note You must start any tasks on slave devices before starting the task on
the master device.
You must set two properties on the slave devices to synchronize the Sample Clock
Timebase. Use the SampClk.Timebase.Src attribute/property to specify the terminal of
the Sample Clock Timebase from the master device. Because the slave devices then
use an external timebase, you must also use the SampClk.Timebase.Rate property to
specify the rate of that timebase. Instead of hard-coding those values, you can query
the Sample Clock Timebase rate and source from the master device and set the rate
and source on the slave devices to the same values.
Sample Clock Timebase synchronization results in skew due to the time required for
the clock to travel between devices.
Related concepts:
• Skew
• Master and Slave Devices
Mixed-Clock Synchronization
For some applications, the other synchronization methods might not be sufficient. In
such cases, you might be able to synchronize by using a clock from one device as a
different clock on another device. For example, to synchronize devices that use a
Reference Clock with devices that use a Master Timebase, such as to synchronize X
Series devices with E Series devices, you can perform Reference Clock synchronization,
but instead of locking the X Series reference clock to a PXI backplane clock, lock it to
the Master Timebase of the E Series device.
Mixing clocks in this manner is often much more complicated than using the same
clocks. You might have to manually configure several other timing parameters, such as
delays, active edges, or clock divisors. Use mixed-clock synchronization only as a last
resort if the other synchronization methods are not an option.
Related concepts:
• Methods of Synchronization
168 ni.com
NI-DAQmx Key Concepts
Counter Synchronization
You cannot synchronize counter input applications using implicit timing in the same
sense as analog input or output applications. These types of counter input
applications cannot be programmed to make their measurements at the same time
because the signals being measured themselves determine when the measurements
are made, and there is no reason to set up multiple devices to measure the same
signal. You also cannot use Start Triggers for these applications.
You can, however, ensure that all counters are using the same timebase for their input
measurements by sharing the CI Counter Timebase signal. Program all devices to use
the same signal (usually the 20MHzTimebase from one of the devices) as their CI
Counter Timebase. More generally, one device can be queried for its CI Counter
Timebase source and that terminal can be set as the source of the CI Counter
Timebase for the other devices.
Related concepts:
When sharing a trigger across multiple devices, the master device must respond to and
export the trigger, and the trigger signal must travel from the master device to slave
devices. This results in skew in the trigger signal. On some devices using Reference
Clock synchronization, you can compensate for that skew by locking the trigger to the
Reference Clock or to a clock derived from the Reference Clock. When you lock triggers
to a clock, the device responds to those triggers on a subsequent edge of that clock,
rather than immediately. Therefore, skew correction results in increased latency.
To enable trigger skew correction for an application, specify which device is the master
and which devices are slaves using the SyncType DAQmx Trigger property.
Related concepts:
Subsystem
A subsystem is the circuitry (ADCs, DACs, clocks, triggers, timing signals, timing
engines, and so on) that a device uses to acquire or generate samples. On DAQ devices,
there are separate subsystems for analog input, analog output, each counter, and
digital I/O. A subsystem is not synonymous with I/O type, however. For instance, each
counter's input and output circuitry make up one subsystem. The trigger bus can also
function as a subsystem.
Timing Engines
A timing engine is the circuitry a device uses to control an acquisition or generation.
Controlling an acquisition or generation includes:
• Utilizing timing signals to control when the device acquires or generates each
sample.
• Determining when to start and stop the acquisition or generation, using triggers
and other control signals.
• Producing clocks, triggers, and other control signals.
• Routing those signals to other devices or other parts of the same device.
Timing engines for different devices and subsystems provide different functionality.
The timing engine for an analog input or output subsystem uses a timebase to
produce a Sample Clock. The capabilities of a digital I/O timing engine depend on the
170 ni.com
NI-DAQmx Key Concepts
device. Some can use change detection and/or handshaking for sample timing, while
others can also produce a Sample Clock. Some timing engines cannot produce a
Sample Clock, but can perform Sample Clock timing if the clock comes from an
external source, such as from another subsystem or from a source external to the
device. For example, counters produce no inherent timing signals, but can utilize a
Sample Clock from an external source. Some devices can perform Sample Clock timing
for digital I/O, but require an external clock.
All timing engines can respond to and route control signals, such as triggers. Not all
triggers are supported by all devices and measurement types.
Most devices have a single timing engine per subsystem. When a task reserves
resources from a timing engine, another task cannot reserve those same resources.
However, another task can use signals routed by that timing engine. For example, a
counter task can use the Sample Clock from an analog input task. One task can use the
Start Trigger from another task to synchronize when the tasks start. Reserving one part
of a timing engine reserves the entire timing engine. For example, if an analog input
task uses the Sample Clock from an analog output task, the analog input task must
reserve the analog input timing engine to utilize that external Sample Clock. As a
result, another task can not use the Sample Clock from the analog input timing engine.
Note On-demand analog input tasks must reserve resources from a timing
engine.
Some devices have multiple timing engines available for some subsystems. Multiple
timing engines allow a device to run multiple tasks simultaneously on the same
subsystem or to use different terminals for handshaking.
Related concepts:
Related reference:
Events
Triggers and clocks are input signals. Exportable triggers and clocks, such as the
sample clock, also can be output signals. Output signals that do not have a trigger or
clock counterpart are called events. Events are emitted to signify a device state
change, the arrival of a certain kind of sample, the production of a certain amount of
samples, or the passage of time.
172 ni.com
NI-DAQmx Key Concepts
Note Some event signals might be missed when you run an application. This
typically happens with high-speed event sources. NI-DAQmx does not
generate an error if this occurs.
Related concepts:
• Handshake Trigger
• Start Trigger
Related reference:
Most exported signals exhibit the pulse behavior. When the event occurs, a finite pulse
is generated. The pulse width of some exported triggers and events is configurable.
The polarity of a signal exported as a pulse is also sometimes configurable. In the
following illustration, the polarity is set to active high, meaning the initial state change
of the signal is from low to high. When an event is exported as a pulse, each time the
event occurs, the exported signal pulses.
When an event is exported as a toggle, each time the event occurs the exported signal
changes state just once and remains at its new state until the next occurrence of the
event. You can also set the initial state. In the following illustration, the initial state is
set to high. The Counter Output Event is an example of a signal that can toggle.
For level behavior, the signal changes state and remains at that state for a period of
time that is dependent on some configurable aspect of your task. If you are exporting
the Sample Clock, the exported signal goes high at the beginning of the sample and
goes low when the last AI Convert Clock pulse begins, as shown in the illustration.
Convert Clock
Note On some devices, the exported signal can go low at the beginning of
the sample and then high when the last AI Convert Clock pulse begins. Refer
to your device documentation for additional information.
Software Events
Software events provide an asynchronous notification mechanism for a set of DAQ
events. Unlike hardware events, software events do not require you to use a thread to
wait until data is available. Using event-based programming, you can write an
application that continues to perform work while waiting for data without resorting to
developing a multi-threaded application.
174 ni.com
NI-DAQmx Key Concepts
• Done Event—Occurs when the task completes execution or when an error causes
the task to finish. Recoverable errors that do not cause the task to finish do not
cause this event to fire. Calling the Stop Task function/VI to complete execution
similarly does not cause this event to fire.
• Signal Event—Occurs when the specified hardware signal occurs. Supported
signals include the counter output event, change detection event, sample
complete event, and the sample clock.
Related concepts:
• Events
• Buffering
• How Is Buffer Size Determined?
• Data Transfer Mechanisms
• When Is A Task Done?
• Sample Clock
Related concepts:
• Buffering
• Selecting Read and Write Data Format and Organization
The read and write VIs have two major selection criteria: data format and data
organization. Data format deals with the type of the data that is returned. For example,
counter reads can return integers or floating-point formats. The second category, data
organization, deals with the structure the data is returned in. For example, analog
reads have a variety of array and scalar organizations.
Related concepts:
Data format deals with the type of the data that is read or written.
Related concepts:
176 ni.com
NI-DAQmx Key Concepts
For input tasks, you can use the additional information for a variety of purposes.
For example, you can update graphs to show the timing information and include
labels with the channel names. Analysis routines can use the timing information
for calculations such as FFTs. Because there is overhead associated with including
this additional information, NI-DAQmx allows you to configure the information you
want to include.
For output tasks, the timing information is the primary field that is useful. A
waveform generated by a library may include timing information that you can use
to set up the timing for your output task.
When reading data, the waveform data includes the time when the first sample in
the waveform was acquired, t0, and the amount of time that elapsed between
each sample, dt. However, there are limitations on these two values.
The dedicated digital format represents digital data similar to logic analyzers and
digital simulation tools. Each channel has no limits on the number of lines. In
addition, the digital format allows for additional states beyond basic 1s and 0s.
The ADE can take advantage of this format by tailoring data and graph displays for
the digital data.
For input tasks, you can use the additional information for a variety of purposes.
For example, you can update graphs to show the timing information and include
labels with the channel names. Because there is overhead associated with
including this additional information, NI-DAQmx allows you to configure the
information you want to include.
For output tasks, the timing information is the primary field that is useful. A
waveform generated by a library may include timing information that you can use
to set up the timing for your output task.
When reading data, the waveform data includes the time when the first sample in
the waveform was acquired, t0, and the amount of time that elapsed between
each sample, dt. However, there are limitations on these two values.
• Line Format (Boolean)—The line format represents each line within a channel as a
single Boolean value (a single byte). The states of the data are limited to 1s (true)
and 0s (false). Line formats are only provided for single sample reads and writes.
Use the line format when it is convenient for manipulating or displaying the digital
data. A typical application is controlling or reading back relay states. For high-
speed digital applications, you should generally not use the line format.
• Port Format (Integer)—The port format matches the native format of digital
devices that can represent only two digital states and organize individual lines into
collections known as ports. For more information, refer to Digital Data-Integer
Format.
The port format is the most efficient in terms of space, as it requires only a bit of
memory per line. In addition, the port format is often the most efficient in time as
it matches the native format of many devices.
The largest integer supported is 32 bits; therefore, you can read and write digital
channels with no more than 32 lines when using the port format.
178 ni.com
NI-DAQmx Key Concepts
The raw data format is defined by the native data format of the device.
Data Organization
The number of channels and the number of samples being read generally affect data
organization. For example, if 100 samples are read for eight analog channels using
64-bit floating-point format, a two-dimensional array is used with one index selecting
the channel and the second index selecting the sample. On the other hand, a simple
floating-point scalar value is sufficient to read one sample for one analog channel
using the 64-bit floating-point format. In general, the data organization for a particular
read or write call is the simplest reasonable format that can handle the number of
channels and samples requested.
There are often multiple legal data organizations to choose from. The main tradeoff to
consider for data organization is difficulty in manipulation of the data. You can use
data organizations that can handle multiple channels and multiple samples, but they
are generally the most complicated to manipulate.
Performance is similar for equivalent operations used to read or write data with
different data organizations.
Scalar data is generally not a good match for high-speed multiple sample
applications.
Scalar data also is not a good choice if multiple channels are acquired or generated
simultaneously. Using a multiple channel organization is easier and in the case of
output operations is actually a requirement.
• Array Data Organization—Array formats allow you to read or write data for
multiple channels and/or multiple samples at the same time. If you acquire or
generate on multiple channels simultaneously, reading and writing them at the
same time is easiest. Reading and writing multiple samples in one call is more
efficient than reading and writing samples one at a time.
• Raw Data Organization—The raw data organization is defined by the native
organization of the device.
Related concepts:
• Raw Data
You typically use an integer format to read or write entire ports. In integer format, each
digital channel you read or write must fit into one integer. For example, if the largest
channel in a task consists of one 8-line port, you can use the 8-bit, 16-bit, or 32-bit
format. If you have more than one 8-line port or a port with more than eight lines in
any channel within a task, you must use the 32-bit format.
Each byte in the integer maps to a port in the channel, in the order in which you added
the ports to the channel. The least significant byte maps to the first port added to the
channel, with all unused bytes zeroed out. Therefore, if a channel contains two 8-line
ports, port0 and port1, and you added port0 to the channel before port1, the
channel uses a 32-bit representation:
Within a particular byte, each bit in the integer maps to a line in the corresponding
180 ni.com
NI-DAQmx Key Concepts
port. NI-DAQmx orders the bits by line number, with the least significant bit mapping
to the lowest line number. Therefore, with these values assigned to the lines in the
channel, you might get the following:
port0/line0 0
port0/line1 0
port0/line2 1
port0/line3 0
port0/line4 1
port0/line5 1
port0/line6 0
port0/line7 1
port1/line0 1
port1/line1 1
port1/line2 1
port1/line3 0
port1/line4 1
port1/line5 0
port1/line6 0
port1/line7 1
If you specify only certain lines in a port to read or write, the full length of the integer is
still used, but all unused bits are zeroed out. Therefore, the following lines and values:
port0/line0 1
port0/line3 1
Interleaving
Interleaved samples prioritize samples before channels, such that the array lists the
first sample from every channel in the task, then the second sample from every
channel, up to the last sample from every channel.
Channel 0—Sample 1
Channel 1—Sample 1
Channel 2—Sample 1
Channel 0—Sample 2
Channel 1—Sample 2
Channel 2—Sample 2
...
Channel 0—Sample N
Channel 1—Sample N
Channel 2—Sample N
Non-interleaved samples prioritize channels before samples, such that the array lists
all samples from the first channel in the task, then all samples from the second
channel, up to all samples from the last channel.
Channel 0—Sample 1
Channel 0—Sample 2
...
Channel 0—Sample N
Channel 1—Sample 1
Channel 1—Sample 2
...
Channel 1—Sample N
Channel 2—Sample 1
182 ni.com
NI-DAQmx Key Concepts
Channel 2—Sample 2
...
Channel 2—Sample N
Raw Data
Raw data is in the native format and organization of the device, read directly from the
device or buffer without scaling or reordering. The native format of a device can be an
8-, 16-, or 32-bit integer, signed or unsigned.
If you use a different integer size than the native format of the device, one integer can
contain multiple samples or one sample can stretch across multiple integers. For
example, if you use 32-bit integers, but the device uses 8-bit samples, one integer
contains up to four samples. If you use 8-bit integers, but the device uses 16-bit
samples, a sample might require two integers. This behavior varies from device to
device. Refer to your device documentation for more information.
NI-DAQmx does not separate raw data into channels. It returns data in an interleaved
or non-interleaved 1D array, depending on the raw ordering of the device. Refer to
your device documentation for more information.
Related concepts:
• Interleaving
• Device Calibration Considerations
Unscaled Data
Unscaled data is in the native format of the device, read directly from the device or
buffer without scaling. The native format of a device can be an 8-, 16-, or 32-bit integer,
signed or unsigned.
Related concepts:
The limitation on t0 is that NI-DAQmx calculates the starting time for the task when
data is read the first time. At this time, NI-DAQmx calculates the starting time for the
task by reading the current system time and subtracting the number of samples
acquired × dt from the system. Therefore, if you call read after the acquisition is
complete, the calculated start time for the task is not accurate. This inaccuracy is
reflected in the t0 returned with the waveform data.
The limitation on dt is that for certain timing types, NI-DAQmx cannot calculate the
value of dt. When you use sample clock timing, NI-DAQmx calculates dt based on the
rate of the clock. Because NI-DAQmx does not know the rate when handshake,
implicit, on demand, or change detection timing is specified, NI-DAQmx returns dt as
0. Waveforms with a dt of 0 often do not work with the waveform analysis functions.
However, you can always update the value of dt in your application if you know the
expected rate of the timing source. Your ADE has an interface to update the value of dt.
Note The waveform data only supports symmetric timing between samples.
If your timing is not symmetric such as if each sample has a time stamp, the
waveform data format cannot contain the timing information. However, you
can use your ADE's analysis library to resample the data using a constant dt.
You can the use the resampled data with the waveform based analysis
library.
Buffering
A buffer is a temporary storage in computer memory for acquired or to-be-generated
samples. Typically this storage is allocated from your computer's memory and is also
184 ni.com
NI-DAQmx Key Concepts
called the task buffer. For input operations, a data transfer mechanism transfers
samples from your device into the buffer where they wait for a call to the Read
function/VI to copy the samples to your application. For output operations, the Write
function/VI copies samples into the buffer where they wait for the data transfer
mechanism to transfer them to your device.
If you use the Timing function/VI and set the sample mode to finite or continuous,
NI-DAQmx creates a buffer. If you set sample mode to Hardware Timed Single Point,
NI-DAQmx does not create a buffer.
If you set the Data Transfer Mechanism to Programmed I/O or set the buffer size to zero
by using either the Input or Output Buffer Config function/VIs, NI-DAQmx does not
create a buffer (even if you also used the Timing function/VI). A data transfer
mechanism of programmed I/O means there is no buffer.
Related concepts:
If your acquisition is finite (sample mode on the Timing function/VI set to Finite
Samples), NI-DAQmx allocates a buffer equal in size to the value of the samples per
channel attribute/property. For example, if you specify samples per channel of 1,000
samples and your application uses two channels, the buffer size would be 2,000
samples. Thus, the buffer is exactly big enough to hold all the samples you want to
acquire. If the acquisition is continuous (sample mode on the Timing function/VI set
to Continuous Samples), NI-DAQmx allocates a buffer equal in size to the value of the
samples per channel attribute/property, unless that value is less than the value listed
in the following table. If the value of the samples per channel attribute/property is less
than the value in the table, NI-DAQmx uses the value in the table.
Note For performance reasons, the default buffer size for continuous
acquisitions differs slightly when logging is enabled.
You can override the default buffer size by calling the Input Buffer Config function/VI.
NI-DAQmx does not create a buffer when the sample mode on the Timing function/
VI is set to Hardware Timed Single Point.
Note Using very large buffers may result in diminished system performance
due to excessive reading and writing between memory and the hard disk.
Reducing the size of the buffer or adding more memory to the system can
reduce the severity of these problems.
Output Tasks
For generations, the amount of data you write before starting a generation determines
the size of the buffer. The first call to a Multiple Samples version of the Write function/
VI creates a buffer and determines its size.
You also can use the Output Buffer Config function/VI to create an output buffer. If you
use this function/VI, you must use it before writing any data.
186 ni.com
NI-DAQmx Key Concepts
The samples per channel attribute/property on the Timing function/VI does not
determine the buffer size for output. Instead it is the total number of samples to
generate. If n is your buffer size, setting samples per channel to 3×n generates the data
in the buffer exactly three times. To generate the data exactly once, set samples per
channel to n.
NI-DAQmx does not create a buffer when the sample mode on the Timing function/
VI is set to Hardware Timed Single Point.
The NI-DAQmx API uses circular buffers as shown in the following figure. For input
operations, portions of data are read from the buffer while the buffer is filled. Likewise
for output operations, portions of the buffer can be written to while the buffer is
emptied. Using a circular buffer, you can set up your device to continuously acquire
data in the background while NI-DAQmx retrieves the acquired data.
Incoming Data
from the device End of Data Current Read Mark End of Data
to the PC
Current Read Mark End of Data End of Data Current Read Mark
When a continuous operation reaches the end of the buffer, it returns to the beginning
and fills up (or in the case of output operations, reads from) the same buffer again.
Your input application must retrieve data in blocks, from one location in the buffer,
while the data enters the circular buffer at a different location, so newer data does not
overwrite unread data.
While a circular buffer works well in many applications, two possible problems can
occur with this type of acquisition: Your application might try to retrieve data from the
buffer faster than data is placed into it, or your application might not retrieve data
from the buffer before NI-DAQmx overwrites the data into the buffer. When your
application tries to read data from the buffer that has not yet been collected, NI-
DAQmx waits for the data to be acquired and then returns the data. If your application
does not read the data from the circular buffer fast enough, you receive an error,
stating that some data has been overwritten and lost. If losing data in this way is not
important to you, change the setting of the OverWrite Mode attribute/property.
Even though you have set the sample mode parameter on the Timing function/VI to
Finite Samples, the acquisition runs continuously until the Reference Trigger occurs.
The number of posttrigger samples in your buffer after the acquisition has finished is
equal to the value of the samples per channel parameter from the Timing
function/VI minus the number of pretrigger samples from the Trigger function/VI.
When using a Reference Trigger, the default read position is Relative To First Pretrigger
Sample with a read Offset of 0.
The place where a read begins is called the Current Read Position. Each time data is
read, the Current Read Position is computed based on the settings of the Relative To
and Offset attributes/properties. When there is no Reference Trigger, the default for
Relative To is Current Read Position. When there is a Reference Trigger, the default for
Relative To is First Pretrigger Sample. In either case, the default for Offset is 0.
Changing the settings of these two attributes/properties controls where in the buffer
data is read.
During a continuous acquisition, for example, you can always read the most recent
1000 points by setting Relative To to Most Recent Sample and Offset to -1000. Even
when a Reference Trigger is configured, you can begin reading samples immediately by
188 ni.com
NI-DAQmx Key Concepts
The three Read Status attributes/properties are useful for observing the progress of
your acquisition.
• The Current Read Position is the place in the buffer where the next read begins if
the Relative To attribute/property is Current Read Position and the Offset is 0. In
any case, the Current Read Position is always where the last read left it.
• Total Samples per Channel Acquired is the total number of samples per channel
acquired by the device and transferred into the buffer.
• Available Samples per Channel is computed by first calculating the Current Read
Position based on the settings of the Relative To and Offset attributes/properties
and then subtracting this number from Total Samples per Channel Acquired.
By default, NI-DAQmx writes samples sequentially beginning with the first sample in
the buffer, and each write begins where the previous one left off. The sample where a
write begins is called the Current Write Position. Each time data is written, the Current
Write Position is computed based on the settings of the Relative To and Offset
attributes/properties. The default write behavior results from the default settings of
these two attributes/properties. The default for Relative To is Current Write Position
and the default for Offset is 0. Changing the settings of these two attributes/properties
controls where in the buffer data is written.
The three Write Status attributes/properties are useful for observing the progress of
your generation.
• The Current Write Position is the place in the buffer where the next write begins if
the Relative To attribute/property is Current Write Position and the Offset is 0. In
any case, the Current Write Position is always where the last write left it.
• Total Samples per Channel Generated is the total number of samples per channel
generated by your device since the task started.
• Space Available in Buffer is computed by first calculating the Current Write Position
based on the settings of the Relative To and Offset attributes/properties and then
subtracting this number from the sum of Total Samples per Channel Generated
and the buffer size. If regeneration is allowed, the Space Available in Buffer value is
capped at the buffer size and grows from 0 to the buffer size repeatedly.
Glitching
NI-DAQmx reduces the likelihood of glitching by ensuring that the writing of new
samples does not overtake the generation. This glitching protection works by pausing
the write until the total samples generated is more than one buffer ahead of the
current write position. However, NI-DAQmx does not ensure that the generation does
not overtake the new samples being written. If this occurs, a glitch results, and NI-
DAQmx reports the kWarningPotentialGlitchDuringWrite warning (error 200015). The
following suggestions can help you to avoid generating glitches:
• Write new samples that are almost one buffer ahead of the total samples
generated. By writing the new samples almost one buffer ahead of the total
samples generated, there is less of a chance that the generation overtakes the new
samples that are being written. If you are updating the entire buffer at a time, wait
to write the new samples until the total samples generated attribute/property is
one sample greater than an integral number of buffer sizes. For example, if the
buffer size is 1000 samples, wait to write new samples until the total samples
generated is either 1001, 2001, 3001, and so on.
• Increase the buffer size. If the buffer size is larger, there is less of a chance that the
generation overtakes the new samples that are being written.
• Decrease the sample clock rate. If the sample clock rate is slower, there is less of a
chance that the generation overtakes the new samples that are being written.
190 ni.com
NI-DAQmx Key Concepts
In the following graphs, the sine wave is generated from old samples and the square
wave is generated from the new samples. The first graph depicts glitching.
10.0
7.5
5.0
2.5
Amplitude
0
–2.5
–5.0
–7.5
Glitching
–10.0
0.0E+0 6.0E+0
Time
10.0
7.5
5.0
2.5
Amplitude
0
–2.5
–5.0
–7.5
–10.0
0.0E+0 6.0E+0
Time
There are four primary ways to transfer data across the PCI bus: Direct Memory Access
(DMA), Interrupt Request (IRQ), Programmed I/O, and USB Bulk.
DMA is a mechanism to transfer data between the device and computer memory
without the involvement of the CPU. This mechanism makes DMA the fastest available
data transfer mechanism. NI uses DMA hardware and software technology to achieve
high throughput rates and to increase system utilization. DMA is the default method of
data transfer for DAQ devices that support it.
IRQ transfers rely on the CPU to service data transfer requests. The device notifies the
CPU when it is ready to transfer data. The data transfer speed is tightly coupled to the
rate at which the CPU can service the interrupt requests. If you are using interrupts to
acquire data at a rate faster than the rate the CPU can service the interrupts, your
systems may start to freeze.
Programmed I/O
Programmed I/O is a data transfer mechanism in which a buffer is not used and instead
the computer reads and writes directly to the device. Software-timed (on-demand)
operations typically use programmed I/O.
USB Bulk
USB Bulk is a buffered, message-based streaming mechanism for data transfer. This
high-speed method is the default transfer mechanism for USB devices.
Memory Mapping
Memory mapping is a technique for reading and writing to a device directly from your
program, which avoids the overhead of delegating the reads and writes to kernel-level
software. Delegation to the kernel is safer, but slower. Memory mapping is less safe
because an entire 4 KB page of memory must be exposed to your program for this to
work, but it is faster. Memory mapping is set by default if your device supports it.
There are a limited number of DMA channels per device (refer to your device
documentation). Each operation (AI, AO, and so on) that requires a DMA channel uses
that mechanism until all of the DMA channels are used. After all of the DMA channels
are used, you receive an error if you try to run another operation requesting a DMA
channel. If appropriate, you can change one of the operations to use interrupts. For NI-
DAQmx, use the Data Transfer Mechanism channel attribute/property.
192 ni.com
NI-DAQmx Key Concepts
Regeneration
Generating the same data more than once is called regeneration. You can configure NI-
DAQmx to allow or disallow regeneration by setting the Regeneration Mode attribute/
property. By default, NI-DAQmx allows regeneration for sample clock timing and
disallows it for handshaking or burst handshaking timing. When regeneration is
disallowed, new data must be continuously written to the device.
When the Use Only Onboard Memory attribute/property is true, NI-DAQmx transfers
data only once to the device and that data is continually regenerated from there.
Attempting to write new data to the device after starting the task returns an error. In
addition, the amount of data written to the device before starting the task must fit in
the onboard memory of the device.
When this attribute/property is false, you can also set the Data Transfer Request
Condition attribute/property to specify when to transfer data from the host buffer to
the device.
TDMS Logging
Technical Data Management Streaming (TDMS) is a binary file format that allows for
high-speed data logging. When you enable TDMS data logging, NI-DAQmx can stream
data directly from the device buffer to the hard disk. NI-DAQmx improves performance
and reduces the disk footprint by writing raw data to the TDMS file, including the
scaling information separately for use when reading back the TDMS file. You can also
read data while logging to disk.
Related information:
You can split TDMS logs across multiple files by using either the DAQmx Start New File
function/VI or the Logging.SampsPerFile attribute/property.
The DAQmx Start New File function/VI starts a new TDMS file with the specified file
name the next time data is written to disk. If the logging mode is set to Log, data is
written to disk on multiples of the Logging.FileWriteSize attribute/property. For
example, if Logging.FileWriteSize is set to 150 when you use this function/VI, a new
TDMS file is created at the next 150 sample interval. If the logging mode is set to
Log and Read, data is written to disk when you call the DAQmx Read function/VI.
194 ni.com
NI-DAQmx Key Concepts
You can set the Logging.FilePath attribute/property while the task is running to change
the file path. The change takes place with the next file created. If you change the log
name, the numbering of the files resets to 0001. You can also change the directory to
save log files to by specifying a name ending in a back slash (for example, D:\). If you
specify a directory, the log file name remains the same and file numbering continues
off of the old directory. For example, if you change the directory from C:\ to D:\
while logging to testlog_0003.tdms, testlog_0003.tdms is written to C:\,
and testlog_0004.tdms is written to D:\.
To change a file immediately, you can also use the DAQmx Start New File function/VI
while the Logging.SampsPerFile attribute/property is active.
On-Demand Logging
For on-demand logging, NI-DAQmx creates a Time channel in the TDMS file that
contains timestamp data. The Time channel can be omitted with the WfmAttr Read
attribute/property, which specifies the data to return. To disable the Time channel, set
WfmAttr to Samples.
Pausing Logging
You can pause or resume logging by setting the Logging.Pause attribute/property. This
can be used if you do not want to initially log data but want to begin when a certain
condition is met. You can also use this attribute/property to temporarily disable
logging.
Before you resume logging data in Log and Read mode, you can set the Offset
attribute/property to log data that was previously read while logging was paused. For
example, if you set Offset to -1000 and resume logging, NI-DAQmx logs the 1000
samples read before Logging.Pause is enabled. After resuming logging, Offset is
automatically reset to 0.
Signal Routing
A single routing API now controls all the digital routing for NI measurements devices.
Signal routing controls the mapping of digital signals or triggers across hardware such
as digital multiplexers or public trigger buses.
• A single unified signal routing API for all devices supported in NI-DAQmx
• Multi-device routing: a single route will be able to span two devices
• Logical inverter support
• Double driving prevention across public trigger buses
Specifying a Route
A route is a connection between a pair of terminals. The source and destination
terminals make a terminal pair. Any time the source or destination terminal of a signal
is specified, a route is created. Usually, you specify only one terminal for the route. For
example, if you export a signal to the I/O connector, you set the destination terminal,
but the source terminal is predetermined by the name of the signal. If you import a
hardware trigger for a task, you can set the source terminal, but the destination
terminal is predetermined by the name of the trigger.
196 ni.com
NI-DAQmx Key Concepts
Task-Based Routing
Task-based routing is the most common form of routing. When you create a hardware
trigger or export a hardware signal, you create a task-based route. These routes are
embedded in a task. You can use Export Signal function/VI to explicitly make a task-
based route. When the task is committed, the route is committed. When the task is
cleared, the route is unreserved. Clearing the task does not always clear the route.
Refer to Lazy Line Transitions for more information.
Related concepts:
Immediate Routing
Immediate routing is not associated with any task. An immediate route is a pair of fully
qualified terminal names specifying the source and destination of the route. When an
immediate route is created, the route gets committed to hardware immediately.
Because an immediate route does not have a task governing its lifetime, you need to
actively destroy the route. Create an immediate route with the Connect Terminals
function/VI and destroy it with the Disconnect Terminals function/VI. Also, if you make
an immediate route multiple times with several calls to Connect Terminals, only one
call to Disconnect Terminals releases the route. There are other ways to destroy routes
such as resetting the device. Refer to Device Resetting and Interactions with Routing
for more information.
Related concepts:
As an example, assume that two separate tasks make the same route. The resources
associated with the routes are not released until both tasks have been unreserved.
198 ni.com
NI-DAQmx Key Concepts
Mixing task-based and immediate routes is acceptable, too. However, the hardware
resources are not released until all task-based routes have been released and the
immediate route has been disconnected.
For instance, assume that you have a device with a single bidirectional terminal on the
I/O connector. The terminal on the I/O connector is called the trigger terminal for
reference purposes. Also, the trigger terminal of the device is bidirectional because it
can accept an external trigger signal or export the internal trigger signal. The exported
internal trigger signal could be different from the external trigger signal.
By default, all tristate buffers associated with I/O connector terminals are disabled.
When a task-based route with a destination on the I/O connector is released, the
tristate buffer associated with the I/O connector terminal is not disabled. This means
that even though the route was released, glitches are minimized on the destination
terminal on the I/O connector. If you do not want this behavior, you can disable the
tristate buffer associated with the I/O terminal with the Tri-State Output Terminal
function/VI. Or, if you initially created the route by exporting a signal with the Export
Signal function/VI, you can also disable the tristate buffer by calling the Export Signal
function/VI with the same signal name but with an empty string as the output
terminal. Putting the terminal back into a tristate mode is necessary if an external
signal must be connected to the I/O terminal. If the terminal is not tristated first,
double driving the terminal damages the hardware.
All other connectors, such as the RTSI connector, use a different rule. When the task-
based route associated with the RTSI connector is released, the tristate buffer
associated with the RTSI terminal is disabled. The RTSI bus is a public bus that is
shared by multiple devices. All drivers using the RTSI bus assume that all devices on
the bus are tristated. The I/O connector is different because you have full control of it.
200 ni.com
NI-DAQmx Key Concepts
You must keep track of which terminals are tristated or being driven by internal or
external signals.
For instance, device A is running a task that performs an analog input operation. This
same analog input operation receives its Start Trigger from device B. This task spans
across device A and B due to the multi-device routing. If device B gets reset, all routes
on device B are destroyed. The invalidation of the task-based route on device B causes
its parent task on device A to be invalidated, too. You must consider these possible
consequences when issuing a device reset. If the route between device A and B is an
immediate route, there is not a relationship between the immediate route and the
task. This could result in the task not being invalidated. You need to decide if you need
to preserve the task.
Note MAX does not display the device routing table for SCXI chassis, SCC
connector blocks, or RTSI cable devices.
Each cell in the table is an index with the valid source and destination terminal for the
device. These are the same terminal names you can find in the Terminal Name I/O
control in LabVIEW.
If a route is possible between a source and destination terminal, the intersecting cell is
colored green or yellow. A green cell indicates the route can be made without
consuming any important resource of your device. A yellow cell indicates that
although the route is possible, something important must be consumed to create the
route. Placing the cursor over a yellow square reveals the resource used in the
subsystem used indicator. Usually, the sacrificed resource is a counter.
When you display the device routing table for a cDAQ chassis or a C Series device, the
table contains all of the terminals for the chassis and all devices installed in the
chassis.
Counters
This section provides an overview of counters in NI-DAQmx and the two counter
measurement method for period and frequency measurements.
Related concepts:
Paired Counters
For more complex and accurate measurements and generations, a counter is paired
with another counter with dedicated connections to and from each counter. This
pairing allows you to perform such operations as finite pulse-train generations, higher
accuracy frequency and period measurements, and cascaded edge counting. Paired
counters are generally numbered sequentially. For example, ctr0 and ctr1 are a pair,
ctr2 and ctr3 are a pair, and so on.
202 ni.com
NI-DAQmx Key Concepts
channel to which you want to connect your input signal. NI-DAQmx automatically
takes care of making the internal routes necessary to perform the measurement across
paired counters.
Related concepts:
To determine if you should use the high-frequency measurement method, refer to the
quantization error tables. If the quantization error listed for the one-counter method is
too high, use the high-frequency measurement method instead.
Related concepts:
• Paired Counters
• Quantization Error
If you measure the digital frequency or the period of a counter signal, you can use this
two-counter method to measure signals with large ranges. This method is useful when
you have a widely varying signal to measure and would like increased accuracy
throughout the entire range. Refer to the quantization error section for more
information on increasing measurement accuracy with the large-range measurement
method. You can also use this method to measure signal frequencies that are faster
than your counter timebase rate as long as the input signal does not exceed the
maximum input frequency supported by the counter.
For example, if you use a 24-bit counter and the Counter Timebase Rate is 100 kHZ, the
measurable frequency range is approximately 0.006 Hz to 50 kHz because
Counter Timebase
Frequency = × Divisor
Count
However, with a divisor of 4, the measurable frequency range is 0.024 Hz to 200 kHz
because
To determine if you should use the large-range measurement method, refer to the
quantization error tables. If the quantization error listed for the one-counter method in
204 ni.com
NI-DAQmx Key Concepts
that section is too high, use the large-range measurement method instead.
Related concepts:
• Quantization Error
• Paired Counters
Quantization Error
• Miss Both Edges—The counter recognizes neither the first rising edge nor the last
rising edge of the counter timebase, giving a count of one less than the expected
value.
• Miss One, Catch One—The counter only recognizes the first rising edge or the last
rising edge of the counter timebase, giving the expected value.
• Catch Both Edges—The counter recognizes both the first rising edge and the last
rising edge of the counter timebase, giving a count of one more than the expected
value.
GATE
SOURCE
Miss Both Edges 0 1 2 3 3
For example, if the counter timebase rate is 20 MHz, and the frequency of the input
signal is 5 MHz, the measured value can be 3, 4, or 5 due to quantization error. This
corresponds to a measured frequency of 6.67 MHz, 5 MHz, or 4 MHz, resulting in a
quantization error of as much as 33%.
For one counter time measurements, the following equation gives the quantization
error.
You can reduce the quantization error for single counter time measurements by
increasing the counter timebase rate. The following table shows the quantization error
for various timebase rates with given input signal frequencies:
For period and frequency measurements, if the quantization error is too large for your
input signal, you might consider using one of the two counter period and frequency
measurements.
For two counter high-frequency measurements, the following equations give the
quantization error.
Increasing the measurement time reduces the quantization error. The quantization
error also decreases with higher frequency input signals. The following table shows
206 ni.com
NI-DAQmx Key Concepts
the quantization error for various measurement times and input signal frequencies:
As the table shows, quantization error is reduced at higher frequencies of the input
signal. However, the advantage of this measurement method disappears at lower
frequency input signals because you need to measure longer to gain accuracy, and you
use up more resources.
For two counter large-range measurements, the following equations give the
quantization error.
Increasing the divisor, increasing the counter timebase rate, or lowering the input
signal frequency reduces the quantization error. The table lists the quantization error
for various divisors and input signal frequencies assuming a counter timebase rate of
20 MHz.
Notice that the use of a divisor reduces the quantization error. Although the high
frequency two-counter measurement method is more accurate at higher frequencies,
the large range two-counter measurement method is more accurate throughout the
range in a shorter amount of time. For example, if the input signal varies between 1
kHz and 1 MHz and you require a maximum quantization error of 2.0% at any signal
range, you need a minimum measurement time of 50 ms using the high frequency
two-counter measurement method. To gain the same accuracy using the large range
two-counter method requires a maximum measurement time of 4 ms for any one
208 ni.com
NI-DAQmx Key Concepts
measurement.
For dynamic averaging method, the following equation gives the quantization error.
To calculate the quantization error, this equation uses the Number of Signal Periods of
the input signal that have been measured and averaged. The number of periods is
dynamically adjusted based on a combination of the measurement time and divisor
settings, plus the period of the input signal being measured as shown in the following
equation.
The following table shows examples of quantization error for various divisor and
measurement time settings for different input signal frequencies. The counter
timebase rate is 100 MHz.
Related concepts:
210 ni.com
NI-DAQmx Key Concepts
configuration options that can be set before the start of an acquisition. These options
affect the amount of averaging or filtering applied to the counter measurements
allowing for tradeoffs in measurement accuracy and noise versus latency. During the
acquisition, the counter continuously measures and filters the input signal periods to
produce frequency or period measurements. The NI 9326 and 9361 use this method.
Related reference:
Related information:
• ni.com/docs
The NI 9326 can enable low pass filtering of counter signals to give accurate
measurement of in-band frequencies while rejecting higher frequency noise. Set the
CI.Filter.Enable attribute/property to true to enable filtering. Filtering is enabled by
default and is recommended as the easiest way to achieve accurate, low-noise counter
measurements.
With filtering enabled, you can then specify the filter cutoff frequency using the
CI.Filter.Freq attribute/property to control amount of filtering applied. Lower cutoffs
provide lower noise but longer latency. The latency of the filter can be queried using
the CI.FilterDelay attribute/property. Each counter can be configured with
independent settings.
Note The input divisor and measurement time settings wired into DAQmx
Create Virtual Channel VI are ignored. Instead, DAQmx calculates default
values for these settings based on the minimum and maximum values wired
to the DAQmx Create Virtual Channel VI. You can use a channel property node
to override these defaults allows for better control over the amount of
averaging applied to your application.
During an acquisition, the dynamic averaging method will average between 1 period
and divisor periods of the input signal to determine the input signal's frequency. The
measurement time property sets an upper limit to the amount of time that is used for
this averaging. As a result, the dynamic averaging method balances measurement
accuracy vs. measurement latency throughout the input signal range as shown in the
following table.
212 ni.com
NI-DAQmx Key Concepts
The measurement time and divisor can also be set manually using the property node
before the acquisition starts if the auto measurement settings are not desired. The
measurement time or divisor can be disabled by setting it to zero.
Measurement
Divisor Notes
Time
Measure 1 period of the input signal, similar to the 1 Counter (Low
0 1
Frequency) method.
Input
Counts the number of periods of the input signal that occur during input
measurement 0
measurement time, similar to the 2 Counters (High Frequency) method.
time
Input Counts how long it takes for the input divisor periods of the signal to
0
divisor elapse, similar to the 2 Counters (Large Range) method.
You can view examples of the dynamic averaging method in the NI 9361 datasheet,
which you can find at ni.com/manuals.
Related concepts:
The following list identifies the names of the advanced terminals as well as their
common uses:
• CtrnGate—The signal at this advanced terminal is used as the Start Trigger, pause
trigger, sample clock, or the input signal being measured. The following table lists
how this terminal is used in various applications:
• CtrnSource—The signal at this advanced terminal is either the input terminal for
the measurement or the counter timebase. The following table lists how this
terminal is used in various applications:
214 ni.com
NI-DAQmx Key Concepts
For the output of a counter to appear at the I/O connector (Ctr0Out, for example),
the signal on the internal output terminal must be routed to a terminal on the I/O
connector. For pulse generations, this route is automatically made to the
dedicated counter output terminal on the I/O connector. For measurements, if you
are interested in observing this signal, you need to manually make this route to the
appropriate pin on the I/O connector using the Export Signal function/VI with
Counter Output Event as the signal name. After you route the internal output of a
counter to the I/O connector, the signal remains on the I/O connector until the
device is reset or you explicitly tristate the terminal.
Counter Parts
A GATE input terminal controls when counting occurs. A GATE input is similar to a
trigger because it starts or stops a count.
A SOURCE (CLK) input terminal is the timebase for a measurement or the signal to
count.
A count register increments or decrements the number of edges to count. If the count
register decrements, it counts down to zero. The count register size is the number of
bits in the counter, and you calculate it as Count Register = 2no. of bits.
An OUT signal terminal can output a pulse or a pulse train, which is a series of pulses.
GATE OUT
Count Register
SOURCE
(CLK)
For non-buffered time-based measurements, calling the Read function/VI initiates the
measurement and returns the next valid sample. Calling the Read function/VI
repeatedly does not return consecutive measurements of the input signal.
216 ni.com
NI-DAQmx Key Concepts
Related concepts:
Implicit Timing
After the acquisition begins, NI-DAQmx measures each consecutive sample of the input
signal and stores the measurement in the input buffer. Due to this consecutive
measurement, the rate of the input signal implicitly determines the rate of the
acquisition.
Some devices support Sample Clock timing for buffered time-based measurements.
After the acquisition begins, your device measures each consecutive sample of the
input signal, but does not store it to the input buffer until an active edge of the Sample
Clock occurs. Using this timing type, the Sample Clock rate determines the acquisition
rate rather than the input signal. When using Sample Clock timing, all measurements
returned are a valid, complete cycle of your input signal. Using this method, you can
measure signals that are much faster than your sample rate, which minimizes the
amount of data transferred from your device to NI-DAQmx.
Related concepts:
Averaging
For frequency and period measurements using Sample Clock timing, some devices can
return an averaged measurement of all periods since the previous Sample Clock pulse,
instead of measuring only the period immediately preceding the current Sample Clock
pulse. Use the EnableAveraging DAQmx Channel property/attribute, associated with
each of those measurement types, to enable averaging.
Related concepts:
• Averaging Support
Depending on the phase of the input signal in relation to the start of the measurement,
the first sample of a buffered measurement is often invalid. For instance, if you are
performing a buffered period measurement, and you start the measurement when the
input signal is halfway through its current cycle, the measured period for the first
sample is half its expected value. Subsequent samples indicate the correct values
because they are guaranteed to be taken after a full period of the input signal. For this
reason, the first sample of buffered period, pulse width, and semi-period
measurements often indicates a smaller value than the actual value. For buffered
frequency measurements, the first sample often indicates a higher frequency than the
actual frequency. Some devices detect these incomplete samples and discard them.
Related concepts:
Pulse Measurement
Some devices support measuring individual pulses, returning each sample as a tuple
of frequency/duty cycle, high/low time, or high/low ticks.
Related concepts:
218 ni.com
NI-DAQmx Key Concepts
the counter, the counter implicitly starts and stops with each Read function/VI call, and
the position is not recorded properly between read calls.
With a buffered displacement measurement, the device latches the current position
onto each active edge of the sample clock and stores the position in the buffer. There
is no onboard clock for buffered displacement measurement, so you must supply an
external sample clock.
Counter Generation
Starts Complete
Initial Delay
High Low High Low High
Time Time Time Time Time
1 2 2 3 3
The high and low times provided in the Create Channel function/VI are ignored in this
case.
If you do not use a software buffer, all pulses generated will be the same, unless you
update the high time and low time while the application is running. This will cause the
pulse specifications to be software timed and change on-demand.
You can use the same attributes/properties that create the channel to update the pulse
specifications of the pulse train generation. Because you need two attributes/
properties to specify the pulse specifications of the pulse train, the specifications only
update when you set one of the two. For example, if you specify the pulse generation
in terms of frequency, the frequency and duty cycle control the specifications of
the generation. However, the pulse specifications only update when you set the
frequency attribute/property. The same is true when you specify pulse generation in
terms of time or ticks; the low time and low ticks control when the pulse
specifications update. When updating the pulse specifications of the pulse generation,
a complete period of the current specification generates before the new pulse
specification takes effect. Updating the pulse specifications while running is not
supported on buffered pulse train generation.
In some devices, such as M Series, E Series, and S Series devices, generating finite
pulse trains requires the use of paired counters. In devices that require paired counters
on a finite pulse train generation, the first counter (for example, Counter 0) generates a
pulse of desired width. The second counter (Counter 1) generates the pulse train,
which is gated by the pulse of the first counter. The routing is done internally. The
following illustration shows a two counter finite pulse train timing diagram.
Counter 0
(Paired Counter)
Counter 1
Generation
Complete
220 ni.com
NI-DAQmx Key Concepts
In Implicit mode, the Samples per Channel input to the Timing function/VI
determines the number of pulses to generate for finite pulse trains. In the following
illustration, three pulses are generated:
Counter Generation
Starts Complete
Initial Delay
High Low High Low High
Time Time Time Time Time
1 2 2 3 3
In Sample Clock mode, which uses a software buffer, the Samples per Channel
input determines the number of distinct pulse specification (High Time/Low Time)
transitions to generate. In the following example, Samples per Channel is set to
three. Notice that the counter increments after the sample clock pulses and the
counter signal transitions from high to low. The device generates the high and low
values specified in the Create Channel function/VI until the first sample clock arrives.
Counter Generation
Starts Complete
Initial Delay
High Low High Low High Low High Low High Low High Low High Low High Low High Low High Low High
Time Time Time Time Time Time Time Time Time Time Time Time Time Time Time Time Time Time Time Time Time
0 0 0 0 0 1 1 1 1 2 2 2 2 2 2 3 3 3 3 3 3
Sample Clock
When you set the idle state to low, the generation starts low for the initial delay, then
transitions to high for the high time. The low time is ignored for the first pulse, but will
be repeated before the high time for each subsequent pulse, as shown in the following
illustration.
Counter Generation
Starts Complete
When you set the idle state to high, the generation starts high for the initial delay, then
transitions to low for the low time. The high time is ignored for the first pulse, but is
repeated after the low time for each subsequent pulse. In both cases, the output rests
at the idle state after the pulse generation completes.
Counter Generation
Starts Complete
222 ni.com
NI-DAQmx Key Concepts
Terminals
A terminal is a named location where a signal is either generated (output or
produced) or acquired (input or consumed). A terminal that can output only one signal
is often named after that signal. A terminal with an input that can be used only for one
signal is often named after the clock or trigger that the signal is used for. Terminals
that are used for many signals have generic names such as RTSI, PXITrig, or PFI.
Related concepts:
When a terminal shares a name with a signal, it is not always clear which is being
referred to—the terminal or the signal. The sample clock provides a good example.
Within most devices, there is a terminal such that the signal at that terminal is always
used as the sample clock. So when you refer to the sample clock signal, you refer to
this terminal. For instance, for M Series analog input tasks, this terminal is named the
ai/SampleClock terminal. For analog output tasks, this terminal is named the ao/
SampleClock terminal.
When you use the Timing function/VI to select the source of the sample clock signal for
your analog input task on an M Series device, you choose a signal at some other
terminal to act as the source for the ai/SampleClock terminal. In other words, NI-
DAQmx connects your chosen terminal (a PFI terminal pin, for instance) to the ai/
Terminal Names
Terminal Names Explanation
An alias for the terminal within a device where the default source for a
clock can be found. If your application does not set the source of a clock
OnboardClock (or uses an empty string as the source), the clock's particular onboard
clock is used. For example, the onboard clock for the ai sample clock is
the ai Sample Clock Timebase.
Programmable Function Interface—general-purpose input
PFIn terminals, fixed-purpose output terminals. The name of the fixed output
signal is often placed on the I/O connector next to the terminal as a hint.
PXI_Trign PXI Trigger bus—general-purpose input/output lines.
Real Time System Integration bus—general-purpose input/
RTSIn output lines. RTSI7 is the exception. It is the only line to use for the 20
MHz Timebase signal.
A terminal within a device where the analog input sample clock can be
ai/SampleClock
found.
A terminal within a device where the analog input Start Trigger can be
ai/StartTrigger
found.
A terminal within a device where the analog input Reference Trigger can
ai/ReferenceTrigger
be found.
A terminal within a device where the analog output sample clock can be
ao/SampleClock
found.
A terminal within a device where the analog output Start Trigger can be
ao/StartTrigger
found.
A terminal within a device where the onboard clock source for the
20MHzTimebase
master timebase can be found.
A terminal within a device where the digital input sample clock can be
di/SampleClock
found.
A terminal within a device where the digital output sample clock can be
do/SampleClock
found.
di/ReferenceTrigger A terminal within a device where the digital input Reference Trigger can
224 ni.com
NI-DAQmx Key Concepts
226 ni.com
NI-DAQmx Key Concepts
228 ni.com
NI-DAQmx Key Concepts
Note M Series, C Series, and X Series devices do not have a master timebase
of an arbitrary frequency. These devices use the 20 MHz/80 MHz/100 kHz
timebase directly.
Related concepts:
The following table lists the revised names for analog input terminal names.
Original Revised
Terminal Terminal Explanation
Names Names
AIGND, The reference point for referenced single-ended measurements and
AIGND
ACHGND the bias current return point for differential measurements
ACH# AI# AI0, AI1, and so on; the analog input channels
AISENSE AISENSE The reference point for NRSE measurements using channels 0-15
AISENSE2 AISENSE2 The reference point for NRSE measurements using channels 16-79
AISENSE3 AISENSE3 The reference point for NRSE measurements using channels 80-143
AISENSE4 AISENSE4 The reference point for NRSE measurements using channels 144-207
AI HOLD
SCANCLK The terminal where the AI Hold Complete Event signal appears
COMP
AI START Placed as a hint next to the PFI terminal where the AI Start Trigger can
TRIG1
TRIG be emitted
Placed as a hint next to the PFI terminal where the AI Reference
TRIG2 AI REF TRIG
Trigger can be emitted
230 ni.com
NI-DAQmx Key Concepts
Original Revised
Terminal Terminal Explanation
Names Names
Placed as a hint next to the PFI terminal where the AI Convert Clock
CONVERT* AI CONV CLK
can be emitted
Placed as a hint next to the PFI terminal where the AI Sample Clock
STARTSCAN AI SAMP CLK
can be emitted
Related concepts:
The following table lists the revised names for analog output terminal names.
The following table lists the revised names for counter terminal names.
The following table lists the revised names for digital terminal names.
Original Revised
Terminal Terminal Explanation
Names Names
Ports on devices are referred to by a number. Port A is called port 0,
DIO# P0.#
for instance. The # symbol refers to a single digital line
PA#, PB#, and P0.#, P1.#, Ports on devices are referred to by a number. Port A is called port 0,
so on and so on for instance. The # symbol refers to a single digital line
P0.#, P1.#,
DIOA#, DIOB# The # symbol refers to a single digital line
and so on
The syntax for terminal names is a unique identifier that refers to a physical terminal in
your system. To guarantee the uniqueness of a terminal name across multiple devices,
terminal names begin with a forward slash, followed by the name of the device as
configured in MAX, such as Dev1. A forward slash and the name of the terminal follow
232 ni.com
NI-DAQmx Key Concepts
the device identifier, such as PFI3. For example, the fully qualified terminal name for
PFI3 on Dev1 is /Dev1/PFI3.
For terminals that exist on multiple subsystems or timing engines, the name of the
subsystem or timing engine precedes the terminal name. For example, the output
terminal of the Start Trigger for the analog input subsystem on Dev1 is /Dev1/ai/
StartTrigger.
Related concepts:
• Timing Engines
Coercion
When a value you set cannot be met exactly, NI-DAQmx sometimes adjusts—or
coerces—that value to a valid one. Coercion often occurs when an attribute/property
supports a set of discrete ranges.
After you set an attribute/property, you can query that attribute/property to determine
its actual value after coercion.
Related concepts:
For instance, suppose your device only supports ranges of 0 to 10 V, -5 to 5 V, and -10 to
0 V. If you set a maximum value of 8 V, NI-DAQmx coerces the maximum value to 10 V.
NI-DAQmx also coerces scaled values, including custom scaling. If you have a
temperature sensor that outputs 100 mV for every 1 °C, NI-DAQmx coerces a maximum
value of 80 °C to 100 °C.
Because NI-DAQmx coerces input limits, code width is calculated based on the coerced
values, which can be outside the minimum and maximum values you expect to
measure.
Related concepts:
• Device Range
• Input Limits (Maximum and Minimum Values)
• Coercion
• Custom Scales
• Calculating the Smallest Detectable Change—Code Width
Related concepts:
• Coercion
• Counter Frequency Coercion
Calibration
There are two types of calibration, channel calibration and device calibration.
Related concepts:
• Channel Calibration
• Device Calibration
Device Calibration
234 ni.com
NI-DAQmx Key Concepts
Related concepts:
Related information:
• Calibration Services
External Calibration
they are stored in a different area of the device memory. You can perform a self-
calibration at any time to adjust the device for use in environments other than those in
which the device was externally calibrated. You use the DAQmx Self Calibrate (or
DAQmxSelfCal) function/VI to perform a self-calibration.
Channel Calibration
Channel calibration is a technique used to achieve higher measurement accuracy. In
most applications, device calibration provides sufficient accuracy. However, in
applications where the highest degree of accuracy is critical, channel calibration is
necessary, but it does not replace device calibration. Channel calibration compensates
for various errors, including those introduced by cabling, wiring, and sensors.
Related concepts:
• Device Calibration
Control in NI-DAQmx
This section explains control concepts as implemented in NI-DAQmx. Timing control
loops, synchronizing analog input and output, using control algorithms, single-point
real-time applications, and setting priorities for control applications in LabVIEW are
described.
For a general introduction to control, independent of the software you are using, refer
to the control overview.
Related concepts:
236 ni.com
NI-DAQmx Key Concepts
Most of these applications use the Wait For Next Sample Clock function/VI, which
guarantees tight synchronization between the hardware layer and the software layers
for hardware-timed single-point tasks. Wait For Next Sample Clock provides an
accurate way to correlate application execution to hardware signals, such as the
sample clock for the given task, while providing feedback on the overall real-time
execution of the control loop.
Related concepts:
• Solution—Use the DAQmx Wait For Next Sample Clock function/VI to verify that a
new sample clock edge has not yet occurred.
Advantages
• The current iteration's output samples are guaranteed to be aligned with the
next iteration's input samples.
• NI-DAQmx returns an error if the DAQmx Wait For Next Sample Clock function/
VI does not start before the next sample clock edge occurs.
• I/O jitter is confined to the jitter of the hardware clock, which is on the order of
a few nanoseconds.
Restrictions
Read, process, and write operations are confined to the time available between the
moment the device starts acquiring data and the moment the next sample clock
edge arrives.
An example of this kind of application is an analog control loop that reads samples
from a specific number of analog input channels, processes the data using a control
algorithm (such as PID), and writes new control values to the analog output channels.
Normal
Idle Time Idle Time Idle Time Idle Time
Priority
Application
Read Waiting
Read Waiting
Read Waiting
Read Waiting
Wait for SC
Wait for SC
Wait for SC
Process
Process
Process
Process
Time-
Read
Read
Read
Read
Write
Write
Write
Critical
Software Layer
Hardware Layer
238 ni.com
NI-DAQmx Key Concepts
Note Although this example is written for LabVIEW users, the principles
apply if you are using another ADE, such as LabWindows/CVI.
LabVIEW Example
• Wire the DAQmx Wait For Next Sample Clock VI to one of the hardware-timed tasks.
Use dataflow wiring to guarantee that the DAQmx Wait For Next Sample Clock VI
executes after the AO Write call.
• If the DAQmx Wait For Next Sample Clock VI does not start before the arrival of the
next sample clock edge, it returns an error.
Note
• Use only one DAQmx Wait For Next Sample Clock VI within a LabVIEW
loop. If you have multiple hardware-timed single-point I/O tasks within
the same LabVIEW loop, you can connect the DAQmx Wait For Next
Sample Clock VI to any one hardware-timed single-point task within
that loop.
• If, when a cycle overflow occurs, you want to receive a warning rather
than an error, set the DAQmx Real-Time»Convert Late Errors to
Warnings property to True.
• The DAQmx Wait For Next Sample Clock VI has two modes of operation:
Polling and Wait For Interrupt. To change these values, use the DAQmx
Real-Time»Wait For Next Sample Clock Wait Mode property. Wait For
Interrupt mode, which is the default, allows lower priority processes to
execute while the time-critical loop waits for the next sample clock.
Polling mode allows for higher sampling rates, but it prevents lower
priority processes in the system from executing while the time-critical
loop waits for the next sample clock.
• The analog instance of DAQmx Read calls have two modes of operation:
Polling and Wait For Interrupt. To change these values, use the DAQmx
Read»Advanced»Wait Mode property. Wait For Interrupt mode allows
lower priority processes to execute while the time-critical loop waits for
all the requested samples to be converted. Polling mode allows for
higher sampling rates, but it prevents lower priority processes in the
system from executing while the time-critical loop waits for the
converted analog samples.
• The specific application shown in this section assumes the use of Wait
For Interrupt mode for both the DAQmx Wait For Next Sample Clock VI
and the analog instance of the DAQmx Read VI. To change these values,
use the DAQmx Read»Advanced»Wait Mode and/or DAQmx Real-
Time»Wait For Next Sample Clock Wait Mode properties.
Advantages
• The current iteration's output samples are guaranteed to be aligned with the
240 ni.com
NI-DAQmx Key Concepts
Restrictions
Read, process, and write operations are confined to the amount of time available
between the moment the device starts acquiring data and the moment the next
sample clock edge arrives.
Sample Application—Hardware-Timed Simultaneously Updated I/O with Data
Exchanges between Time-Critical and Non-Time-Critical Loops
An example of this kind of application is an analog control loop that reads samples
from a specific number of analog input channels, processes the data using a control
algorithm (such as PID), and writes the new control values to the analog output
channels. The application uses a real-time FIFO to stop the control loop based on a
Boolean value provided by a lower-priority process. A similar approach can employ the
use of real-time FIFOs to vary the PID parameters on the fly, or to transfer acquired and
control output values to lower-priority processes for data logging and remote
monitoring.
Timing Diagram
Idle Time
Idle Time
Idle Time
Idle Time
Idle Time
Idle Time
Normal
Idle Time
Priority
Application
RT-FIFO Comm
RT-FIFO Comm
RT-FIFO Comm
Read Waiting
Read Waiting
Read Waiting
Read Waiting
Wait for SC
Wait for SC
Wait for SC
Process
Process
Process
Process
Time-
Read
Read
Read
Read
Write
Write
Write
Critical
Software Layer
Hardware Layer
Sample
Clock (SC) Sample Period Sample Period Sample Period Sample Period
Note Although this example is written for LabVIEW users, the principles
apply if you are using another ADE, such as LabWindows/CVI.
• Wire the Wait For Next Sample Clock VI to one of the hardware-timed tasks. Use
dataflow wiring to guarantee that the Wait For Next Sample Clock VI executes after
the AO Write call.
• Use dataflow wiring to guarantee that the real-time FIFO operations execute after
the Wait For Next Sample Clock VI executes.
• If the Wait For Next Sample Clock VI does not execute before the arrival of the next
sample clock edge, it returns an error.
242 ni.com
NI-DAQmx Key Concepts
Note
• Use only one Wait For Next Sample Clock VI within a LabVIEW loop. If
you have multiple hardware-timed I/O tasks within the same LabVIEW
loop, you can connect the Wait For Next Sample Clock VI to any one
hardware-timed single-point task within that loop.
• If, when a cycle overflow occurs, you want to receive a warning rather
than an error, set the DAQmx Real-Time»Convert Late
Errors to Warnings property to True.
• Although you do not have to place the real-time FIFO code after the
Wait For Next Sample Clock VI, it is highly recommended that you do so
when dealing with multiple-channel analog input operations on
multiplexed devices (such as E and M Series). Because the device can
spend up to 50% of the sample period converting samples on the
analog input channels, executing the FIFO code during this conversion
period has the advantage of using up otherwise idle time.
• You can increase the Analog Input Conversion Rate manually through
the DAQmx Timing Property Node. This reduces the total amount of
time spent converting the requested number of samples. It is important
to consider the minimum settling time specifications for the complete
data acquisition system to avoid signal degradation and interference.
Advantages
Restrictions
Output updates suffer from software jitter because they are not hardware-timed.
An example of this kind of application is an analog control loop that reads samples
from a specific number of multiplexed analog input channels, processes the data using
a control algorithm (such as PID), and writes the new control values to the analog
output channels using a software-timed task.
Timing Diagram
Idle Time
Idle Time
Idle Time
Application
Read Waitng
Read Waitng
Read Waitng
Read Waitng
Read
Read
Read
Read
Write
Write
Write
Time-
Process Process Process
Critical
Software Layer
Hardware Layer
Note Although this example is written for LabVIEW users, the principles
apply if you are using another ADE, such as LabWindows/CVI.
244 ni.com
NI-DAQmx Key Concepts
• Set the Report Missed Samples property for the analog input operation to True.
• The analog input operation returns an error if new samples are available before
the read operation finishes converting samples from the previous iteration.
Note
• If, when an Analog Input Read overflow error occurs, you prefer to
receive a warning rather than an error, set the Convert Late Errors to
Warnings property to True.
• Do not use the Wait For Next Sample Clock VI and the Report Missed
Samples property within the same LabVIEW loop.
• Only hardware-timed single-point analog input tasks support the
Report Missed Samples property.
• Because the analog output task is software timed, the value is written
out as soon as the write call is initiated. It does not wait for a hardware
clock to output the data.
Advantages
• Counter tasks allow for flexible timing and event detection operations that can
drive the software processing of the control loop. In other words, the control
loop can have a dynamic clock rate.
• NI-DAQmx returns an error if the Wait For Next Sample Clock function/VI does
not start before the next sample clock edge arrives.
Restrictions
Read, process, and write operations are confined to the time available between the
moment the device starts acquiring data and the moment the next sample clock
edge arrives.
Related concepts:
An example of this kind of application is a control loop that uses a counter input task,
such as count edges, while controlling digital lines based on some predefined control
logic. This sample application performs communication through the use of real-time
FIFOs. In LabWindows/CVI, you can use a thread-safe queue instead of real-time FIFOs.
Timing Diagram
Idle Time
Idle Time
Idle Time
Normal
Priority
Application
RT-FIFO Comm
RT-FIFO Comm
RT-FIFO Comm
RT-FIFO Comm
Wair for SC
Wait for SC
Wait for SC
Time-
Process
Process
Process
Process
Read
Read
Read
Read
Write
Write
Write
Write
Critical
Software Layer
Hardware Layer
246 ni.com
NI-DAQmx Key Concepts
Another example application is a control loop that monitors discrete inputs and uses
the values to update a counter output task, using pulse frequency mode to generate
pulse-width modulation control signals. This example application performs
communication through the use of real-time FIFOs. In LabWindows/CVI, you can use a
thread-safe queue instead of real-time FIFOs.
Timing Diagram
Idle Time
Idle Time
Idle Time
Normal
Priority
Application
RT-FIFO Comm
RT-FIFO Comm
RT-FIFO Comm
Wait for SC
Wait for SC
Wait for SC
Process
Process
Process
Process
Time-
Read
Read
Read
Read
Write
Write
Write
Critical
Software Layer
Hardware Layer
Note Although this example is written for LabVIEW users, the principles
apply if you are using another ADE, such as LabWindows/CVI.
• Wire the Wait For Next Sample Clock VI to the counter input task.
• If the Wait For Next Sample Clock VI does execute before the arrival of the next
sample clock edge, it returns an error.
Example 2
• Wire the Wait For Next Sample Clock VI to the counter output task.
• If the Wait For Next Sample Clock VI does not execute before the arrival of the next
sample clock edge, it returns an error.
Note
• Use only one Wait For Next Sample Clock VI within a LabVIEW loop. If
you have multiple hardware-timed I/O tasks within the same LabVIEW
loop, you can connect the Wait For Next Sample Clock VI to any one
hardware-timed single-point task within that loop.
• If, when a cycle overflow occurs, you want to receive a warning rather
than an error, set the DAQmx Real-Time»Convert Late Errors to
Warnings property to True.
• Hardware-timed counter operations have no conversion period similar
to that of multiplexed analog input. Therefore, the real-time FIFO can
be placed anywhere within the LabVIEW loop.
• NI-DAQmx provides a mechanism to recover after missing a sample
clock edge when performing counter writes. If this write recovery
248 ni.com
NI-DAQmx Key Concepts
Advantages
• Using a timing source allows you to specify an I/O signal (for example, the
sample clock signal) to trigger the execution of Timed Loop iterations.
• Timing sources such as the Control Loop From Task provide strict lateness
checking and allow other threads to execute while several analog channels are
being multiplexed and sampled.
• The Timed Loop provides feedback as to whether the iterations complete in
time.
• Multi-rate applications, using distinct I/O hardware subsystems, are possible
by extending this approach to multiple Timed Loops.
Restrictions
An example of this kind of application is an analog control loop that reads samples
from a specific number of analog input channels, processes the data using a control
algorithm (such as PID), and writes the new control values to the analog output
channels.
You can create such an application with the Control Loop From Task timing source. The
Control Loop From Task timing source uses the sample clock signal from the analog
input task, which allows strict lateness-checking of all tasks associated with that
sample clock.
The Control Loop From Task timing source also allows you to specify a delay between
the time the sample clock event is handled and the time the Timed Loop starts
executing. This delay, or sleep time, keeps the DAQmx Read function/VI inside the
Timed Loop from using 100% of the CPU time available while waiting for the analog
input samples to be multiplexed and digitized.
Timing Diagram
Idle Time
Idle Time
Idle Time
Application
Clock
Sample Clock
Sample Clock
Timed
Process
Process
Process
Read
Read
Read
Read
Write
Write
Write
• Create a Control Loop From Task timing source for the Timed Loop. This signal
250 ni.com
NI-DAQmx Key Concepts
serves as the timebase that drives the execution of the Timed Loop.
• The Timed Loop provides feedback to the application as to whether the previous
iteration completed in time. It does this through the "Finished Late [i-1]" node.
• Allow a few warm-up iterations to account for the effects of processor-caching and
other events that may occur during the first iterations of the loop.
Note
The following diagram shows, for multiple channel configurations, the effect of the
amount of sleep over the maximum achievable rate and the amount of work lower-
priority threads can execute at such rates.
The graph shows that, when acquiring 8 channels using a specific hardware and
software configuration, the maximum achievable rate decreases as soon as the
amount of sleep time increases from 0 to 5 µs. This is not, however, the case for the 12-
and 16-channel configurations, for which increasing the amount of sleep up to 10 and
15 µs respectively has no visible effect on the maximum achievable I/O rates. In the 12-
and 16-channel case, the additional sleep interval allows other threads to execute
252 ni.com
NI-DAQmx Key Concepts
more work (refer to definition below) without affecting the overall I/O rate of the
application.
Benchmark Configuration
• Hardware Configuration:
◦ NI PXI-8196 RT Controller
◦ NI PXI-6070 E Series MIO device
◦ NI PXI-6723 Analog Output device
• Software Configuration:
◦ LabVIEW Real-Time 8.0
◦ NI-DAQmx 8.0
◦ Ethernet driver set to polling mode
• Benchmark details:
◦ A work unit is defined as the number of times a normal-priority loop can
increment an unsigned 64-bit number while the I/O Timed Loop, depicted in
the sample block diagram above, runs in parallel with it.
◦ The analog input conversion is not explicitly configured. This means that the
DAQmx driver auto-calculates it based on the number of channels and desired
sample clock rate.
Software-Timed I/O
Advantages
• You can perform I/O control loops with operations that are not hardware-
timed.
• Read, process, and write operations are confined to the software timing period
that you define with the Timed Loop or asynchronous timers.
Restrictions
An example of this kind of application is a digital I/O control loop. The application
monitors the state of several discrete inputs and toggles the corresponding output
based on the control algorithm. Hardware timing is not available for single-point
digital I/O tasks in NI-DAQmx.
Timing Diagram
Idle Time
Idle Time
Normal
Priority
Application
Process
Process
Process
Process
Read
Read
Read
Read
Write
Write
Write
Write
Timed
Loop
Software Layer
Hardware Layer
Note Although this example is written for LabVIEW users, the principles
apply if you are using another ADE, such as LabWindows/CVI.
• A Timed Loop running off the system's time sources (millisecond or microsecond
resolution) accomplishes the task. Configure the Timed Loop to run at the desired
rate.
• Configure all tasks to be software-timed (on demand).
• The Timed Loop provides feedback to the application as to whether the previous
iteration completed in time. It does this through the "Finished Late [i-1]" node.
254 ni.com
NI-DAQmx Key Concepts
Note
• The Timed Loop allows the application to adjust its period from within
the loop, allowing the implementation of dynamic timing algorithms
for control.
• Lower-priority processes can execute while the Timed Loop waits until
its next iteration.
• Other software timing methods include the use of the Wait and Wait
Until next multiple VIs (with microsecond or milliseconds resolution).
These methods provide no feedback when the application falls behind.
For software timing, the software and operating system determines the rate at which
the loop executes. Software timing is not deterministic. Controlling a while loop and
using the Wait Until Next ms Multiple VI to handle timing is an example of a software-
timed loop. Hardware timing uses the DAQ device internal clock or an external clock to
control when a read executes within a loop. The example block diagram shown in
Control Loops in the Common Applications section uses hardware timing.
The Timed Loop structure is hardware timed. It is ideal for multirate applications. By
default, the Timed Loop uses the 1 kHz clock of the Windows operating system as its
timing source. Refer to your LabVIEW Help for more information about the Timed
Loop structure.
Related concepts:
• Real Time
Control Algorithms
There are many data processing algorithms to consider when creating a control
application. You can create custom control algorithms using LabVIEW. You also can use
VIs, such as the LabVIEW Control Design and Simulation Module VIs and Functions, to
process control application data. This module offers several libraries that you can use
to design, analyze, simulate, and deploy dynamic system models, including
controllers.
Input Input
(first point) (second point)
Time
Processing
Related concepts:
• Synchronization
256 ni.com
NI-DAQmx Key Concepts
each with its own priority. By setting priorities, time-critical tasks can take precedence
over non-time-critical tasks. The time-critical task must periodically yield processor
resources to the lower-priority tasks so they can execute. By properly separating the
time-critical task from lower priority tasks, you can reduce application jitter. Refer to
the LabVIEW Real-Time Module Help for details on assigning priorities to tasks.
Related concepts:
I/O Cycles
The input and output operations along with any processing performed during a single
sample clock period are called I/O cycles. I/O cycles can consist of reads or writes
only, but an I/O cycle in a typical control application consists of reading data,
processing that data, then writing a result.
Refer to the Measurement & Automation Explorer Help for NI-DAQmx for
detailed instructions on creating NI-DAQmx simulated devices and importing NI-
DAQmx simulated device configurations onto physical devices.
Related concepts:
• NI-DAQmx simulated devices simulate timing for continuous analog input, digital
input, and all output tasks. Timing is not simulated for counter tasks.
• NI-DAQmx simulated devices do not cause a timed loop to execute.
• NI-DAQmx simulated devices support software events. However, events that rely
on the hardware, such as a sample clock event, are not supported.
• Triggers always occur immediately.
• Watchdog timers do not expire.
Note NI-DAQmx simulated devices cannot be included in the same task with
physical devices.
Reading Data
All NI-DAQmx simulated devices return analog input data in the form of a full-scale sine
wave with 3% of full-scale noise.
When multiple channels are in the task, the data for each channel is offset 5° in time.
Setting the minimum and maximum signal input range determines the amplitude of
the simulated signal. If you decrease the minimum and maximum values the
258 ni.com
NI-DAQmx Key Concepts
amplitude of the simulated sine wave decreases. However, on real hardware , your
analog input signal clips at the maximum and minimum signal input range that is set.
For simulated AO data, set the minimum and maximum values for Signal Output
Range. The range cannot exceed the specifications for the real hardware. Set the Test
Signal Type to Sine Wave, Square Wave, or Triangle Wave. If you are using a Test Panel,
there are options for DC and Sinewave generation.
Digital data is always returned as if each eight-bit port were a binary counter for both
digital input and output.
Writing Data
Data written to an NI-DAQmx simulated device is scaled as if the device were real. So,
any custom scales implemented in a task would affect the simulated data
appropriately.
Distributed Applications
This section includes information about deploying applications and using the DAQmx
I/O Server for distributed applications.
Related concepts:
• Deployment
• DAQmx I/O Server and Virtual Channels
Deployment
When deploying an application, you must coordinate the use of configuration items
that can be shared among multiple tasks. This includes devices, scales, and global
virtual channels.
• You can use the MAX Export Wizard to deploy an entire setup to another computer,
including tasks, channels, scales, and devices.
• You can use the MAX Export Wizard to deploy an entire setup, except the device
configurations, to another computer. You might choose to do this if the target
computer already has tasks that rely on existing device configurations. In this case,
you might have to make modifications after deployment so that your tasks and
channels refer to the device configurations on the target computer.
• You can use the MAX Export Wizard initially to deploy a fixed set of device, scale,
and global virtual channel configurations among a group of users. Each member of
the group can create tasks that rely on the shared configurations, then create
applications that use these tasks, and finally share the applications within the
group. In some cases, the tasks deploy with the applications automatically. In
other cases, you must deploy the tasks separately from the applications. Refer to
the Deploying Tasks and Channels section for more information.
Your tasks and channels deploy automatically with your application under the
following circumstances:
• You use LabVIEW Express VIs for your DAQ applications, and the tasks use local
channels only.
• You save your tasks within a LabWindows/CVI or Measurement Studio project, and
the tasks use local channels only.
• You create your tasks and channels programmatically using the NI-DAQmx API.
You must deploy your tasks and channels using the MAX Export Wizard if you create
your tasks and channels in the following ways:
260 ni.com
NI-DAQmx Key Concepts
Note If your project uses global virtual channels that were added, not
copied, generating a LabVIEW diagram from SignalExpress still requires
deployment of channels using the MAX Export Wizard.
Note You must have at least one global virtual channel defined either in the
project or in Measurement & Automation Explorer (MAX) to use the NI-DAQmx
I/O Server. Global virtual channels of any I/O type can be bound to shared
variables, but tasks cannot.
When using a third-party OPC client, connect to the variable engine server to access
DAQ channels on the network.
Refer to the LabVIEW Help for information about binding to a DAQ channel using a
shared variable in a LabVIEW Project.
• Properties for LabVIEW, Visual C++, Visual Basic .NET, and Visual C#
• Get and Set Attribute functions for ANSI C and LabWindows/CVI
You also can use external reference voltages to apply a gain to a DC voltage or to a
time-varying waveform. For example, set your external reference voltage level to 1.0,
and write a sine wave buffer with values from -1.0 to +1.0 V. When you apply an actual
reference voltage of 2.0 V, your signal jumps to ±2 V in amplitude. Increasing the
reference voltage level to 3.0 again jumps the signal to ±3 V. Applying a reference
voltage level of 0.0 V immediately flat-lines your time-varying voltage signal at 0.0 V.
The terminal you use for external reference sources varies depending on your device.
Related concepts:
Custom Scales
You can create scales to specify a conversion from the prescaled units measured by a
channel to the scaled units associated with your transducer or actuator. For input
channels, the scale converts samples read to the final scaled units. For example, a
scale could convert a voltage to a linear position. For output channels, the scale
converts samples written to the prescaled units of the channel. For example, a scale
262 ni.com
NI-DAQmx Key Concepts
could convert a linear position to a voltage. You also can use scales to calibrate
samples read or written so that the final scaled units are identical to the prescaled
units of the channel.
Often, you do not need to create a scale because NI-DAQmx has explicit support for
many of the most common transducers, sensors, and actuators. For example, when
creating an analog input temperature channel, you can specify the type of transducer
(for example, thermistor, RTD, or thermocouple) used to make the measurement when
creating the channel. However, if NI-DAQmx does not explicitly support your
transducer or actuator, you can create a scale that specifies how to convert from the
prescaled units to the scaled units. You can associate the same scale with multiple
channels. You do not need to create a scale for each channel if the scale is the same.
After a scale is assigned to a channel, the scale applies to all attributes normally
expressed in the prescaled units of the channel. For example, if a custom scale, which
converts volts to meters, is assigned to a voltage channel, the channels minimum and
maximum attributes are expressed in meters.
Prescaled refers to values expressed in the unit of the channel prior to the custom
scale being applied. Usually, these prescaled units are volts or amps since scales are
most often associated with channels that natively measure or generate signals using
these units. However, it is possible to associate a scale with a channel that contains a
transducer explicitly supported by NI-DAQmx. In this case, the prescaled units are the
units of the channel including the explicitly supported transducer. For example, you
can create a analog input resistance channel and associate a scale with this channel. In
this example, the prescaled units would be ohms and the scale would specify how to
convert from ohms to the desired scaled units.
Scaled refers to values expressed in the final unit after NI-DAQmx applies the custom
scale. For example, a linear-position-to-voltage scale is assigned to a voltage output
channel. In this case, the prescaled samples are in volts while the scaled samples
could be specified in meters. Scaled units are the units that are most convenient for
your application. You have complete control over the scaled units when specifying
your scale. The scale specifies the conversion from the prescaled units of the signal
measured or generated by the channel to your specified scaled units. When you read
samples from a channel associated with a scale, the samples are in scaled units.
Likewise, when you write samples to a channel associated with a scale, the samples
are in scaled units.
You can create scales in the DAQ Assistant or programmatically. When you
programmatically associate a scale with a channel, you must set the custom scale
name attribute/property to the name of the scale and set the units attribute/property
to From Custom Scale.
Note Unscaled data is not synonymous with prescaled units. Unscaled data
refers to an 8-, 16-, or 32-bit integer in the native format of the device.
Prescaled refers to the units of measurement, such as volts or amps, before a
custom scale is applied.
Related concepts:
• Unscaled Data
264 ni.com
NI-DAQmx Key Concepts
from the scaled value to the prescaled values is ambiguous. The conversion is well
defined and predictable even in these cases. While not disallowed, non-monotonically
increasing scales should be avoided or used with caution.
NI DAQmx
NI-DAQmx has the following advantages over Traditional NI-DAQ (Legacy):
• You are using an OS supported by NI-DAQmx; refer to the NI-DAQmx Readme for a
list of supported OSes.
If you are using NI application software with NI-DAQmx, you must use supported
versions of LabVIEW, LabWindows/CVI, Measurement Studio, NI SignalExpress, or the
LabVIEW Real-Time Module. Refer to the NI-DAQmx Readme for specific versions of NI
application software supported in your version of NI-DAQmx.
If you use one of the Microsoft .NET languages, Visual C# and/or Visual Basic .NET, or a
device supported only by NI-DAQmx, such as an M Series device, you must use NI-
DAQmx.
You also can use NI-DAQmx with a supported compiler, such as an ANSI C compiler.
• You have a device that is not supported by NI-DAQmx, such as the AT E Series
multifunction DAQ devices.
• You are using an unsupported version of LabVIEW, LabWindows/CVI, or
Measurement Studio.
• You are upgrading from NI-DAQ 6.9.x and have existing applications that you do
not want to port to NI-DAQmx now.
266 ni.com
NI-DAQmx Device Considerations
FieldDAQ
• FD-11601
• FD-11603
• FD-11605
• FD-11613
• FD-11614
• FD-11634
• FD-11637
• sbRIO-9603
• sbRIO-9608
• sbRIO-9609
• sbRIO-9628
• sbRIO-9629
• sbRIO-9638
CompactRIO Controllers
• cRIO-9040
• cRIO-9041
• cRIO-9042
• cRIO-9043
• cRIO-9045
• cRIO-9046
• cRIO-9047
• cRIO-9048
• cRIO-9049
• cRIO-9053
• cRIO-9054
• cRIO-9055
• cRIO-9056
• cRIO-9057
• cRIO-9058
• NI 6320
• NI 6321
• NI 6323
• NI 6341
• NI 6343
• NI 6345
• NI 6346
• NI 6349
• NI 6351
• NI 6353
• NI 6355
• NI 6356
• NI 6358
• NI 6361
• NI 6363
• NI 6365
• NI 6366
• NI 6368
• NI 6374
• NI 6375
• NI 6376
• NI 6378
268 ni.com
NI-DAQmx Device Considerations
• NI 6386
• NI 6396
• NI 6210/11/12/15/16/18
• NI 6220
• NI 6221
• NI 6224
• NI 6225
• NI 6229
• NI 6230/32/33/36/38/39
• NI 6250
• NI 6251
• NI 6254
• NI 6255
• NI 6259
• NI 6280
• NI 6281
• NI 6284
• NI 6289
S Series DAQ
• NI 6110
• NI 6111
• NI 6115
• NI 6120
• NI 6122
• NI 6123
• NI 6124
• NI 6132
• NI 6133
• NI 6143
• NI 6154
SC Express
• NI 4300
• NI 4302
• NI 4303
• NI 4304
• NI 4305
• NI 4309
• NI 4310
• NI 4322
• NI 4330
• NI 4331
• NI 4339
• NI 4340
• NI 4353
• NI 4357
• NI 9201
• NI 9202
• NI 9203
• NI 9204
• NI 9205
• NI 9206
• NI 9207
• NI 9208
• NI 9209
• NI 9210
• NI 9211
• NI 9212
• NI 9213
• NI 9214
• NI 9215
• NI 9216
• NI 9217
• NI 9218
270 ni.com
NI-DAQmx Device Considerations
• NI 9219
• NI 9220
• NI 9221
• NI 9222
• NI 9223
• NI 9224
• NI 9225
• NI 9226
• NI 9227
• NI 9228
• NI 9229
• NI 9230
• NI 9231
• NI 9232
• NI 9234
• NI 9235
• NI 9236
• NI 9237
• NI 9237 (DSUB)
• NI 9238
• NI 9239
• NI 9242
• NI 9244
• NI 9246
• NI 9247
• NI 9250
• NI 9251
• NI 9252
• NI 9253
• NI 9260
• NI 9262
• NI 9263
• NI 9264
• NI 9265
• NI 9266
• NI 9269
• NI 9326
• NI 9344
• NI 9361
• NI 9375
• NI 9401
• NI 9402
• NI 9403
• NI 9411
• NI 9421
• NI 9422
• NI 9423
• NI 9425
• NI 9426
• NI 9435
• NI 9436
• NI 9437
• NI 9469
• NI 9472
• NI 9474
• NI 9475
• NI 9476
• NI 9477
• NI 9478
• NI 9481
• NI 9482
• NI 9485
• NI 9775
CompactDAQ Chassis
• NI cDAQ-9171
• NI cDAQ-9174
• NI cDAQ-9178
• NI cDAQ-9179
• NI cDAQ-9181
• NI cDAQ-9184
• NI cDAQ-9185
• NI cDAQ-9188
272 ni.com
NI-DAQmx Device Considerations
• NI cDAQ-9189
• NI cDAQ-9188XT
• NI cDAQ-9191
CompactDAQ Controllers
• NI cDAQ-9132
• NI cDAQ-9133
• NI cDAQ-9134
• NI cDAQ-9135
• NI cDAQ-9136
• NI cDAQ-9137
AO Series
• NI 6703
• NI 6704
• NI 6711
• NI 6713
• NI 6722
• NI 6723
• NI 6731
• NI 6733
• NI 6738
• NI 6739
Digital I/O
• NI 6501
• NI 6503
• NI 6508
• NI 6509
• NI 6510
• NI 6511
• NI 6512
• NI 6513
• NI 6514
• NI 6515
• NI 6516
• NI 6517
• NI 6518
• NI 6519
• NI 6520
• NI 6521
• NI 6525
• NI 6527
• NI 6528
• NI 6529
• NI 6533
• NI 6534
• NI 6535
• NI 6535B
• NI 6536
• NI 6536B
• NI 6537
• NI 6537B
• NI DIO-32HS
• NI DIO-96
TIO Series
• NI 6601
• NI 6602
• NI 6608
• NI 6612
• NI 6614
• NI 6624
• NI 4431
• NI 4432
• NI 4461
• NI 4462
• NI 4463
274 ni.com
NI-DAQmx Device Considerations
• NI 4464
• NI 4466
• NI 4472/B
• NI 4474
• NI 4480
• NI 4481
• NI 4492
• NI 4495
• NI 4496
• NI 4497
• NI 4498
• NI 4499
• NI 4610
Academic Devices
• NI ELVIS II
• NI ELVIS II+
• NI myDAQ
Low-Cost USB
• NI 6000
• NI 6001
• NI 6002
• NI 6003
• NI 6008
• NI 6009
• NI TC01
Analog Triggering
This section contains information about analog triggering for C Series, NI ELVIS II
Family, DSA, E Series, M Series, S Series, and SC Express devices.
Note Not all E Series, M Series, S Series, and C Series devices support analog
triggering. Refer to the specifications for your device to determine if your
device supports analog triggering.
Certain C Series, E Series, M Series, S Series devices and TestScale modules contain a
single analog trigger circuit that you can configure for analog triggering. The analog
trigger circuitry is a shared resource for the device, and any of the subsystems can use
it. This trigger circuitry supports level and slope triggering with hysteresis as well as
analog window triggering. After it is configured, the output of this circuitry appears as
the Analog Comparison Event, which can be the source for various triggers and clocks
within the analog input, analog output, and counter subsystems.
Even though the analog trigger is a shared resource, only one analog input or analog
output task at a time can configure and reserve it. If you want to share the analog
trigger among multiple tasks, configure and reserve it in one task, and use the trigger
in subsequent tasks by referring to the source of your trigger, clock, or signal of
interest as the Analog Comparison Event. For tasks that support multiple types of
analog triggers within the same task, all triggers must share the same configuration
settings, or you receive an error. For instance, if you want to use an analog trigger for
both your Start and Reference Trigger within an analog input task, the configuration
settings for the start and Reference Trigger must be identical.
• PFI 0
276 ni.com
NI-DAQmx Device Considerations
Typically, when configuring an analog trigger, you connect your analog signal to
the PFI 0 terminal. Because PFI 0 is the trigger source for both analog and digital
signals, NI-DAQmx automatically tristates this terminal when a task exporting a
signal on the terminal is not in the committed or running state. This behavior when
exporting a signal on PFI 0 differs from typical task-based routing with other PFI
lines. It prevents accidental connections of an analog signal directly to digital
circuitry, which could permanently damage the device. Also, notice that when
connecting an analog signal to PFI 0, the terminal configuration is referenced
single-ended.
Even when PFI 0 is not the source of your analog trigger, you cannot use PFI 0 for
other digital signal routes because the analog trigger takes over the PFI 0 terminal
internal to the device when it is enabled. If you try to use the analog trigger and PFI
0 for digital signals at the same time, you receive a routing error.
In addition to PFI 0, analog input tasks can trigger off of one of the analog input
channels being sampled. Because E Series devices use a scanning architecture,
many restrictions are placed on how you can use an analog trigger when the
source is one of the channels you are sampling. When you use an analog Start
Trigger, the trigger channel must be the first channel in the channel list. When you
use an Analog Reference or Pause Trigger, and the analog channel is the source of
the trigger, there can be only one channel in the channel list. If you have more than
one channel for Pause or Reference Triggers, you must use PFI 0. Since S Series
devices do not use a scanning architecture, none of these restrictions apply.
Therefore, for an S Series device, you can use any analog input channel as the
source of the trigger regardless of how many channels are being sampled or the
order of the trigger channel in the sequence.
Scaling, including custom scales, is not applied if PFI 0 is the trigger source. For
instance, you would specify the DAQmx Trigger Analog Edge Level
When configuring an analog trigger, connect your analog signal to either the APFI 0
or APFI 1 terminal and specify APFI 0 or APFI 1 as your trigger source.
In addition to APFI 0 and APFI 1, analog input tasks can trigger off of one of the
analog input channels being sampled. Because M Series devices use a scanning
architecture, many restrictions are placed on how you can use an analog trigger
when the source is one of the channels you are sampling. When you use an Analog
Start Trigger, the trigger channel must be the first channel in the channel list. When
you use an Analog Reference or Pause Trigger, and the analog channel is the source
of the trigger, there can be only one channel in the channel list. If you have more
than one channel for Pause or Reference Triggers, you must use APFI 0 or APFI 1.
Scaling, including custom scales, is not applied if APFI 0 or APFI 1 is the trigger
source. For instance, you would specify the DAQmx Trigger Analog Edge Level
attribute/property in volts. However, if you use an analog input channel as the
trigger source, you could use scaled units.
The trigger DACs in the analog trigger circuitry on an E Series, M Series, C Series, or S
Series device typically contain four less bits of accuracy than the ADC of the device. No
hardware calibration is provided for the analog trigger circuitry. In addition, the
propagation delay from when a valid trigger condition is met to when the analog
trigger circuitry emits the Analog Comparison Event may have an impact on your
measurements if the trigger signal has a high slew rate. If you find these conditions
have a noticeable impact on your measurements, you can perform software calibration
278 ni.com
NI-DAQmx Device Considerations
on the analog trigger circuitry by configuring your task as normal and applying a
known signal for your analog trigger. Comparing the observed results against the
expected results, you can calculate the necessary offsets to apply in software to fine
tune the desired triggering behavior.
C Series and TestScale Module Valid Sources for the Analog Trigger
The NI 9204, NI 9205, and TS-15100 have no APFI 0 or APFI 1 terminal. Analog input
tasks using the NI 9204, NI 9205, or TS-15100 can trigger off one of the analog input
channels being sampled. When you use an Analog Start Trigger, the trigger channel
must be the first channel from the NI 9204, NI 9205, or TS-15100 in the channel list, but
channels from other C Series devices can come first. When you use an Analog
Reference or Pause Trigger, you can use only one channel from the NI 9204, NI 9205, or
TS-15100 in the channel list, but you can use channels from other C Series devices. You
can combine Analog Start, Reference, and Pause Triggers with different configuration
settings by using multiple NI 9204 or NI 9205 devices. All analog triggers on the same
device must share the same configuration settings.
The NI 9775 can only use an analog trigger that is an active channel. See NI 9775
Considerations for further restrictions on analog trigger usage. When you use a
trigger with the NI 9775 in Analog Multi Edge, all of the trigger channels must come
from the same device. When using multiple NI 9775 modules, those modules can be in
the same task as long as the trigger source comes from one of the NI 9775 modules.
Related concepts:
• NI 9775 Considerations
The frequency of the trigger signal is also limited by lowpass filtering on the device's
analog front end. On the NI 4300 and NI 4310, the lowpass filter can be controlled
using the AI.Lowpass.Enable and AI.Lowpass.CutoffFreq channel attributes/properties.
On the NI 433x devices, the lowpass filter cutoff frequency is determined by the
sampling rate. The analog trigger source can be set to any one of the channels on the
device.
Analog triggering on SC Express devices supports only Reference Triggers, not Start
and Pause Triggers. Digital triggering on SC Express devices does not have this
restriction.
Note Analog triggers are not supported on the NI 4309, NI 4322, NI 4353, or
NI 4357.
280 ni.com
NI-DAQmx Device Considerations
using external standards, then you adjust the device calibration constants. The new
calibration constants are stored in the EEPROM. These calibration constants are loaded
from memory as needed to adjust for the error in the measurements taken by the
device.
AO Series Calibration
Your device uses software calibration to fine-tune the analog output circuitry. The
software must be programmed (or loaded) with certain numbers called calibration
constants. Those constants are stored in nonvolatile memory (EEPROM) on your device
or are maintained by NI-DAQmx. To achieve specification accuracy, you should self-
calibrate your device just before a measurement session but after your computer and
the device have been powered on and warmed up for at least 15 minutes. You should
allow this same warm-up time before performing any calibration of your system.
Frequent calibration produces the most stable and repeatable measurement
performance. The device is not harmed in any way if you recalibrate it often.
Note
NI-DAQmx automatically loads calibration constants into the software whenever you
call functions/VIs that depend on them.
Related concepts:
Related information:
• Calibration Procedures
C Series Calibration
Your device uses software calibration to adjust the software scaling of signals read
from and produced by your device. Using a precise reference signal, your device
measures and calculates scaling constants for analog input and analog output. The
scaling constants are stored in nonvolatile memory (EEPROM) on your device. NI
recommends that you calibrate your device just before a measurement session but
after your module has been powered on and warmed up for at least 15 minutes. You
should allow this same warm-up time before performing any calibration of your
system. Frequent calibration produces the most stable and repeatable measurement
performance. The device is not harmed in any way if you recalibrate it often.
Note
Related information:
• Calibration Procedures
282 ni.com
NI-DAQmx Device Considerations
• NI DAQPad-6015
• NI DAQPad-6016
• NI PCI-6010
• NI PCI-6013
• NI PCI-6014
• NI USB-6000
• NI USB-6001
• NI USB-6002
• NI USB-6003
• NI USB-6008
• NI USB-6009
• SensorDAQ
DSA Calibration
Your device contains digital correction circuitry to compensate for gain and offset
errors in the analog and ADC circuitry. The gain and offset calibration constants are
stored in nonvolatile memory (EEPROM) on your device. NI-DAQmx writes these
calibration constants to the digital correction circuitry.
To achieve the maximum accuracy, you should perform external calibration at least
once per year (the recommended external calibration interval) and perform self-
calibration prior to measurement sessions or otherwise, as desired. You should
calibrate your device only after your computer and the device have been powered on
and warmed up for at least 15 minutes.
Self-Calibration
Self-calibration is executed with the Self Calibrate VI/function. When you self-calibrate
a DSA device, you do not need signal connections. However, for devices with analog
output channels, values generated on those output channels can change during the
calibration process. If you have external equipment connected to the AO channels and
changing the AO voltage could damage the external equipment, you should
External Calibration
E Series Calibration
Your device uses hardware calibration to adjust the analog circuitry. This calibration is
done with calibration digital-to-analog converters, called calDACs, that fine-tune the
analog circuitry. The calDACs must be programmed (or loaded) with certain numbers
called calibration constants. Those constants are stored in nonvolatile memory
(EEPROM) on your device or are maintained by NI-DAQmx. NI recommends that you
self-calibrate your device just before a measurement session but after your computer
and the device have been powered on and warmed up for at least 15 minutes. You
should allow this same warm-up time before performing any calibration of your
system. Frequent calibration produces the most stable and repeatable measurement
performance. The device is not harmed in any way if you recalibrate it often.
Note
284 ni.com
NI-DAQmx Device Considerations
NI-DAQmx automatically loads calibration constants into calDACs whenever you call
functions/VIs that depend on them. The following conditions apply:
Related concepts:
FieldDAQ Calibration
FieldDAQ devices use software calibration to adjust the software scaling of signals read
from and produced by your device. Using a precise reference signal, your device
measures and calculates scaling constants for analog input. The scaling constants are
stored in nonvolatile memory (EEPROM) on your device. Frequent calibration produces
the most stable and repeatable measurement performance. The device is not harmed
in any way if you recalibrate it often.
Note
Related information:
• Calibration Procedures
286 ni.com
NI-DAQmx Device Considerations
constants for analog input and analog output. The scaling constants are stored in
nonvolatile memory (EEPROM) on your device. NI recommends that you self-calibrate
your device just before a measurement session but after your computer and the device
have been powered on and warmed up for at least 15 minutes. You should allow this
same warm-up time before performing any calibration of your system. Frequent
calibration produces the most stable and repeatable measurement performance. The
device is not harmed in any way if you recalibrate it often.
Note
• Calibrating your device takes some time. Do not be alarmed if the Self-
Calibrate or Adjust M Series Calibration function/VI takes several
seconds to execute.
• For best results, stop any ongoing tasks and disconnect any
unnecessary external connections before running calibration.
NI 6154 Calibration
Your device uses software calibration to adjust the software scaling of signals read
from and produced by your device. Using calibration pulse-width modulated (PWM)
sources with a reference voltage, your device measures and calculates scaling
constants for analog input and analog output. The scaling constants are stored in
nonvolatile memory (EEPROM) on your device. NI recommends that you self-calibrate
your device just before a measurement session but after your computer and the device
have been powered on and warmed up for at least 15 minutes. You should allow this
same warm-up time before performing any calibration of your system. Frequent
calibration produces the most stable and repeatable measurement performance. The
device is not harmed in any way if you recalibrate it often.
Note
• Calibrating your device takes some time. Do not be alarmed if the Self-
Calibrate or Adjust S Series Calibration function/VI takes several
seconds to execute.
• For best results, stop any ongoing tasks and disconnect any
unnecessary external connections before running calibration.
NI 6614 Calibration
Only external calibration, not self-calibration, is supported for NI 6614 devices. You
should allow 15 minutes of warm-up time before performing any calibration of your
system. Frequent calibration produces the most stable and repeatable measurement
performance. The device is not harmed in any way if you recalibrate it often.
Note
NI PXI-6608 Calibration
You cannot calibrate the PXI-6608 in NI-DAQmx. The device must be calibrated using
the Traditional NI-DAQ (Legacy) driver. To use the NI PXI-6608 in NI-DAQmx after
calibrating it in Traditional NI-DAQ (Legacy), you must do one of the following:
—or—
• Right-click the Traditional NI-DAQ (Legacy) Devices folder in MAX and select Reset
Driver for Traditional NI-DAQ.
288 ni.com
NI-DAQmx Device Considerations
S Series Calibration
Your device uses hardware calibration to adjust the analog circuitry. This calibration is
done with calibration digital-to-analog converters, called calDACs, that fine-tune the
analog circuitry. The calDACs must be programmed (or loaded) with certain numbers
called calibration constants. Those constants are stored in nonvolatile memory
(EEPROM) on your device or are maintained by NI-DAQmx. NI recommends that you
self-calibrate your device just before a measurement session but after your computer
and the device have been powered on and warmed up for at least 15 minutes. You
should allow this same warm-up time before performing any calibration of your
system. Frequent calibration produces the most stable and repeatable measurement
performance. The device is not harmed in any way if you recalibrate it often.
Note
Related concepts:
SC Express Calibration
The NI 4300, NI 4309, NI 4310, and NI 4340 use software calibration to adjust the
software scaling of signals read from and produced by your device. Using onboard
calibration pulse-width modulated (PWM) sources and an external reference voltage,
your device calculates scaling constants for analog input. The scaling constants are
stored in nonvolatile memory (EEPROM) on your device. NI recommends that you self-
calibrate your device just before a measurement session but after your computer and
the device have been powered on and warmed up for at least 15 minutes. You should
allow this same warm-up time before performing any calibration of your system.
Frequent calibration produces the most stable and repeatable measurement
performance. The device is not harmed in any way if you recalibrate it often.
Note
• Calibrating your device takes some time. Do not be alarmed if the Self-
Calibrate or Adjust 4300 Calibration function/VI takes several minutes
to execute.
• For best results, stop any ongoing tasks and disconnect any
unnecessary external connections before running calibration.
Related information:
• Calibration Procedures
SCXI-1600 Calibration
The external calibration process for the SCXI-1600 module is nearly identical to the E
Series devices. However, when applying a precision voltage to the module, you must
connect the signal to the EXTCAL BNC connector on the front of the SCXI-1600, instead
of the AI0 analog input channel. In LabVIEW, use the Adjust E-Series Calibration VI,
instead of the Adjust SC Baseboard Calibration VI.
X Series Calibration
Your device uses software calibration to adjust the software scaling of signals read
from and produced by your device. Using calibration pulse width modulated (PWM)
sources with a reference voltage, your device measures and calculates scaling
constants for analog input and analog output. The scaling constants are stored in
nonvolatile memory (EEPROM) on your device. NI recommends that you self-calibrate
your device just before a measurement session but after your computer and the device
have been powered on and warmed up for at least 15 minutes. You should allow this
290 ni.com
NI-DAQmx Device Considerations
same warm-up time before performing any calibration of your system. Frequent
calibration produces the most stable and repeatable measurement performance. The
device is not harmed in any way if you recalibrate it often.
Note
• Calibrating your device takes some time. Do not be alarmed if the Self-
Calibrate or Adjust X Series Calibration function/VI takes several
seconds to execute.
• For best results, stop any ongoing tasks and disconnect any
unnecessary external connections before running calibration.
Signal Connections
This section contains information about calibration signal connections for AO Series, E
Series, M Series, NI 6010, NI 6154, S Series, and X Series devices.
Related concepts:
When you self-calibrate your AO Series device, no signal connections are necessary.
However, values generated on the analog output channels change during the
calibration process.
When externally calibrating your AO Series device, connect the signals as described
below for the type of AO Series device you are calibrating. Set the reference voltage
between +6.000 V and +9.999 V. Typically, you use a calibrator or other stable voltage
source for the reference voltage. Do not use a power supply as its signals are not very
stable.
1. Connect the positive output of your reference voltage source to the EXT REF
terminal.
2. Connect the negative output of your reference voltage source to the AO GND
terminal.
Related information:
• Calibration Procedures
When you self-calibrate your E Series device, no signal connections are necessary.
However, values generated on the analog output channels change during the
calibration process. If you have external circuitry connected to the analog output
channels and you do not want changes on these channels, you should disconnect the
circuitry before beginning the self-calibration.
When externally calibrating your E Series device, connect the signals as described
below for the type of E Series device you are calibrating. Set the reference voltage
between +6.000 V and +9.999 V. Typically, you use a calibrator or other stable voltage
source for the reference voltage. Do not use a power supply as its signals are not very
stable.
292 ni.com
NI-DAQmx Device Considerations
each other, connect the AI SENSE terminal to the AI GND terminal as well as to
the negative output of your reference voltage source.
When you self-calibrate your S Series device, no signal connections are necessary.
However, values generated on the analog output channels change during the
calibration process. If you have external circuitry connected to the analog output
channels that is sensitive to these changes, you should disconnect the circuitry before
beginning self-calibration.
When externally calibrating your S Series device, connect the signals as described
below. Set the reference voltage to the following:
Typically, you should use a calibrator or other stable voltage source for calibration. Do
not use a power supply as its signals are not very stable.
When you self-calibrate your M Series or NI 6010 device, no signal connections are
necessary. However, values generated on the analog output channels change during
the calibration process. If you have external circuitry connected to the analog output
channels and you do not want changes on these channels, you should disconnect the
circuitry before beginning the self-calibration.
When externally calibrating your M Series or NI 6010 device, connect the signals as
described below for the type of device you are calibrating. Set the reference voltage
between +6.0 V and +8.5 V for M Series devices, between +3.5 V and 4.0 V for NI 6010
devices. Typically, you use a calibrator or other stable voltage source for the reference
voltage. Do not use a power supply as its signals are not very stable.
When you self-calibrate your NI 6154 device, no signal connections are necessary.
However, values generated on the analog output channels change during the
calibration process.
When externally calibrating your NI 6154 device, connect the signals as described
below for the type of device you are calibrating. Set the reference voltage between +6.0
V and +9.998 V. Typically, you use a calibrator or other stable voltage source for the
reference voltage. Do not use a power supply as its signals are not very stable.
294 ni.com
NI-DAQmx Device Considerations
For signal connections needed to externally calibrate your NI 6614, refer to the
calibration procedure for the NI 6614.
When you self-calibrate your X Series device, no signal connections are necessary.
However, values generated on the analog output channels change during the
calibration process. If you have external circuitry connected to the analog output
channels and you do not want changes on these channels, you should disconnect the
circuitry before beginning the self-calibration.
When externally calibrating (or adjusting) your X Series device, connect the signals as
described below for the type of device you are calibrating. Set the reference voltage
between +6.0 V and +8.5 V for X Series devices. You should use a calibrator or other
stable voltage source for the reference voltage. Do not use a power supply as its signals
are not very stable.
Counters
This section contains information on counter signal connections and routing diagrams
that illustrate the internal counter routing.
Averaging Support
The following devices support averaging digital frequency and period measurements:
Related concepts:
• Duty cycle
• Event counting
• Encoder position
• Frequency
• Period
• Pulse width
1. cDAQ-9171, 9174, 9178, 9179, 9181, 9184, 9185, 9188, 9188XT, 9189, and 9191
2. TS-15000 and TS-15010
3. cDAQ-9132, 9133, 9134, 9135, 9136, and 9137
4. cRIO-9040, 9041, 9042, 9043, 9045, 9046, 9047, 9048, 9049, 9053, 9054, 9055, 9056, 9057, and 9058
5. sbRIO-9603, 9608, 9609, 9628, 9629, and 9638
296 ni.com
NI-DAQmx Device Considerations
• Velocity
The NI 9361 has eight counters and supports adding multiple counter channels to the
same task. A single task can have different measurement types. Multiple counter
module channels can be added to the same task.
Note
• You cannot mix module and chassis counters in the same task.
• You cannot use the chassis counter through the counter module.
• You cannot create multiple counter tasks with a single NI 9361.
• You cannot have more than two NI 9361 with different timing/triggering
configuration in a single chassis.
Related reference:
The following table lists the default input terminals for various counter measurements
on bus-powered M Series devices. You can use a different PFI line for any of the input
terminals. To change the PFI input for a measurement, use the NI-DAQmx channel
attributes/properties.
• A: PFI 0 • A: PFI 3
Position Measurement • B: PFI • B: PFI 10
• Z: PFI 1 • Z: PFI 2
The following table lists the output terminals for counter output. You can use a
different PFI line for any of the output terminals.
Ctr0 Ctr1
PFI 4 PFI 5
298 ni.com
NI-DAQmx Device Considerations
• A: PFI 8 • A: PFI 3
Position Measurement • B: PFI 10 • B: PFI 11
• Z: PFI 9 • Z: PFI 4
The following table lists the output terminals for counter output. You can use a
different PFI line for any of the output terminals.
Ctr0 Ctr1
PFI 12 PFI 13
• A: PFI 0 • A: PFI 3
Position Measurement • B: PFI 1 • B: PFI 2
• Z: PFI 2 • Z: PFI 1
The following table lists the output terminals for counter output. You can use a
different PFI line for any of the output terminals.
Ctr0 Ctr1
PFI 4 PFI 5
Related concepts:
300 ni.com
NI-DAQmx Device Considerations
The following tables lists the default input terminals for various counter
measurements. You can use a different PFI line for any of the input terminals. To
change the PFI input for a measurement, use the NI-DAQmx channel attributes/
properties.
302 ni.com
NI-DAQmx Device Considerations
NI 9411 (6-Channel)
The following tables list the output terminals for counter output. You can use a
different PFI line for any of the output terminals.
NI 9361 (8-Counters)
Duty Cycle
PFI 0 PFI 1 PFI 2 PFI 3 PFI 4 PFI 5
Measurement
Pulse Width
PFI 0 PFI 1 PFI 2 PFI 3 PFI 4 PFI 5
Measurement
Period/
Frequency
Measurement PFI 0 PFI 1 PFI 2 PFI 3 PFI 4 PFI 5
(Dynamic
Averaging)
304 ni.com
NI-DAQmx Device Considerations
Related concepts:
The following table lists the default input terminals for various counter measurements.
You can use a different PFI line for any of the input terminals, with the exception of the
count direction terminal for edge counting. To change the PFI input for a
measurement, use the NI-DAQmx channel attributes/properties.
The following table lists the default output terminals for counter output. You must use
the default output terminal, with the exception that for Ctr0, you can select a RTSI line.
6. The count direction terminal must be tristated to use an external signal. Reset the device to ensure
the terminal is tristated
Ctr0 Ctr1
CTR 0 OUT CTR 1 OUT
The following table lists the default input terminals for various counter measurements
on myDAQ. You can use a different PFI line for any of the input terminals. To change
the PFI input for a measurement, use the NI-DAQmx channel attributes/properties.
Measurement Ctr0
• Edges: PFI 0
Count Edges
• Count Direction: PFI 2
• Start: PFI 2
Two-Edge Separation Measurement
• Stop: PFI 1
• A: PFI 0
Position Measurement • B: PFI 2
• Z: PFI 1
The following table lists the output terminals for counter output. You can use a
different PFI line for the output terminal.
Ctr0
PFI 3
306 ni.com
NI-DAQmx Device Considerations
The following table lists the default input terminals for various counter measurements.
You can use a different PFI line for any of the input terminals. To change the PFI input
for a measurement, use the NI-DAQmx channel attributes/properties.
• A: PFI 8 • A: PFI 3
Position Measurement • B: PFI 10 • B: PFI 11
• Z: PFI 9 • Z: PFI 4
The following table lists the output terminals for counter output. You can use a
different PFI line for any of the output terminals.
Ctr0 Ctr1
PFI 12 PFI 13
The following table lists the default input terminals for various counter measurements
on mioDAQ devices. You can use a different PFI line for any of the input terminals. To
change the PFI input for a measurement, use the NI-DAQmx channel attributes/
properties.
308 ni.com
NI-DAQmx Device Considerations
The following table lists the output terminals for counter output. You can use a
different PFI line for any of the output terminals.
The following table lists the default input terminals for various counter measurements.
You can use a different PFI line for any of the input terminals. To change the PFI input
for a measurement, use the NI-DAQmx channel properties/attributes.
Note You cannot change the default PFI lines for quadrature encoder-based
position measurements on NI 660x devices.
Pulse Width
PFI 38 PFI 34 PFI 30 PFI 26 PFI 22 PFI 18 PFI 14
Measurement
Period/
Frequency
Measurement
(Low PFI 38 PFI 34 PFI 30 PFI 26 PFI 22 PFI 18 PFI 14
Frequency
with One
Counter)
Period/
Frequency
Measurement
PFI 39 PFI 35 PFI 31 PFI 27 PFI 23 PFI 19 PFI 15
(High
Frequency
with Two
• Start: PFI • Start: PFI • Start: PFI • Start: PFI • Start: PFI • Start: PFI • Start: P
Two-Edge
37 33 29 25 21 17 13
Separation
• Stop: PFI • Stop: PFI • Stop: PFI • Stop: PFI • Stop: PFI • Stop: PFI • Stop: P
Measurement
38 34 30 26 22 18 14
GPS
Timestamp N/A N/A N/A N/A N/A N/A N/A
Measurement
Note The NI 6601 has only four counters (ctr0-ctr3). The entries in the
previous table for cntr4, cntr5, cntr6, and cntr7 do not apply for that device.
The following table lists the output terminals for counter output. You can use a
different PFI line for any of the output terminals.
Note The NI 6601 has only four counters (ctr0-ctr3). The entries in the
310 ni.com
NI-DAQmx Device Considerations
previous table for cntr4, cntr5, cntr6, and cntr7 do not apply for that device.
NI 6624 Issues
The eight PFI lines listed as the defaults for counter output are dedicated for output,
and they are the only terminals you can use for counter output. For example, you can
use PFI 8 (the default for Ctr7) as the output terminal for any counter, but you cannot
use it as an input terminal.
When using counter output, if the Idle State attribute/property is low, the optocouplers
on the NI 6624 will still be driving your output load. Set the Idle State attribute/
property to high to prevent driving the output after your task completes.
The following table lists the default input terminals for various counter measurements
on X Series devices. You can use a different PFI line for any of the input terminals. To
change the PFI input for a measurement, use the NI-DAQmx channel attributes/
properties.
The following table lists the output terminals for counter output. You can use a
different PFI line for any of the output terminals.
The following table lists the default input terminals for various counter measurements
for devices that use the 37-Pin DSUB connector such as the NI 6010, NI 6154, and NI
623x. You can use a different PFI line for any of the input terminals. To change the PFI
input for a measurement, use the NI-DAQmx channel attributes/properties.
312 ni.com
NI-DAQmx Device Considerations
The following table lists the output terminals for counter output. You can use a
different PFI line for any of the output terminals.
Ctr0 Ctr1
PFI 6 PFI 7
The following table lists the default input terminals for various counter measurements
on M Series devices, including M Series USB devices, such as the NI USB 6259 screw
terminal and NI USB-6229 BNC devices. You can use a different PFI line for any of the
input terminals. To change the PFI input for a measurement, use the NI-DAQmx
channel attributes/properties.
• A: PFI 8 • A: PFI 3
Position Measurement • B: PFI 10 • B: PFI 11
• Z: PFI 9 • Z: PFI 4
The following table lists the output terminals for counter output. You can use a
different PFI line for any of the output terminals.
Ctr0 Ctr1
PFI 12 PFI 13
Some M Series devices, including the NI 6010, NI 6154, NI 6221 (37-pin), and NI 623x,
use the 37-pin DSUB connector. These devices have different counter terminal
defaults. Refer to the 37-Pin DSUB Signal Connections for Counters for the
default input terminals on these devices. Bus-powered M Series devices, such as the NI
USB-621x devices, also have different counter terminal defaults. Refer to the Bus-
Powered M Series Signal Connections for Counters for the default input
terminals on these devices.
Related reference:
314 ni.com
NI-DAQmx Device Considerations
Related concepts:
The following figure shows the internal routing for DAQ devices with the STC counter/
timer such as E Series devices. The black circles represent terminals.
PFI, RTSI
20 MHz, 100 kHz Ctr 0
Timebase Pulsed Ctr0OutputPulse Ctr0InternalOutput
Ctr0Source
Output
Ctr0Out
PFI, RTSI Toggled
Ctr0Gate
ai/Reference Trigger Output
ai/Start Trigger
Ctr 1
PFI, RTSI
Pulsed
20 MHz, 100 kHz Ctr1Source
Output
Timebase Ctr1OutputPulse
Ctr1Out
Toggled
Ctr1Gate Ctr1InternalOutput
Output
PFI, RTSI
ai/Reference Trigger
ai/Start Trigger
The following figure shows the internal routing for DAQ devices with the STC III
counter/timer such as X Series devices. The black circles represent terminals.
Ctr1Aux
PFI 0-15, RTSI 0-7, PairedCtrOutputPulse,
ctr1/Gate, aiReference Trigger, PairedCtrGate,
Star_Trigger, ai/StartTrigger, di/ChangeDetectEvent,
Analog_Trigger, PairedCtrSource
Ctr3Aux
PFI 0-15, RTSI 0-7, PairedCtrOutputPulse,
ctr3/Gate, aiReference Trigger, PairedCtrGate,
Star_Trigger, ai/StartTrigger, di/ChangeDetectEvent,
Analog_Trigger, PairedCtrSource
316 ni.com
NI-DAQmx Device Considerations
The following figure shows the internal routing for C Series devices used with a NI
cDAQ-91xx7 or TestScale modules connected to a TestScale chassis8. The figure shows
direct routes available. Indirect routes are available as well, but use extra internal
resources. The black circles represent terminals.
7. cDAQ-9132, 9133, 9134, 9135, 9136, 9137, 9171, 9174, 9178, 9179, 9181, 9184, 9185, 9188, 9188XT,
9189, and 9191
8. TS-15000 and TS-15010
Ctr0Source
Pulsed
Output
Ctr0OutputPulse
ai/di/Start Trigger, PFIs,
di/ChangeDetectEvent, AnalogComparisonEvent, SampleClk
te0/te1/ai/ao/di/do/SampleClk, ai/Reference Trigger
di/ChangeDetectEvent, PFIs,
di/ai/ReferenceTrigger, ai/ao/di/do/StartTrigger,
Ctr0Gate
PairedCtrOutputPulse, PairedCtrSource,
AnalogComparisonEvent, te0/te1//SampleClk
Toggled Ctr0InternalOutput
Ctr0Aux Output
ctr0/Gate, ai/ReferenceTrigger, PFIs,
PairedCtrOutputPulse, te0/te1//SampleClock,
PairedCtrGate, ai/StartTrigger, di/ChangeDetectEvent,
AnalogComparisonEvent, PairedCtrSource
Ctr1Source
di/ChangeDetectEvent, PFIs,
di/ai/ReferenceTrigger, ai/ao/di/do/StartTrigger, Pulsed
Ctr1Gate Output
PairedCtrOutputPulse, PairedCtrSource, Ctr1OutputPulse
AnalogComparisonEvent, te0/te1//SampleClk Toggled Ctr1InternalOutput
Output
Ctr1Aux
ctr1/Gate, ai/ReferenceTrigger, PFIs,
PairedCtrOutputPulse, te0/te1//SampleClock,
PairedCtrGate, ai/StartTrigger, di/ChangeDetectEvent,
AnalogComparisonEvent, PairedCtrSource
Ctr0Source
Pulsed
Output
Ctr0OutputPulse
ai/di/Start Trigger, PFIs,
di/ChangeDetectEvent, AnalogComparisonEvent, SampleClk
te0/te1/ai/ao/di/do/SampleClk, ai/Reference Trigger
di/ChangeDetectEvent, PFIs,
di/ai/ReferenceTrigger, ai/ao/di/do/StartTrigger,
Ctr0Gate
PairedCtrOutputPulse, PairedCtrSource,
AnalogComparisonEvent, te0/te1//SampleClk
Toggled Ctr0InternalOutput
Ctr0Aux Output
ctr0/Gate, ai/ReferenceTrigger, PFIs,
PairedCtrOutputPulse, te0/te1//SampleClock,
PairedCtrGate, ai/StartTrigger, di/ChangeDetectEvent,
AnalogComparisonEvent, PairedCtrSource
Ctr1Source
di/ChangeDetectEvent, PFIs,
di/ai/ReferenceTrigger, ai/ao/di/do/StartTrigger, Pulsed
Ctr1Gate Output
PairedCtrOutputPulse, PairedCtrSource, Ctr1OutputPulse
AnalogComparisonEvent, te0/te1//SampleClk Toggled Ctr1InternalOutput
Output
Ctr1Aux
ctr1/Gate, ai/ReferenceTrigger, PFIs,
PairedCtrOutputPulse, te0/te1//SampleClock,
PairedCtrGate, ai/StartTrigger, di/ChangeDetectEvent,
AnalogComparisonEvent, PairedCtrSource
318 ni.com
NI-DAQmx Device Considerations
The following figure shows the internal routing for NI 661x devices. The black circles
represent terminals. These devices have eight counters which are paired together.
Only counters 0 and 1 are shown in the illustration, but the remaining pairs (counters 2
and 3, counters 4 and 5, and counters 6 and 7) are routed identically.
Ctr1Aux
PFI 0-39, PXI_Trig/RTSI 0-7,
PairedCtrOutputPulse, ctr1/Gate, PairedCtrGate,
Star_Trigger, di/ChangeDetectEvent,
PairedCtrSource
the task stops. To prevent the acquisition of incorrect samples, only data within either
the 128- or 16-sample group is reported. For instance, if you attempt to acquire 256
samples, and an error occurs after sample 250, the task returns 128 samples instead of
249. If you attempt to acquire a number of samples less than or equal to 128 or 16 and
an error occurs, the task returns no samples.
Related concepts:
The following figure shows a buffered period measurement that uses an external
signal as the Source.
Rising Edge
of Gate
Counter detects rising edge
of Gate on the next rising
edge of Source.
Gate
Source
Counter Value 6 7 1 2 1
Buffer 7 2
7
On the first rising edge of the Gate, the current count of 7 is stored. On the next rising
edge of the Gate, the counter stores a 2 since two Source pulses occurred after the
previous rising edge of Gate.
320 ni.com
NI-DAQmx Device Considerations
The counter synchronizes or samples the Gate signal with the Source signal. So the
counter does not detect a rising edge in the Gate until the next Source pulse. In this
example, the counter stores the values in the buffer on the first rising Source edge after
the rising edge of Gate.
In the following figure, after the first rising edge of Gate, no Source pulses occur. So the
counter does not write the correct data to the buffer.
No Source edge, so no
value written to buffer.
Gate
Source
Counter Value 6 7 1
Buffer 7
With duplicate count prevention enabled, the counter synchronizes both the Source
and Gate signals to the maximum timebase. By synchronizing to the timebase, the
counter detects edges on the Gate even if the Source does not pulse. This enables the
correct current count to be stored in the buffer even if no Source edges occur in
between Gate signals. Refer to the following example.
Counter detects
rising Gate edge. Counter value
increments only
Gate one time for each
Source pulse.
Source
80 MHz Timebase
Counter Value 6 7 0 1
Buffer 7 0
7
Even if the Source pulses are long, the counter increments only once for each Source
pulse.
Normally, the counter value and Counter n Internal Output signals change
synchronously to the Source signal. With duplicate count prevention, the counter
value and Counter n Internal Output signals change synchronously to the maximum
timebase.
In all other cases, you should not use duplicate count prevention.
NI-DAQmx enables duplicate count prevention by default except in the following cases:
You can enable and disable duplicate count prevention in NI-DAQmx with the
CI.DupCountPrevention attribute/property.
9. cDAQ-9171, 9174, 9178, 9179, 9181, 9184, 9185, 9188, 9188XT, 9189, and 9191
322 ni.com
NI-DAQmx Device Considerations
Related concepts:
Prescaling
Prescaling allows the counter to count a signal that is faster than the maximum
timebase of the counter. The TIO counters offer 8X and 2X prescaling on each counter.
You can disable prescaling. Each prescaler consists of a small, simple counter that
counts to eight (or two) and rolls over. This counter is specifically designed for this
application and can count signals that are faster than the general purpose counters.
The CtrN source signal on the general purpose counter is the divided signal from the
simple counter.
Related concepts:
• Pulse Measurement
• Configuring a Time-Based Measurement in NI-DAQmx
• Digital I/O Considerations for C Series and TestScale Devices
Note You cannot use Sample Clock timing for semi-period measurements on
15. TS-15000 and TS-15010
16. cDAQ-9132, 9133, 9134, 9135, 9136, and 9137
17. cRIO-9040, 9041, 9042, 9043, 9045, 9046, 9047, 9048, 9049, 9053, 9054, 9055, 9056, 9057, and 9058
18. sbRIO-9603, 9608, 9609, 9628, 9629, and 9638
19. cDAQ-9171, 9174, 9178, 9179, 9181, 9184, 9185, 9188, 9188XT, 9189, and 9191
20. TS-15000 and TS-15010
21. cDAQ-9132, 9133, 9134, 9135, 9136, and 9137
22. cRIO-9040, 9041, 9042, 9043, 9045, 9046, 9047, 9048, 9049, 9053, 9054, 9055, 9056, 9057, and 9058
23. sbRIO-9603, 9608, 9609, 9628, 9629, and 9638
324 ni.com
NI-DAQmx Device Considerations
X Series devices.
Related concepts:
Digital Filtering
Digital filtering rejects state transitions that do not stay at a state for a specified
amount of time. For example, for an edge counting measurement with digital filtering,
the device does not count an edge if the pulse width is not at least the specified time.
For digital input tasks, the device does not recognize that a signal changed from one
state to another unless the signal remains at that state for the specified amount of
time.
This section contains information about digital filtering for C Series, DIO, M Series, SC
Express, TIO, and X Series devices.
You can configure digital filters on the device by choosing three fixed values (112.5 nS,
6.4 µS, 2.56 mS) or a custom filter value. The custom filter value must be the same for
all lines across the device. For example, if you choose a filter value of 2 µS for PFI 0, any
other filterable line on the device can only choose from the three fixed values and the 2
µs value selected for the custom filter. For each digital line or input terminal, there are
four attributes/properties associated with these digital filters: Digital Filter Enable,
Digital Filter Minimum Pulse Width, Digital Filter Timebase Source, and Digital Filter
Timebase Rate.
When you set the Digital Filter Enable to true, you must also configure the Digital Filter
Minimum Pulse Width attribute/property. When you select a filter value with the Digital
Filter Minimum Pulse Width attribute/property, the device uses an internal 32-bit
utility counter to generate the desired filter value. If you would like to generate the
filter clock using your own external signal, you can use the Digital Filter Timebase
Source and Digital Filter Timebase Rate attributes/properties. You must configure both
to use an external signal as the source for the digital filter. The Digital Filter Minimum
Pulse Width attribute/property represents the minimum value that is guaranteed to be
passed into the device. The maximum pulse width guaranteed to be blocked by the
device is one filter clock tick smaller than the minimum pulse width guaranteed to
pass the filter.
The following table lists the attributes/properties for terminals that can be digitally
filtered.
Type Attribute/Property
Frequency Input Terminal
Period Input Terminal
Count Edges Input Terminal
Count Edges Count Direction
Position A Input Terminal
Position B Input Terminal
Position Z Input Terminal
Channel
Pulse Input Terminal (Time, Ticks, and Frequency)
Pulse Width Input Terminal
Two-Edge First Input Terminal
Two-Edge Second Input Terminal
Semi-Period Input Terminal
Counter Input Timebase Source (External Only)
Counter Output Timebase Source (External Only)
Timing Sample Clock Source
Triggering Arm Start Digital Edge Source
326 ni.com
NI-DAQmx Device Considerations
Type Attribute/Property
Pause Analog Level Source
Pause Analog Window Source
Pause Digital Level Source
Reference Analog Edge Source
Reference Analog Window Source
Reference Digital Edge Source
Start Analog Edge Source
Start Analog Window Source
Start Digital Edge Source
Filters are also available on digital input lines, such as cDAQ1Mod1/port0/line0, but
the filters do not support the fixed values mentioned previously or external timebase
sources. The minimum filter pulse width for digital input lines is 50 nS and can be set
in increments of 25 nS. All digital input lines on a module must use the same minimum
filter pulse width. The maximum pulse width guaranteed to be rejected by the filter is
half the pulse width guaranteed to pass the filter.
This filtering circuitry exists on the chassis and is available for all digital lines that exist
on parallel digital modules. With a parallel digital module, input or output data is
communicated in parallel between the module and the chassis backplane rather than
being communicated serially.
Parallel Digital Input Modules for C Series Devices and TestScale Modules
• NI 9344
• NI 9401
• NI 9402
• NI 9411
• NI 9421
• NI 9422
• NI 9423
• NI 9435
• NI 9436
• NI 9437
• TS-15050 DIO P0
Note The NI 9361 also performs digital filtering, but its filtering is done on
the module rather than on the chassis. Refer to the NI 9361 Datasheet for
more information about its filtering capabilities.
• PCI-6510
• PCI-6511
• PCI-6514
• PCI-6515
• PCI-6518
• PCI-6519
• PCI-6527
Digital Filtering Enabled by Default • PCI-6528
• PXI-6511
• PXI-6514
• PXI-6515
• PXI-6527
• PXI-6528
• PXI-6529
• USB-6525
• PCI-6509
• PCIe-6509
Digital Filtering Disabled by Default
• PXI-6509
• PXIe-6509
328 ni.com
NI-DAQmx Device Considerations
• PCI-6503
• PCI-6512
• PCI-6513
• PCI-6516
• PCI-6517
Digital Filtering Not Supported
• PCI-DIO-96
• PXI-6508
• PXI-6512
• PXI-6513
• USB-6501
Note For digital filtering with NI 661x devices, refer to Digital Filtering
Considerations for X Series and NI 661x Devices.
There are two methods for filtering and synchronizing digital signals. One method is to
synchronize the input signal to the maximum onboard timebase on the device. To do
this, set Digital Synchronization Enable to true.
The other method is to pass the input of any PFI line through a digital debouncing
filter. Each PFI line can independently select from four fixed values (5 µs, 1 µs, 500 ns,
100 ns) and one custom filter value. The custom filter value must be the same for each
PFI line. That is, if you choose a filter value of 2 µs for a PFI line, other PFI lines on the
device at the same time can only choose from the four fixed values and the 2 µs value
selected as the custom filter value. For each counter input property, there are four
attributes/properties associated with digital debounce filtering: Digital Filter Enable,
Digital Filter Minimum Pulse Width, Digital Filter Timebase Source, and Digital Filter
Timebase Rate.
When you set the Digital Filter Enable to true, you must also configure the Digital Filter
Minimum Pulse Width attribute/property. This value represents the minimum value
that is guaranteed to pass into the TIO. The minimum pulse width guaranteed to be
blocked is one-half of the Digital Filter Minimum Pulse Width attribute/property. When
you select a custom filter value with the Minimum Pulse Width attribute/property, NI-
DAQmx uses an internal 32-bit utility counter to generate the desired filter value. If you
would like to generate the filter clock using your own external signal, you can use the
Digital Filter Timebase Source and Digital Filter Timebase Rate attributes/properties.
You must configure both to use an external signal as the source for the digital filter.
You cannot set both Digital Filter Enable and Digital Synchronization Enable to true at
the same time. You can use only one of these digital filtering methods at a time.
The following table lists the counter input terminals that can be digitally filtered.
Type Attribute/Property
Frequency Input Terminal
Period Input Terminal
Count Edges Input Terminal
Count Edges Count Direction
Position A Input Terminal
Position B Input Terminal
Channel Position Z Input Terminal
Pulse Width Input Terminal
Two-Edge First Input Terminal
Two-Edge Second Input Terminal
Semi-Period Input Terminal
Counter Input Timebase Source
Counter Output Timebase Source
Timing Sample Clock Source
Start Trigger Source
Triggering Pause Trigger Source
Arm Start Trigger Source
330 ni.com
NI-DAQmx Device Considerations
You can configure digital filters on the device by choosing three fixed values (90 nS,
5.12 µS, 2.56 mS). For each digital line or input terminal, there are four attributes/
properties associated with these digital filters: Digital Filter Enable, Digital Filter
Minimum Pulse Width, Digital Filter Timebase Source, and Digital Filter Timebase Rate.
When you set the Digital Filter Enable to true, you must also configure the Digital Filter
Minimum Pulse Width attribute/property. This value represents the minimum value
that is guaranteed to be passed into the device. The maximum pulse guaranteed to be
blocked by the device varies by digital line. Refer to your device documentation for
details. When you select a custom filter value with the Minimum Pulse Width attribute/
property, NI-DAQmx uses an internal 32-bit utility counter to generate the desired filter
value. If you would like to generate the filter clock using your own external signal, you
can use the Digital Filter Timebase Source and Digital Filter Timebase Rate attributes/
properties. You must configure both to use an external signal as the source for the
digital filter.
When using digital filtering on port 0, you can enable bus mode using the Enable Bus
Mode attribute/property. When enabled, the device observes changes to multiple lines
as a single change if these conditions are met:
• The skew between them is less than the minimum pulse width of the filter.
• The lines remain stable for an additional minimum pulse width of the filter.
When using any other signal on the device that supports filtering (excluding port 0),
you can select a custom filter value in addition to the three fixed values mentioned
previously. The custom filter value must be the same for all lines across the device. For
example, if you choose a filter value of 2 µS for PFI 0, any other filterable line on the
device can only choose from the three fixed values and the 2 µs value selected for the
custom filter.
The following table lists the attributes/properties for terminals that can be digitally
filtered.
Type Attribute/Property
Digital Input Channel
Frequency Input Terminal
Period Input Terminal
Count Edges Input Terminal
Count Edges Count Direction
Position A Input Terminal
Position B Input Terminal
Channel Position Z Input Terminal
Pulse Input Terminal
Pulse Width Input Terminal
Two-Edge First Input Terminal
Two-Edge Second Input Terminal
Semi-Period Input Terminal
Counter Input Timebase Source
Counter Output Timebase Source
Sample Clock Source
Timing
AI Convert Clock Source
Arm Start Trigger Source
Pause Analog Level Source
Pause Analog Window Source
Pause Trigger Source
Reference Analog Edge Source
Triggering
Reference Analog Window Source
Reference Digital Edge Source
Start Analog Edge Source
Start Analog Window Source
Start Trigger Source
332 ni.com
NI-DAQmx Device Considerations
You can configure digital filters on the device by choosing three fixed values (90 ns,
5.12 µs, 2.56 ms). For each digital line or input terminal, there are four attributes/
properties associated with these digital filters: DI.DigFltr.Enable,
DI.DigFltr.MinPulseWidth, DI.DigFltr.TimebaseSrc, and DI.DigFltr.TimebaseRate.
When you set the DI.DigFltr.Enable to true, you must also configure the
DI.DigFltr.MinPulseWidth attribute/property. This value represents the minimum value
that is guaranteed to be passed into the device. When you select a custom filter value
with the DI.DigFltr.MinPulseWidth attribute/property, NI-DAQmx uses an internal 32-bit
utility counter to generate the desired filter value.
You can select a custom filter value in addition to the three fixed values mentioned
previously. The custom filter value must be the same for all lines across the device. For
example, if you choose a filter value of 2 µs for PFI 0, any other filterable line on the
device can only be set to one of the three fixed values or the 2 µs value selected for the
custom filter.
The following table lists the attributes/properties for terminals that can be digitally
filtered.
Type Attribute/Property
Timing Sample Clock Source (SampClk.Src)
Pause Digital Level Source (Pause.DigLvl.Src)
Reference Analog Edge Source (Ref.AnlgEdge.Src)
Triggering Reference Analog Window Source (Ref.AnlgWin.Src)
Reference Digital Edge Source (Ref.DigEdge.Src)
Start Digital Edge Source (Start.DigEdge.Src)
FieldDAQ Filtering
The FD-11601, FD-11603, FD-11605, FD-11634, and FD-11637 can use filtering to
provide an accurate representation of in-band signals while rejecting out-of-band
signals. The filters discriminate between signals based on the frequency range, or
bandwidth, of the signal. Use the AI.Filter.Enable DAQmx Channel property to enable
or disable a filter. You can then specify the center or cutoff frequency (AI.Filter.Freq),
the filter order (AI.Filter.Order), and choose a Brickwall, Butterworth, or Comb filter
response (AI.Filter.Response). The filter selection applies to all channels on a bank.
In NI-DAQmx, you can specify the center or cutoff frequency (AI.Filter.Freq), the filter
order (AI.Filter.Order), and choose a Comb filter response (AI.Filter.Response). The NI
9252/9253 also provide a Butterworth filter.
Refer to the hardware datasheets for additional details on filtering for these devices.
Digital I/O
This section contains information specific to DIO devices.
Change Detection
This section contains information about change detection for C Series, DIO, and M
Series devices.
Related concepts:
334 ni.com
NI-DAQmx Device Considerations
Serial digital I/O modules: NI 9375, NI 9403, NI 9425, NI 9426, NI 9476, NI 9477, NI 9478,
TS-15120, and TS-15130.
Parallel digital I/O modules: NI 9344, NI 9401, NI 9402, NI 9411, NI 9421, NI 9422, NI
9423, NI 9435, NI 9436, NI 9437, NI 9472, NI 9474, NI 9475, NI 9481, NI 9482, NI 9485, and
TS-15050 DIO P0.
Onboard parallel digital I/O modules on sbRIO-9628 and 9638: DIO 0-3, DIO 4-11, DIO
12-19, and DIO 20-27.
Parallel modules:
• Counter/timer tasks
• Accessing PFI signal tasks (can be used in up to two slots)
Related concepts:
• Software-Timed Tasks
• NI 673x
CompactDAQ
• cDAQ-9132
• cDAQ-9133
• cDAQ-9134
• cDAQ-9135
• cDAQ-9136
• cDAQ-9137
• cDAQ-9138/9139
• cDAQ-9171
• cDAQ-9174
• cDAQ-9178
336 ni.com
NI-DAQmx Device Considerations
• cDAQ-9179
• cDAQ-9181
• cDAQ-9184
• cDAQ-9185
• cDAQ-9188
• cDAQ-9188XT
• cDAQ-9189
• cDAQ-9191
CompactRIO
• cRIO-9040
• cRIO-9041
• cRIO-9042
• cRIO-9043
• cRIO-9045
• cRIO-9046
• cRIO-9047
• cRIO-9048
• cRIO-9049
• cRIO-9053
• cRIO-9054
• cRIO-9055
• cRIO-9056
• cRIO-9057
• cRIO-9058
• sbRIO-9603
• sbRIO-9608
• sbRIO-9609
• sbRIO-9628
• sbRIO-9629
• sbRIO-9638
M Series 1
• NI 622x
• NI 625x
• NI 628x
S Series 1
• NI 6115
• NI 6120
• NI 6132
• NI 6133
NI 653x
• PCI-6533 (DIO-32HS)
• PXI-6533
• PCI-6534
• PXI-6534
• PCIe-6535
• PXIe-6535
• PCIe-6536
• PXIe-6536
• PCIe-6537
• PXIe-6537
NI 661x Devices
• NI 6612
• NI 6614
X Series Devices
All X Series devices support sample clock timing for digital I/O.
Related concepts:
338 ni.com
NI-DAQmx Device Considerations
• PCI-6025E
• PCI-6533 (DIO-32HS)
• PCI-6534
• PCI-DIO-24
• PCI-DIO-96
• PCIe-6535
• PCIe-6536
• PCIe-6537
• PXI-6025E
• PXI-6508
• PXI-6533
• PXI-6534
• PXIe-6535
• PXIe-6536
• PXIe-6537
Note The NI 6533 and NI 6534 have two timing engines, Timing Engine 1 and
Timing Engine 0. Each timing engine is associated with PFI lines. The timing
engine you use is determined by the digital lines you use. If the least
significant port is Port 0, NI-DAQmx picks Timing Engine 0. If the least
significant port is Port 2, NI-DAQmx picks Timing Engine 1.
The recommended sample clock terminal for burst handshake timing is PFI 4 (Timing
Engine 0) or PFI 5 (Timing Engine 1).
• PCI-6533 (DIO-32HS)
• PCI-6534
• PCIe-6535
• PCIe-6536
• PCIe-6537
• PXI-6533
• PXI-6534
• PXIe-6535
• PXIe-6536
• PXIe-6537
Related concepts:
Note The NI 6533 and NI 6534 have two timing engines, Timing Engine 1 and
Timing Engine 0. Each timing engine is associated with PFI lines. The timing
engine you use is determined by the digital lines you use. If the least
significant port is Port 0, NI-DAQmx picks Timing Engine 0. If the least
340 ni.com
NI-DAQmx Device Considerations
The recommended sample clock terminal for burst handshake timing is PFI 4 (Timing
Engine 0) or PFI 5 (Timing Engine 1).
Watchdog Timers
Watchdog timers are a hardware feature that you can use to detect a failure in the
software controlling the device. Software failures could include a system crash or a
loop rate that is slower than you intend. To use a watchdog timer, you must use a
watchdog timer task. When you create a watchdog timer task, you specify the timeout
value for the watchdog timer and a set of expiration states for output physical
channels on the device. The channels go to those expiration states if the watchdog
timer expires. In addition, you cannot perform any actions with the task until you reset
it.
Your application must continuously reset the watchdog timer to prevent it from
expiring. For example, if you have a digital I/O application, and you expect a loop in the
application to acquire and analyze data 10 times per second, you should set the
watchdog timer to expire in 100 ms and reset the timer inside the digital I/O loop. If the
loop does not execute once every 100 ms, the watchdog timer expires and the device
goes into the expired state. You must then clear the expiration or reset the device.
Also, you can use the Expiration Trigger to cause the watchdog timer to expire. Set the
timeout of the watchdog timer task to -1 to disable expiration due to timeout if you
want the Expiration Trigger to be the only mechanism to cause expiration.
Note For X Series devices, PFI lines used for routing either by the Connect
Note For the NI 9260, all channels on a watchdog task must use the same
expiration state. If the expiration state is set to Voltage, you can specify
different voltage levels for each channel. If the expiration state is set to No
Change, the channels revert to their idle output behavior on expiration.
Pause Triggering
This section contains information about Pause Triggering for AO Series, DSA, E Series,
M Series, S Series, SC Express, and TIO devices.
Analog Output
When you generate analog output signals, the generation pauses as soon as the Pause
Trigger is asserted. If the source of your sample clock is the onboard clock, the
generation resumes as soon as the Pause Trigger is deasserted. The NI 6733 and NI
6251 behave as if an external clock is being used, even if the source of the sample clock
is the onboard clock. For these devices, the generation resumes as soon as the Pause
Trigger is deasserted and another edge of the sample clock is received.
Pause Trigger
Sample Clock
If you are using any signal other than the onboard clock as the source of your sample
clock, the generation resumes as soon as the Pause Trigger is deasserted and another
edge of the sample clock is received, as shown in the following figure.
342 ni.com
NI-DAQmx Device Considerations
Pause Trigger
Sample Clock
Counters
Pause Trigger
Pulse Train
Nonbuffered edge counting: The counter stops counting edges as soon as the Pause
Trigger is asserted and resumes counting edges after the Pause Trigger is deasserted.
Pause Trigger
Counter Source
Counter Value 1 2 3 4 5
When you acquire counter input signals, the acquisition pauses as soon as Pause
Trigger is asserted. If the source of your sample clock is the onboard clock, the
acquisition resumes after the Pause Trigger is deasserted, and the leftover period (A)
elapses. The leftover period is the unknown time in the sample clock period in which
the pause trigger occurred. In the following image, T represents the signal period and
A represents the unknown time between the clock pulse and the pause trigger.
A
T T–A
Sample Clock
Pause Trigger
If you are using any signal other than the onboard clock as the source of your sample
clock, the acquisition resumes as soon as the Pause Trigger is deasserted and another
edge of the sample clock is received as shown in the following figure.
Pause Trigger
Sample Clock
Counter Gate
Counter Source
Counter Value 1 2 3 4 5
Analog Input
When you measure analog input signals and the Pause Trigger is asserted, the current
sample across all channels finishes before pausing. For instance, if you are sampling
four channels and the second channel is being sampled at the time the Pause Trigger is
asserted, the second, third, and fourth channels complete their sample before the
acquisition pauses. If you are using the onboard clock as the source of your sample
clock, the acquisition resumes as soon as the Pause Trigger is deasserted.
344 ni.com
NI-DAQmx Device Considerations
Pause Trigger
Sample Clock
Convert Clock
If you are using any signal other than the onboard clock as the source of your sample
clock, the acquisition resumes as soon as the Pause Trigger is deasserted and another
edge of the sample clock is received as shown in the following figure.
Pause Trigger
Sample Clock
Convert Clock
Analog Output
When you generate analog output signals, the generation pauses as soon as the Pause
Trigger is asserted. If the source of your sample clock is the onboard clock, the
generation resumes as soon as the Pause Trigger is deasserted.
Pause Trigger
Sample Clock
If you are using any signal other than the onboard clock as the source of your sample
clock, the generation resumes as soon as the Pause Trigger is deasserted and another
edge of the sample clock is received as shown in the following figure.
Pause Trigger
Sample Clock
Counters
Pause Trigger
Pulse Train
Nonbuffered edge counting: The counter stops counting edges as soon as the Pause
Trigger is asserted and resumes counting edges after the Pause Trigger is deasserted.
Pause Trigger
Counter Source
Counter Value 1 2 3 4 5
When you generate analog output signals or acquire analog input signals, the
generation/acquisition pauses as soon as the Pause Trigger is asserted. If the source of
your sample clock is the onboard clock, the generation/acquisition resumes as soon as
the Pause Trigger is deasserted.
Pause Trigger
Sample Clock
If you are using any signal other than the onboard clock as the source of your sample
clock, the generation/acquisition resumes as soon as the Pause Trigger is deasserted
and another edge of the sample clock is received as shown in the following figure.
Pause Trigger
Sample Clock
Pause triggers also require special consideration when used on a device with a
pipelined ADC. See Timing Considerations for S Series for how pipelined ADCs
346 ni.com
NI-DAQmx Device Considerations
Related concepts:
Counters
Pause Trigger
Pulse Train
Nonbuffered edge counting: The counter stops counting edges as soon as the Pause
Trigger is asserted and resumes counting edges after the Pause Trigger is deasserted.
Pause Trigger
Counter Source
Counter Value 1 2 3 4 5
The counter stops counting edges as soon as the Pause Trigger is asserted and
resumes counting edges after the Pause Trigger is deasserted.
Pause Trigger
Counter Source
Counter Value 1 2 3 4 5
The pulse-train generation pauses as soon as the Pause Trigger is asserted, not at the
end of a pulse. The pulse train resumes after the Pause Trigger is deasserted. A Pause
Trigger elongates either the high or low pulse depending on which one was being
generated at the time the Pause Trigger was asserted.
Pause Trigger
Pulse Train
Note NI 433x devices and the NI 4340 do not support pause triggering.
The source of your sample clock often can affect when your acquisition pauses and
resumes with the assertion and deassertion of a Pause Trigger.
When you generate analog output signals or acquire analog input signals on a
simultaneous sampling SC Express device, such as the NI 4322 or NI 4300, the
generation/acquisition pauses as soon as the Pause Trigger is asserted. If the source of
your sample clock is the onboard clock, the generation/acquisition resumes as soon as
the Pause Trigger is deasserted.
Pause Trigger
Sample Clock
If you are using any signal other than the onboard clock as the source of your sample
clock, the generation/acquisition resumes as soon as the Pause Trigger is deasserted
348 ni.com
NI-DAQmx Device Considerations
and another edge of the sample clock is received, as shown in the following figure.
Pause Trigger
Sample Clock
The NI 4353 has three ADCs. There is ADC0, which is for the even analog input channels
(for instance, ai4, ai6, and ai10), ADC1, which is for the odd analog input channels (for
instance, ai1, ai3, and ai5), and ADC2, which is for the cold-junction compensation
channels.
If the Pause Trigger is asserted, and you sample from multiple cold-junction
compensation channels, multiple odd-numbered analog input channels, or multiple
even-numbered analog output channels, the current sample across all channels
finishes before pausing. For instance, if you are sampling eight channels, ai0:7, and ai4
is being sampled when the Pause Trigger is asserted, the remaining four channels
complete their sample before the acquisition pauses. If you are using the onboard
clock as the source of your sample clock, the acquisition resumes as soon as the Pause
Trigger is deasserted.
Pause Trigger
Sample Clock
If you are using any signal other than the onboard clock as the source of your sample
clock, the acquisition resumes as soon as the Pause Trigger is deasserted and another
edge of the sample clock is received, as shown in the following figure.
Pause Trigger
Sample Clock
• ADC0 maps to the analog input channels ai0, ai5, ai10, ai15
• ADC1 maps to the analog input channels ai1, ai6, ai11, ai16
• ADC2 maps to the analog input channels ai2, ai7, ai12, ai17
• ADC3 maps to the analog input channels ai3, ai8, ai13, ai18
• ADC4 maps to the analog input channels ai4, ai9, ai14, ai19
If the Pause Trigger is asserted, and you sample from multiple channels on the same
ADC, the current sample across all channels finishes before pausing. For instance, if
you are sampling eight channels, ai0:7, and ai4 is being sampled when the Pause
Trigger is asserted, the remaining four channels complete their sample before the
acquisition pauses. If you are using the onboard clock as the source of your sample
clock, the acquisition resumes as soon as the Pause Trigger is deasserted.
Pause Trigger
Sample Clock
ADC0
ADC1
If you are using any signal other than the onboard clock as the source of your sample
clock, the acquisition resumes as soon as the Pause Trigger is deasserted and another
edge of the sample clock is received, as shown in the following figure.
Pause Trigger
Sample Clock
ADC0
ADC1
Physical Channels
This section contains information about physical channels for AO Series, bus-powered
M Series, C Series, E Series, M Series, NI 6010, NI 6154, NI 6221 (37-pin), NI 623x, NI
6533/6534, NI 6535/6536/6537, NI ELVIS II Family, S Series, SC Express, SCXI, SCC, TIO,
USB DAQ, and X Series devices.
350 ni.com
NI-DAQmx Device Considerations
Related reference:
Analog Output
An AO Series device has between four and 64 analog output physical channels named
Dev1/ao0 to Dev1/ao63.
For more detailed information on the device physical AO characteristics, refer to your
device user manual and specifications.
All AO Series devices have eight lines of digital input and output named Dev1/
port0/line0 through Dev1/port0/line7. These lines belong to a single port,
and the physical channel Dev1/port0 refers to all eight lines at once.
All AO Series devices have two counter/timers referred to by the physical channel
names Dev1/ctr0 and Dev1/ctr1. Unlike the other I/O types, these physical
channel names do not refer to terminals on the I/O connector but instead to circuits
within the device. There are three primary terminals associated with each counter.
These are the terminals used as the SOURCE, GATE and OUT functions. NI-DAQmx has
default values for these terminals. For counter input tasks, if you know whether your
signal provides the SOURCE or GATE function and wire your signal to the default, you
do not have to set the Input Terminal attribute/property.
• cDAQ1Mod1 is the default device name for a C Series device plugged into a USB or
Standalone CompactDAQ chassis, where cDAQ1 is the default chassis device name,
and Mod1 refers to the slot number
• TS1Mod1 is the default device name for a TestScale module plugged into a
Standalone TestScale chassis, where TS1 is the default chassis device name, and
Mod1 refers to the slot number
For C Series devices plugged into a network CompactDAQ chassis, such as the NI
cDAQ-9188, the default chassis device name is the host name of the chassis. You can
change these names in MAX. For C Series devices plugged into a supported
CompactRIO26 or CompactRIO Single-Board27 controller, Mod1 is the default device
name.
Related concepts:
Related reference:
Analog Input
The following table lists the number and naming of analog input physical channels for
C Series devices and TestScale modules.
26. cRIO-9040, 9041, 9042, 9043, 9045, 9046, 9047, 9048, 9049, 9053, 9054, 9055, 9056, 9057, and 9058.
27. sbRIO-9603, 9608, 9609, 9628, 9629, and 9638.
352 ni.com
NI-DAQmx Device Considerations
Number
Device of Naming
Channels
cDAQ1Mod1/ai0 to
NI 9218, NI 9250, NI 9251 2
cDAQ1Mod1/ai1
cDAQ1Mod1/ai0 to
NI 9225, NI 9230, NI 9232, NI 9246, NI 9247 3
cDAQ1Mod1/ai2
NI 9210, NI 9211, NI 9215, NI 9217, NI 9219, NI 9222, NI
cDAQ1Mod1/ai0 to
9223, NI 9227, NI 9229, NI 9234, NI 9237, NI 9238, NI 4
cDAQ1Mod1/ai3
9239, NI 9775
cDAQ1Mod1/ai0 to
NI 9242, NI 9244 4 cDAQ1Mod1/ai2,
cDAQ1Mod1/neutral
NI 9201, NI 9203, NI 9212, NI 9216, NI 9221, NI 9226, NI
cDAQ1Mod1/ai0 to
9224, NI 9228, NI 9231, NI 9235, NI 9236, NI 9252, NI 8
cDAQ1Mod1/ai7
9253
NI 9202, NI 9204, NI 9207, NI 9208, NI 9209, NI 9213, NI cDAQ1Mod1/ai0 to
16
9214 , NI 9220 cDAQ1Mod1/ai15
cDAQ1Mod1/ai0 to
NI 9205, NI 9206 32
cDAQ1Mod1/ai31
TS1Mod1/ai0 to TS1Mod1/
TS-15100 32
ai31
On the NI 9204, you can configure channels 0-7 as the positive channel of a differential
pair. On the NI 9205 and NI 9206, you can configure channels 0-7 and 16-23 as the
positive channel of a differential pair. If N is this channel, channel N + 8 is the negative
input of the pair. For instance, if you configure channel 1 in differential mode, the
positive input is channel 1, and channel 9 is the negative input. Use only the physical
channel name of the positive channel (not both) when creating a differential channel.
You can use channels from multiple analog input C Series devices in the same NI-
DAQmx task.
• Up to three analog input tasks can run at a given time per chassis in a cDAQ-91xx28
or TestScale29 chassis.
28. cDAQ-9132, 9133, 9134, 9135, 9136, 9137, 9174, 9178, 9179, 9184, 9185, 9188, 9188XT, and 9189
• Up to eight analog input tasks can run a given time in a CompactRIO controller or a
CompactRIO Single-Board controller.
• Up to two analog input tasks with a C Series Delta-Sigma device can run at a given
time per chassis in a cDAQ-91xx30 or TestScale31 chassis.
• Up to eight analog input tasks with a C Series Delta-Sigma device can run at a
given time in a CompactRIO controller or a CompactRIO Single-Board controller.
Related concepts:
The NI 9235, NI 9236, and NI 9237 support only the AI Strain Gage, AI Force Bridge, AI
Pressure Bridge, AI Torque Bridge, AI Bridge (V/V), and AI Custom Voltage With
Excitation channel types.
When using the NI 9218, NI 9219, NI 9235, NI 9236, or NI 9237 with an AI Custom Voltage
With Excitation channel, you must set the AI.Excit.UseForScaling attribute/property to
true. This attribute/property causes the channel to return ratiometric data: Vin/Vex.
The NI 9219, NI 9235, NI 9236, and NI 9237 modules perform this division in hardware.
For the NI 9219, NI-DAQmx requires the AI.Excit.Val attribute/property to be set to 2.5 V
for AI Strain Gage and AI Custom Voltage With Excitation channel types and to 500 µA
for resistance and RTD measurements. The actual excitation voltage or current output
by the NI 9219 varies with the sensor resistance or the load being measured.
For the NI 9218, NI-DAQmx requires the AI.Excit.Val attribute/property to be set to 3.3 V
or 2 V for AI Strain Gage and AI Custom Voltage With Excitation (bridge mode), to 12 V
for AI Custom Voltage With Excitation (no bridge mode) for powered sensors, and to 2
mA for IEPE.
NI 9218, NI 9219, NI 9235, NI 9236, and NI 9237 devices return a voltage ratio rather
than a voltage. Therefore, use the AI.Bridge.InitialRatio attribute/property to specify
the initial voltage ratio, or set the AI.Bridge.InitialVoltage attribute/property to the
354 ni.com
NI-DAQmx Device Considerations
The NI 9219 does not have quarter bridge completion circuitry, which affects AI Strain
Gage Quarter Bridge I channels and AI Custom Voltage With Excitation Quarter Bridge
channels (but not AI Strain Gage Quarter Bridge II channels). With these channels, the
NI 9219 performs a 2-wire resistance measurement on the active gage element, then
NI-DAQmx uses software scaling to convert the resistance measurement into a bridge
ratio. For these channels, the polynomial coefficients specified by the
AI.DevScalingCoeff attribute/property convert unscaled data into Ohms, not into V/V.
Likewise, the AI.Rng.High/AI.Rng.Low attributes/properties should be specified in units
of Ohms, not V/V.
When the NI 9219 is in quarter bridge mode, you need to use the
AI.Bridge.NomResistance attribute/property to control whether the channel uses the
120 Ω range or the 350 Ω range.
The NI 9218 has an internal full bridge. However, it can support quarter-bridge and
half-bridge measurements with the proper accessories.
The NI 9218 supports powered sensor measurements. For voltage powered sensor
measurements, you can use either the DAQmx Create Channel function/VI (the AI
Custom Voltage with Excitation measurement type) with the Bridge Configuration set
to No Bridge, or you can use the DAQmx Create Channel function/VI (voltage
measurement type) with the AI.Excit.Val attribute/property. For current powered
sensor measurements, you have to use the DAQmx Create Channel function/VI (current
measurement type) with the AI.Excit.Val attribute/property.
Analog Output
The following table lists the number and naming of analog output physical channels
for C Series devices.
You can use channels from multiple analog output C Series devices in the same analog
output task. With certain cDAQ-91xx32 or TestScale33 chassis, if the task is hardware-
timed and uses only onboard memory, there is a limit of 16 channels per task, but if
the task is software-timed or does not use only onboard memory, the number of
channels is limited only by the number of devices. Only one hardware-timed analog
output task per CompactDAQ chassis can run at a given time. With a CompactRIO
controller or CompactRIO single-board controller, up to eight hardware-timed analog
output tasks can run at a given time.
When using the NI 9262, NI 9263, NI 9264, NI 9265, NI 9266, or TS-15110 you can run
only one type of timing at a time. You can have one software-timed task per channel or
one hardware-timed task running on a device at one time, but you cannot have a
combination of timing on that device. For instance, you can run up to four software-
timed tasks on the NI 9265 concurrently, but running one hardware-timed task with
one software-timed task generates an error.
When using the NI 9260, if you start a task that uses a different channel than the one
you are currently using, the channel no longer in use reverts to the calibrated 0 V value.
The following table lists the number, type, and naming of digital input/output lines for
C Series devices.
32. cDAQ-9132, 9133, 9134, 9135, 9136, 9137, 9174, 9178, 9179, 9184, 9185, 9188, 9188XT, and 9189
33. TS-15000 and TS-15010
356 ni.com
NI-DAQmx Device Considerations
Note Digital I/O module capabilities depend on the type of digital signals
that the module can measure or generate and the chassis the module is used
in. Refer to Digital I/O Considerations for C Series for more
information.
onboard I/O connectors in addition to C Series device access through the RMC
connector. See CompactRIO Single-Board Controller Physical Channels for
more information and counter terminal default configuration of CompactRIO single-
board controller onboard I/O connectors.
Each counter has four primary terminals associated with it. These are the terminals
used as the SOURCE, GATE, AUX, and OUT functions. NI-DAQmx has default values for
these terminals. For counter input tasks, if you know whether your signal provides the
SOURCE, AUX, or GATE function and wire your signal to the default, you do not have to
set the Input Terminal attribute/property.
Counter/timers are only supported on parallel digital I/O modules. Refer to Digital
I/O Considerations for C Series for more information.
The following table shows the counter terminal defaults for 8-channel DIO/DI/DO C
Series devices.
The following table shows the counter terminal defaults for 6-channel DIO/DI/DO C
Series devices.
358 ni.com
NI-DAQmx Device Considerations
The following table shows the counter terminal defaults for 4-channel DIO/DI/DO C
Series devices.
The following table lists the number, type, and naming of counter input lines for C
Series counter modules.
There are 8 PFI lines, from PFI0 to PFI7. Each counter can use any of the input PFI lines
to perform measurements. Two counters can use the same PFI line as inputs for their
measurements, as long as the input configurations are the same for both counters.
The following table shows the terminal defaults for edge counting measurements for C
Series counter modules.
The following table shows the terminal defaults for position measurements for C
Series counter modules.
Counter A B Z
ctr0 PFI0 PFI4 PFI7
ctr1 PFI1 PFI5 PFI6
ctr2 PFI2 PFI6 PFI5
ctr3 PFI3 PFI7 PFI4
ctr4 PFI4 PFI0 PFI3
ctr5 PFI5 PFI1 PFI2
ctr6 PFI6 PFI2 PFI1
ctr7 PFI7 PFI3 PFI0
The following table shows the terminal defaults for velocity measurements for C Series
counter modules that support velocity measurements.
Counter A B
ctr0 PFI0 PFI4
ctr1 PFI1 PFI5
360 ni.com
NI-DAQmx Device Considerations
Counter A B
ctr2 PFI2 PFI6
ctr3 PFI3 PFI7
ctr4 PFI4 PFI0
ctr5 PFI5 PFI1
ctr6 PFI6 PFI2
ctr7 PFI7 PFI3
The following table shows the terminal defaults for frequency, period, duty cycle, and
pulse width measurements for C Series counter modules.
Connections for PFI lines should be based on the terminal configuration property. PFI
+ and PFI- should be connected in differential mode, and PFI + and COM should be
connected for RSE. The default terminal configuration for all counter input terminals is
RSE.
Analog Input
Number of
Device Naming
Channels
sbRIO-9628, sbRIO-9629, Conn0_AI/ai0 to Conn0_AI/
16
sbRIO-9638 ai15
Analog Output
The sbRIO-9628, 9629, and 9638 have four counters. You can use counters/timers with
a C Series device using the RMC connector or with onboard I/O on models where these
I/O connectors are available. The following information applies to CompactRIO Single-
Board controller onboard I/O. See C Series Physical Channels for more
information and counter terminal default configuration of C Series device I/O using the
RMC connector.
362 ni.com
NI-DAQmx Device Considerations
Each counter has four primary terminals associated with it. These are the terminals
used as the SOURCE, GATE, AUX, and OUT functions. NI-DAQmx has default values for
these terminals. For counter input tasks, if you know whether your signal provides the
SOURCE, AUX, or GATE function and wire your signal to the default, you do not have to
set the Input Terminal attribute/property.
Counter/timers are supported on the DIO 0-3, DIO 4-11, DIO 12-19 and DIO 20-27
onboard DIO devices and on parallel digital I/O modules. Refer to Digital I/O
Considerations for C Series and the counter section in C Series Physical
Channels for more information about C Series device specific behavior.
The following table shows the counter terminal defaults for the DIO 0-3 onboard
device.
The following table shows the counter terminal defaults for the DIO 4-11 onboard
device.
The following table shows the counter terminal defaults for the DIO 12-19 onboard
device.
The following table shows the counter terminal defaults for the DIO 20-27 onboard
device
364 ni.com
NI-DAQmx Device Considerations
Related reference:
Analog Input
A 16-channel E Series device has physical channels ranging from Dev1/ai0 to Dev1/
ai15. You can configure only channels 0 through 7 in differential mode. When you
configure a channel in differential mode, the channel is the positive input and channel
plus eight is the negative input. For instance, if you configure channel 1 in differential
mode, the positive input is channel 1, and channel 9 is the negative input.
A 64-channel E Series device has physical channels ranging from Dev1/ai0 to Dev1/
ai63. You can configure channels in banks of every other eight beginning with 0
through 7 as the positive channel of a differential pair (0-7, 16-23, 32-39, and 48-55). If
N is this channel, channel N + 8 is the negative input of the pair.
Use only the physical channel name of the positive channel when creating a
differential channel (not both).
Analog Output
An E Series device that supports analog output has two analog output physical
channels named Dev1/ao0 and Dev1/ao1.
All E Series devices except the NI 6025E have eight lines of digital input and output
named Dev1/port0/line0 through Dev1/port0/line7. These lines belong to
a single port, and the physical channel Dev1/port0 refers to all eight lines at once.
The NI 6025E has 32 lines of digital input and output with eight lines belonging to one
of four ports. The names are of the form Dev1/portP/line0 through Dev1/
portP/line7, where P ranges from 0 through 3. There are also four physical channel
names that refer to all eight lines in a port at once of the form Dev1/portP, where P
ranges from 0 through 3. There are two more physical channel names that refer to all
the lines in multiple consecutive ports. They are both of the form Dev1/portP_N,
where P is the port number of the lowest numbered port, and N is the total number of
lines. All 32 lines at once can be configured as a single virtual channel with the physical
channel name Dev1/port0_32. You can configure the two ports that can be
handshaked as a single virtual channel by using the physical channel name Dev1/
port1_16.
All E Series devices have two counter/timers referred to by the physical channel names
Dev1/ctr0 and Dev1/ctr1. Unlike the other I/O types, these physical channel
names do not refer to terminals on the I/O connector but instead to circuits within the
device. There are three primary terminals associated with each counter. These are the
terminals used as the SOURCE, GATE and OUT functions. NI-DAQmx has default values
for these terminals. For counter input tasks, if you know whether your signal provides
the SOURCE or GATE function and wire your signal to the default, you do not have to
set the Input Terminal attribute/property.
366 ni.com
NI-DAQmx Device Considerations
Analog Input
The following table lists the number and naming of analog input physical channels for
FieldDAQ devices.
Number of
Device Naming
Channels
FD-11601-xxxxxxx-Bank1/ai0 to
FD-11601-xxxxxxx-Bank1/ai3
FD-11601 8
FD-11601-xxxxxxx-Bank2/ai0 to
FD-11601-xxxxxxx-Bank2/ai3
FD-11603-xxxxxxx-Bank1/ai0 to
FD-11603-xxxxxxx-Bank1/ai3
FD-11603 8
FD-11603-xxxxxxx-Bank2/ai0 to
FD-11603-xxxxxxx-Bank2/ai3
FD-11605-xxxxxxx-Bank1/ai0 to
FD-11605-xxxxxxx-Bank1/ai3
FD-11605 8
FD-11605-xxxxxxx-Bank2/ai0 to
FD-11605-xxxxxxx-Bank2/ai3
FD-11613-xxxxxxx-Bank1/ai0 to
FD-11613 8
FD-11613-xxxxxxx-Bank1/ai7
FD-11614-xxxxxxx-Bank1/ai0 to
FD-11614-xxxxxxx-Bank1/ai7
FD-11614 16
FD-11614-xxxxxxx-Bank2/ai0 to
Number of
Device Naming
Channels
FD-11614-xxxxxxx-Bank2/ai7
FD-11634-xxxxxxx-Bank1/ai0 to
FD-11634-xxxxxxx-Bank1/ai3
FD-11634 8
FD-11634-xxxxxxx-Bank2/ai0 to
FD-11634-xxxxxxx-Bank2/ai3
FD-11637-xxxxxxx-Bank1/ai0 to
FD-11637-xxxxxxx-Bank1/ai3
FD-11637 8
FD-11637-xxxxxxx-Bank2/ai0 to
FD-11637-xxxxxxx-Bank2/ai3
The FD-11637 supports only the AI Strain Gage, AI Rosette Strain Gage, AI Force Bridge,
AI Pressure Bridge, AI Torque Bridge, AI Bridge (V/V), and AI Custom Voltage With
Excitation channel types.
When using the FD-11637 with an AI Custom Voltage With Excitation channel, you must
set the AI.Excit.UseForScaling attribute/property to true. This attribute/property
causes the channel to return ratiometric data: Vin/Vex.
The FD-11637 returns a voltage ratio rather than a voltage. Therefore, use the
AI.Bridge.InitialRatio attribute/property to specify the initial voltage ratio, or set the
AI.Bridge.InitialVoltage attribute/property to the ratio Vin/Vex returned by the device,
multiplied by Vex.
When the FD-11637 is in quarter bridge mode, you need to use the
AI.Bridge.NomResistance attribute/property to control whether the channel uses the
120 Ω range or the 350 Ω range.
The FD-11637 has internal half-bridge completion, and quarter-bridge completion for
120 Ω and 350 Ω strain gauges.
368 ni.com
NI-DAQmx Device Considerations
M Series
The section contains information about M Series Physical Channels, Bus-Powered M
Series Physical Channels, NI 6221 (37-Pin) Device Physical Channels, and NI 623x
Physical Channels.
Related concepts:
In physical channel names, Dev1 is the default device name for M Series devices. You
can change these names in MAX.
Related reference:
Analog Input
Depending on your M Series device, you can have from 16 to 80 analog input channels.
A 16-channel M Series device has physical channels ranging from Dev1/ai0 to
Dev1/ai15, a 32-channel device from Dev1/ai0 to Dev1/ai31, and so on. You
can configure the first eight channels as the positive channel of a differential pair. If N
is this channel, channel N + 8 is the negative input of the pair. For instance, if you
configure channel 1 in differential mode, the positive input is channel 1, and channel 9
is the negative input. For devices with more than 16 AI channels, 16-23, 32-39, 48-55,
and 64-71 are also positive channels of a differential pair.
Use only the physical channel name of the positive channel (not both) when creating a
differential channel.
Analog Output
An M Series device that supports two analog outputs has analog output physical
channels named Dev1/ao0 and Dev1/ao1.
An M Series device that supports four analog outputs has analog output physical
channels named Dev1/ao0, Dev1/ao1, Dev1/ao2, and Dev1/ao3.
All M Series devices have eight, 16, or 32 lines of digital input and output named
Dev1/port0/line0 through Dev1/port0/line7, Dev1/port0/line0
through Dev1/port0/line15, or Dev1/port0/line0 through Dev1/port0/
line31. These lines belong to a single port, and the physical channel Dev1/port0
refers to all eight or 32 lines at once. Port 0 can perform both hardware-timed and
static digital operations.
M Series devices have two more ports, port 1 and port 2. Port 1 has eight digital I/O
lines, Dev1/port1/line0 through Dev1/port1/line7. Port 2 has eight digital
I/O lines, Dev1/port2/line0 through Dev1/port2/line7. Port 1 and port 2 can
be used as static digital I/O lines or PFI lines, PFI 0..15. When any of PFI lines 0..15 is
used as a digital I/O signal, it uses the physical channel name shown in the following
table.
370 ni.com
NI-DAQmx Device Considerations
All M Series devices have two counter/timers referred to by the physical channel
names Dev1/ctr0 and Dev1/ctr1 . Unlike the other I/O types, these physical
channel names do not refer to terminals on the I/O connector but instead to circuits
within the device. There are four primary terminals associated with each counter.
These are the terminals used as the SOURCE, GATE, AUX, and OUT functions. NI-
DAQmx has default values for these terminals. For counter input tasks, if you know
whether your signal provides the SOURCE, AUX, or GATE function and wire your signal
to the default, you do not have to set the Input Terminal attribute/property.
In physical channel names, Dev1 is the default device name for M Series devices. You
can change these names in MAX.
Related concepts:
Related reference:
Analog Input
Depending on your M Series device, you can have from 16 to 32 analog input channels.
A 16-channel M Series device has physical channels ranging from Dev1/ai0 to
Dev1/ai15, a 32-channel device from Dev1/ai0 to Dev1/ai31, and so on. You
can configure the first eight channels as the positive channel of a differential pair. If N
is this channel, channel N + 8 is the negative input of the pair. For instance, if you
configure channel 1 in differential mode, the positive input is channel 1, and channel 9
is the negative input. For devices with more than 16 AI channels, 16-23, 32-39, 48-55,
and 64-71 are also positive channels of a differential pair.
Use only the physical channel name of the positive channel (not both) when creating a
differential channel.
Analog Output
An M Series device that supports two analog outputs has analog output physical
channels named Dev1/ao0 and Dev1/ao1.
An M Series device that supports four analog outputs has analog output physical
channels named Dev1/ao0, Dev1/ao1, Dev1/ao2, and Dev1/ao3.
Most bus-powered M Series devices have two ports, port 0 and port 1. For devices with
eight PFI lines, Port 0 has four digital input lines, Dev1/port0/line0 through
Dev1/port0/line3, and port 1 has four digital output lines, Dev1/port1/
line0 through Dev1/port1/line3. For devices with 16 PFI lines such as the NI
6218, Port 0 has eight digital input lines, Dev1/port0/line0 through Dev1/
372 ni.com
NI-DAQmx Device Considerations
The NI 6212 and NI 6216 have 16 lines of digital input and output named Dev1/
port0/line0 through Dev1/port0/line15. These lines belong to a single port,
and the physical channel Dev1/port0 refers to all 16 lines at once. Port 0 can
perform static digital I/O operations only.
The NI 6212 and NI 6216 have two more ports, port 1 and port 2. Port 1 has eight digital
I/O lines, Dev1/port1/line0 through Dev1/port1/line7. Port 2 has eight
digital I/O lines, Dev1/port2/line0 through Dev1/port2/line7. Port 1 and
port 2 can be used as static digital I/O lines or PFI lines, PFI 0..15. When any of PFI lines
0..15 is used as a digital I/O signal, it uses the physical channel name shown in the
following table.
374 ni.com
NI-DAQmx Device Considerations
All M Series devices have two counter/timers referred to by the physical channel
names Dev1/ctr0 and Dev1/ctr1. Unlike the other I/O types, these physical channel
names do not refer to terminals on the I/O connector but instead to circuits within the
device. There are four primary terminals associated with each counter. These are the
terminals used as the SOURCE, GATE, AUX, and OUT functions. NI-DAQmx has default
values for these terminals. For counter input tasks, if you know whether your signal
provides the SOURCE, AUX, or GATE function and wire your signal to the default, you
do not have to set the Input Terminal attribute/property.
In physical channel names, Dev1 is the default device name for NI 6221 (37-pin)
devices. You can change these names in MAX.
Analog Input
A 16-channel NI 6221 (37-pin) device has physical channels ranging from Dev1/ai0 to
Dev1/ai15. You can configure only channels 0 through 7 in differential mode. When
you configure a channel in differential mode, the channel is the positive input and
channel plus eight is the negative input. For instance, if you configure channel 1 in
differential mode, the positive input is channel 1, and channel 9 is the negative input.
Analog Output
NI 6221 (37-pin) devices have two analog outputs corresponding to two analog output
physical channels named Dev1/ao0 and Dev1/ao1.
NI 6221 (37-pin) devices have two ports, port 0 and port 1. Port 0 has two digital I/O
lines, Dev1/port0/line0 and Dev1/port0/line1. Port 1 has eight digital I/O
lines, Dev1/port1/line0 through Dev1/port1/line7. Port 1 can be used as
static digital I/O lines or input PFI lines, PFI 0..7. When any of PFI lines 0..7 is used as a
digital I/O signal, it uses the physical channel name shown in the following table.
376 ni.com
NI-DAQmx Device Considerations
NI 6221 (37-pin) devices have two counter/timers referred to by the physical channel
names Dev1/ctr0 and Dev1/ctr1. Unlike the other I/O types, these physical
channel names do not refer to terminals on the I/O connector but instead to circuits
within the device. There are four primary terminals associated with each counter.
These are the terminals used as the SOURCE, GATE, AUX, and OUT functions. NI-
DAQmx has default values for these terminals. For counter input tasks, if you know
whether your signal provides the SOURCE, AUX, or GATE function and wire your signal
to the default, you do not have to set the Input Terminal attribute/property.
In addition, the NI 6221 (37-pin) has one frequency generator. The output terminal of
the frequency generator is FREQOUT. The default for FREQOUT is PFI 5. When using
FREQOUT, you can continue to use both ctr0 and ctr1 to perform other operations.
In physical channel names, Dev1 is the default device name for NI 623x devices. You
can change these names in MAX.
Related reference:
Analog Input
Refer to the following table for the physical channel naming conventions for each 623x
device.
Differential RSE
Device
+ - + -
NI 6230 Dev1/ai n Dev1/ai (n+4) Dev1/ai0..Dev1/ai n, where n=0..3 AI Gnd
NI 6232 Dev1/ai n Dev1/ai (n+8) Dev1/ai0..Dev1/ai n, where n=0..7 AI Gnd
NI 6233 Dev1/ai n Dev1/ai (n+8) Dev1/ai0..Dev1/ai n, where n=0..7 AI Gnd
NI 6236 Dev1/ai n+ Dev1/ai n- Dev1/ai0..Dev1/ai n, where n=0..3 AI Gnd
NI 6238 Dev1/ai n+ Dev1/ai n- Dev1/ai0..Dev1/ai n, where n=0..7 AI Gnd
NI 6239 Dev1/ai n+ Dev1/ai n- Dev1/ai0..Dev1/ai n, where n=0..7 AI Gnd
Analog Output
NI 623x devices have two ports, port 0 and port 1. Port 0 has six digital input lines,
Dev1/port0/line0 through Dev1/port0/line5. Port 1 has four digital output
lines, Dev1/port1/line0 through Dev1/port1/line3. You can use port 0 as
static digital input lines or input PFI lines, PFI 0..5. You can use port 1 as static digital
output lines or output PFI lines, PFI 6..9. When any of PFI lines 0..9 is used as a digital
I/O signal, it uses the physical channel name shown in the following table.
378 ni.com
NI-DAQmx Device Considerations
NI 6230/6236 devices support tristating for port 1, the four digital output lines. The
power-on state default is to tristate port 1. Tristating is supported only for the entire
port at a time, not on a per-line basis. For instance, port 1 remains tristated as long as
no lines on port 1 are toggled to generate a value. After a line on port 1 is toggled, all
lines on the port are driven to logic high or logic low depending on what you choose.
The default is logic low.
NI 623x devices have two counter/timers referred to by the physical channel names
Dev1/ctr0 and Dev1/ctr1. Unlike the other I/O types, these physical channel
names do not refer to terminals on the I/O connector but instead to circuits within the
device. There are four primary terminals associated with each counter. These are the
terminals used as the SOURCE, GATE, AUX, and OUT functions. NI-DAQmx has default
values for these terminals. For counter input tasks, if you know whether your signal
provides the SOURCE, AUX, or GATE function and wire your signal to the default, you
do not have to set the Input Terminal attribute/property.
In addition, NI 623x devices have one frequency generator. The output terminal of the
frequency generator is FREQOUT. The default for FREQOUT is PFI 8. When using
FREQOUT, you can continue to use both ctr0 and ctr1 to perform other operations.
NI 623x devices use the same default terminals for common counter applications as
other 37-Pin DSUB devices.
Related reference:
Analog Input
myDAQ has two analog input channels, myDAQ1/ai0 and myDAQ1/ai1. These
channels support only the differential terminal configuration. You can configure the
first channel, myDAQ1/ai0, as the positive channel of a differential pair. Use only the
physical channel name of the positive channel (not both) when creating a differential
channel.
myDAQ also has a DMM physical channel, myDAQ1/dmm, available from the device.
On myDAQ, the DMM physical channels cannot be used in the same task with other
channels. There are also two audio input channels, myDAQ1/audioInputLeft and
myDAQ1/audioInputRight. These channels support only the referenced signal-ended
terminal configuration. Analog input tasks do not work simultaneously with audio
input.
Analog Output
myDAQ has two analog outputs with analog output physical channels named
myDAQ1/ao0 and myDAQ1/ao1. myDAQ also has two audio output channels,
myDAQ1/audioOutputLeft and myDAQ1/audioOutputRight. Analog output
tasks do not work simultaneously with audio out.
380 ni.com
NI-DAQmx Device Considerations
myDAQ has eight lines of digital input and output named myDAQ1/port0/line0
through myDAQ1/port0/line7. These lines belong to a single port, and the
physical channel myDAQ1/port0 refers to all 8 lines at once.
myDAQ has one counter/timer referred to by the physical channel name myDAQ1/
ctr0. Unlike the other I/O types, these physical channel names do not refer to
terminals on the I/O connector but instead to circuits within the device. There are four
primary terminals associated with each counter. These are the terminals used as the
SOURCE, GATE, AUX, and OUT functions. NI-DAQmx has default values for these
terminals. For counter input tasks, if you know whether your signal provides the
SOURCE, AUX, or GATE function and wire your signal to the default, you do not have to
set the Input Terminal attribute/property.
Related reference:
Analog Input
A 16-channel NI 6010 device has physical channels ranging from Dev1/ai0 to Dev1/
ai15. You can configure only channels 0 through 7 in differential mode. When you
configure a channel in differential mode, the channel is the positive input and channel
plus eight is the negative input. For instance, if you configure channel 1 in differential
mode, the positive input is channel 1, and channel 9 is the negative input.
Use only the physical channel name of the positive channel (not both) when creating a
differential channel.
Analog Output
NI 6010 devices have two analog outputs corresponding to two analog output physical
channels named Dev1/ao0 and Dev1/ao1.
NI 6010 devices have two ports, port 0 and port 1. Port 0 has six digital input lines,
Dev1/port0/line0 through Dev1/port0/line5. Port 1 has four digital output
lines, Dev1/port1/line0 through Dev1/port1/line3. You can use port 0 as
static digital input lines or input PFI lines, PFI 0..5. You can use port 1 as static digital
output lines or output PFI lines, PFI 6..9. When any of PFI lines 0..9 is used as a digital
I/O signal, it uses the physical channel name shown in the following table.
382 ni.com
NI-DAQmx Device Considerations
NI 6010 devices have two counter/timers referred to by the physical channel names
Dev1/ctr0 and Dev1/ctr1. Unlike the other I/O types, these physical channel
names do not refer to terminals on the I/O connector but instead to circuits within the
device. There are four primary terminals associated with each counter. These are the
terminals used as the SOURCE, GATE, AUX, and OUT functions. NI-DAQmx has default
values for these terminals. For counter input tasks, if you know whether your signal
provides the SOURCE, AUX, or GATE function and wire your signal to the default, you
do not have to set the Input Terminal attribute/property.
Related reference:
Analog Input
A 4-channel NI 6154 device has physical channels ranging from Dev1/ai0 to Dev1/
ai3.
Analog Output
NI 6154 devices have four analog outputs corresponding to four analog output
physical channels ranging from Dev1/ao0 to Dev1/ao3.
NI 6154 devices have two ports, port 0 and port 1. Port 0 has six digital input lines,
Dev1/port0/line0 through Dev1/port0/line5. Port 1 has four digital output
lines, Dev1/port1/line0 through Dev1/port1/line3. You can use port 0 as
static digital input lines or input PFI lines, PFI 0..5. You can use port 1 as static digital
output lines or output PFI lines, PFI 6..9. When any of PFI lines 0..9 is used as a digital
I/O signal, it uses the physical channel name shown in the following table.
NI 6154 devices have two counter/timers referred to by the physical channel names
Dev1/ctr0 and Dev1/ctr1. Unlike the other I/O types, these physical channel
names do not refer to terminals on the I/O connector but instead to circuits within the
device. There are four primary terminals associated with each counter. These are the
terminals used as the SOURCE, GATE, AUX, and OUT functions. NI-DAQmx has default
values for these terminals. For counter input tasks, if you know whether your signal
384 ni.com
NI-DAQmx Device Considerations
provides the SOURCE, AUX, or GATE function and wire your signal to the default, you
do not have to set the Input Terminal attribute/property.
In addition, the NI 6154 has one frequency generator. The output terminal of the
frequency generator is FREQOUT. The default for FREQOUT is PFI 8. When using
FREQOUT, you can continue to use both ctr0 and ctr1 to perform other operations.
The NI 6154 uses the same default terminals for common counter applications as other
37-Pin DSUB devices.
All NI 6533/6534 devices have 32 individually configurable lines of digital input and
output that are grouped into four 8-bit ports.
For Ports 0 through 3, you can configure a port width of eight, 16, or 32 bits. To
configure a 32-bit port, use the physical channel name Dev1/port0_32. To configure a
34. This physical channel name refers to all eight lines in a port at once.
16-bit port, use channel names that refer to all the lines in multiple consecutive ports:
Dev1/portP_N, where P is the port number of the lowest numbered port, and N is
the total number of lines. For instance, combining Port 2 and 3 into a 16-bit port, you
would specify Dev1/port2_16 as the physical channel.
NI 6533/6534 devices also have eight fixed-direction lines, grouped into two ports, that
use PFI lines. Port 4 is used for input operations; Port 5 is for output.
Port 4 and port 5 can be used as static digital I/O lines or PFI lines. When any of these
PFI lines is used as a digital I/O signal, it uses the physical channel name shown in the
following table.
The following table shows the channel names you can use to configure your task in NI-
DAQmx. Dev1 in physical channel names is the default device name for NI 6535/6536/
6537 devices. You can change the device name in MAX.
386 ni.com
NI-DAQmx Device Considerations
For Ports 0 through 3, you can configure a port width of 8, 16, or 32 bits. To configure a
32-bit port, use the physical channel name Dev1/port0_32. To configure a 16-bit
port, use channel names that refer to all the lines in multiple consecutive ports:
Dev1/portP_N, where P is 0 or 2 (whichever port number is lower) and N is the total
number of lines. For example, to combine Port 2 and 3 into a 16-bit port, specify
Dev1/port2_16 as the physical channel.
Using NI-DAQmx, you can configure each physical channel individually by inverting or
tristating the physical channel.
Related concepts:
PFI Lines
The NI 6535/6536/6537 has six PFI lines. These bidirectional digital lines allow you to
route synchronization and timing signals to and from the I/O connector. The following
table lists the PFI lines and their timing function.
You can use control lines as extra data lines while using the On Demand sample timing
type.
Related concepts:
Related reference:
Analog Input
NI ELVIS II Family devices have 16 analog input channels, ranging from Dev1/ai0 to
Dev1/ai15. You can configure the first eight channels as the positive channel of a
differential pair. If N is this channel, channel N + 8 is the negative input of the pair. For
instance, if you configure channel 1 in differential mode, the positive input is channel
1, and channel 9 is the negative input.
Use only the physical channel name of the positive channel (not both) when creating a
differential channel.
388 ni.com
NI-DAQmx Device Considerations
dmm. On the NI ELVIS II Family devices, the DMM and oscilloscope physical channels
cannot be used in the same task with other channels. However, scopeCh0 and
scopeCh1 can be used together.
Analog Output
NI ELVIS II Family devices have two analog outputs with analog output physical
channels named Dev1/ao0 and Dev1/ao1. NI ELVIS II Family devices also have two
function generator channels, Dev1/fgen and Dev1/fgenBNC, and two variable
power supply channels, Dev1/vpsPos (the positive variable power supply) and
Dev1/vpsNeg (the negative variable power supply). The function generator
channels, Dev1/fgen and Dev1/fgenBNC, use the FGEN Create Channel function/
VI. These function generator terminals also share the same resource.
NI ELVIS II Family devices have 24 lines of digital input and output named Dev1/
port0/line0 through Dev1/port0/line23. These lines belong to a single port,
and the physical channel Dev1/port0 refers to all 24 lines at once. Port 0 can
perform static digital operations.
NI ELVIS II Family devices have two more ports, port 1 and port 2. Port 1 has eight
digital I/O lines, Dev1/port1/line0 through Dev1/port1/line7. Port 2 has
seven digital I/O lines, Dev1/port2/line0 through Dev1/port2/line6. Port 1
and port 2 can be used as static digital I/O lines or PFI lines, PFI 0..14. When any of PFI
lines 0..14 is used as a digital I/O signal, it uses the physical channel name shown in
the following table.
NI ELVIS II Family devices have two counter/timers referred to by the physical channel
names Dev1/ctr0 and Dev1/ctr1. Unlike the other I/O types, these physical
channel names do not refer to terminals on the I/O connector but instead to circuits
within the device. There are four primary terminals associated with each counter.
These are the terminals used as the SOURCE, GATE, AUX, and OUT functions. NI-
DAQmx has default values for these terminals. For counter input tasks, if you know
whether your signal provides the SOURCE, AUX, or GATE function and wire your signal
to the default, you do not have to set the Input Terminal attribute/property.
390 ni.com
NI-DAQmx Device Considerations
Analog Input
Depending on your mioDAQ device, you can have from 16 to 32 analog input channels.
A 16-channel mioDAQ device has physical channels ranging from Dev1/ai0 to
Dev1/ai15, a 32-channel device from Dev1/ai0 to Dev1/ai31.
Use only the physical channel name of the positive channel (not both) when creating a
differential channel.
Analog Output
A mioDAQ device that supports two analog outputs has analog output physical
channels named Dev1/ao0 and Dev1/ao1.
A mioDAQ device that supports four analog outputs has analog output physical
channels named Dev1/ao0, Dev1/ao1, Dev1/ao2, and Dev1/ao3.
All mioDAQ devices have 16 lines of digital input and output named Dev1/port0/
line0 through Dev1/port0/line15. These lines belong to a single port, and the
physical channel Dev1/port0 refers to all 16 lines at once. Port 0 can perform both
hardware-timed and static digital operations.
The mioDAQ device digital lines can also be used as pins for Counter/Timer operations
and Trigger routing. Such pins are sometimes referred to as Programmable Function
Interface (PFI) pins. On the mioDAQ devices, the same physical pins can be used as
either digital I/O or PFI. The channel name mapping of PFI pins to digital I/O physical
channels is shown in the following table.
All mioDAQ devices have four counter/timers referred to by the physical channel
names Dev1/ctr0, Dev1/ctr1, Dev1/ctr2, and Dev1/ctr3. Unlike the other
I/O types, these physical channel names do not refer to terminals on the I/O connector
but instead to circuits within the device. There are five primary signals associated with
each counter: SOURCE, GATE, AUX, OUT, and sample clock. NI-DAQmx has default
terminals for these signals, except for the sample clock.
For counter input tasks, if you know whether your signal provides the SOURCE, AUX, or
GATE function and wire your signal to the default, you do not have to set the Input
Terminal attribute/property.
Related reference:
392 ni.com
NI-DAQmx Device Considerations
Analog Input
An S Series device has between two and eight analog input physical channels named
Dev1/ai0 to Dev1/ai7.
Analog Output
An S Series device that supports analog output has two analog output physical
channels named Dev1/ao0 and Dev1/ao1.
All S Series devices have eight lines of digital input and output named Dev1/port0/
line0 through Dev1/port0/line7. These lines belong to a single port, and the
physical channel Dev1/port0 refers to all eight lines at once.
All S Series devices have two counter/timers referred to by the physical channel names
Dev1/ctr0 and Dev1/ctr1. Unlike the other I/O types, these physical channel
names do not refer to terminals on the I/O connector but instead to circuits within the
device. There are three primary terminals associated with each counter. These are the
terminals used as the SOURCE, GATE and OUT functions. NI-DAQmx has default values
for these terminals. For counter input tasks, if you know whether your signal provides
the SOURCE or GATE function and wire your signal to the default, you do not have to
set the Input Terminal attribute/property.
Analog Input
An SCXI module usually has eight or 32 analog input channels; refer to your device
documentation to be sure. These physical channel names are of the form
SC1Mod<slot#>/ai0 to SC1Mod<slot#>/aiN, where <slot#> is the chassis slot
number of the module, and N equals the number of analog input channels on the
module minus one. For example, SCI1Mod1/ai31 is the highest numbered physical
channel for a module with 32 analog input channels.
An SCC module has either one or two physical channels named SCC1Mod<J
connector#>aiN, where <J connector#> is the number of the J connector where the
SCC module resides, and N is the channel number. SCC1 is the SCC connector block ID
(for example, SCC1Mod1/ai0).
NI PXI-4224 Only—You cannot scan channel ai7 and the CJC channel simultaneously in
a task, since the CJC channel is multiplexed to channel 7. However, when you make a
thermocouple measurement on ai0:7 with internal CJC, NI-DAQmx automatically reads
the CJC channel at the beginning of the measurement and then scans the rest of the
channels correctly.
Analog Output
An SCXI module has some number of output channels for voltage or current. These
physical channel names are of the form SC1Mod<slot#>/ao0 to
SC1Mod<slot#>/aoN, where <slot#> is the chassis slot number of the module, and N
equals the number of analog output channels on the module minus one. For example,
SC1Mod1/ao5 is the highest numbered physical channel on a module with six
channels.
394 ni.com
NI-DAQmx Device Considerations
An SCC module has either one digital input line or one digital output line with names
of the form SCC1Mod<J connector#>diN or SCC1Mod<J connector#>doN, where <J
connector#> is the number of the J connector where the SCC module resides, and N is
the channel number. SCC1 is the SCC connector block ID (for example, SCC1Mod1/
di0).
Analog Input
SC Express Devices have from four to 32 analog input channels. A 4-channel device has
physical channels ranging from PXISlot1/ai0 to PXISlot1/ai3, an 8-channel
device has physical channels ranging from PXISlot1/ai0 to PXISlot1/ai7, and
a 32-channel device has channels ranging from PXISlot1/ai0 to PXISlot1/
ai31.
You can use channels from multiple analog input SC Express devices in the same NI-
DAQmx task.
Analog Output
NI 4322 devices have eight analog output channels ranging from PXI1Slot1/ao0 to
PXISlot1/ao7. You can use channels from multiple analog output SC Express
devices in the same NI-DAQmx task.
The NI 4330 and 4331 devices support only the AI Strain Gage, AI Force Bridge, AI
Pressure Bridge, AI Torque Bridge, AI Bridge (V/V), and AI Custom Voltage With
Excitation channel types. The NI 4339 supports AI Voltage in addition to the previously
mentioned measurement types.
When using NI 4330 and 4331 devices with an AI Custom Voltage With Excitation
NI 4330 and 4331 devices return a voltage ratio rather than a voltage. Therefore, use
the AI.Bridge.InitialRatio attribute/property to specify the initial voltage ratio, or set
the AI.Bridge.InitialVoltage attribute/property to the ratio Vin/Vex returned by the
device, multiplied by Vex.
Analog Input
SensorDAQ has two AI physical channels, Dev1/ai0 and Dev1/ai1. When you
configure a channel in differential mode, Dev1/ai0 is the positive input and Dev1/
ai1 is the negative input.
Analog Output
Digital Input/Output
There is one counter channel referred to by the physical channel name Dev1/ctr0.
pfi0 is the terminal used for this physical channel.
396 ni.com
NI-DAQmx Device Considerations
TIO devices have up to eight counter/timers referred to by the physical channel names
Dev1/ctr0 to Dev1/ctr7. Unlike the other I/O types, these physical channel
names do not refer to terminals on the I/O connector but instead to circuits within the
device.
There are four primary terminals associated with each TIO counter. These are the
terminals used as the SOURCE, GATE, AUX, and OUT functions. NI-DAQmx has default
values for these terminals. For counter input tasks, if you know whether your signals
provide the SOURCE, GATE, or AUX functions and wire your signal to the default input,
you do not have to set the Input Terminal attribute/property.
Note The NI 6601 has only four counters (ctr0–ctr3). The entries in the
previous table for cntr4, cntr5, cntr6, and cntr7 do not apply for that device.
NI 661x devices have two ports, port 0 and port 1. Port 0 has 32 lines of digital input
and output named Dev1/port0/line0 through Dev1/port0/line31. Port 1
has 8 lines of digital input and output named Dev1/port1/line0 through Dev1/
port1/line7. The physical channel Dev1/port0 refers to all 32 lines at once, and the
physical channel Dev1/port1 refers to all 8 lines at once. Port 0 can perform hardware-
timed and static digital operations, while port 1 can perform only static digital
operations.
Port 0 and port 1 can be used as static PFI lines, PFI 0..39. When any of PFI lines 0..39 is
used as a digital I/O signal, it uses the physical channel name shown in the following
table.
398 ni.com
NI-DAQmx Device Considerations
Analog Input
The following table lists the number and naming of analog input physical channels for
Number of
Device Naming
Channels
NI USB-9211A, NI USB-9215A, NI USB-9219, NI USB-9229, cDAQ1Mod1/ai0 to
4
NI USB-9234, NI USB-9237, NI USB-9239 cDAQ1Mod1/ai3
cDAQ1Mod1/ai0 to
NI USB-9201, NI USB-9221 8
cDAQ1Mod1/ai7
cDAQ1Mod1/ai0 to
NI USB-9213 16
cDAQ1Mod1/ai15
The NI 9235, NI 9236, and NI 9237 support only the AI Strain Gage, AI Force Bridge, AI
Pressure Bridge, AI Torque Bridge, AI Bridge (V/V), and AI Custom Voltage With
Excitation channel types.
When using the NI USB-9219 or I USB-9237 with an AI Custom Voltage With Excitation
channel, you must set the AI.Excit.UseForScaling attribute/property to true. This
attribute/property causes the channel to return ratiometric data: Vin/Vex. The NI
USB-9219 and NI USB-9237 modules perform this division in hardware.
NI USB-9219 and NI USB-9237 devices return a voltage ratio rather than a voltage.
Therefore, use the AI.Bridge.InitialRatio attribute/property to specify the initial voltage
ratio, or set the AI.Bridge.InitialVoltage attribute/property to the ratio Vin/Vex returned
by the device, multiplied by Vex.
The NI USB-9219 does not have quarter bridge completion circuitry, which affects AI
Strain Gage Quarter Bridge I channels and AI Custom Voltage With Excitation Quarter
Bridge channels (but not AI Strain Gage Quarter Bridge II channels). With these
channels, the NI USB-9219 performs a 2-wire resistance measurement on the active
400 ni.com
NI-DAQmx Device Considerations
gage element, then NI-DAQmx uses software scaling to convert the resistance
measurement into a bridge ratio. For these channels, the polynomial coefficients
specified by the AI.DevScalingCoeff attribute/property convert unscaled data into
Ohms, not into V/V. Likewise, the AI.Rng.High/AI.Rng.Low attributes/properties should
be specified in units of Ohms, not V/V.
When the NI USB-9219 is in quarter bridge mode, you need to use the
AI.Bridge.NomResistance attribute/property to control whether the channel uses the
120 Ω range or the 350 Ω range.
Analog Output
The following table lists the number and naming of analog output physical channels
for USB DAQ devices.
When using the NI USB-9263, NI-USB 9264, or NI USB-9265, you can run only one type
of timing at a time. You can have one software-timed task per channel or one
hardware-timed task running on a device at one time, but you cannot have a
combination of timing on that device. For instance, you can run up to four software-
timed tasks on an the NI USB-9263 concurrently, but running one hardware-timed task
with one software-timed task generates an error. Additionally, the NI USB-9263, NI-USB
9264, and NI USB-9265 can run only one hardware-timed analog output task per
device at a given time.
Related reference:
Analog Input
Depending on your X Series device, you can have from eight to 208 analog input
channels. An 8-channel X Series device has physical channels ranging from Dev1/ai0
to Dev1/ai7, a 208-channel device from Dev1/ai0 to Dev1/ai207.
Use only the physical channel name of the positive channel (not both) when creating a
differential channel.
Analog Output
An X Series device that supports two analog outputs has analog output physical
channels named Dev1/ao0 and Dev1/ao1.
An X Series device that supports four analog outputs has analog output physical
channels named Dev1/ao0, Dev1/ao1, Dev1/ao2, and Dev1/ao3.
All X Series devices have eight or 32 lines of digital input and output named Dev1/
port0/line0 through Dev1/port0/line7 or Dev1/port0/line0 through
Dev1/port0/line31. These lines belong to a single port, and the physical channel
Dev1/port0 refers to all eight or 32 lines at once. Port 0 can perform both hardware-
timed and static digital operations.
X Series devices have two more ports, port 1 and port 2. Port 1 has eight digital I/O
lines, Dev1/port1/line0 through Dev1/port1/line7. Port 2 has eight digital
I/O lines, Dev1/port2/line0 through Dev1/port2/line7. Port 1 and port 2 can
be used as static digital I/O lines or PFI lines, PFI 0..15. When any of PFI lines 0..15 is
used as a digital I/O signal, it uses the physical channel name shown in the following
table.
402 ni.com
NI-DAQmx Device Considerations
All X Series devices have four counter/timers referred to by the physical channel names
Dev1/ctr0, Dev1/ctr1, Dev1/ctr2, and Dev1/ctr3. Unlike the other I/O
types, these physical channel names do not refer to terminals on the I/O connector but
instead to circuits within the device. There are five primary signals associated with
each counter: SOURCE, GATE, AUX, OUT, and sample clock. NI-DAQmx has default
terminals for these signals, except for the sample clock. For counter input tasks, if you
know whether your signal provides the SOURCE, AUX, or GATE function and wire your
signal to the default, you do not have to set the Input Terminal attribute/property.
Internal Channels
On some devices, you can either acquire a signal present on the I/O connector or
acquire a signal that is being generated from the internal multiplexer (an internal
channel). The internal channels available on the multiplexer are typically used for
calibration purposes, but you can also sample them as you would a physical signal
present on the I/O connector. To read from one of these internal channels, you must
use the internal channel as the device's physical channel (for example,
Dev1/_aignd_vs_aignd) when creating the virtual channel.
Related concepts:
404 ni.com
NI-DAQmx Device Considerations
Internal
Description
Channel Name
A referenced single-ended terminal with the positive and negative terminals
_aignd_vs_aignd
both connected to the ground reference for analog input.
A differential terminal with the positive terminal connected to the internal
_calref_vs_aignd calibration reference voltage and the negative terminal connected to the ground
reference for analog input.
A referenced single-ended terminal with the positive terminal connected to the
_cjtemp onboard temperature sensor and the negative terminal connected to the ground
reference for analog input. This channel is used for cold-junction compensation.
Internal
Description
Channel Name
A differential terminal with the positive and negative terminals both connected
_aignd_vs_aignd
to the ground reference for analog input.
A differential terminal with the positive terminal connected to the internal
_calref_vs_aignd calibration reference voltage and the negative terminal connected to the ground
reference for analog input.
A differential terminal with the positive terminal connected to the onboard
_cjtemp temperature sensor and the negative terminal connected to the ground
reference for analog input. This channel is used for cold-junction compensation.
Internal
Channel Description
Name
A differential terminal with the positive terminal connected to the onboard temperature
_cjtemp0 sensor and the negative terminal connected to the ground reference for analog input.
This channel is used for cold-junction compensation.
_cjtemp1 This channel is used for cold-junction compensation.
Internal
Description
Channel Name
A differential terminal with the positive and negative terminals both connected
_aignd_vs_aignd
to the ground reference for analog input.
A differential terminal with the positive terminal connected to the onboard
_cjtemp temperature sensor and the negative terminal connected to the ground
reference for analog input. This channel is used for cold-junction compensation.
Internal
Description
Channel Name
A differential terminal with the positive and negative terminals both connected
_aignd_vs_aignd
to the ground reference for analog input.
A differential terminal with the positive terminal connected to the onboard
_cjtemp0 temperature sensor and the negative terminal connected to the ground
reference for analog input. This channel is used for cold-junction compensation.
_cjtemp1 This channel is used for cold-junction compensation.
_cjtemp2 This channel is used for cold-junction compensation.
Internal Channels for the NI 9204, NI 9205, NI 9206, and TS-15100 Devices
406 ni.com
NI-DAQmx Device Considerations
Internal
Channel Description
Name
A differential terminal with the positive terminal connected to the onboard temperature
_cjtemp0 sensor and the negative terminal connected to the ground reference for analog input.
This channel is used for cold-junction compensation for analog input channel 0.
_cjtemp1 This channel is used for cold-junction compensation for analog input channel 1.
_cjtemp2 This channel is used for cold-junction compensation for analog input channel 2.
_cjtemp3 This channel is used for cold-junction compensation for analog input channel 3.
Internal
Channel Description
Name
This physical channel name does not refer to a terminal on the I/O connector but instead
to a circuit within the device. You must set the Input Terminal or Output Terminal
_ctr0
attributes/properties that are appropriate for the measurement/generation being
performed.
This physical channel name does not refer to a terminal on the I/O connector but instead
to a circuit within the device. You must set the Input Terminal or Output Terminal
_ctr1
attributes/properties that are appropriate for the measurement/generation being
performed.
This physical channel name does not refer to a terminal on the I/O connector but instead
to a circuit within the device. You must set the Input Terminal or Output Terminal
_ctr2
attributes/properties that are appropriate for the measurement/generation being
performed.
This physical channel name does not refer to a terminal on the I/O connector but instead
to a circuit within the device. You must set the Input Terminal or Output Terminal
_ctr3
attributes/properties that are appropriate for the measurement/generation being
performed.
This physical channel name does not refer to a terminal on the I/O connector but instead
_freqout to a circuit within the device. You must set the Output Terminal attribute/property that is
appropriate for the generation being performed.
• cDAQ-9132, 9133, 9134, 9135, 9136, 9137, 9171, 9174, 9178, 9179, 9181, 9184, 9185,
9188, 9188XT, 9189, and 9191
• cRIO-9040, 9041, 9042, 9043, 9045, 9046, 9047, 9048, 9049, 9053, 9054, 9055, 9056,
9057, and 9058
• TS-15000 and TS-15010
• sbRIO-9603, 9608, 9609, 9628, 9629, and 9638
On a DSA device, you can either acquire a signal present on the I/O connector, or you
408 ni.com
NI-DAQmx Device Considerations
can acquire a signal that is generated from the internal calibration multiplexer. The
channels available on this multiplexer are typically used for calibration purposes, but
you can also sample them as you would a physical signal present on the I/O connector.
To read from one of these internal channels, you must use one of the device's AI
physical channels (for instance, Dev1/ai0) when creating the channel to select which
ADC to use, then set the appropriate string value on the Input Source channel
attribute/property.
For all DSA devices, only one internal channel can be read at a time, although the same
internal channel can be read on multiple physical channels (with additional
restrictions for NI 447x devices). For example, you cannot simultaneously read the
internal 5 V reference on one physical channel and the analog ground on another
physical channel.
The NI 447x AI physical channels are grouped into pairs, for instance {ai0, ai1}, {ai2,
ai3}, and so on. NI 447x devices cannot read an internal channel on more than one
physical channel group, and when reading an internal channel, both physical channels
in the group are connected to the internal channel source. For example, if the Input
Source for channel ai0 is set to 5Vref_vs_aignd and the Input Source for channel ai1 is
left at the default value of _external_channel, ai1 still reads the internal channel
5Vref_vs_aignd since ai0 and ai1 are in the same physical channel group.
The following table is a list of internal physical channels for all E Series devices.
Different E Series devices have different subsets of channels. These channels are
typically for self-calibration, and you can sample them as you would a physical
channel present on the I/O connector.
410 ni.com
NI-DAQmx Device Considerations
412 ni.com
NI-DAQmx Device Considerations
414 ni.com
NI-DAQmx Device Considerations
The following table is a list of internal physical channels for the PXI-42xx devices. The
subset of channels present on your device depends on the specific E Series device
being used. These channels are typically for self-calibration, and you can sample them
as you would a physical channel present on the I/O connector
416 ni.com
NI-DAQmx Device Considerations
Internal
Channel Description
Name
A differential terminal with the positive terminal connected to the onboard temperature
_cjtemp sensor and the negative terminal connected to the ground reference for analog input.
This channel is used for cold-junction compensation.
On an S Series device, you can either acquire a signal present on the I/O connector, or
you can acquire a signal that is being generated from the internal calibration
multiplexer. The channels available on this multiplexer are typically used for
calibration purposes, but you can also sample them as you would a physical signal
present on the I/O connector. To read from one of these internal channels, you must
use one of the device's AI physical channels ( Dev1/ai0 through Dev1/ai7) when
creating the virtual channel. The physical channel specifies the ADC for the internal
channel. You can then set the appropriate string value on the Input Source channel
attribute/property.
Note All S Series devices must have the same Input Source setting on all
channels. The NI PCI-6110 and NI PCI-6111 devices cannot acquire from more
than one ADC at a time when using an internal channel.
418 ni.com
NI-DAQmx Device Considerations
◦ _external_channel
◦ _aignd_vs_aignd
◦ _calref_vs_aignd
◦ _calSrcHi_vs_aignd
◦ _aignd_vs_calSrcHi
◦ _calref_vs_calSrcHi
◦ _calSrcHi_vs_calSrcHi
◦ _aox_vs_aognd
Internal Channel
Description
Name
The differential terminal on the I/O connector that is typically used for
_external_channel
acquiring data.
A differential terminal with the positive and negative terminals both
_aignd_vs_aignd
connected to the ground reference for analog input.
A differential terminal with the positive and negative terminals both
_aognd_vs_aognd
connected to the ground reference for analog output.
A differential terminal with the positive terminal connected to the ground
_aognd_vs_aignd reference for analog output and the negative terminal connected to the
ground reference for analog input.
A differential terminal with the positive terminal connected to the analog
_aox_vs_aognd output physical channel, such as ao0, and the negative terminal
connected to the ground reference for analog output.
A differential terminal with the positive terminal connected to physical
_ao1_vs_aognd channel ao1 and the negative terminal connected to the ground reference
for analog output.
A differential terminal with the positive terminal connected to the internal
_calref_vs_calref calibration reference voltage and the negative terminal connected to the
internal calibration reference voltage.
A differential terminal with the positive terminal connected to the internal
_calref_vs_aignd calibration reference voltage and the negative terminal connected to the
ground reference for analog input.
A differential terminal with the positive terminal connected to physical
_ao0_vs_calref
channel ao0 and the negative terminal connected to the internal
Internal Channel
Description
Name
calibration reference voltage.
A differential terminal with the positive terminal connected to physical
_ao1_vs_calref channel ao1 and the negative terminal connected to the internal
calibration reference voltage.
A differential terminal with the positive terminal connected to the
_calSrcHi_vs_aignd calibration PWM and the negative terminal connected to the ground
reference for analog input.
A differential terminal with the positive terminal connected to the internal
_calref_vs_calSrcHi calibration reference voltage and the negative terminal connected to the
calibration PWM.
A differential terminal with the positive and negative terminals connected
_calSrcHi_vs_calSrcHi
to the calibration PWM.
A differential terminal with the positive terminal connected to the ground
_aignd_vs_calSrcHi reference for analog input and the negative terminal connected to the
calibration PWM.
A differential terminal with the positive terminal connected to the
calibration PWM and the negative terminal connected to the ground
_calSrcMid_vs_aignd
reference for analog input. _calSrcMid is the divided down version of
_calSrcHi.
A differential terminal with the positive and negative terminals connected
_calSrcMid_vs_calSrcHi to the calibration PWM. _calSrcMid is the divided down version of
_calSrcHi.
On an NI 4300 or NI 433x device, you can either acquire a signal present on the I/O
connector, or you can acquire an onboard signal, via an internal multiplexer. The
channels available on this multiplexer are typically used for calibration purposes, but
you can also sample them as you would a physical signal present on the I/O connector.
To read from one of these internal channels, you must use one of the device's AI
physical channels (Dev1/ai0 through Dev1/ai7) when creating the virtual channel. The
physical channel specifies the ADC for the internal channel. You can then set the
appropriate string value on the Input Source channel attribute/property.
420 ni.com
NI-DAQmx Device Considerations
On the NI 4353, you can acquire internal channels by specifying their names for the
physical channels input of the DAQmx Create Channel VI/function.
On the NI 4309, you can acquire internal channels by specifying their names for the
422 ni.com
NI-DAQmx Device Considerations
On the NI 4353, you can acquire internal channels by specifying their names for the
physical channels input of the DAQmx Create Channel VI/function.
Some SCXI modules also have internal channels. These are physical channels that are
not accessible from an I/O connector. To measure the signals present at these internal
physical channels, use them to create virtual channels. The SCXI-1100, SCXI-1102,
SCXI-1120, SCXI-1121, SCXI-1122, and SCXI-1125 modules have an internal physical
channel called _cjTemp channel. It is the cold-junction compensation channel for
measuring the temperature at the connector for thermocouples.
The SCXI-1520 has eight pairs of internal channels _pPos0 and _pNeg0 through _pPos7
and _pNeg7. These channels read back the excitation on the corresponding analog
input channel. The pPos half of the pair is the positive side of the excitation, and the
pNeg half is the negative side of the excitation. The real excitation value is the pPos
value minus the pNeg value.
The SCXI-1521/B has 24 voltage excitation internal channels _Vex0 through _Vex23.
These channels read back the excitation on the corresponding analog input channel.
In addition, the SCXI-1521/B has 24 pairs of internal channels _IexPos0 and _IexNeg0
through _IexPos23 and _IexNeg23. The current through a sensor connected to channel
x is the _IexPosx value minus the _IexNegx value.
The following table lists the internal channel for the USB-9211 device.
Internal
Channel Description
Name
A differential terminal with the positive terminal connected to the onboard temperature
_cjtemp sensor and the negative terminal connected to the ground reference for analog input.
This channel is used for cold-junction compensation.
The following table lists the internal channels for the USB-9219 device.
Internal
Channel Description
Name
A differential terminal with the positive terminal connected to the onboard temperature
_cjtemp0 sensor and the negative terminal connected to the ground reference for analog input.
This channel is used for cold-junction compensation for analog input channel 0.
_cjtemp1 This channel is used for cold-junction compensation for analog input channel 1.
_cjtemp2 This channel is used for cold-junction compensation for analog input channel 2.
_cjtemp3 This channel is used for cold-junction compensation for analog input channel 3.
On an X Series device, you can either acquire a signal present on the I/O connector, or
you can acquire a signal that is being generated from the internal calibration
multiplexer. The channels available on this multiplexer are typically used for
calibration purposes, but you can also sample them as you would a physical signal
424 ni.com
NI-DAQmx Device Considerations
present on the I/O connector. To read from one of these internal channels on a X Series
multiplexed sampling device, you must use the internal channel as the device's
physical channel (for example, Dev1/_aignd_vs_aignd) when creating the virtual
channel.
The following table describes all internal channels for X Series multiplexed sampling
devices.
Related concepts:
426 ni.com
NI-DAQmx Device Considerations
On an X Series device, you can either acquire a signal present on the I/O connector, or
you can acquire a signal that is being generated from the internal calibration
multiplexer. The channels available on this multiplexer are typically used for
calibration purposes, but you can also sample them as you would a physical signal
present on the I/O connector. To read from one of these internal channels on a X Series
simultaneous sampling device, you must use one of the device's AI physical channels
(for example, Dev1/ai0) when creating the virtual channel. The physical channel
specifies the ADC for the internal channel. You can then set the appropriate string
value on the Input Source channel attribute/property.
Note All X Series simultaneous sampling devices must have the same Input
Source setting on all channels.
Internal Channel
Description
Name
The differential terminal on the I/O connector that is typically used for
_external_channel
acquiring data.
A differential terminal with the positive terminal connected to physical
_ai0_vs_calSrcHi
channel ao0 and the negative terminal connected to the calibration PWM.
A differential terminal with the positive terminal connected to physical
_ai1_vs_calSrcHi
channel ao1 and the negative terminal connected to the calibration PWM
A differential terminal with the positive terminal connected to physical
_ai0_vs_aignd channel ai0 and the negative terminal connected to the ground reference
for analog input
A differential terminal with the positive terminal connected to the
_ai8_vs_aignd negative terminal of ai0 and the negative terminal connected to the
ground reference for analog input.
A differential terminal with the positive terminal connected to the
_ai8_vs_calSrcHi negative terminal of ai0 and the negative terminal connected to the
calibration PWM.
A single-ended terminal with the positive and negative terminals both
_aignd_vs_aignd
connected to the ground reference for analog input.
_aignd_vs_calSrcHi A differential terminal with the positive terminal connected to the ground
Internal Channel
Description
Name
reference for analog input and the negative terminal connected to the
calibration PWM.
A differential terminal with the positive terminal connected to physical
_ao0_vs_aognd channel ao0 and the negative terminal connected to the ground reference
for analog output.
A differential terminal with the positive terminal connected to physical
_ao0_vs_calSrcHi
channel ao0 and the negative terminal connected to the calibration PWM.
A differential terminal with the positive terminal connected to physical
_ao1_vs_aognd channel ao1 and the negative terminal connected to the ground reference
for analog output.
A differential terminal with the positive terminal connected to physical
_ao1_vs_calSrcHi
channel ao1 and the negative terminal connected to the calibration PWM.
A differential terminal with the positive terminal connected to physical
_ao2_vs_aognd channel ao2 and the negative terminal connected to the ground reference
for analog output.
A differential terminal with the positive terminal connected to physical
_ao3_vs_aognd channel ao3 and the negative terminal connected to the ground reference
for analog output.
A single-ended terminal with the positive terminal connected to the
_calref_vs_aignd internal calibration reference voltage and the negative terminal
connected to the ground reference for analog input.
A single-ended terminal with the positive terminal connected to the
_calSrcHi_vs_aignd calibration PWM and the negative terminal connected to the ground
reference for analog input.
A differential terminal with the positive and negative terminals connected
_calSrcHi_vs_calSrcHi
to the calibration PWM.
A differential terminal with the positive terminal connected to the internal
_calref_vs_calSrcHi calibration reference voltage and the negative terminal connected to the
calibration PWM.
A single-ended terminal with the positive terminal connected to the
calibration PWM and the negative terminal connected to the ground
_calSrcMid_vs_aignd
reference for analog input. _calSrcMid is the divided down version of
_calSrcHi.
_calSrcMid_vs_calSrcHi A differential terminal with the positive and negative terminals connected
428 ni.com
NI-DAQmx Device Considerations
Internal Channel
Description
Name
to the calibration PWM. _calSrcMid is the divided down version of _
calSrcHi .
A differential terminal with the positive terminal connected to the
_calSrcHi_vs_ai0 calibration PWM and the negative terminal connected to physical channel
ai0.
A differential terminal with the positive terminal connected to the
_calSrcHi_vs_ai8 calibration PWM and the negative terminal connected to physical channel
ai8.
Related concepts:
Default
Output
Device Default Input Terminal Configuration
Terminal
Configuration
Referenced
AO Series N/A
single-ended
DSA Pseudodifferential Differential
For devices with eight channels:
differential for the first four channels,
NI 60xx (E Series), NI 62xx (M Series), NI referenced single-ended for the next
63xx (X Series), NI ELVIS II, NI PCI-6010, NI four channels. For devices with 16 Referenced
USB-6001, NI USB-6002, NI USB-6003, NI channels or more: differential for eight single-ended
USB-6008, NI USB-6009, and NI TC01 channels followed by referenced single-
ended for eight channels. For instance,
channels 0-7, 16-23, and 32-39 are
Default
Output
Device Default Input Terminal Configuration
Terminal
Configuration
differential. Channels 8-15, 24-31, and
40-47 are referenced-single ended.
Differential for the analog input
Referenced
myDAQ channels, referenced single-ended for
single-ended
the audio input channels.
Referenced single-ended for scopeCh0
and scopeCh1. For other analog input
Referenced
NI ELVIS II+ channels: differential for channels 0-7,
single-ended
referenced single-ended for channels
8-15.
NI USB-6000 Referenced single-ended N/A
NI PXI-6132, NI PXI-6133, NI PXI-6143 Differential N/A
Referenced
NI PCI-6110, NI PCI-6111, NI 6115, NI 6120 Pseudodifferential
single-ended
NI PXI-42xx Differential N/A
Referenced
SCC Non-referenced single-ended
single-ended
Differential. On the NI 4353, the cold-
SC Express junction compensation channels are N/A
referenced single ended by default.
SCXI Differential Differential
NI 9201, NI USB-9201, NI 9203, NI 9208, NI
9217, NI 9221, NI USB-9221, NI 9253, NI Referenced single-ended N/A
[1]38
9775
Differential for voltage channels,
NI 9207 referenced single-ended for current N/A
channels
For devices with 16 channels or more:
NI 9204, NI 9205, NI 9206, NI 9209, and AI
differential for eight channels followed
0-15 on CompactRIO single-board N/A
by referenced single-ended for eight
controllers
channels. For instance, channels 0-7,
38. All listed devices have a fixed terminal configuration
430 ni.com
NI-DAQmx Device Considerations
Default
Output
Device Default Input Terminal Configuration
Terminal
Configuration
16-23, and 32-39 are differential.
Channels 8-15, 24-31, and 40-47 are
referenced-single ended.
FD-11601, FD-11603, FD-11605, FD-11613,
FD-11614, FD-11637, NI 9202, NI 9210, NI
9211, NI USB-9211A, NI 9212, NI 9213, NI
USB-9213, NI 9215, NI USB-9215A, NI
9216, NI 9218, NI 9219, NI USB-9219, NI
9220, NI 9224, NI 9225, NI 9226, NI 9227, Differential N/A
NI 9229, NI USB-9229, NI 9235, NI 9236, NI
9237, NI 9228, NI USB-9237, NI 9238, NI
9239, NI USB-9239, NI 9246, NI 9247, NI
9250, NI 9251, NI 9252 [1]
FD-11634, NI 9230, NI 9231, NI 9232, NI
Pseudodifferential N/A
9234, NI USB-9234
Nonreferenced single-ended for ai0,
NI 9242, NI 9244 ai1, and ai2. Referenced single-ended
for neutral.
NI 9262, NI 9263, NI USB-9263, NI 9264, NI
USB-9264, NI 9265, NI USB-9265, NI 9266, Referenced
N/A
and AO 0-3 on CompactRIO single-board single-ended
controllers
NI 9269 N/A Differential
AI +
Isolation
Barrier
Ground- +
Referenced Instrumentation
Vs Amplifier
Signal +
Source –
PGIA +
Digital
AI –
Measured Isolators
– Vm
Voltage
Common- –
Mode +
Noise and Vcm
Ground
Potential –
Input Multiplexers
AI GND
I/O Connector
M Series Isolated Device Configured in DIFF Mode
RSE and NRSE measurement systems are the same for isolated devices in that the
measurement is made with respect to a floating or isolated ground, AI GND. AI GND is
the floating reference for all RSE and NRSE channels. AI GND is isolated from earth
ground through an isolation barrier on the device.
Routing
This section contains information about routing for AO Series, E Series, S Series, and
TIO devices.
432 ni.com
NI-DAQmx Device Considerations
route signals across subsystems. They can also be used to route signals to/from
the I/O connector. However, when a counter is used as part of a route, you may not
be able to use the counter for other applications while the route remains reserved.
Most routes do not require an internal counter terminal, but many advanced
routes do. For example, if you want to use the signal present at PFI 4 on Dev1 as
the Start Trigger for an acquisition on Dev2, you simply need to specify /Dev1/
PFI4 as the source of the trigger. However, to make the route, the signal is
internally routed from /Dev1/PFI4 to /Dev1/Ctr0Source to a RTSI bus line
or PXI_Trig to Dev2/ai/StartTrigger. These terminals need not be explicitly
specified when programming the route. In this case, it is not obvious that a counter
terminal is used to make the route. Subsequent attempts at using the counter
while it is in use result in a routing reservation error. To see if the route you are
making uses counter resources, consult the table displayed under the Device
Routes tab in MAX.
• CtrnAux —PFI 37, PFI 33, PFI 29, PFI 25, PFI 21, PFI 17, PFI 13, PFI 9
• CtrnGate—PFI 38, PFI 34, PFI 30, PFI 26, PFI 22, PFI 18, PFI 14, PFI 10
• CtrnSource—PFI 39, PFI 35, PFI 31, PFI 27, PFI 23, PFI 19, PFI 15, PFI 11
For output, the same rules apply. Though the counter can output on any PFI line, there
are a subset of preferred PFIs that do not use internal resources to make the routes.
• CtrnInternalOutput—PFI 36, PFI 32, PFI 28, PFI 24, PFI 20, PFI 16, PFI 12, PFI 8
To see if the route you are making uses internal resources, consult the table displayed
under the Device Routes tab in MAX.
Switches
This section contains information specific to switch devices about API support and
434 ni.com
NI-DAQmx Device Considerations
Supported Topologies
Every switch module supports one or more topologies. Changing the topology alters
the functionality of the switch and, in many cases, changes the list of supported
channel names.
Special Considerations
Some switch modules have specific behaviors that you must consider when
developing applications. These are described in the following table.
Supported
Device Supported Topologies
APIs
• NI 2810A/B • Immediate
2810/1-Wire 4×43 Matrix
• Reed Matrix for NI SwitchBlock • Relay
• NI 2811A/B • Immediate
2811/1-Wire 8×21 Matrix
• Reed Matrix for NI SwitchBlock • Relay
• NI 2812A/B • Immediate
2812/1-Wire 16x9 Matrix
• Reed Matrix for NI SwitchBlock • Relay
• NI 2813A/B • Immediate
2813/2-Wire 4x21 Matrix
• Reed Matrix for NI SwitchBlock • Relay
• NI 2814A/B • Immediate
2814/2-Wire 8x9 Matrix
• Reed Matrix for NI SwitchBlock • Relay
• NI 2815A/B • Immediate
2815/1-Wire 4×86 Matrix
• Reed Matrix for NI SwitchBlock • Relay
• NI 2816A/B • Immediate
2816/1-Wire 8×46 Matrix
• Reed Matrix for NI SwitchBlock • Relay
• NI 2817A/B • Immediate
2817/1-Wire 16x22 Matrix
• Reed Matrix for NI SwitchBlock • Relay
436 ni.com
NI-DAQmx Device Considerations
Supported
Device Supported Topologies
APIs
• NI 2833
• Immediate
• Electromechanical Latching Matrix for NI 2833/2-Wire 4x71 Matrix
• Relay
SwitchBlock
• NI 2834
• Immediate
• Electromechanical Latching Matrix for NI 2834/2-Wire 8x34 Matrix
• Relay
SwitchBlock
• NI 2865
• Immediate
• Matrix with Analog Bus Protection for NI 2865/1-Wire 4x84 Matrix
• Relay
SwitchBlock
Supported
Device Supported Topologies
APIs
• Immediate
• PXI-2510
• Relay Independent
• 68-Channel 2A Fault Insertion Unit
• Scanning
• Immediate
• PXI-2512, PXIe-2512
• Relay Independent
• 7-Channel 10A Fault Insertion Unit
• Scanning
• Immediate
• PXI-2514, PXIe-2514
• Relay Independent
• 7-Channel 40A Fault Insertion Unit
• Scanning
• Immediate
• PXI-2520
• Relay • 80-SPST Switch
• 80-Channel SPST Relay Module
• Scanning
• Immediate
• PXI-2521
• Relay • 40-DPST Switch
• 40-Channel DPST Relay Module
• Scanning
• Immediate
• PXI-2522
• Relay 53-SPDT Switch
• 53-Channel SPDT Relay Module
• Scanning
438 ni.com
NI-DAQmx Device Considerations
Supported
Device Supported Topologies
APIs
• Relay
• 26-Channel DPDT Relay Module
• Scanning
Supported
Device Supported Topologies
APIs
• 2530/Independent
• Immediate
• PXI-2533
• Relay 2533/1-Wire 4x64 Matrix
• 256-Crosspoint SSR Matrix
• Scanning
• Immediate
• PXI-2534
• Relay 2534/1-Wire 8x32 Matrix
• 256-Crosspoint SSR Matrix
• Scanning
440 ni.com
NI-DAQmx Device Considerations
Supported
Device Supported Topologies
APIs
• Immediate
• PXI-2535
• Relay 2535/1-Wire 4x136 Matrix
• 544-Crosspoint FET Matrix
• Scanning
• Immediate
• PXI-2536
• Relay 2536/1-Wire 8x68 Matrix
• 544-Crosspoint FET Matrix
• Scanning
• Immediate
• PXI-2542, PXIe-2542 2542/Quad 2x1 Terminated
• Relay
• Quad Terminated 2x1 Multiplexer Mux
• Scanning
• Immediate
• PXI-2543, PXIe-2543
• Relay 2543/Dual 4x1 Terminated Mux
• Dual Terminated 4x1 Multiplexer
• Scanning
• Immediate
• NI PXI-2544, PXIe-2544
• Relay 2544/8x1 Terminated Mux
• Terminated 8x1 Multiplexer
• Scanning
• Immediate
• PXI-2545
• Relay 2545/4x1 Terminated Mux
• 2.7 GHz 4x1 Terminated 50 Ohm Multiplexer
• Scanning
• Immediate
• PXI-2546
• Relay 2546/Dual 4x1 Mux
• 2.7 GHz Dual 4x1 50 Ohm Multiplexer
• Scanning
Supported
Device Supported Topologies
APIs
• Relay
• 2.7 GHz 8x1 50 Ohm Multiplexer
• Scanning
• Digital
Output
• PXI-2548
• Immediate 2548/4-SPDT
• 2.7 GHz 4-SPDT 50 Ohm Relay Module
• Relay
• Scanning
• Digital
• PXI-2549 Output
• 2.7 GHz Terminated 2-SPDT 50 Ohm Relay • Immediate 2549/Terminated 2-SPDT
Module • Relay
• Scanning
• Immediate
• PXI-2554
• Relay 2554/4x1 Mux
• 2.5 GHz 4x1 75 Ohm Multiplexer
• Scanning
• Immediate
• PXI-2555
• Relay 2555/4x1 Terminated Mux
• 2.5 GHz 4x1 Terminated 75 Ohm Multiplexer
• Scanning
• Immediate
• PXI-2556
• Relay 2556/Dual 4x1 Mux
• 2.5 GHz Dual 4x1 75 Ohm Multiplexer
• Scanning
• Immediate
• PXI-2557
• Relay 2557/8x1 Mux
• 2.5 GHz 8x1 75 Ohm Multiplexer
• Scanning
442 ni.com
NI-DAQmx Device Considerations
Supported
Device Supported Topologies
APIs
• Digital
Output
• PXI-2558
• Immediate 2558/4-SPDT
• 2.5 GHz 4-SPDT 75 Ohm Relay Module
• Relay
• Scanning
• Digital
• PXI-2559 Output
• 2.5 GHz Terminated 2-SPDT 75 Ohm Relay • Immediate 2559/Terminated 2-SPDT
Module • Relay
• Scanning
• Digital
Output
• PXI-2564 • 2564/8-DPST
• Immediate
• 16-SPST Relay Module • 2564/16-SPST
• Relay
• Scanning
• Digital
Output
• PXI-2565
• Immediate 2565/16-SPST
• 16-SPST Power Relay Module
• Relay
• Scanning
• Digital
Output
• PXI-2566 • 2566/8-DPDT
• Immediate
• 16-SPDT Relay Module • 2566/16-SPDT
• Relay
• Scanning
• PXI-2567 • Digital
2567/Independent
• 64-Channel Relay Driver Module Output
Supported
Device Supported Topologies
APIs
• Immediate
• Relay
• Scanning
• Digital
Output
• PXI-2568 • 2568/15-DPST
• Immediate
• 31-Channel SPST Relay Module • 2568/31-SPST
• Relay
• Scanning
• Digital
Output
• PXI-2569 • 2569/50-DPST
• Immediate
• 100-Channel SPST Relay Module • 2569/100-SPST
• Relay
• Scanning
• Digital
Output
• PXI-2570 • 2570/20-DPDT
• Immediate
• 40-Channel SPDT Relay Module • 2570/40-SPDT
• Relay
• Scanning
• Digital
Output
• PXI-2571
• Immediate 2571/66-SPDT
• 66-Channel SPDT Relay Module
• Relay
• Scanning
444 ni.com
NI-DAQmx Device Considerations
Supported
Device Supported Topologies
APIs
• 2584/Independent
• Immediate
• PXI-2584 • 2584/1-Wire 12x1 Mux
• Relay
• High-Voltage Multiplexer • 2584/1-Wire Dual 6x1 Mux
• Scanning
• 2584/2-Wire 6x1 Mux
• Immediate
• PXI-2585
• Relay 2585/1-Wire 10x1 Mux
• 10-Channel Multiplexer
• Scanning
• Digital
Output
• PXI-2586 • 2586/5-DPST
• Immediate
• 10-Channel SPST Relay Module • 2586/10-SPST
• Relay
• Scanning
• Immediate
• PXI-2590
• Relay 2590/4x1 Mux
• 1.3 GHz 4x1 50 Ohm Multiplexer
• Scanning
• PXI-2591 • Immediate
2591/4x1 Mux
• 4 GHz 4x1 50 Ohm Multiplexer • Scanning
• 2593/16x1 Mux
• Immediate • 2593/Dual 8x1 Mux
• PXI-2593
• Relay • 2593/8x1 Terminated Mux
• 500 MHz Dual 8x1 50 Ohm Multiplexer
• Scanning • 2593/Dual 4x1 Terminated
Mux
Supported
Device Supported Topologies
APIs
• 2593/Independent
• Immediate
• PXI-2594
• Relay 2594/4x1 Mux
• 1x4 2.5 GHz Multiplexer
• Scanning
• Immediate
• PXI-2595
• Relay 2595/4x1 Mux
• 1x4 5.5 GHz Multiplexer
• Scanning
• Immediate
• PXI-2596
• Relay 2596/Dual 6x1 Mux
• Dual 1x6 26.5 GHz Multiplexer
• Scanning
• Immediate
• PXI-2597
• Relay 2597/6x1 Terminated Mux
• 1x6 26.5 GHz Terminated Multiplexer
• Scanning
• Immediate
• PXI-2598
• Relay 2598/Dual Transfer
• Dual 26.5 GHz Transfer Switch
• Scanning
• Immediate
• PXI-2599
• Relay 2599/2-SPDT
• Dual 26.5 GHz SPDT
• Scanning
• Immediate
• PXIe-2720
• Relay Independent
• Ten 8-Bit Channel Resistor Module
• Scanning
446 ni.com
NI-DAQmx Device Considerations
Supported
Device Supported Topologies
APIs
• Immediate
• PXIe-2722
• Relay Independent
• Five 16-Bit Channel Resistor Module
• Scanning
• Immediate
• PXIe-2725
• Relay Independent
• Eighteen 8-Bit Channel Resistor Module
• Scanning
• Immediate
• PXIe-2727
• Relay Independent
• Nine 16-bit Channel Resistor Module
• Scanning
• Immediate
• PXIe-2790
• Relay Independent
• RF Power Combiner and Switch
• Scanning
• Immediate
• PXIe-2796
• Relay 2796/Dual 6x1 Mux
• Dual 6x1 40 GHz Multiplexer
• Scanning
• Immediate
• PXIe-2797
• Relay 2797/6x1 Terminated Mux
• 6x1 40 GHz Terminated Multiplexer
• Scanning
• Immediate
• PXIe-2798
• Relay 2798/Dual Transfer
• Dual 40 GHz Transfer Switch
• Scanning
Supported
Device Supported Topologies
APIs
• Relay
• Dual 40 GHz SPDT
• Scanning
448 ni.com
NI-DAQmx Device Considerations
Supported
Device Supported Topologies
APIs
• Digital
• SCXI-1160 Output
1160/16-SPDT
• 16-SPDT General-Purpose Relay Module • Immediate
• Relay
• Digital
• SCXI-1161 Output
1161/8-SPDT
• 8-SPDT Power Relay Module • Immediate
• Relay
• Digital
• SCXI-1163R Output
1163R/Octal 4x1 Mux
• 32-Channel SSR • Immediate
• Relay
• Digital
Output
• SCXI-1166 • 1166/16-DPDT
• Immediate
• 32-SPDT Relay Module • 1166/32-SPDT
• Relay
• Scanning
Supported
Device Supported Topologies
APIs
• Digital
Output
• SCXI-1167
• Immediate 1167/Independent
• 64-Channel Relay Driver Module
• Relay
• Scanning
• Digital
Output
• SCXI-1169 • 1169/50-DPST
• Immediate
• 100-Channel SPST Relay Module • 1169/100-SPST
• Relay
• Scanning
• SCXI-1190
• Immediate 1190/Quad 4x1 Mux
• 1.3 GHz Quad 4x1 50 Ohm Multiplexer
• SCXI-1191
• Immediate 1191/Quad 4x1 Mux
• 4 GHz Quad 4x1 50 Ohm Multiplexer
• Digital
• SCXI-1192 Output
1192/8-SPDT
• 18 GHz 8-SPDT 50 Ohm Relay Module • Immediate
• Relay
• 1193/32x1 Mux
• Immediate
• SCXI-1193 • 1193/Dual 16x1 Mux
• Relay
• 500 MHz Quad 8x1 50 Ohm Multiplexer • 1193/Quad 8x1 Mux
• Scanning
• 1193/16x1 Terminated
450 ni.com
NI-DAQmx Device Considerations
Supported
Device Supported Topologies
APIs
Mux
• 1193/Dual 8x1 Terminated
Mux
• 1193/Quad 4x1
Terminated Mux
• 1193/Independent
• Immediate
• SCXI-1194
• Relay 1194/Quad 4x1 Mux
• Quad 1x4 2.5 GHz Multiplexer
• Scanning
• Immediate
• SCXI-1195
• Relay 1195/Quad 4x1 Mux
• Quad 1x4 5.5 GHz Multiplexer
• Scanning
SCXI-1127 Considerations
To route signals to the analog bus backplane, you must enable the switch device
property AutoConnAnlgBus. As a result, if you connect a channel (ch1) to the common
channel (com0), the signal is automatically routed from com0 to the analog bus (ab0).
If you have used immediate or relay operations to change relay states before starting a
scan, all of those relays are opened when the scan starts. After the scan completes, the
relays are returned to their previous state prior to the scan.
Early revisions of this hardware reserve the SCXI_TRIG1 line. If you place an older
revision of this hardware (earlier than revision E) into an SCXI chassis that also
contains an SCXI analog input module that performs track and hold (such as the
SCXI-1140 or SCXI-1520), you may get reservation errors when trying to use the SCXI
analog input module.
SCXI-1128 Considerations
To route signals to the analog bus backplane, you must enable the switch device
property AutoConnAnlgBus. As a result, if you connect a channel (ch1) to the common
channel (com0), the signal is automatically routed from com0 to the analog bus (ab0).
If you have used immediate or relay operations to change relay states before starting a
scan, all of those relays are opened when the scan starts. After the scan completes, the
relays are returned to their previous state prior to the scan.
Switching Capacity
Signal levels through a switch must account for the following specifications:
• Switching voltage
• Switching current
• Switching power
The following figure shows the valid operating range defined by these limits.
V
Maximum Switching Current
I
Related concepts:
• Switching Voltage
• Switching Current
452 ni.com
NI-DAQmx Device Considerations
• Switching Power
Switching Current
Switching current is the maximum rated current that can flow through the switch
as it makes or breaks a contact. Switching active currents higher than those specified
in the switch documentation can result in arcing that can damage the contacts of
electromechanical relays. A minimum current specification indicates the smallest
current that can reliably flow through the switch.
Switches can also have carry current. Carry current is the maximum rated current
that can pass through a closed switch, or the current that a switch can carry. Carry
current can be larger than switching current. However, since carry current can only
flow while the switch is closed, the current needs to be stopped while the switch
operates.
Switching Power
Switching power is the limit on the combined open-contact voltage and closed-
contact current of a signal in the switch.
Switching Voltage
Switching voltage refers to the maximum signal voltage that the switch module can
safely maintain. Switching voltage is defined from channel-to-ground and from
channel-to-channel. Channel-to-ground is the voltage potential between the signal
line and the grounded chassis. Channel-to-channel is the voltage potential between
any pair of signal lines within the module. This voltage includes voltages across open
relay contacts, as well as voltages between adjacent connection terminals.
Synchronization
This section contains information on synchronizing multiple devices.
Note If the devices are connected to the network through a real-time host,
you must discover these devices in MAX through the real-time host. Refer to
the MAX Help for NI-DAQmx for more information on how to discover devices
remotely.
Related information:
454 ni.com
NI-DAQmx Device Considerations
Related concepts:
Refer to the Device Routes tab in MAX to determine which PXI and RTSI lines can route
synchronization signals.
Note You cannot use a RTSI cable to connect multiple USB X Series devices.
Related concepts:
• Multidevice Tasks
• Start Trigger Synchronization
• Reference Clock Synchronization
• Sample Clock Synchronization
Refer to the Device Routes tab in MAX to determine which PXI and RTSI lines can route
synchronization signals.
Related concepts:
456 ni.com
NI-DAQmx Device Considerations
via the PXI_CLK10 signal. In a PXIe chassis, the PXIe_Clk100 signal is phase-locked to
the PXI_CLK10, so PXIe_Clk100 will also inherit the OCXO accuracy and stability.
Refer to the NI 6608 documentation for more information about the stability of the
OCXO.
Note For the automatic override to occur in NI-DAQmx, you must put the NI
6608 in slot 2 or the NI 6614 in the system timing slot. For more information
about configuring your PXI chassis, refer to the Measurement &
Automation Explorer Help for PXI.
• SC Express devices
• X Series devices
Related concepts:
Timing
This section contains information about timing for AO Series, C Series, DSA, E Series,
FieldDAQ, M Series USB, NI ELVIS II Family, S Series, and SC Express devices.
Static AO devices, such as the NI 6703 and NI 6704, do not have hardware timing and
have multiplexed output. Refer to your device documentation for specifics concerning
your device.
Related concepts:
You can use multiple analog input devices of different types in the same task, and NI-
DAQmx automatically synchronizes them.
NI-DAQmx supports:
458 ni.com
NI-DAQmx Device Considerations
• Only one analog input task at a time per NI cDAQ-9171, 9181, and 9191 chassis.
• Up to three analog input tasks at a time per cDAQ-9132, 9133, 9134, 9135, 9136,
9137, 9174, 9178, 9179, 9184, 9185, 9188, 9188XT, and 9189 chassis.
• Up to eight analog input tasks at a time per supported CompactRIO39 controller.
• One analog input task at a time per slot or onboard IO module, per CompactRIO
Single-Board40 controller.
Related concepts:
C Series Scanned devices, such as the NI 9201, NI 9204, NI 9205, and NI 9221, use
multiplexed sampling controlled by a per-slot AI Convert Clock.
If you have multiple devices in one task, their AI Convert Clocks run in parallel, which
may cause channels on multiple devices to be sampled at the same time. You can set
the AI Convert Rate and the Delay From Sample Clock differently on each device. When
setting AI Convert instances of the DAQmx Timing attribute/property, you must use the
ActiveDev attribute/property to specify the device to which you are referring. External
clocking of the AI Convert Clock is not supported.
Devices with a reference clock, such as the NI 9775, do not support on-demand timing.
These devices require hardware timing from a continuous clock. This clock
synchronizes the onboard oscillators using a phase-locked loop and serves as the
Sample Clock Timebase. When devices with reference clocks are in a task, you cannot
set an external SampClk.Src or SampClkTimebase. Similar to DSA devices, devices with
a reference clock do not support external sample clocks from arbitrary signal sources.
39. cRIO-9040, 9041, 9042, 9043, 9045, 9046, 9047, 9048, 9049, 9053, 9054, 9055, 9056, 9057, and 9058.
40. sbRIO-9603, 9608, 9609, 9628, 9629, and 9638
The default AI Convert Clock rate for the C Series Scanned devices uses 10 µs of
additional settling time between channels, compared to the fastest AI Convert Clock
rate for the device. When the Sample Clock rate is too high to allow for 10 µs of
additional settling time, the default AI Convert Clock rate uses as much settling time as
is allowed by the Sample Clock rate. If there are multiple C Series Scanned devices in
the same task, the same amount of additional settling time is used for all devices in
the task, even if their maximum AI Convert Clock rates differ.
In a CompactDAQ chassis with C Series Slow Sample devices, such as the NI 9211, if the
sampling rate of a hardware-timed acquisition exceeds the maximum sampling rate of
the module, the most recently acquired sample may be read multiple times and no
warning or error is generated. Exceeding the maximum sampling rate of other devices
in the same task generates warnings or errors. The first sample of a hardware-timed
acquisition with C Series Slow Sample devices is sampled when the task is committed.
Software-timed acquisitions with C Series Slow Sample devices always wait for a new
sample to be acquired.
The NI 9213/9214 maximum sample rate of 100 S/s applies to tasks with 13 or less
analog input channels per module. To determine the maximum sample rate for an NI
9213/9214, query the AI.MaxMultiChanRate attribute/property and divide that
returned value by the number of channels. For instance, if your analog input task uses
14 channels and AI.MaxMultiChanRate returns 1360.54, the maximum sample rate
would be 97.18 S/s. You can also query the maximum sample rate used in the task with
the SampClk.MaxRate attribute/property.
The maximum sampling rate of the NI 9215 depends on which channel(s) you are
acquiring from. For instance, a task acquiring from any combination of ai0, ai1, and ai2
460 ni.com
NI-DAQmx Device Considerations
can sample at faster rates than a task that includes ai3. The maximum sampling rates
are attainable only when sampling from ai0. If you have multiple NI 9215 devices in the
same task, they sample in parallel. For instance, multiple NI 9215 devices acquiring
from ai0 may be able to achieve a faster sampling rate than a single NI 9215 acquiring
from ai3.
The C Series Delta-Sigma devices, such as the NI 9225, NI 9227, NI 9235, and NI 9239,
have both a maximum and a minimum sampling rate. Refer to the specifications for
your device to determine the sampling rate range.
When you set a sampling rate for the NI 9230, NI 9231, NI 9232, or NI 9234, NI-DAQmx
selects the highest possible decimation rate. Refer to the operating instructions for
your device for more information about available sampling rates.
When C Series Delta Sigma devices, such as the NI 9230, NI 9231, NI 9232, NI 9234, NI
9250, or NI 9251 are in a task with a C Series device that has a different sample clock
timebase, NI-DAQmx always chooses the sample clock timebase with the highest
frequency. To override this selection, you can set the sample clock timebase in the
SampClk.Timebase.Src attribute/property.
All acquisitions and generations for C Series Delta-Sigma devices require hardware
timing from a steady clock. You cannot set the SampClk.Src attribute/property to an
external source when a C Series Delta-Sigma device is in the task. With C Series Delta-
Sigma devices, external clocking from arbitrary external signal sources such as
encoders and tachometers is not supported.
Only one hardware-timed analog output task per CompactDAQ chassis at a given time
is supported, but the number of concurrent software-timed analog output tasks is
limited only by the available channels. A single C Series analog output device cannot
be used for hardware-timed and software-timed tasks at the same time.
CompactRIO and Single-Board RIO controllers can support more than one hardware-
Related concepts:
Only one hardware-timed digital input task and one hardware-timed digital output
task per CompactDAQ chassis at a given time is supported, but the number of
concurrent software-timed digital I/O tasks is limited only by the available lines.
Refer to Digital I/O Considerations for C Series for more information about
hardware-timed digital input/output.
CompactRIO and Single-Board RIO controllers can support more than one hardware-
timed digital input task and one hardware-timed digital output task per controller.
Refer to CompactRIO Timing Engines.
Related concepts:
On the NI 9212, NI 9219, and NI USB-9219 you can also configure low-noise
measurements using the AI.ADCTimingMode attribute/property.
For all modules in the CompactRIO and Single-Board RIO controllers, the default value
in hardware-timed mode is automatically determined based on Sample Clock Rate.
462 ni.com
NI-DAQmx Device Considerations
For the NI 9207, NI 9208, NI 9209, NI 9212, NI 9213, NI USB-9213, NI 9214, NI 9216, NI
9217, NI 9219, and NI 9226 in CompactDAQ, the AI.ADCTimingMode attribute/property
is set to High Resolution by default. To increase the conversion rate, set this attribute/
property to High Speed.
For the NI USB-9219, this attribute/property is set to High Resolution by default in on-
demand mode, and the default value in hardware-timed mode is automatically
determined based on Sample Clock Rate. To increase power line noise rejection on the
NI 9212 and NI 9219, set this attribute/property to Best 60 Hz Rejection or Best 50 Hz
Rejection.
For the NI 9224 and NI 9228, this attribute/property is set by default to Automatic,
which causes the module to sample with the highest resolution timing mode that is
faster than the rate you specified.
For the NI 9775, this attribute/property has a default timing mode of Automatic. The
Automatic timing mode automatically configures the module to sample with the
highest resolution timing mode that is compatible with the user-specified rate. If the
AI.Lowpass.Enable attribute/property is set to false, the timing mode will remain in
High Speed regardless of the user-specified sample rate.
Slow sample modules are able to sample just fast enough to avoid returning repeated
data. If the user-specified rate is above the maximum rate, the module will enter
background convert and return repeated data. Slow sample modules on the
cDAQ-9171 and cDAQ-9191 chassis have a default timing mode of Automatic.
For the NI 9361, you can use multiple counter input devices in the same task, and NI-
DAQmx automatically synchronizes them. A single NI 9361 cannot be used for
hardware-timed and software-timed tasks at the same time. The CompactDAQ chassis
and CompactRIO controllers support up to four of the onboard chassis counters at a
time.
Related concepts:
Unlike some other DAQmx devices, DSA devices have both a maximum and a
minimum sampling rate. Refer to the specifications for your device to determine
the sampling rate range.
DSA devices do not support the on-demand timing type. All DSA acquisitions and
generations require hardware timing from a steady clock. The NI 4464, 4480, and
4481 are an exception. The NI 4464, 4480, and 4481 support on-demand timing
type.
DSA devices do not support external clocking from arbitrary external signal
sources such as encoders and tachometers. The PFI lines on DSA devices cannot
accept external clocks. You can program a DSA device to use an external clock only
when it is a slave in multi-device synchronized system. Refer to Synchronizing DSA
Devices for more details.
Related concepts:
• ai/ConvertClock
When using the ai/ConvertClock as the source of a route, one extra convert pulse is
464 ni.com
NI-DAQmx Device Considerations
generated than you might expect. For example, if you perform a finite acquisition
of 100 samples with four channels, you see 401 convert pulses instead of 400. This
extra convert pulse is necessary to set up the configuration memory in hardware
and occurs as the task transitions to the committed state.
• ao/SampleClock
When using an external ao/SampleClock for finite generations, you need to provide
one extra sample clock pulse than the number of samples in the generation for the
Wait Until Done function/VI to indicate the task is complete. For example, if you
want to generate 1000 samples using an external sample clock, you need to
provide 1001 sample clock pulses or the Wait Until Done function/VI never
indicates the task is done. All of the samples are generated, but the analog output
timing engine needs one additional clock pulse to indicate the generation is
complete. If you are trying to synchronize an analog output generation with
another acquisition or generation by sharing a common clock, use the ao/
SampleClock as the master clock or key off of the generation or acquisition
providing the master clock to determine when the generation is complete.
For the FD-11613 and FD-11614, if the sampling rate of a hardware-timed acquisition
exceeds the maximum sampling rate of the module, the most recently acquired
sample may be read multiple times and no warning or error is generated. Exceeding
the maximum sampling rate of other devices in the same task generates warnings or
errors. The first sample of a hardware-timed acquisition with these devices is sampled
when the task is committed. Software-timed acquisitions with these devices always
wait for a new sample to be acquired.
If you do not specify a sample clock timebase source or rate, NI-DAQmx auto-selects
the sample clock timebase with the closest sampling rate greater than or equal to your
requested sampling rate. If you do specify the sample clock timebase source or rate,
NI-DAQmx respects the setting and only chooses a sampling rate supported with that
sample clock timebase.
On-Demand Timing
The FD-11601, FD-11603, FD-11605, FD-11634, and FD-11637 do not support the on-
demand timing type.
466 ni.com
NI-DAQmx Device Considerations
Related concepts:
Note Not all S Series devices have pipelined ADCs. Refer to the specifications
for your device to determine if your device contains pipelined ADCs.
Many S Series devices have pipelined ADCs with an intrinsic pipeline depth. This
pipelining allows the device to sample at higher rates, but it also has other
consequences on the timing requirements for the device. S Series devices, except for
the NI 6143, do not support AI hardware-timed single-point sample mode. Since the
data needs to travel through the pipeline before it can be read, the data being read is
always pipeline-depth points old. For instance, if the pipeline depth for a device is
three, the first sample is acquired on clock tick 1, but it is not available for reading until
clock tick 4. Following this logic, you must supply pipeline-depth extra clock pulses for
a finite acquisition to flush the pipeline. Continuing with the previous example, if the
pipeline depth is three and you want to acquire 1000 samples, you need to generate
1003 sample clock pulses. If you are using the onboard sample clock, NI-DAQmx
automatically generates the appropriate number of sample clock pulses. However,
when using an external sample clock or when synchronizing devices, you need to
ensure you supply the appropriate number of sample clock pulses.
There is also a finite amount of time a sample can be held in the pipeline before it
starts to degrade and lose measurement accuracy. This time limit imposes a minimum
sampling rate that must be met to achieve the measurement accuracy specified for the
device. Although you can sample slower than this minimum recommend sampling
rate, the accuracy specifications for the device are not guaranteed. Refer to the
specifications for your device to determine the recommended minimum sampling
rate.
468 ni.com
NI-DAQmx Device Considerations
to remain asserted and three sample clocks to be detected before the data in the
pipeline deteriorates past specifications. In the case of a Pause Trigger, NI-DAQmx does
not detect or throw out any invalid samples. You must detect this situation and deal
with any invalid samples as appropriate.
Analog Output
When using an external ao/SampleClock for finite generations, you need to provide
one more sample clock pulse than the number of samples in the generation for the
Wait Until Done function/VI to indicate the task is complete. For example, if you want
to generate 1000 samples using an external sample clock, you need to provide 1001
sample clock pulses, or the Wait Until Done function/VI never indicates the task is
done. All of the samples are generated, but the analog output timing engine needs one
additional clock pulse to indicate the generation is complete. If you are trying to
synchronize an analog output generation with another acquisition or generation by
sharing a common clock, use the ao/SampleClock as the master clock, or key off of the
generation or acquisition providing the master clock to determine when the
generation is complete.
Note For S Series devices that use the STC2 timing chip, such as the NI 6154,
you do not need to apply an extra sample clock pulse to complete the task.
NI 433x devices and the NI 4340 have both a maximum and a minimum sampling rate.
Refer to the specifications for your device to determine the sampling rate range.
The NI 4309, NI 4353, and NI 4357 use multiplexed sampling with multiple ADCs. The
maximum sampling rate of a NI 4309, NI 4353, or NI 4357 depends on how many
channels you are acquiring, and which channels you are acquiring from. Setting the
AI.ADCTimingMode and AI.ADCCustomTimingMode properties/attributes for the NI
NI 433x devices do not support external clocking from arbitrary external signal sources
such as encoders and tachometers. You can program a NI 433x device to use an
external timebase only when it is a slave in multi-device synchronized system. Refer to
Synchronizing X Series, M Series, and SC Express Devices for more details.
Note
470 ni.com
NI-DAQmx Device Considerations
your device, the number of channels in the task, and whether your device uses
simultaneous sampling (one ADC per channel) or multiplexed sampling (one ADC for
all analog input channels). To find the maximum sample rate for your device, use the
Sample Clock:Maximum Sample Rate attribute/property.
Each multiplexed C Series device has a separate convert clock. The convert clock
timing is based on the number of channels for that device in the task, not the total
number of channels in the task. You can set the convert clock rate on a per-device
basis using the Active Devices and AI Convert Rate attributes/properties on the DAQmx
Timing property node. The following figure depicts a ten-channel analog input task on
two simultaneous sampling C Series devices and two multiplexed sampling C Series
devices with different AI convert rates:
41. cDAQ-9171, 9174, 9178, 9179, 9181, 9184, 9185, 9188, 9188XT, 9189, and 9191
42. TS-15000 and TS-15010
43. cDAQ-9132, 9133, 9134, 9135, 9136, and 9137
44. cRIO-9040, 9041, 9042, 9043, 9045, 9046, 9047, 9048, 9049, 9053, 9054, 9055, 9056, 9057, and 9058
45. sbRIO-9603, 9608, 9609, 9628, 9629, and 9638
Sample Clock
Mod1/Ch1 Mod1/Ch1
Mod1/Ch2 Mod1/Ch2
Mod2/Ch1 Mod2/Ch1
Mod2/Ch2 Mod2/Ch2
Mod3/Ch2
Mod3/Ch3
Mod3/Ch1
Mod3/Ch2
Mod3/Ch3
Mod4 Convert Clock
Mod4/Ch1
Mod4/Ch2
Mod4/Ch3
Mod4/Ch1
Mod4/Ch2
Mod4/Ch3
Related concepts:
Timestamps
Network-synchronized devices support four timestamp resources that allow for
timestamping the first sample clock, start trigger, arm start trigger (counters only) or
reference trigger.
The timestamp resources will be used to provide an accurate t0 for waveform reads
with timed acquisitions that will correspond to the first sample clock for Analog Input
and Digital Input tasks. Therefore, the first sample timestamp is enabled by default for
these types of tasks.
472 ni.com
NI-DAQmx Device Considerations
time scale (for example, related to a point in the distant past, such as the Linux
1970 epoch), it removes other sources of skew related to Windows system time or
other systems that are not network-synchronized to the same 802.1AS subnet. In
that way, it provides best time trigger and timestamp accuracy but may reduce
usability if it is not correlated to a recognizable global time. I/O Device Time also
has the advantage of being monotonically increasing, so time triggers and
timestamps spread across multiple devices or tasks accurately maintain their
offsets from each other.
• Host Time
The timescale your PC or NI Linux Real-Time controller uses. In cases where the NI
Linux Real-Time controller is the Grand Master of your 802.1AS subnet, Host Time
and I/O Device Time are the same. However, Host Time is typically synchronized to
a local Real Time Clock or a Network Time Protocol server, and it is usually
traceable to global time. Using Host Time is more intuitive because triggers and
timestamps on the chassis are specified in times that are easily correlated to your
local system time. However, this usability comes at the cost of reduced relative
accuracy between time triggers and timestamps that are spread across multiple
devices or tasks, because using the calculated offset between the two timescales is
not as accurate as using I/O Device Time directly. To help account for this loss of
accuracy in a specific and common use-case, NI-DAQmx guarantees that two
events that are scheduled for the same Host Time are guaranteed to start at the
same I/O Device Time, preserving precise synchronization between chassis.
Related concepts:
The Wait for Valid Timestamp VI waits until the selected timestamp is available and a
value is returned. Possible timestamps are Start Trigger, Reference Trigger, Arm Start
Trigger and First Sample.
The first sample timestamp corresponds to the time of the first sample clock pulse in a
task.
The First Sample Timestamp attribute/property can only be enabled for hardware
timed tasks, and is enabled by default for Analog Input and Digital Input tasks. For
Digital Input tasks as well as C Series Slow Sample and Delta-Sigma Devices, the first
sample timestamp will be the t0 for waveform reads. For C Series Scanned Devices, the
t0 for waveform reads will be the first sample timestamp plus an additional delay to
more accurately reflect the time at which the sample was taken.
Related concepts:
474 ni.com
NI-DAQmx Device Considerations
Related concepts:
• NI 4302, 4303, 4304, 4305, 4339, 4340, 4463, 4464, 4480, and 4481
• NI 6533 and 6534
• cDAQ-9132, 9133, 9134, 9135, 9136, 9137, 9174, 9178, 9179, 9184, 9185, 9188,
9188XT, and 9189
• TS-15000 and TS-15010
• cRIO-9040, 9041, 9042, 9043, 9045, 9046, 9047, 9048, 9049, 9053, 9054, 9055, 9056,
9057, and 9058
• sbRIO-9603, 9608, 9609, 9628, 9629, and 9638
Related concepts:
• Timing Engines
• NI 4302, 4303, 4304, 4305 Timing Engines
• NI 4339, 4463, 4464 Timing Engines
• NI 4340 Timing Engines
• NI 4480, 4481 Timing Engines
Each timing engine can use any AI channel and can control up to eight channels. Each
channel can only be used once across all timing engines.
Note You must reserve the task before querying the timing engine unless
you explicitly specified the timing engine.
If a task has more than eight channels, NI-DAQmx automatically uses multiple timing
engines, synchronizing and sharing settings across all timing engines. All timing
engines in a single task must share the same settings.
For example, if a task has 10 channels, NI-DAQmx uses two timing engines, which
476 ni.com
NI-DAQmx Device Considerations
leaves two timing engines for other tasks. If the task has 32 channels, all four timing
engines are used.
Each channel's digital filter settings can be configured independently if the channel is
used in a task in buffered sample mode. For tasks using HWTSP sample mode, all
channels in the task must have the same digital filter configuration.
Related concepts:
• Digital AI Filtering
Note You must reserve the task before querying the timing engine unless
you explicitly specified the timing engine.
On the NI 4339, 4463, and 4464, the Sample Clock and Sample Clock Timebase, as well
as the Start and Reference triggers, exist on each timing engine. Therefore, the names
of the output terminals for those signals include the associated timing engine. If NI-
DAQmx automatically selects the timing engine for a task, the timing engine, thus the
output terminals for those signals, are undefined until you reserve the task. To
reference one of those terminals, such as to share a Start Trigger across multiple tasks,
use the Terminal attribute/property associated with each signal to determine the
terminal name.
Note You must reserve the task before querying the terminal name unless
you explicitly specify the timing engine.
Note The NI 4339 only supports running a single buffered task and a single
hardware-timed single-point task simultaneously.
Related concepts:
• Timing Engines
• Reserved State
• Syntax for Terminal Names
• Terminals
Each timing engine can use any AI channel and can control up to four channels. Each
channel can only be used once across all timing engines.
Note You must reserve the task before querying the timing engine unless
you explicitly specified the timing engine.
478 ni.com
NI-DAQmx Device Considerations
Note You must reserve the task before querying the timing engine unless
you explicitly specified the timing engine.
The Sample Clock and Sample Clock Timebase, as well as the Start and Reference
triggers, exist on each timing engine. Therefore, the names of the output terminals for
those signals include the associated timing engine. If NI-DAQmx automatically selects
the timing engine for a task, the timing engine, thus the output terminals for those
signals, are undefined until you reserve the task. To reference one of those terminals,
such as to share a Start Trigger across multiple tasks, use the Terminal attribute/
property associated with each signal to determine the terminal name.
Note You must reserve the task before querying the terminal name unless
you explicitly specify the timing engine.
Note You must reserve the task before querying the timing engine unless
you explicitly specified the timing engine.
On the NI 4480 and 4481, the Sample Clock and Sample Clock Timebase, as well as the
480 ni.com
NI-DAQmx Device Considerations
Start and Reference triggers, exist on each timing engine. Therefore, the names of the
output terminals for those signals include the associated timing engine. If NI-DAQmx
automatically selects the timing engine for a task, the timing engine, thus the output
terminals for those signals, are undefined until you reserve the task. To reference one
of those terminals, such as to share a Start Trigger across multiple tasks, use the
Terminal attribute/property associated with each signal to determine the terminal
name.
Note You must reserve the task before querying the terminal name unless
you explicitly specify the timing engine.
By default, NI-DAQmx assigns a timing engine based on the ports used in the task.
Refer to device documentation to determine which ports use which timing engine. Use
the DAQmx Timing property/attribute SampTimingEngine to specify the timing engine
to use or to determine which timing engine NI-DAQmx automatically selected.
On NI 6533 and 6534 devices, the Sample Clock and Sample Clock Timebase, as well as
the Start and Reference triggers, exist on each timing engine. Therefore, the names of
the output terminals for those signals include the associated timing engine.
Related concepts:
• Timing Engines
• Handshake Timing Defaults
• Burst Handshaking Timing Defaults for NI 653x Devices
• Syntax for Terminal Names
• Terminals
The cDAQ-91xx46[1] or TestScale47[2] chassis provide three timing engines for analog
input. Multiple timing engines allow those chassis to run up to three analog input
tasks simultaneously, each using independent timing and triggering configurations.
Note You must reserve the task before querying the timing engine unless
you explicitly specified the timing engine.
46. cDAQ-9132, 9133, 9134, 9135, 9136, 9137, 9174, 9178, 9179, 9184, 9185, 9188, 9188XT, and 9189
47. TS-15000 and TS-15010
482 ni.com
NI-DAQmx Device Considerations
task, the timing engine, thus the output terminals for those signals, are undefined
until you reserve the task. To reference one of those terminals, such as to share a Start
Trigger across multiple tasks, use the Terminal attribute/property associated with each
signal to determine the terminal name.
Note You must reserve the task before querying the terminal name unless
you explicitly specify the timing engine.
Related concepts:
• Timing Engines
• Reserved State
• Syntax for Terminal Names
• Terminals
The eight output timing engines are shared between analog output and digital output.
Multiple output timing engines allow those chassis to run up to eight analog output or
digital output tasks simultaneously, each using independent timing and triggering
configurations.
selected.
Note You must reserve the task before querying the timing engine unless
you explicitly specified the timing engine.
On the CompactRIO and CompactRIO Single-Board controllers, the Sample Clock and
Sample Clock Timebase, as well as the Start, Reference (for analog input, digital input,
and NI 9361 tasks only), and Pause triggers, exist on each timing engine. Therefore, the
names of the output terminals for those signals include the associated timing engine.
If NI-DAQmx automatically selects the timing engine for a task, the timing engine, thus
the output terminals for those signals, are undefined until you reserve the task. To
reference one of those terminals, such as to share a Start Trigger across multiple tasks,
use the Terminal attribute/property associated with each signal to determine the
terminal name.
Note You must reserve the task before querying the terminal name unless
you explicitly specify the timing engine.
484 ni.com
NI-DAQmx Device Considerations
DSA
This section contains information specific to DSA devices.
Likewise, interpolators and delta-sigma DACs provide digital filtering on analog output
signals to eliminate out-of-band imaging and quantization noise. As with analog input,
the digital output filtering results in a deterministic delay through the DAC.
You can safely ignore the effects of the digital filter delay for most input-only or output-
only applications. The filter delay can become significant for applications requiring
input and output synchronization such as stimulus-response testing and tight loop
control. For DSA and C Series devices, if your application employs external digital
triggering, the acquisition returns data that occurred in time before the trigger event.
The number of samples preceding the trigger matches the ADC filter delay. Refer to
your device documentation for more details on the ADC and DAC digital filter delays.
At very low sample rates, the anti-aliasing filters for AI channels on DSA devices, C
Series Delta-Sigma devices, NI 4330, and NI 4331 devices may not completely reject all
out-of-band signals. This is primarily due to the internal digital filter of the delta-sigma
ADC, which cannot suppress signals with frequencies near the multiples of the
oversample rate (sampling rate multiplied by oversample factor). These devices also
employ fixed cutoff analog lowpass anti-aliasing filters, but at low sample rates, some
multiples of the oversample rate can fall below the cutoff frequency of the analog anti-
aliasing filter.
For example, for a device using ADCs with an oversample factor of 128X and sampling
at a rate of 1 kS/s, the oversample rate is 128 kHz. Some multiples of that oversample
rate fall below the cutoff of the analog anti-aliasing filter. If the signal to be digitized
contains energy near these frequencies, aliasing can result.
One way to prevent aliasing is to raise the sample rate so that the first 128X multiple of
the sample rate falls above the cutoff of the analog anti-aliasing filter. For example, a
sample rate of 25.6 kS/s is not subject to aliasing because the first 128X multiple (3.2
MHz) is well above the cutoff frequency of the analog anti-aliasing filter. Some DSA
devices support enhanced alias rejection, which automatically handles alias rejection
at low sample rates. Refer to the device documentation for the specifics of your device.
Related concepts:
To avoid aliasing at low sample rates, some DSA devices support enhanced alias
rejection. With enhanced alias rejection enabled, the device clocks the ADCs at a
multiple of the user-specified sample rate. This results in an improvement in low-
frequency alias rejection. With enhanced alias rejection enabled, you do not need to
scale the desired sample rate, and you do not need to programmatically decimate data
the device returns.
Note The original versions of NI 447x devices do not support Enhanced Alias
Rejection. Refer to Dynamic Signal Acquisition Help for more
information.
Related concepts:
486 ni.com
NI-DAQmx Device Considerations
Synchronization Issues
Channel Order
On DSA devices, you must list channels in a task in ascending order. For example, if
your task includes ai0 and ai1, you must arrange the channel list such that ai0
precedes ai1.
This constraint applies to virtual channels as well as physical channels. For example, if
you include a virtual channel for ai0 named vibration and a virtual channel for ai1
named proxProbe, vibration must precede proxProbe in the channel list.
Related concepts:
On NI 4302, 4303, 4304, 4305, 433x, 4340, 4464, 4466, 4467, 4480, and 4481 devices, the
AI.RemoveFilterDelay attribute/property is enabled by default. On the NI 4330/4331,
filter delay removal is always enabled.
On NI 4302, 4303, 4304, 4305, 4339, 4340, 4464, 4466, 4467, 4480, and 4481 devices,
you can use the AI.FilterDelayAdjustment attribute/property to further adjust which
samples to discard. This adjustment is relative to the amount of filter delay in the
device, which is indicated by the AI.FilterDelay attribute/property.
Related concepts:
For analog input operations, a negative gain value implies attenuation of the signal
before the ADC, increasing the range beyond ±10 V. Thus, an input gain setting of –10
dB corresponds to an input range of ±31.6 V. On analog output, a negative gain value
488 ni.com
NI-DAQmx Device Considerations
implies attenuation following the DAC. This decreases the output range. For instance,
an output gain setting of –20 dB corresponds to an output range of ±1 V.
NI-DAQmx has three separate attribute/property sets you can use to control the
hardware gain setting. Each has a different priority. If you write values to two or more
of these attributes/properties that correspond to different hardware gain settings, the
one with the highest priority will determine the hardware behavior.
50. Devices are listed as examples and are not intended to be a comprehensive list. Refer to the device
documentation for the IEPE specifications of your device.
per-channel basis.
To enable the IEPE current source on your device, use the Channel attribute/property
AI.Excit.Val to specify a current in amperes. Some devices allow multiple excitation
current values such as 0.004 A and 0.01 A. Other devices allow only a single value such
as 0.004 A. A value of 0 A disables the IEPE excitation. Refer to the device
documentation for details on your device.
Note
• You cannot enable IEPE excitation on DSA devices when the terminal
configuration is differential. The exception is NI 9218 which has
optional IEPE excitation and supports a differential terminal
configuration.
• Changing the IEPE excitation level may cause transient voltages to
appear in the signal. NI-DAQmx does not implement a delay to allow
the signal to settle. Therefore, after changing the IEPE level and
committing this change to the hardware with the Start function/VI or
the Control Task function/VI, you might add a software delay to allow
the signal to settle before proceeding with your application.
A DC offset is generated equal to the product of the excitation current and sensor
impedance when IEPE signal conditioning is enabled. To remove the unwanted offset,
you should enable AC coupling. Using DC coupling with IEPE excitation enabled is
appropriate only if the offset does not exceed the voltage range of the channel.
Input Coupling
You can configure each AI channel of your DSA device to be either AC or DC coupled,
with the exception of the NI 4495, the NI 4496, and the NI 4498 devices, which are AC
coupled only. If you select DC coupling, any DC offset present in the source signal is
passed to the ADC. The DC-coupled configuration is usually best if the signal source
has only small amounts of offset voltage, less than ±100 mV, or if the DC content of the
acquired signal is important.
If the source has a significant amount of unwanted DC offset (bias voltage), you should
490 ni.com
NI-DAQmx Device Considerations
select AC coupling to take full advantage of the input dynamic range. Selecting AC
coupling enables a single-pole, high-pass resistor-capacitor (RC) filter into the positive
and negative signal path. Refer to your device documentation for additional
information on the filter circuitry.
Use the NI-DAQmx Channel attribute/property AI.Coupling to set the input coupling
mode on your DSA device.
If you create a virtual channel for acceleration or sound pressure measurements with
your DSA device, the input coupling for the channel defaults to AC. For other types of
virtual channels, the input coupling defaults to DC.
Note NI-DAQmx does not compensate for the settling time or delay
introduced by the RC filter.
Overload Detection
DSA devices support overload detection in both the analog domain (pre-digitization)
and digital domain (post-digitization). An analog overrange can occur independently
from a digital overrange, and vice versa. For example, an IEPE accelerometer might
have a resonant frequency that, when stimulated, can produce an overrange in the
analog signal. However, because the delta-sigma technology of the ADC uses very
sharp anti-aliasing filters, the overrange is not passed into the digitized signal.
Conversely, a sharp transient on the analog side might not overrange, but the step
response of the delta-sigma anti-aliasing filters might result in clipping in the digital
data.
Some DSA devices support both analog and digital overload detection, while others
support only digital overload detection. Consult your device documentation for more
information on the overload detection capabilities for your device.
Two NI-DAQmx Read attributes/properties allow you to check for overloaded channels.
OverloadedChansExist reads the overload condition from the device and caches it in
the driver. It also resets the overload condition of the device after it is read.
Subsequent reads of OverloadedChans attribute/property will read the overloaded
channel information cached in the driver from the previous OverloadedChansExist
query.
Note NI-DAQmx returns all data whether or not an overload occurs. If your
application requires overload checking, it is recommended that you read the
overload attributes/properties after each call to Read. Your program should
discard questionable data or return a flag when the driver reports an
overload.
Simultaneous Tasks
The following devices can run multiple tasks simultaneously on some subsystems.
• NI 4302, 4303, 4304, 4305, 4339, 4340, 4463, 4464, 4466, and 4467
• NI 6533 and 6534
• cDAQ-9132, 9133, 9134, 9135, 9136, 9137, 9174, 9178, 9179, 9184, 9185, 9188,
9188XT, and 9189
• TS-15000 and TS-15010
• cRIO-9040, 9041, 9042, 9043, 9045, 9046, 9047, 9048, 9049, 9053, 9054, 9055, 9056,
9057, and 9058
• sbRIO-9603, 9608, 9609, 9628, 9629, and 9638
Related concepts:
492 ni.com
NI-DAQmx Device Considerations
Each timing engine can control up to eight channels. If a task has more than eight
channels, NI-DAQmx automatically uses multiple timing engines for the task,
synchronizing and sharing settings across all timing engines. For example, if a task has
10 channels, NI-DAQmx uses two timing engines for the task, which leaves two timing
engines for other tasks. If the task has 32 channels, all four timing engines are used for
one task.
Each bank of 8 ADCs (ai0:7, ai8:15, ai16:23, ai23:31) must all be in the same sample
mode (buffered or hardware timed single point). For example, if ai0 is used in a task
configured for hardware timed single point, any task using ai1:7 must also use the
hardware timed single point sample mode.
Each channel's gain can be independently configured regardless of what task it's in or
what sample mode it's used with.
Related concepts:
The NI 4339 only supports running a single buffered task and a single hardware-timed
single-point task simultaneously.
Related concepts:
The remainder of this topic provides information regarding how many tasks you can
494 ni.com
NI-DAQmx Device Considerations
Because hardware timed tasks typically use more onboard resources than software
timed tasks, the total number of possible concurrent tasks typically depends on
whether you are running tasks that use hardware timing or software (on demand)
timing.
Related concepts:
Hardware-Timed Tasks
Hardware-timed tasks require timing information from the System Timing Controller
to use for sample clocks, reference clocks, triggers, and so on.
The System Timing Controller for the Gen II chassis has the following timing engines
built in:
The System Timing Controller for the CompactRIO controller has the following timing
The following table illustrates the number of hardware timed tasks available to the
user.
CompactDAQ,
CompactDAQ and CompactRIO/Single- CompactRIO, Single-
Hardware-Timed
TestScale: Number of Board RIO: Number of Board RIO, TestScale:
Tasks
Tasks per Chassis Tasks per Controller Number of Tasks per
Module
51. The number of analog input tasks for Dynamic Signal Analyzer (DSA) devices in Gen II NI
CompactDAQ chassis is limited to two because the chassis support a maximum of two
synchronization pulse signals, which is required when using devices with different oversample clock
timebases, such as DSA.
52. On Single-Board RIO controllers, you can have one task at a time per slot or onboard IO module. The
number of slots and onboard IO modules varies by sbRIO device. See the specifications for your
device.
53. On the Gen II NI CompactDAQ chassis, there is a limit of two NI 9361 tasks per chassis.
54. On CompactRIO controllers, there is a limit of eight NI 9361 tasks per chassis. On Single-Board RIO
Controllers, there is a limit of one NI 9361 task per slot. You can add counter channels from one or
more NI 9361s to a single task. Using the NI 9361s and the 4 general purpose counters, there can be a
total of 12 tasks.
55. One NI 9361 only supports a single task. Therefore, multiple counters from a NI 9361 must be used in
the same task. Other parallel digital modules allow creating separate tasks for each one of the four
onboard counters from the chassis.
496 ni.com
NI-DAQmx Device Considerations
On CompactDAQ and TestScale chassis, there is also a streaming buffer for hardware
timed tasks that puts a limit on the total number of hardware timed tasks that can run
simultaneously. The NI cDAQ-9171/9181/9191 support six data streams and the
remaining models support seven data streams. These independent, high-speed data
streams allow for up to six or seven simultaneous hardware-timed tasks, such as
analog input, analog output, buffered counter/timers, hardware-timed digital input/
output, or CAN communication.
Note CAN communication always takes up two data streams, but does not
use any timing engines.
Software-Timed Tasks
Most software-timed tasks do not require a signal from the System Timing Controller
to run. Software timed means the host computer is controlling how often a sample is
read from or written to the C Series module.
Analog Input tasks will still use one of the AI timing engines, so the limit for AI tasks is
always the same as hardware times tasks. Each counter input task using an NI 9361
will also use an AI timing engine. This is not the case for AO, DI, or DO. Subsequently,
the software timed task limits for these types of acquisitions depends on the number
of channels you have available to use. See following table for a summary.
CompactDAQ,
CompactDAQ and CompactRIO, Single- CompactRIO, Single-
Software-Timed (On
TestScale: Number of Board RIO: Number of Board RIO, TestScale:
Demand) Tasks
Tasks per Chassis Tasks per Controller Number of Tasks per
Module
The number of counter tasks is always limited by the fact that you have four counters.
Depending on whether you are using a counter task that uses two counters (like
measuring frequency using the two counter methods), you may be restricted to only
two counter tasks. But typically, you can have all fout counters running
simultaneously. To determine if you need one or two counters for your counter task,
see the KnowledgeBase topic KB 4L0A62E9.
Related concepts:
Related information:
498 ni.com
NI-DAQmx Device Considerations
• KB 4L0A62E9
Multidevice Tasks
Tasks can contain channels from multiple devices for these devices:
• C Series
• FieldDAQ
• S Series
• DSA, SC Express, and X Series
Related concepts:
• All channels in the task must be of the same I/O type. Multiple counter I/O
channels are only allowed for Devices That Support Multi-Counter Tasks.
• If the task includes channels from a mixture of C Series Delta-Sigma devices, you
must account for filter delay differences between the devices. This delay is also
known as the input delay. Refer to your device specifications for the value.
• The modules must all be in the same NI CompactDAQ chassis or meet the
conditions for multichassis device tasks.
Note
Related concepts:
A task can include channels from multiple C Series modules in separate CompactDAQ
chassis58, CompactDAQ controllers59, CompactRIO controllers60 and CompactRIO
Single-Board controllers61, given the following conditions:
500 ni.com
NI-DAQmx Device Considerations
Exceptions
Related concepts:
Related concepts:
Analog Input
You must use a RTSI cable to connect the devices, and you must identify the cable
in MAX.
• PXI/PXIe Devices
◦ The devices must be in a single chassis, and you must identify the chassis in
MAX.
◦ NI-DAQmx accounts for filter delay differences between devices with some
qualifications:
▪ NI 4461 and 4462 devices lack the ability to compensate for filter delay.
▪ For all other devices, if the task includes channels from different device
families, NI-DAQmx will account for filter delay differences between the
devices.
Use the following table to check the multidevice task compatibility of any one device
to another device. A checkmark in a cell indicates that the devices in the
corresponding row and column can be used together in a multidevice task. For groups
of more than two devices, every device must be compatible with every other device.
An example of a group of devices that can be used in a multidevice task is the NI 4300,
4353, 4357 and PXIe X Series (63xx) as all of these devices are compatible with every
other device listed in the group.
502 ni.com
NI-DAQmx Device Considerations
4303/
4304/
4305
4309 - - - - - - - - - - - -
4310 - - - - - -
4330/
- - - - - - - -
4331
4339 - - - -
4340 - - - - - -
4353 - - - - - - - - - -
4357 - - - - - - - - - - - -
4461/
- - - - - - - - -
4462
4464 - - - -
4466/
4467
4480/
- - - - -
4481
449x - - - - - - - - - - - - -
6386/
- - - - - -
6396
Other
X Series - - -
(63xx)
Analog Output
The devices must be in a single chassis and the chassis must be identified in MAX.
All devices in the task must be PXIe-4463s.
The devices must be in a single chassis and the chassis must be identified in MAX.
You must use a RTSI cable to connect the devices, and you must identify the cable
in MAX.
• All Devices
When you include channels from different S Series devices and use an external
clock setup, you must import the external clock into the device with the longest
pipeline of all the devices in the task. Failing to do so results in an incomplete
acquisition, with the device importing the clock not receiving enough sample clock
pulses.
• PXI Devices
The devices must all be in a single chassis, and you must identify the chassis in
MAX.
• PCI Devices
You must use a RTSI cable to connect the devices, and you must identify the cable
in MAX.
Related concepts:
504 ni.com
NI-DAQmx Device Considerations
• NI FD-11637
• PXIe-433x
• NI 9218
• NI 9219
• NI 9235
• NI 9236
• NI 9237
• NI 9217
• NI 9221
• NI 9226
506 ni.com
NI-DAQmx Device Considerations
• NI 9242
• NI 9244
• NI 9246
• NI 9247
• NI 9250
• NI 9251
• NI 9260
If a common-mode voltage out of range is detected, the accuracy of the data on any
channel in the task may be impacted. If a thermocouple is connected to the device, but
is not in the task, make sure the channel does not exceed the common-mode voltage
range. A floating thermocouple, or a channel that is left unconnected, will not exceed
the common-mode voltage range. Refer to the devices Specifications document for
more information about the common-mode voltage range.
Isolation Isolation
Barrier Barrier
AI + AI +
Differential (DIFF) AI – AI –
AI GND AI GND
Isolation Isolation
Barrier Barrier
AI + AI
Related concepts:
508 ni.com
NI-DAQmx Device Considerations
CompactRIO Considerations
This section contains information on using the following CompactRIO and
CompactRIO single-board controllers with NI-DAQmx:
• cRIO-9040, 9041, 9042, 9043, 9045, 9046, 9047, 9048, 9049, 9053, 9054, 9055, 9056,
9057, and 9058 controllers.
• sbRIO-9603, 9608, 9609, 9628, 9629, and 9638 controllers.
Related concepts:
• Real-Time (NI-DAQmx)
• Real-Time Scan
• LabVIEW FPGA
In order for DAQmx to communicate with the module, the module must be in Real-
Time (NI-DAQmx) mode.
Related concepts:
Model Names
CompactRIO may use slightly different C Series model names and product IDs
compared to CompactDAQ. For CompactRIO, see C Series Module IDs on ni.com.
Related information:
Timing Considerations
CompactRIO controllers handle sampling rate and the default value for the hardware-
timed mode differently than CompactDAQ chassis.
510 ni.com
NI-DAQmx Device Considerations
For all modules in the CompactRIO and Single-Board RIO controllers, the default value
in hardware-timed mode is automatically determined based on Sample Clock Rate.
Related concepts:
• Four fixed direction LabVIEW FPGA to NI- • Two fixed direction LabVIEW FPGA to NI-
DAQmx Lines: DAQmx Lines:
◦ cRIO_Trig0, cRIO_Trig1, cRIO_Trig2, and ◦ cRIO_Trig0 and cRIO_Trig1 are
cRIO_Trig3 are terminals that are driven terminals that are driven from LabVIEW
from LabVIEW FPGA to NI-DAQmx. FPGA to NI-DAQmx.
◦ LabVIEW FPGA: output boolean chassis ◦ LabVIEW FPGA: output boolean chassis
I/O I/O
◦ NI-DAQmx: common-visibility source ◦ NI-DAQmx: common-visibility source
terminals terminals
▪ Can be used with Immediate ▪ Can be used with Immediate
Routing and Task-Based Routing and Task-Based
Routing Routing
▪ Does not prescribe to Lazy Line ▪ Does not prescribe to Lazy Line
Transitions rules Transitions rules
63. cRIO-9040, 9041, 9042, 9043, 9045, 9046, 9047, 9048, 9049, 9053, 9054, 9055, 9056, 9057, and 9058
64. sbRIO-9603, 9608, 9609, 9628, 9629, and 9638
• Four Fixed Direction NI-DAQmx to LabVIEW • Two Fixed Direction NI-DAQmx to LabVIEW
FPGA Lines: FPGA Lines:
◦ cRIO_Trig4, cRIO_Trig5, cRIO_Trig6, and ◦ cRIO_Trig2 and cRIO_Trig3 are
cRIO_Trig7 are terminals that are driven terminals that are driven from NI-
from NI-DAQmx to LabVIEW FPGA. DAQmx to LabVIEW FPGA.
◦ LabVIEW FPGA: input boolean chassis ◦ LabVIEW FPGA: input boolean chassis
I/O I/O
▪ Minimum pulse width ▪ Minimum pulse width
requirements: requirements:
▪ 12.5 ns for most destination ▪ 12.5 ns for most destination
terminals terminals
▪ 150 ns for SyncPulse terminals ▪ 150 ns for SyncPulse terminals
◦ NI-DAQmx: common-visibility ◦ NI-DAQmx: common-visibility
destination terminals destination terminals
▪ Can be used with Immediate ▪ Can be used with Immediate
Routing and Task-Based Routing and Task-Based
Routing Routing
▪ Does not prescribe to Lazy Line ▪ Does not prescribe to Lazy Line
Transitions rules Transitions rules
Note The signals available for export from DAQmx vary in pulse width. On a
cRIO controller, if you route any of the following signals over the cRIO_Trig
bus to the FPGA Target, the pulse is too short to be seen in the default top
level clock domain of 40 MHz:
• Counter output event exported from a counter task that configures its
output behavior to pulse
To fix this problem, consider routing the signal to a counter to widen the
pulse.
512 ni.com
NI-DAQmx Device Considerations
Related concepts:
• Immediate Routing
• Task-Based Routing
• Lazy Line Transitions
• NI 9361
Digital AI Filtering
The NI 4302, 4303, 4304, 4305, 4339, 4480, and 4481 modules have a user-configurable
lowpass filter for their analog input channels. This filtering is implemented with a
digital elliptical filter. It is configured independently of the tracking anti-aliasing filter.
It may be helpful when measuring in an environment with excessive high frequency
noise below the anti-aliasing filter's cutoff.
When sampling in hardware-timed single point mode, the filter is always enabled. You
can set or query its cutoff frequency using the AI.DigFltr.Lowpass.CutoffFreq attribute/
property. If your application does not require this additional filtering, leave this
property set to its default value. This will configure the widest bandwidth filter
possible.
Digital AI filtering for hardware-timed single point mode is supported on the following
modules:
When using other sampling modes, the filter is optional. This filter can be enabled by
using the AI.DigFltr.Enable attribute/property, and you can set or query its cutoff
frequency using the AI.DigFltr.Lowpass.CutoffFreq attribute/property.
Note User-defined cutoff frequencies for the 4480 and 4481 are supported
only for sample rates greater than 1.25 MHz.
ExcitFaultChansExist reads the excitation fault condition from the device and stores it
in NI-DAQmx. Subsequent reads of ExcitFaultChans will read the excitation fault
channel information stored in NI-DAQmx from the previous ExcitFaultChansExist
query.
NI-DAQmx returns all data regardless of whether an excitation fault happens. If your
application needs excitation fault checking, you should read the excitation fault
attributes/properties after each call to read. Your program should discard questionable
data or return a flag when NI-DAQmx reports an excitation fault.
The NI 9218 can detect if there is an overcurrent fault between EX+ and EX- pins of
either channel for either the strain mode case or the powered sensor measurement
514 ni.com
NI-DAQmx Device Considerations
case. When the NI 9218 is configured for powered sensor measurement, which requires
a +12 V excitation, it can also detect the absence of the required 9-30 V external power
supply connected to the Vsup terminal. Both of these types of faults are reported as
excitation faults.
The PXIe-4340 can detect if there is an overcurrent fault between the EX+ and EX- pins
of any channel. This fault occurs when a voltage source is connected to the EX+ and EX-
pins of any channel, or the load impedance is too low (excessive current). Ensure that
only the primary winding of an LVDT/RVDT sensor is connected to the EX+ and EX- pins
of any channel on this module.
Consult your device documentation for more information on fault reporting thresholds
and capabilities specific to your device.
Excitation
Quarter-Bridge Completion
Shunt Calibration
The FD-11637 has a built-in resistor for shunt calibration. Shunt calibration also only
works in Quarter-Bridge mode.
516 ni.com
NI-DAQmx Device Considerations
NI-DAQmx sets all digital I/O lines to the configured power-up state. NI-DAQmx
tristates all digital I/O lines on devices that do not support configurable power-up
states. NI-DAQmx outputs 0 on all digital output-only lines on devices that do not
support configurable power-up states.
• PFI Lines
NI-DAQmx tristates all PFI lines, unless they are also digital I/O lines. In that case,
the digital I/O line behavior applies.
• AO Channels
On E Series, S Series, and AO Series devices, NI-DAQmx does not alter the AO
channels. They continue to generate the DC voltage you last set them to.
With static AO devices, all voltage outputs are at their user-defined values to full
accuracy within 1 s of power-up device reset. Before this time, the voltage outputs
can float to unspecified values.
The fault detection applies to both positive and negative inputs. For instance, if you
specify a lower limit of 2 mA and an upper limit of 12 mA, NI-DAQmx detects a fault at
15 mA and -15 mA, but not at -6 mA because it is in the range of -2 mA to -12 mA.
PLL.UnlockedChansExist can only be used when the task is in a stop state but is still
reserved. You can also explicitly commit, start, and then stop the task without
explicitly uncommitting using the DAQmx Control Task VI.
NI 9775 Considerations
The NI 9775 module operates in two different modes, Continuous Mode and Record
Mode. You can set the NI 9775 operation to be Record Mode by setting the
DataXferReqCond attribute/property to When Acquisition Complete. Any other
supported value of the DataXferReqCond attribute/property will force the NI 9775 into
Continuous Mode. If a value is not set for DataXferReqCond attribute/property, the
518 ni.com
NI-DAQmx Device Considerations
Continuous Mode
While in Continuous Mode, the NI 9775 returns data as the data is acquired from the
source.
The module does not use the module's onboard buffer when in Continuous Mode. NI-
DAQmx will automatically put the NI 9775 in Continuous Mode if the task is set for
continuous acquisition or if the specified rate is less than or equal to 4 MS/s aggregate
for each module.
The NI 9775 also does not support Analog Triggering or Retriggering, unless in a task
with the NI 9204, NI 9205, or NI 9206. While in Continuous Mode, Reference and Start
triggers can be configured on the same task.
Record Mode
While in Record Mode, the data is stored on a buffer in the module until the entire
acquisition is complete. The data on the buffer is stored in records based on a trigger
signal sent to the device.
Acquisition is considered complete when any of the following conditions are satisfied:
• The maximum number of triggers are detected and the data for all detected
triggers have been acquired.
By default, the NI 9775 acquires one record. To acquire more than one record, you
can set the Retriggerable attribute/property to true, which will give you as many
records that can fit in the buffer, up to 32 records. Or, you can use the Maximum
Number of Triggers to Detect attribute/property to specify how many records you
want, up to 32 records. Any ignored triggers do not count towards the maximum of
32 records.
This time setting can be configured through the Trigger Window attribute/
property. The Trigger Window begins when the modules receive a sync pulse,
which synchronizes modules in a task. This sync pulse is sent during the commit
stage of the task which happens in the Start Task function/VI. If the Trigger Window
expires, the module finishes acquiring post-trigger data. If the module is already
finished acquiring post-trigger data, the module returns all of the acquired data.
This time setting can be configured through the Retrigger Window attribute/
property. The Retrigger Window begins once the module has detected a trigger
and resets every time it detects another trigger. If the Retrigger Window expires,
the module finishes acquiring post-trigger data. If the module is already finished
acquiring post-trigger data, the module returns all of the acquired data.
NI-DAQmx will automatically put the NI 9775 in Record Mode if the channels on the
module are used for trigger sources or if the rate is specified to be greater than 4 MS/s
aggregate for finite acquisitions. When in Record Mode, the NI 9775 may only be in the
same task as other NI 9775 modules in Record Mode.
Note The module will ignore triggers when acquiring pre-trigger buffer
data or post-trigger data.
520 ni.com
NI-DAQmx Device Considerations
NI USB-TC01 Considerations
If you are acquiring data from the device in a NI-DAQmx task or using the device's
temperature logger, the NI USB-TC01 launch screen cannot acquire data.
In MAX, the Reset Device option is disabled for the NI USB-TC01. If you attempt to reset
the device with the Reset Device VI/function, it returns an error if any task is using the
device. To reset the NI USB-TC01, disconnect and reconnect the device.
OpenChansExist reads the open channel condition from the device and caches it in the
driver. Subsequent reads of OpenChans attribute/property will read the channel
information cached in the driver from the previous OpenChansExist query.
NI-DAQmx returns all data whether an open channel is detected. If your application
requires open channel checking, it is recommended that you read the open channel
attributes/properties after each call to Read/Write. Your program should discard
questionable data or return a flag when the driver reports an open channel.
You can also check for shorted channels using the DAQmx Read OvercurrentChansExist
Related concepts:
• Overcurrent Detection
OpenCurrentLoopChansExist reads the open current loop condition from the device
and caches it in the driver. Subsequent reads of OpenCurrentLoopChans attribute/
property will read the open current loop channel information cached in the driver from
the previous OpenCurrentLoopChansExist query.
Note
• NI-DAQmx returns all data whether or not an open current loop occurs.
If your application requires open current loop checking, it is
recommended that you read the open current loop attributes/
properties after each call to Read. Your program should discard
questionable data or return a flag when the driver reports an open
current loop.
• For Analog Input devices with IEPE, the IEPE excitation current source
must be enabled for open current loop detection to work. If IEPE is not
turned on, an error is returned when OpenCurrentLoopChans is read.
522 ni.com
NI-DAQmx Device Considerations
Devices have a set of pull-up and bias resistor networks that connect to channels,
forming a voltage divider when a thermocouple is connected and working properly.
When a thermocouple breaks or becomes open, the open thermocouple detection
circuitry uses a small current source to push the input voltage out of range, which is
possible to detect in software using limits or conditions. In normal operation, this
current causes a voltage error on the input, known as a lead offset, when pushing
against a source resistance. In many applications, this error is minimal, but in some
applications where high accuracy is required and there are large source resistances
caused by long, narrow gauge thermocouple wires, the error can be significant.
taking the difference between a measurement with the bias current from open
thermocouple detection and one without the bias current. This difference is then
stored in the AI.Thrmcpl.LeadOffsetVoltage attribute/property and is applied to
measurements to compensate for current from open thermocouple detection.
Overcurrent Detection
Two NI-DAQmx Read/Write attributes/properties allow you to check for shorted
channels. The first is OvercurrentChansExist. This attribute/property returns a Boolean
true if one or more channels experience an overcurrent condition. The second is
OvercurrentChans. This attribute/property returns an array of strings indicating which
channels (if any) experienced an overcurrent condition. You must query the
OvercurrentChansExist attribute/property before querying the OvercurrentChans
attribute/property.
OvercurrentChansExist reads the overcurrent condition from the device and caches it
in the driver. Subsequent reads of OvercurrentChans attribute/property will read the
overcurrent channel information cached in the driver from the previous
OvercurrentChansExist query.
NI-DAQmx returns all data whether or not a short occurs. If your application requires
overcurrent checking, it is recommended that you read the overcurrent attributes/
properties after each call to Read/Write. Your program should discard questionable
data or return a flag when the driver reports a short.
IEPE must be turned on for overcurrent detection to work (except for the NI 4322, NI
4610, NI 9219, and NI 9269). If IEPE is not turned on, an error is returned when
OvercurrentChansExist is read.
524 ni.com
NI-DAQmx Device Considerations
Overtemperature Detection
An overtemperature condition occurs when the ambient temperature of the device
exceeds a safe operating level. The device may disable any overtemperature channels
until the ambient temperature returns to a safe level. Use the
OvertemperatureChansExist attribute/property to determine if the device is
experiencing an overtemperature condition. Devices may have front panel LEDs that
will indicate an overtemperature condition has occurred.
Remote sense uses a separate connection to quantify the voltage drop. This accounts
for the length of the cable in the original connection. To use remote sense, you must
connect the RS+ and RS- terminals on the device to the primary winding terminals on
the sensor.
Local sense measures the voltage drop internally at the excitation terminals. This
method does not require the use of additional wires, but is not as accurate as remote
sense.
On the PXIe-4340, you can set each channel to use either remote sense or local sense
by using the AI.Excit.Source attribute/property.
Default Values
The following property values take effect when the task is committed or started.
Use the DAQmx Create Channel VI/function to set the current and voltage setpoints.
Two properties reflect the current and voltage setpoints for a power channel, and are
settable at runtime via the DAQmx Channel property node:
Use the DAQmx Create Channel VI/function with the Pwr.OutputEnable property to
enable or disable power channel output. At runtime, set this property via the DAQmx
Channel property node.
Use the DAQmx Channel property node with the Pwr.IdleOutputBehavior property to
enable or disable power channel output when the task is uncommitted.
Use the DAQmx Channel property node to read the Pwr.OutputState property and
determine the channel state.
526 ni.com
NI-DAQmx Device Considerations
in I16 format. These instance will always return a value of 0 for current and
voltage while a power channel is disabled. Verify the power output state to
validate a current or voltage sample value of 0.
Use the DAQmx Read property node to read auxiliary power supply errors. Two
properties reflect the error state for auxiliary power.
Use the DAQmx Read property node to read remote sense errors. Two properties
reflect the error state for Remote Sense.
Use the DAQmx Read property node to read over-temperature errors. Two properties
reflect an over-temperature condition.
Use the DAQmx Read property node to read reverse voltage errors. Two properties
reflect the reverse voltage error state of channel
528 ni.com
NI-DAQmx Device Considerations
The NI USB-6008 has open-collector (open-drain) mode only, but each channel on the
NI USB-6501, the NI USB-6009, and SensorDAQ are programmable as either push-pull
or open-collector (open-drain) mode. The default configuration of the SensorDAQ, the
NI USB-6008, the NI USB-6009, and the NI USB-6501 DIO ports is open-drain, allowing 5
V operation, with an onboard 4.7 k pull-up resistor. An external, user-provided, pull-up
resistor can be added to increase the source current drive up to a 8.5 mA limit per line.
Refer to the device documentation for more information and instructions on
determining the value of the pull-up resistor.
When using USB or Ethernet DAQ devices, these samples may not reach your
computer's buffer in time, resulting in an incorrect number of samples available being
displayed. To ensure all samples get read, either use a second read also querying -1
(which will then contain the desired samples), or specify the number of samples to
read so the device waits until the specified number of samples have entered the
Supported
Accessory Description
Connections
Connects all TC channels to the calibration input. This
_tc_calibration
connection is used to verify and adjust TC gain accuracy.
Connects one CJC channel to the calibration input. This
CAL-4353
_cjc_calibration connection is used to verify and adjust CJC gain and offset
accuracy.
_short_tc_terminals Connects all TC channels together.
_remote_sense_floating Disconnects remote sensing for calibration.
RM-4339
_cal_channel Connects all channels to an external calibration source.
RM-4302 _cal_channel Connects all channels to an external calibration source.
RM-4304 _cal_channel Connects all channels to an external calibration source.
In a single stage AI SCC configuration, you connect your external signal to an SCC
module which conditions the signal and passes it to the DAQ device. You can install
single stage AI modules in sockets J1-J8 in the SC-2345 carrier.
Sometimes, you can cascade two AI SCC modules together on a single AI channel to
530 ni.com
NI-DAQmx Device Considerations
form a dual-stage configuration. In this configuration, you connect the external signal
to the first-stage AI module, which conditions the signal and passes it to the second-
stage AI module. Then, the signal is passed to the DAQ device. First-stage of dual-stage
AI modules can be located in sockets J9-J16. Second-stage of dual-stage AI modules
can be located in sockets J1-J8.
SCC modules that are not listed in the table above do not support dual-stage
configuration. This includes all analog output, digital input, and digital output SCC
modules.
• NI mioDAQ devices
◦ USB-6421
◦ USB-6423
◦ USB-6451
◦ USB-6453
• M Series devices
◦ NI 6210
◦ NI 6211
◦ NI 6212
◦ NI 6215
◦ NI 6216
◦ NI 6218
Self-powered USB devices require an external power source such as a wall outlet or a
battery. Self-powered devices can drive higher currents than bus-powered devices.
532 ni.com
NI-DAQmx Device Considerations
up states with the Set Power Up States (Digital) function/VI, but using MAX is the
recommended method. You can only specify a programmable power-up state of
tristate on devices with configurable direction. Refer to your device documentation to
see if your device supports configurable direction. For NI 6230/36 devices, you can also
specify a power-up state of tristate for digital output. The power-up state can be
specified on a port basis only. The power-up state of all other NI 623x devices can be
specified by line but cannot be set to tristate.
534 ni.com
NI-DAQmx Device Considerations
536 ni.com
NI-DAQmx Device Considerations
538 ni.com
NI-DAQmx Device Considerations
540 ni.com
NI-DAQmx Device Considerations
542 ni.com
NI-DAQmx Device Considerations
544 ni.com
NI-DAQmx Device Considerations
546 ni.com
NI-DAQmx Device Considerations
548 ni.com
NI-DAQmx Device Considerations
550 ni.com
NI-DAQmx Device Considerations
552 ni.com
NI-DAQmx Device Considerations
554 ni.com
NI-DAQmx Device Considerations
Setting the use excitation for scaling input to False will prevent the
PXIe-4339's ADCs from scaling the measured voltage ratiometrically to the excitation
voltage.
Setting the use excitation for scaling input to True, will enable the
PXIe-4339 to use the excitation value that the user sets with the DAQmx driver for
scaling the ratiometric input. The device will not use the voltage present on the remote
sense lines for scaling as it does when providing internal excitation. Thus, while the
driver will support using external excitation for ratiometric measurements, this is not a
recommended configuration.
The table below covers each possible combination of AI channel type, voltage
excitation source input value, and use excitation for scaling input
value. The cases highlighted will throw DAQmx errors, and the reasons for the errors
are described in the Use Case and Notes column of the table.
Basic bridge
True
measurement
Internal
False Bridge measurements are
always ratiometric
True Bridge measurement with
Bridge / Strain
external excitation
External
Bridge measurements are
False
always ratiometric
True Bridge measurements
None
False require excitation
Basic bridge
True
measurement
Internal
Powered sensor using
False
PXIe-4339 excitation
Bridge measurement using
True
external excitation
Custom Voltage External
Powered sensor using
False
external excitation
Bridge measurements
True
require excitation
None
Basic voltage
False
measurement
The cDAQ-9185/9189 are tethered chassis that can be daisy-chained to each other or
connected to external networks that support 802.1AS synchronization. To learn about
556 ni.com
NI-DAQmx Device Considerations
this feature, refer to the cDAQ-9185/9189 User Manual and the related concepts in
this help.
The FD-116xx are devices that can be daisy-chained to each other and connected to
external networks that support 802.1AS synchronization. To learn about this feature,
refer to your FieldDAQ User Guide and the related concepts in this help.
Related concepts:
• Time Triggering
• C Series Multichassis Device Tasks
• Sync Lock Lost Detection
• Timestamps
The NI 4309 supports chopping but disables it by default. Chopping can be enabled
with the AI.Chop.Enable attribute/property, or when configuring a voltage input
task in the DAQ Assistant by selecting the Enable Chopping option. Refer to the NI
4309 User Manual for wiring instructions.
Excitation
The RM-4339 has a connection for an external excitation source. Each channel can also
use it's own channel-specific internal excitation. Use the AI.Excit.Src attribute/property
to set the excitation connection.
Quarter-Bridge Completion
The RM-4339 includes three internal resistors you can use for quarter-bridge
completion. These resistors are 120 Ω, 350 Ω, and 1 kΩ. Use the
AI.Bridge.NomResistance attribute/property to set quarter-bridge completion.
Shunt Calibration
The RM-4339 includes two independent shunt calibration resistors, named A and B.
You can select which resistor to use using the AI.Bridge.ShuntCal.Select attribute/
property.
You can use an internal or external resistor for shunt resistor A. Use the
AI.Bridge.ShuntCal.ShuntCalASrc attribute/property to set this. Select Built-In to use
the internal 100 kΩ resistor, or User Provided to use an external resistor.
Shunt resistor B is an internal resistor that you can use only with quarter-bridge
completion. You can use a 50 kΩ or 100 kΩ resistor by setting the
AI.Bridge.ShuntCal.ShuntCalBResistance attribute/property.
Note
The DAQmx Perform Shunt Calibration function/VI and the Strain Gage
Calibration Wizard in MAX do not support AI.Bridge.ShuntCal.ShuntCalASrc
or AI.Bridge.ShuntCal.ShuntCalBResistance.
Related concepts:
• NI 6320
• NI 6321
558 ni.com
NI-DAQmx Device Considerations
• NI 6323
• NI 6341
• NI 6343
• NI 6345
• NI 6351
• NI 6353
• NI 6355
• NI 6361
• NI 6363
• NI 6365
• NI 6375
• NI 6346
• NI 6349
• NI 6356
• NI 6358
• NI 6366
• NI 6368
• NI 6374
• NI 6376
• NI 6378
• NI 6386
• NI 6396
Measurement Fundamentals
Measurement Fundamentals covers API-independent information that might help you
as you develop applications. Topics include an explanation of different signal types,
sensors commonly used with measurement devices, signal conditioning, and control
fundamentals.
560 ni.com
Measurement Fundamentals
Physical Phenomena
Light, Pressure, Temperature, and So On
+ + + +
V HV mV
– – – –
Signal Conditioning
345
SC-2
Data Acquisition
Configuration
Measurement & Automation Explorer (MAX), DAQ Assistant, and So On
Driver Engines
NI-DAQmx, NI-488.2
Application Software
LabVIEW, LabWindows/CVI, Measurement Studio, or Other Programming Environments
NI measurement devices and application software are packaged with NI-DAQmx driver
software to program all the features of your NI measurement device such as
configuring, acquiring, and generating data from and sending data to NI measurement
devices. Using NI-DAQmx saves you from having to write these programs yourself.
Application software, such as LabVIEW, LabWindows™/CVI™, and Measurement Studio,
sends the commands to the driver, such as acquire and return a thermocouple
reading, and then displays and analyzes the data acquired.
You can use the NI-DAQmx driver from NI application software or from any
programming environment that supports calling dynamic link libraries (DLLs) through
ANSI C interfaces. Regardless of the programming environment, your DAQ application
uses NI-DAQmx, as shown in the figure.
Signal Types
A signal is classified as analog or digital by the way it conveys information. A digital (or
binary) signal has only two possible discrete levels—high level (on) or low level (off).
An analog signal, on the other hand, contains information in the continuous variation
of the signal with respect to time. A breakdown of the main signal types is shown in the
following figure.
on
On-Off TTL Line off State
t
Digital
1
Pulse Train Counter/ Rate
0 t
Timer
Signals 0.985
DC ADC/DAC Level
(slow) t
Freq.
Frequency ADC (fast)
Domain Analysis f Content
Related concepts:
Signal connections vary depending on your device, connector block, and signal
conditioning module. The DAQ Assistant contains connection diagrams that show
562 ni.com
Measurement Fundamentals
terminal connections for all common analog input measurements, such as measuring
strain, temperature, current, voltage, and so on. Refer to Viewing Connection
Diagrams in the DAQ Assistant Help for additional information.
In a floating source, the voltage signal is not connected to any absolute reference or
any common ground, such as earth or building ground as shown in the following
figure.
+
VS
–
Ground
Floating signal sources are also called nonreferenced signal sources. Some common
examples of floating signal sources are batteries, thermocouples, transformers, and
isolation amplifiers. Notice in the figure that neither terminal of the source is
connected to the electrical outlet ground, so each terminal is independent of the
system ground.
You can measure floating signal sources with both differential and single-ended
measurement systems. In the case of the differential measurement system, however,
make sure the common-mode voltage level of the signal with respect to the
measurement system ground remains in the common-mode input range of the
measurement device. A variety of phenomena—for example, the instrumentation
amplifier input bias currents—can move the voltage level of the floating source out of
the valid range of the input stage of a DAQ device.
Related concepts:
A grounded source is one in which the voltage signals are referenced to a system
ground, such as earth or building ground, as shown in the following figure.
+
VS
–
Ground
Because such sources use the system ground, they share a common ground with the
measurement device. The most common examples of grounded sources are devices
that plug into the building ground through wall outlets, such as signal generators and
power supplies.
However, you can still use an RSE measurement system if the signal voltage levels are
564 ni.com
Measurement Fundamentals
high and the interconnection wiring between the source and the measurement device
has a low impedance. In this case, the signal voltage measurement is degraded by
ground loop, but the degradation may be tolerable. You must observe the polarity of a
grounded signal source before connecting the signal to a ground-referenced
measurement system because the signal source can be short-circuited to ground,
which can damage the signal source.
Related concepts:
The type of input signal source (grounded or floating) and the configuration of the
measurement system (differential, single-ended, pseudodifferential) determine how
you connect signals to measurement devices.
AI +
AI + +
+ +
+ Vs
Vs AI –
– AI – –
– –
Differential (DIFF)
Rext
AI GND AI GND
Single-Ended (RSE)
AI AI
+ +
+ +
Vs V1
– AI GND –
– –
Note: AI GND is shared + Vg –
RSE channels
Ground-loop losses, Vg, are added to
measured signal.
Nonreferenced Single-
Ended (NRSE)
AI AI
+ + +
+
Vs Vs
– AI SENSE AI SENSE
–
Note: AI SENSE is
Rext
shared as a reference AI GND AI GND
for all NRSE channels
AI GND
AI + AI +
+ +
+ +
Vs Vs
– AI – – AI –
– –
Pseudodifferential Z Z
AI GND AI GND
Related concepts:
566 ni.com
Measurement Fundamentals
CH2+
CH1+
Instrumentation
CH7+ + Amplifier
+
MUX
CH0– –
Vm
CH2–
CH1–
–
CH7–
AIGND
Related concepts:
Common-Mode Voltage
The common-mode voltage range limits the allowable voltage swing on each input
with respect to the measurement system ground. Violating this constraint results not
only in measurement error but also in possible damage to components on the device.
Common-mode voltage (Vcm) is defined using the following formula:
where V+ is the voltage at the noninverting terminal of the measurement system with
respect to the measurement system ground, and V– is the voltage at the inverting
terminal of the measurement system with respect to the measurement system ground.
CMRR
568 ni.com
Measurement Fundamentals
A simple circuit is shown in the following figure. In this circuit, CMRR in decibels is
measured as 20 log Vout/Vcm, where Vcm = (V+ + V–)/2.
V+ –
Vout
V–
CH2+
CH1+
Instrumentation
CH7+ + Amplifier
–
Vm
AIGND –
MUX
CH0+
CH2+
CH1+
Instrumentation
CH7+ + Amplifier
AISENSE –
Vm
In an NRSE measurement system, all measurements are still made with respect to a
single-node analog input sense (AISENSE), but the potential at this node can vary with
respect to the measurement system ground. The previous figure illustrates that a
single-channel NRSE measurement system is the same as a single-channel differential
measurement system.
570 ni.com
Measurement Fundamentals
general, a differential input offers a better common-mode rejection ratio (CMRR) than
a pseudodifferential input.
Instrumentation
Amplifier
CH+ +
Z in +
CH– –
Vm
Z1
–
Signal connections vary depending on your device, connector block, and signal
conditioning module. The following figure shows how to make analog output
connections for a typical NI device.
AO 0
+ Channel 0
Load V OUT 0
–
AO GND
–
Load V OUT 1
+ AO 1
Channel 1
Sampling Considerations
When sampling a signal it is important to consider device range, input limits, sampling
rate, resolution, and code width.
Related concepts:
• Device Range
• Input Limits (Maximum and Minimum Values)
• Sampling Rate
• Resolution
• Calculating the Smallest Detectable Change—Code Width
Device Range
Device range refers to the minimum and maximum analog signal levels that the ADC
can digitize. Many measurement devices can select from several ranges by changing
from unipolar mode to bipolar mode or by selecting from multiple gains, allowing the
ADC to take full advantage of its resolution to digitize the signal.
Related concepts:
Unipolar mode means that a device only supports a range of 0 V to +X V. Bipolar mode
means that a device supports a range of -X V to +X V. Some devices support only one
mode or the other, while other devices can change from unipolar mode to bipolar
mode.
Devices that can change from unipolar to bipolar mode are able to select the mode
that best fits the signal to measure. The first chart of the following figure illustrates
unipolar mode for a 3-bit ADC. The ADC has eight digital divisions in the range from 0
to 10 V. In bipolar mode, the range is -10.00 to 10.00 V, as shown in the second chart.
The same ADC now separates a 20 V range into eight divisions. The smallest detectable
difference in voltage increases from 1.25 to 2.50 V, and you now have a much less
accurate representation of the signal. The device selects the best mode available
based on the input limits you specify when you create a virtual channel.
572 ni.com
Measurement Fundamentals
Range = 0 to 10 V
10.00
111
8.75
Amplitude (volts)
110
7.50
101
6.25
100
5.00
011
3.75
010
2.50
001
1.25
000
0.00
0 50 100 150 200
Time (s)
Range = –10 to 10 V
10.00
111
7.50
Amplitude (volts)
110
5.00
101
2.50
100
0.00
011
–2.50
010
–5.00
001
–7.50
000
–10.00
0 50 100 150 200
Time (s)
Gain Adjustment
If a device has multiple gains, it multiplies an input signal by one of the gains to make
the signal take up more of the full device range. This essentially gives the device
multiple ranges it can select from. For example, a device with an overall range of -10 V
to 10 V and possible gains of 1, 2, and 4 can select between ranges of -10 V to 10 V, -5 V
to 5 V, and -2.5 V to 2.5 V. The device selects the best gain available according to the
input limits you specify when you create a virtual channel.
Input limits are the maximum and minimum values you expect to measure, after any
scaling, including custom scaling.
Input limits are sometimes confused with device range. Device range refers only to the
input range of a particular device.
If you set your minimum to 0 and your maximum to 7, and your device only has a 0-5
and a 0-10 device range, the device range will be coerced to 0-10 by NI-DAQmx. This
also applies when using a custom scale.
The maximum and minimum input limit values will match the units of measurement of
the task. For instance, the device range for a DAQ device might be 0 to 10 V, but that
device might be used with a temperature sensor that outputs 100 mV for every 1 °C.
The input limits in that case could be 0 to 100, with 10 V corresponding to 100 °C. For
an analog current input task, the units would be amps.
Input limits in a smaller range can improve the precision of your measurement. If your
device has multiple input ranges, you can strategically choose the minimum and
maximum values to detect smaller differences in your signal of interest. Consider a
device that has a 0-10 V and a 0-5 V range. In the previous temperature sensor
example, if you knew that the temperature would never be higher than 50 °C, you
could choose a minimum value of 0 and a maximum value of 50. The device can then
detect smaller differences in temperature because it is digitizing a voltage between 0
and 5 V, rather than 0 and 10 V.
Related concepts:
• Device Range
Sampling Rate
One of the most important parameters of an analog input or output system is the rate
at which the measurement device samples an incoming signal or generates the output
signal. The sampling rate, which is called the scan rate in Traditional NI-DAQ
(Legacy), is the speed at which a device acquires or generates a sample on each
channel. A fast input sampling rate acquires more points in a given time and can form
a better representation of the original signal than a slow sampling rate. Generating a 1
Hz signal using 1000 points per cycle at 1000 S/s produces a much finer representation
than using 10 points per cycle at a sample rate of 10 S/s.
Resolution
Resolution is the smallest amount of input signal change that a device or sensor can
detect. The number of bits used to represent an analog signal determines the
574 ni.com
Measurement Fundamentals
resolution of the ADC. You can compare the resolution on a measurement device to the
marks on a ruler. The more marks you have, the more precise your measurements.
Similarly, the higher the resolution, the higher the number of divisions into which your
system can break down the ADC range, and therefore, the smaller the detectable
change.
A 3-bit ADC divides the range into 23 or 8 divisions. A binary or digital code between
000 and 111 represents each division. The ADC translates each measurement of the
analog signal to one of the digital divisions. The following figure shows a sine wave
digital image as obtained by a 3-bit ADC. Clearly, the digital signal does not represent
the original signal adequately, because the converter has too few digital divisions to
represent the varying voltages of the analog signal. By increasing the resolution to 16
bits, however, the number of divisions of the ADC increases from 8 to 65,536 (216). The
ADC now can obtain an extremely accurate representation of the analog signal.
10.00
111
8.75
110 16-Bit
7.50
Amplitude (volts)
101
6.25
100
5.00
011
3.75
010 3-Bit
2.50
001
1.25
000
0.00
0 50 100 150 200
Time (s)
The resolution and device range of a measurement device determine the smallest
detectable change, called the code width, in the input signal. The smaller your code
width, the more accurate your measurements are.
You can calculate the code width using the following formula:
A high-resolution A/D converter (ADC) provides a smaller code width given the
preceding device voltage ranges.
The following table shows how the code width of a 12-bit measurement device varies
by device range. The device selects the best possible range based on the input limits
you specify when you create a virtual channel. Select input limits that accurately
reflect the signal you want to measure in order to achieve the smallest possible code
width. NI-DAQmx coerces those input limits to fit the selected device range.
Overall Device Range Possible Device Ranges with Gain Adjustment Precision65
• 0 to 10 V • 2.44 mV
• 0 to 5 V • 1.22 mV
• 0 to 2.5 V • 610 µV
0 to 10 V • 0 to 1.25 V • 305 µV
• 0 to 1 V • 244 µV
• 0 to 0.1 V • 24.4 µV
• 0 to 20 mV • 4.88 µV
• -5 to 5 V • 2.44 mV
• -2.5 to 2.5 V • 1.22 mV
• -1.25 to 1.25 V • 610 µV
–5 to 5 V • -0.625 to 0.625 V • 305 µV
• -0.5 to 0.5 V • 244 µV
• -50 to 50 mV • 24.4 µV
• -10 to 10 mV • 4.88 µV
• -10 to 10 V • 4.88 mV
-10 to 10 V
• -5 to 5 V • 2.44 mV
65. The value of 1 Least Significant Bit (LSB) of the 12-bit ADC. In other words, the voltage increment
corresponding to a change of 1 count in the ADC 12-bit count.
576 ni.com
Measurement Fundamentals
Overall Device Range Possible Device Ranges with Gain Adjustment Precision
Related concepts:
• Resolution
• Device Range
• Input Limits (Maximum and Minimum Values)
• Input Limit Coercion
Digital Signals
A digital signal has two discrete levels—a high and a low level. One example of a digital
signal is a transistor-transistor logic (TTL) compatible signal. A TTL-compatible signal
has the following characteristics:
+5.0 V
High
+2.0 V
Indeterminate
+0.8 V
Low
0V
Digital devices can monitor the state of the pulse and can transition the pulse from one
state to another. A counter can also monitor the state as well as detect rising edges, a
transition from logic low to logic high, and falling edges, a transition from logic high to
logic low. Counters are used commonly to count edges and for time measurements,
such as measuring digital frequency or the period of a signal.
The number of digital lines varies from device to device. The following figure shows
signal connections for three typical DIO applications.
+5 V
LED
P0.<4..7>
TTL Signal
P0.<0..3>
+5 V
Switch
D GND
I/O Connector
The figure shows PO <0..3> configured for digital input and PO <4..7> configured for
digital output. Digital input applications include receiving TTL signals and sensing
external device states such as the state of a switch. Digital output applications include
sending TTL signals and driving external devices such as the LED shown in the figure.
Counters
Counters measure and generate digital signals. Counters are used commonly to count
edges and for time measurements, such as measuring digital frequency or the period
of a signal. The signal connections required for counters vary depending on the device
and your application.
Related concepts:
578 ni.com
Measurement Fundamentals
Test engineers can choose from a number of different digital I/O instruments with a
range of features for communication and test applications. Beyond the basic
capabilities of driving a digital pattern of 1s and 0s, digital instruments often support
waveforms that can include some or all of the logic states shown in the following table.
The six logic states control the voltage driver and, if supported, the compare engine of
the digital tester (such as a DAQ device) on a per clock cycle basis. Drive states specify
what stimulus data the digital tester drives on a particular channel or when to disable
the voltage driver (referred to as the tristate or high-impedence state). Compare states
indicate the expected response from the device under test. These six logic states make
it possible to perform bidirectional communication and real-time hardware
comparison of acquired response data.
Duty Cycle
The duty cycle is a characteristic of a pulse. Use the following equation to calculate the
duty cycle of a pulse whose high time and low time are unequal:
The duty cycle of a pulse is between 0 and 1 and is often expressed as a percentage.
Refer to the following figure for examples of duty cycles. A pulse with a high time equal
to the low time has a duty cycle of 0.5, or 50%. A duty cycle less than 50% indicates
that the low time is greater than the high time, and a duty cycle greater than 50%
indicates that the high time is greater than the low time.
Counter
Starts
Initial
Delay
Signal Analysis
Signal analysis is the process of transforming an acquired signal to extract information
about the signal, filter noise from the signal, and present the signal in a more
understandable form than the raw signal.
Related concepts:
• Filtering
• Windowing
Filtering
Filtering is one of the most commonly used signal processing techniques. Signal
conditioning systems can filter unwanted signals or noise from the signal you are
measuring. Use a noise filter on low-rate, or slowly changing, signals, such as
temperature, to eliminate higher frequency signals that can reduce signal accuracy. A
common use of a filter is to eliminate the noise from a 50 or 60 Hz AC power line. A
lowpass filter of 4 Hz removes the 50 or 60 Hz AC noise from signals sampled at low
rates. A lowpass filter eliminates all signal frequency components above the cutoff
580 ni.com
Measurement Fundamentals
frequency. Many signal conditioning modules have lowpass filters that have software-
selectable cutoff frequencies from 10 Hz to 25 kHz.
Windowing
Spectral Leakage
Discrete Fourier Transform (DFT) and Fast Fourier Transform (FFT) are mathematical
techniques that resolve a given signal into the sum of sines and cosines. It is the basis
for spectrum analysis. Using the DFT/FFT when you sample a noninteger number of
cycles, such as 7.5 cycles, returns a spectrum in which it appears as if the energy at one
frequency leaks into all the other frequencies because the FFT assumes that the data is
a single period of a periodically repeating waveform. The artificial discontinuities
appear as very high frequencies that were not present in the original signal. Because
these frequencies are higher than the Nyquist frequency, they appear aliased between
0 and fs/2.
The type of window to use depends on the type of signal you acquire and on the
application. Choosing the correct window requires some knowledge of the signal that
you are analyzing. The following table lists common types of windows, the appropriate
signal types, and example applications.
Note In many cases, you might not have sufficient knowledge of the signal,
so you need to experiment with different windows to find the best one.
Signal Conditioning
Sensors can generate electrical signals to measure physical phenomena, such as
temperature, force, sound, or light. To measure signals from transducers, you must
convert them into a form that a DAQ device can accept. For example, the output
voltage of most thermocouples is very small and susceptible to noise. Therefore, you
may need to amplify or filter the thermocouple output before digitizing it.
Amplification
Amplification is a type of signal conditioning that improves accuracy in the resulting
582 ni.com
Measurement Fundamentals
For the highest possible accuracy, amplify the signal so the maximum voltage swing
equals the maximum input range of the ADC, or digitizer. Your system should amplify
low-level signals at the measurement device located nearest the signal source, as
shown in the following figure.
Noise
Instrumentation
Amplifier
+
– Lead MUX ADC
Low-Level Wires
Signals External
Amplifier Measurement
Device
If you amplify the signal at the measurement device, the signal is measured and
digitized with noise that may have entered the lead wires. However, if you amplify the
signal close to the signal source with an SCXI module, noise has less impact on the
measured signal.
Linearization
Linearization is a type of signal conditioning in which software linearizes the voltage
levels from transducers, so the voltages can be scaled to measure physical
phenomena. For example, a change in voltage of 10 mV for a thermocouple usually
does not reflect a change of 10 degrees. However, with linearization in software or
hardware, the thermocouple can be scaled to the appropriate temperature in your
application. Most transducers have linearization tables that describe scaling the
transducer.
Transducer Excitation
Signal conditioning systems can generate excitation for some transducers. Strain gages
and RTDs require external voltage and current, respectively, to excite their circuitry
into measuring physical phenomena. This type of excitation is similar to the power a
radio needs to receive and decode audio signals. Several measurement devices
provide the necessary excitation for transducers. Consult your device documentation
to see if your device can generate excitation.
Isolation
Signals often can exceed the limits that a measurement device can handle. Trying to
measure a signal that is too large for the measurement device can damage the device
or you. To keep you and your device safe from large voltages, you can apply a signal
conditioning technique called isolation. The signal conditioning hardware attenuates
high common mode voltages and extracts a signal that measurement devices can
handle. Isolation also ensures that differences in ground potentials do not affect your
device.
Common Sensors
Depending on your application, you may use several different kinds of sensors. Some
commonly used ones are strain gages, thermocouples, thermistors, angular encoders,
linear encoders, bridge-based sensors, and resistance temperature detectors (RTDs).
Related concepts:
• Strain Gages
• Thermocouples
• Thermistors
• Quadrature Encoders
• Two-Pulse Encoders
• Bridge-Based Sensors
• Resistance Temperature Detectors (RTDs)
2-Wire Resistance
Resistance measurements in the range above 100 Ω are generally made using the
2-wire method shown in the following figure. The excitation current flows through the
leads and the unknown resistance, Rmeas. Your device measures the voltage across the
584 ni.com
Measurement Fundamentals
resistance through the same set of leads and computes the resistance accordingly.
Errors in the 2-wire measurements are introduced by the lead resistance, RLead, when
measuring lower resistances. Because there is a voltage drop across the lead
resistance equal to I × RLead, the voltage measured by your device is not exactly the
same as the voltage across the resistance, Rmeas. Because typical lead resistances lie in
the range of 0.01–1 Ω, accurate 2-wire resistance measurements are very difficult to
obtain if Rmeas is below 100 Ω.
Test
Current
DAQ Device EX+ RLead
+
IEX ADC Σ Rmeas
–
EX– RLead
3-Wire Resistance
Use the 3-wire resistance method, as shown in the following figure, to measure
resistance on resistors that have three lead wires.
Test
RLead Current
DAQ Device EX+
+ +
IEX ADC Σ Σ Rmeas
– –
RLead
+ Sense–
×2 Σ
–
RLead
EX–
The 3-wire method uses three test leads, one pair for the excitation current (EX+, EX-),
and a third wire (Sense-) to compensate for the lead wire resistances. The third wire
measures the voltage developed over the lead resistance in the EX- leg of the excitation
current path. By subtracting its value from the overall differential signal, the device can
compensate for parasitic lead resistances in the EX+ leg. However, this would only
compensate for lead resistance in the EX+ leg and not in the EX- leg. To compensate for
lead resistance both in the EX- leg and in the EX+ leg, the device approximates the EX+
leg by assuming the voltage is the same as in the EX- leg. Thus the voltage between
Sense- and EX- is multiplied by two before being subtracted from the overall
differential signal. This method works well when lead resistances in the EX+ leg match
resistances in the EX- leg.
Some legacy devices do not provide compensation. In that case, you need to specify
the lead-wire resistance so that it can be subtracted in software.
4-Wire Resistance
Use the 4-wire resistance method, as shown in the following figure, to measure
resistances of less than 100 Ω. The 4-wire method is more accurate than the 2-wire
method.
Test
DAQ Device RLead Current
EX+
RLead
Sense–
+
IEX ADC Σ Rmeas
–
RLead
Sense–
RLead
EX–
The 4-wire method uses four test leads, one pair for the injected current (the test lead)
and the other pair for sensing the voltage across the resistor Rmeas (the sense lead).
Because no current flows in the sense lead, the device measures only the voltage
developed across the resistance. Thus, a 4-wire resistance eliminates errors that test
lead and contact resistance cause.
586 ni.com
Measurement Fundamentals
Bridge-Based Sensors
Bridge-based sensors operate by correlating a physical phenomena, such as strain,
temperature, or force, to a change in resistance in one or more legs of a Wheatstone
bridge. The general Wheatstone bridge, shown in the following figure, is a network of
four resistive legs with an excitation voltage, VEX, that is applied across the bridge. One
or more of these legs can be active sensing elements.
R1 R4
+ – +
VEX VCH
–
R2 R3
The Wheatstone bridge is the electrical equivalent of two parallel voltage divider
circuits. R1 and R2 compose one voltage divider circuit, and R4 and R3 compose the
second voltage divider circuit. You measure the output of a Wheatstone bridge
between the middle nodes of the two voltage dividers.
• Strain gage—Use the strain gage measurement type for performing strain
measurements.
• Force, pressure, and torque—Use these measurement types for performing
bridge-based force, pressure, or torque measurements on supported devices.
NI-DAQmx provides additional measurement types from which you read data in
electrical units. Use a custom scale or write scaling code to convert the electrical units
to physical units.
• Bridge (V/V)—Channels using the bridge V/V measurement type return a voltage
ratio instead of physical units. Use this measurement type on supported devices
for other bridge-based sensors, for sensors that scale data to physical units NI-
DAQmx does not support, or to measure torsional strain.
• Custom voltage with excitation—Use this measurement type for bridge-based
measurements on devices that do not support the strain gage, force, pressure,
torque, or bridge (V/V) measurement types. Specify to use excitation for scaling to
acquire a voltage ratio instead of a voltage. On ratiometric devices, you must
specify to use excitation for scaling because those devices can only acquire a
voltage ratio.
• Voltage—Use this measurement type with bridge-based sensors that include an
internal amplifier and output voltage.
• Current—Use this measurement type with bridge-based sensors that include an
internal amplifier and output current.
Related concepts:
(V – VIB) × G
VR =
(VEX)
where VR is the voltage ratio; V is the voltage output from the bridge; VIB is the initial
bridge voltage, as determined by offset nulling; VEX is the excitation voltage supplied
to the bridge; and G is the gain adjustment from shunt calibration.
Ratiometric devices divide the voltage output from the bridge by the excitation voltage
in hardware. Therefore, V/VEX must be within the device range of the device. On
voltage devices, the voltage output from the bridge must be within the device range.
The initial bridge voltage and gain adjustment affect the association between device
range and input limits. For example, on a device that can measure ±5 V, an initial
bridge voltage of 1 V means that the minimum and maximum input limits must
correspond to -6 V to 4 V.
588 ni.com
Measurement Fundamentals
NI-DAQmx uses various methods to scale that voltage ratio to physical units,
depending on the bridge configuration for strain measurements or on the scaling type
that best matches the specifications provided by the sensor manufacturer for other
bridge-based sensors NI-DAQmx supports.
Related concepts:
Bridge Configurations
There are three types of bridge configurations: quarter-bridge, half-bridge, and full-
bridge. The number of active element legs in the Wheatstone bridge determines the
kind of bridge configuration.
Related concepts:
• Bridge completion
In addition, you should calibrate your sensor periodically to account for changes in the
physical characteristics of the sensor and in the material the sensor is measuring, to
account for variations in the lead wire resistance, and to compensate for imperfections
in the measurement system. Calibrating bridge-based sensors usually involves two
steps: offset nulling, or bridge balancing, and shunt calibration, or gain adjustment.
Related concepts:
• Bridge Completion
• Bridge Excitation
• Signal Amplification
• Offset Nulling (Bridge Balancing)
• Shunt Calibration (Gain Adjustment)
Bridge Completion
Unless you are using a full-bridge sensor, you must complete the bridge with reference
resistors. Therefore, signal conditioners for bridge-based sensors typically provide
half-bridge completion networks consisting of two high-precision reference resistors.
The nominal resistance of the completion resistors is less important than how well the
two resistors match. Ideally, the resistors match well and provide a stable reference
voltage of VEX/2 to the negative input lead of the measurement channel. The high
resistance of the completion resistors helps minimize the current draw from the
excitation voltage. However, using completion resistors that are too large can result in
increased noise and errors due to bias currents.
Signal Amplification
The output of bridge-based sensors is relatively small. For example, most strain gage
bridges and strain-based transducers output less than 10 mV/V, or 10 millivolts of
output per volt of excitation voltage. Therefore, signal conditioners for bridge-based
sensors usually include amplifiers to boost the signal level, to increase measurement
resolution, and to improve signal-to-noise ratios. For example, SCXI signal
conditioning modules include configurable gain amplifiers with gains up to 2,000.
Other devices support multiple device ranges.
590 ni.com
Measurement Fundamentals
Related concepts:
• Device Range
Bridge Excitation
Bridge-based sensors require a constant voltage to power the bridge. Bridge signal
conditioners typically include a voltage source. While there is no standard voltage level
that is recognized industry wide, excitation voltage levels of around 3 V and 10 V are
common.
Excitation sources can suffer from stability and accuracy issues. To compensate,
ratiometric devices constantly measure the actual excitation voltage and use it, rather
than an intended excitation value, when scaling data.
Related concepts:
Remote Sensing
If the bridge circuit is located away from the signal conditioner and excitation source, a
possible source of error is voltage drops caused by resistance in the wires that connect
the excitation voltage to the bridge. Therefore, some signal conditioners include a
feature called remote sensing to compensate for this error. There are two common
methods of remote sensing.
With feedback remote sensing, you connect extra sense wires to the point where the
excitation voltage wires connect to the bridge circuit. The extra sense wires serve to
regulate the excitation supply, to compensate for lead losses, and to deliver the
needed voltage at the bridge.
Related concepts:
When you install a bridge-based sensor, the bridge probably will not output exactly 0 V
when not under load. Slight variations in resistance among the bridge legs generate
some nonzero initial offset voltage. Use the DAQmx Perform Bridge Offset Nulling
Calibration VI/function or the DAQ Assistant to perform an offset nulling calibration,
which performs bridge balancing in a few different ways. Refer to the device
documentation to determine the offset nulling methods your device provides.
Related concepts:
This method of bridge balancing compensates for the initial voltage in software. With
this method, NI-DAQmx measures the bridge while not under load. NI-DAQmx then
uses this measurement as the initial bridge voltage when scaling readings from the
bridge. This method is simple, fast, and requires no manual adjustments. The
disadvantage of the software compensation method is that the method does not
remove the offset of the bridge. If the offset is large enough, it limits the amplifier gain
you can apply to the output voltage, thus limiting the dynamic range of the
measurement.
592 ni.com
Measurement Fundamentals
The third method, like the software compensation method, does not affect the bridge
directly. A nulling circuit adds an adjustable DC voltage, positive or negative, to the
output of the instrumentation amplifier to compensate for initial bridge offset.
You can verify the output of a bridge-based measurement system by comparing the
measured bridge output with a calculated value if the physical load on the sensor is
known. NI-DAQmx can then use the difference (if any) between the calculated and the
measured values as a gain adjustment factor for each measurement. You can simulate
applying a load to the bridge by connecting a large known resistor in parallel with the
bridge. This resistor, called a shunt resistor, offsets the zero voltage of the bridge.
Because the value of the shunt resistor is known, you can calculate the physical load
corresponding to the voltage drop of the resistor.
Use the DAQmx Perform Shunt Calibration VI/function or the DAQ Assistant to perform
a shunt calibration, which sets the gain adjustment for a virtual channel. NI-DAQmx
then uses this gain adjustment when scaling readings from the bridge. Some NI
products include internal shunt resistors.
Related concepts:
Sensors for measuring force, pressure, and torque, such as a load cell, are often based
on a Wheatstone bridge. These sensors typically use a full-bridge configuration with a
350 Ω nominal bridge resistance.
electrical values scale to the physical phenomena the sensor measures. NI-DAQmx
provides several scaling types for scaling data according to the specifications provided
by the sensor manufacturer.
Related concepts:
• Bridge-Based Sensors
• Bridge Configurations
• Bridge Scaling Types
NI-DAQmx provides three methods to scale electrical values (voltage ratios) from a
bridge-based sensor to physical units:
Note Strain gages use specific equations for scaling, depending on the
bridge configuration.
594 ni.com
Measurement Fundamentals
Related concepts:
Strain Gages
You can measure strain with a strain gage, which is a device with electrical resistance
that varies in proportion to the amount of strain in the device, and with signal
conditioning. When using a strain gage, you bond the strain gage to the device under
test, apply force, and measure the strain by detecting changes in resistance (Ω). Strain
gages return varying voltages in response to stress or vibrations in materials.
Resistance changes in parts of the strain gage to indicate deformation of the material.
Strain gages require excitation, generally voltage excitation, and linearization of the
voltage measurements.
Strain measurements rarely involve quantities larger than a few microstrain (µε).
Therefore, measuring strain requires accurate measurements of very small changes in
resistance. For example, if a test specimen undergoes a substantial strain of 500 µε, a
strain gage with a gage factor of 2 exhibits a change in electrical resistance of only 2 ×
(500 × 10 -6 ) = 0.1%. For 120 Ω, this is a change of only 0.12 Ω.
NI-DAQmx supports measuring axial strain, bending strain, or both. While you can use
some similar configuration types to measure torsional strain, NI software scaling does
not support these configuration types. It is possible to use NI products to measure
torsional strain, but to properly scale these configuration types you must use a custom
scale with a bridge (V/V) or a custom voltage with excitation channel.
Gage Factor
quantitatively as the gage factor (GF). Gage factor is the ratio of the fractional change
in electrical resistance to the fractional change in length, or strain. The gage factor
must be the same for each gage in the bridge.
The gage factor for metallic strain gages is usually around 2. You can obtain the actual
gage factor of a particular strain gage from the sensor vendor or sensor
documentation.
Related concepts:
• Strain Rosette
• Signal Conditioning Requirements for Bridge-Based Sensors
• Bridge-Based Sensors
• Strain Gage Bridge Configurations
• Custom Scales
Related concepts:
• Bridge Configurations
• Quarter-Bridge Type I
• Quarter-Bridge Type II
• Half-Bridge Type I
• Half-Bridge Type II
• Full-Bridge Type I
• Full-Bridge Type II
596 ni.com
Measurement Fundamentals
Quarter-Bridge Type I
The following figure shows how to position a strain gage resistor in an axial
configuration for the quarter-bridge type I.
R4 (+ )
The following figure shows how to position a strain gage resistor in a bending
configuration for the quarter-bridge type I.
R4 (+ )
• A single active strain gage element mounted in the principle direction of axial or
bending strain.
• A passive quarter-bridge completion resistor, known as a dummy resistor, in
addition to half-bridge completion.
• Temperature variation decreasing the accuracy of the measurements.
• Sensitivity at 1000 µε is ~ 0.5 mVout / VEX input.
Related concepts:
RL
R1
R4 (+ )
+ RL
– +
VEX VCH
–
RL
R2 R3
The following equation converts voltage ratios to strain units for quarter-bridge
configurations.
–4Vr RL
strain( ) = 1+
GF(1+2Vr) Rg
where Vr is the voltage ratio that virtual channels use in the voltage-to-strain
conversion equation, GF is the gage factor, RL is the lead resistance, and Rg is the
nominal gage resistance.
Quarter-Bridge Type II
The following figure shows how to position a strain gage resistor in an axial
configuration for the quarter-bridge type II.
598 ni.com
Measurement Fundamentals
R 4 (+ )
R3
The following figure shows how to position a strain gage resistor in a bending
configuration for the quarter-bridge type II.
R 4 (+ )
R3
• One active strain gage element and one passive, temperature-sensing quarter-
bridge element, known as a dummy resistor. The active element is mounted in the
direction of axial or bending strain. The dummy gage is mounted in close thermal
contact with the strain specimen but is not bonded to the specimen, and is usually
mounted transverse, or perpendicular, to the principle axis of strain. This
configuration is often confused with the half-bridge type I configuration, but in the
half-bridge type I configuration, the R3 element is active and bonded to the strain
specimen to measure the effect of Poisson's ratio.
• Completion resistors which provide half-bridge completion.
• Compensation for temperature.
• Sensitivity at 1000 µε is ~ 0.5 mVout/ VEX input.
Related concepts:
RL
R2
R4 (+ )
+ RL
– +
VEX VCH
–
R2 R3
RL
The following equation converts voltage ratios to strain units for quarter-bridge
configurations.
–4Vr RL
strain( ) = 1+
GF(1+2Vr) Rg
where Vr is the voltage ratio that virtual channels use in the voltage-to-strain
conversion equation, GF is the gage factor, RL is the lead resistance, and Rg is the
nominal gage resistance.
Half-Bridge Type I
The following figure shows how to position strain gage resistors in an axial
configuration for the half-bridge type I.
R4 (+ )
R3 ( )
600 ni.com
Measurement Fundamentals
The following figure shows how to position strain gage resistors in a bending
configuration for the half-bridge type I.
R4 (+ )
R3 ( )
• Two active strain gage elements, one mounted in the direction of axial strain and
the other acting as a Poisson gage and mounted transverse, or perpendicular, to
the principal axis of strain.
• Completion resistors which provide half-bridge completion.
• Sensitivity to both axial and bending strain.
• Compensation for temperature.
• Compensation for the aggregate effect on the principle strain measurement due to
the Poisson's ratio of the material.
• Sensitivity at 1000 µε is ~ 0.65 mVout/ VEX input
Related concepts:
RL
R1
R 4 (+ )
+ RL
– +
VEX VCH
–
R2 R 3 (– )
RL
effect (–ε).
• R4 is the active strain gage element measuring tensile strain (+ε).
• VEX is the excitation voltage.
• RL is the lead resistance.
• VCH is the measured voltage.
The following equation converts voltage ratios to strain units for half-bridge type I
configurations.
–4Vr RL
strain( ) = 1+
GF[(1+ )–2Vr( –1)] Rg
where Vr is the voltage ratio that virtual channels use in the voltage-to-strain
conversion equation, GF is the gage factor, v is the Poisson's ratio, RL is the lead
resistance, and Rg is the nominal gage resistance.
Half-Bridge Type II
The half-bridge type II configuration only measures bending strain.
R 4 (+ )
R 3 (– )
The following figure shows how to position strain gage resistors in a bending
configuration for the half-bridge type II.
602 ni.com
Measurement Fundamentals
R4 (+ )
R3 ( )
• Two active strain gage elements, one mounted in the direction of axial strain on
the top side of the strain specimen and the other mounted in the direction of axial
strain on the bottom side.
• Completion resistors which provide half-bridge completion.
• Sensitivity to bending strain.
• Rejection of axial strain.
• Compensation for temperature.
• Sensitivity at 1000 µε is ~ 1 mVout / VEX input.
Related concepts:
RL
R1 R4 (+ )
+ RL
– +
VEX VCH
–
R2 R3 (– )
RL
The following equation converts voltage ratios to strain units for half-bridge type II
configurations.
–2V r RL
Strain( ) =
GF
(1+ Rg
)
where Vr is the voltage ratio that virtual channels use in the voltage-to-strain
conversion equation, GF is the gage factor, RL is the lead resistance, and Rg is the
nominal gage resistance.
Full-Bridge Type I
The full-bridge type I configuration only measures the bending strain.
R2
R1
R4
R3
The following figure shows how to position strain gage resistors in a bending
configuration for the full-bridge type I.
R2 (+ )
R1 (– )
R4 (+ )
R3 (– )
• Four active strain gage elements, two mounted in the direction of bending strain
on the top side of the strain specimen and the other two mounted in the direction
604 ni.com
Measurement Fundamentals
Related concepts:
R1 (– ) R4 (+ )
+ – +
VEX VCH
–
R2 (+ ) R3 (– )
The following equation converts voltage ratios to strain units for full-bridge type I
configurations.
–V r
Strain( ) =
GF
where Vr is the voltage ratio that virtual channels use in the voltage-to-strain
conversion equation, and GF is the gage factor.
Full-Bridge Type II
The full-bridge type II configuration only measures bending strain.
R4
R1
R3
R2
The following figure shows how to position strain gage elements in a bending
configuration for the full-bridge type II.
R4 (+ )
R1 ( )
R3 ( )
R2 (+ )
• Four active strain gage elements. Two are mounted in the direction of bending
strain with one on the top side of the strain specimen and the other on the bottom
side. The other two act together as a Poisson gage and are mounted transverse, or
perpendicular, to the principal axis of strain with one on the top side of the strain
specimen and the other on the bottom side.
• Rejection of axial strain.
• Compensation for temperature.
• Compensation for the aggregate effect on the principle strain measurement due to
the Poisson's ratio of the material.
• Compensation for lead resistance.
606 ni.com
Measurement Fundamentals
Related concepts:
R1 (– ) R4 (+ )
+ – +
VEX VCH
–
R2 (+ ) R3 (– )
• R1 is the active strain gage element measuring compressive Poisson effect (–ε).
• R2 is the active strain gage element measuring tensile Poisson effect (+ε).
• R3 is the active strain gage element measuring compressive strain (–ε).
• R4 is the active strain gage element measuring tensile strain (+ε).
• VEX is the excitation voltage.
• RL is the lead resistance.
• VCH is the measured voltage.
The following equation converts voltage ratios to strain units for full-bridge type II
configurations.
–2V r
Strain( )=
GF( +1)
where Vr is the voltage ratio that virtual channels use in the voltage-to-strain
conversion equation, GF is the gage factor, and v is the Poisson's ratio.
R2 (+ )
R1 ( )
R4 (+ )
R3 ( )
The full-bridge type III configuration only measures the axial configuration.
R2
R1
R4
R3
Full-bridge type III strain gage configurations have the following characteristics:
• Four active strain gage elements. Two are mounted in the direction of axial strain
with one on the top side of the strain specimen and the other on the bottom side.
The other two act together as a Poisson gage and are mounted transverse, or
perpendicular, to the principal axis of strain with one on the top side of the strain
specimen and the other on the bottom side.
• Compensation for temperature.
• Rejection of bending strain.
• Compensation for the aggregate effect on the principle strain measurement due to
the Poisson's ratio of the material.
• Compensation for lead resistance.
• Sensitivity at 1000 µε is ~ 1.3 mVout / VEX input.
Related concepts:
608 ni.com
Measurement Fundamentals
R 1 (– ) R 4 (+ )
+ – +
VEX VCH
–
R 2 (+ ) R 3 (– )
• R1 is the active strain gage element measuring compressive Poisson effect (–ε).
• R2 is the active strain gage element measuring tensile strain (+ε).
• R3 is the active strain gage element measuring compressive Poisson effect (–ε).
• R4 is the active strain gage element measuring the tensile strain (+ε).
• VEX is the excitation voltage.
• RL is the lead resistance.
• VCH is the measured voltage.
The following equation converts voltage ratios to strain units for full-bridge type III
configurations.
–2V r
Strain( )=
GF[( +1)–V r ( –1)]
where Vr is the voltage ratio that virtual channels use in the voltage-to-strain
conversion equation, GF is the gage factor, and v is the Poisson's ratio.
Strain Rosette
A strain gage can measure strain in only one direction—the axis along which the strain
gage is mounted. To effectively measure the three independent components of plane
strain (extensional strain along X and Y axis, as well as shear strain), three independent
strain measurements are needed. Strain gage rosettes are used to perform such
measurements.
A strain gage rosette is an arrangement of two or three closely positioned strain gages,
separately oriented to measure the strains along different directions of the underlying
• Tee Rosette—A tee rosette consists of two gages oriented at 90 degrees with
respect to each other.
• Rectangular Rosette—A rectangular rosette consists of three strain gages, each
separated by a 45 degree angle.
• Delta Rosette—A delta rosette consists of three strain gages, each separated by a
60 degree angle.
Related concepts:
• Strain Gages
Eddy current proximity probes contain a driver and a monitor or regulated DC supply.
The monitor or DC supply applies a power input of -24 VDC to the driver. The driver's
internal oscillator converts some of the energy into a high-frequency radio signal. The
signal is directed to the probe coil through a coaxial cable. The coil at the tip of the
probe broadcasts the signal as a magnetic field into the surrounding area. If a
conductive material intercepts the magnetic field, eddy currents are generated and the
high-frequency radio signal loses power. The closer the conductive material is to the
probe tip, the more power the signal loses. This power loss triggers a change in the
voltage of the driver.
610 ni.com
Measurement Fundamentals
Differential Voltage
Sensitivity =
Differential Gap
You can calculate the sensitivity by measuring two points in the sensor's dynamic
range, using the following formula:
Offset voltage can occur when the tip of the probe touches the conductive material.
Use the following formula to determine the offset voltage where offset is the output
voltage of the sensor when the tip contacts the conductive material. In most cases,
offset should be 0 V.
After you calibrate your proximity probe, you need to update the sensitivity and offset
attributes. You can determine the physical distance between the sensor's tip and the
target material by using the following formula:
Encoders
There are two common types of encoders used for measuring position: two-pulse
encoders and quadrature encoders.
Related concepts:
• Two-Pulse Encoders
• Quadrature Encoders
Quadrature Encoders
Quadrature encoders measure position by causing two signals to pulse while the
encoder moves. These signals are signal A (also called channel A) and signal B (also
called channel B). Signal A and B are offset by 90°, which determines the direction the
encoder moves. For instance, in an angular quadrature encoder, if signal A leads, the
encoder rotates clockwise. If signal B leads, the encoder rotates counter clockwise.
Counters on M Series, C Series, NI-TIO devices support three types of decoding for
quadrature encoders: X1, X2, and X4. With X1 decoding, when signal A leads signal B,
the counter increments on the rising edge of signal A. When signal B leads signal A, the
counter decrements on the falling edge of signal A.
Signal A
Signal B
Counter
Value 5 6 7 7 6 5
With X2 decoding, the same behavior holds as with X1, except the counter increments
and decrements on both rising and falling edges of signal A.
Signal A
Signal B
Counter
Value 5 6 7 8 9 9 8 7 6 5
Similarly, with X4 decoding, the counter increments and decrements on both rising
and falling edges of both signal A and signal B. X4 decoding is more sensitive to
position, but is also more likely to provide an incorrect measurement if there is
vibration in the encoder.
Signal A
Signal B
Counter
5 6 7 8 9 10 11 12 13 13 12 11 10 9 8 7 6 5
Value
Many encoders also use z indexing for precise determination of a reference position.
Related concepts:
• Z Indexing
612 ni.com
Measurement Fundamentals
Two-Pulse Encoders
A two pulse encoder is a position measurement sensor that has two channels, A and B.
When the encoder is moved, either signal A or signal B on the encoder pulses. A pulse
on signal A represents a movement in one direction, and a pulse on signal B represents
movement in the opposite direction. When signal A pulses, the counter increments.
When signal B pulses, the counter decrements.
Signal A
Signal B
Count 1 2 3 2 1 0
Many encoders also use z indexing for precise determination of a reference position.
Related concepts:
• Z Indexing
Z Indexing
Encoders typically use a third signal for Z indexing, which produces a pulse at fixed
positions that you can use for precise determination of a reference position. For
instance, if the Z index is 45° for an angular encoder, the encoder sends a pulse on the
Z input terminal every time the encoder is turned to the 45° mark.
The behavior of signal Z differs with designs. You must refer to the documentation for
an encoder to obtain the timing of signal Z in relation to the A and B signals. In NI-
DAQmx, you can configure Z indexing with the Z Index Phase attribute/property.
Accelerometers
Both types of accelerometers come with either both leads insulated, or isolated, from
the case or with one lead grounded to the case. Some accelerometers rely on the
piezoelectric effect to generate voltage. To measure acceleration with this type of
sensor, the sensor must be connected to a charge-sensitive amplifier.
When choosing an accelerometer, pay attention to the most critical parameters. If the
sensor must operate in extreme temperatures, you are limited to a sensor that relies
614 ni.com
Measurement Fundamentals
• If the sensor is DC coupled, the DC offset of the accelerometer can drift with both
temperature and age. This applies to both types of sensors because charge-
sensitive amplifiers are prone to drift. AC coupling the output of the amplifier can
minimize the drift in the system.
• Motors, transformers, and other industrial equipment can induce noise currents in
the sensor cables. These currents can be an especially large source of noise with
sensor systems that rely on the piezoelectric effect to generate voltage. Carefully
routing sensor cables can minimize the noise in the cables.
• Accelerometers might have ground loops. Some accelerometers have their cases
tied to a sense wire, while others are completely isolated from their cases. If you
use a case-grounded sensor in a system with a grounded input amplifier, you set
up a large ground loop, creating a source of noise.
Related concepts:
• Velocity Transducers
Piezoelectric force sensors are typically used to measure dynamic force events. Such
sensors are divided into two main categories: load cells and impact hammers.
Piezoelectric load cells measure the amount of force transmitted through the sensor in
response to an external stimulus, such as shaking or an impact.
Impact hammers allow you to apply an impact to a material and measure the actual
amount of force applied. You can then correlate that force to the force measured by a
load cell or to readings from accelerometers. Impact hammers can use tips of different
size, shape, or material for measuring different frequencies.
Sensor manufacturers make load cells and impact hammers with varying sensitivity
and other characteristics. Refer to the documentation from your sensor manufacturer
for specifications and theory of operation for your load cell or impact hammer.
Sensor Calibration
Force sensors can drift from their documented sensitivity over time. Calibrating a force
sensor involves determining its actual sensitivity. Use ratio calibration with a
calibrated accelerometer to determine the actual sensitivity of a force sensor.
Related concepts:
• Accelerometers
• Velocity Transducers
Microphones
AP
616 ni.com
Measurement Fundamentals
The major characteristics of a microphone are its sensitivity, usually expressed in mV/
Pa, and its frequency response. Microphones are available in different diameters.
Common diameters include: 1/8 in., 1/4 in., 1/2 in., and 1 in. Each diameter offers a
specific compromise in terms of sensitivity and frequency response.
• For measurements in a free field (a sound field with no major nearby reflections),
use a free-field microphone pointed at the source of sound.
• For measurements in a diffuse field, such as inside in a highly reverberant room,
where sound is coming from all directions, use a random incidence microphone.
• For measurements when the microphone is part of the surface of a room or of the
object being measured, use a pressure microphone.
• For outdoor measurements, fit the microphone with suitable protection against
the environment. This may include windscreens, rain caps, and built-in heaters to
prevent condensation.
• To prevent vibrations from influencing the measurement, you might need to shock
mount the microphone. Check the microphone specifications for vibration
sensitivity.
• For reproducible measurements, make sure the microphone is mounted firmly and
at a precisely reproducible location, both compared to the unit being tested and to
the environment.
• Always calibrate the entire measurement chain, including the microphone, before
starting the measurement. For highly critical measurements, as an extra
precaution, you may want to perform a new calibration immediately after the
measurements are completed to make sure the system is still within tolerances.
Velocity Transducers
Velocity transducers are used to measure dynamic velocity such as that produced by a
running machine or a vibrating structure.
Older velocity probes use a moving coil in a permanent magnetic field to generate a
signal that is proportional to the velocity of the vibration.
Sensor manufacturers make IEPE velocity transducers with varying sensitivity and
other characteristics. Use a sensor appropriate for your application.
Related concepts:
• Thermocouples
• Resistance Temperature Detectors (RTDs)
• Thermistors
618 ni.com
Measurement Fundamentals
Numerous types of RTDs exist, and they are typically defined by their material, their
nominal resistance, and their temperature coefficient of resistance (TCR). The TCR of
an RTD is the average temperature coefficient of resistance of the RTD from 0 to 100 °C
and is the most common method of specifying the behavior of an RTD. The TCR for
platinum RTDs is determined by the Callendar-Van Dusen equation.
Related concepts:
The following table lists common platinum RTD types and standards. All of these RTD
types are supported in NI-DAQmx. Notice that there are some shared standards. The
TCR and the Callendar-Van Dusen coefficients are more important than the standards.
• IEC-751
• DIN 43760 • 100 • A = 3.9083 × 10-3
• BS 1904 Ω Most common
• ASTM-E1137
Platinum 3851
• 1000 • B = -5.775 × 10-7 RTDs
• EN-60751 Ω • C = -4.183 × 10-12
• IEC-60751
• A = 3.81 × 10-3
Low-cost vendor
compliant RTD66
Platinum 3750 1000 Ω • B = -6.02 × 10-7 Low-cost RTD
• C = -6.0 × 10-12
• A = 3.9739 × 10-3
Used primarily in
JISC 1604 1997 Platinum 3916 100 Ω • B = -5.870 × 10-7 Japan
• C = -4.4 × 10-12
• A = 3.9787 × 10-3
US Industrial Standard
D-100 American
Platinum 3920 100 Ω • B = -5.8686 × 10-7 Low-cost RTD
• C = -4.167 × 10-12
• A = 3.9692 × 10-3
US Industrial Standard
American
Platinum 3911 100 Ω • B = -5.8495 × 10-7 Low-cost RTD
• C = -4.233 × 10-12
• A = 3.9888 × 10-3
The definition of
ITS-90 Platinum 3928 100 Ω • B = -5.915 × 10-7 temperature
• C = -3.85 × 10-12
620 ni.com
Measurement Fundamentals
Related concepts:
Platinum RTDs use a linearization curve known as the Callendar-Van Dusen equation
to measure the temperature of RTDs. The equation is as follows:
R T = R0[1 + A × T + B × T2]
Where:
Related concepts:
Thermistors
A thermistor is a piece of semiconductor made from metal oxides, pressed into a small
bead, disk, wafer, or other shape, heated at high temperatures, and coated with epoxy
or glass.
Like RTDs, by passing a current through a thermistor, you can read the voltage across
the thermistor and thus determine its temperature. Unlike RTDs, thermistors have a
higher resistance (anywhere from 2,000 to 10,000 Ω) and a much higher sensitivity
(~200 Ω/°C). However, thermistors are generally used only up to the 300 °C
temperature range.
where T is the temperature in Kelvins, R is the measured resistance, and A, B, and C are
constants provided by the thermistor manufacturer.
Because thermistors have high resistance, lead-wire resistance does not affect the
accuracy of the measurements. Unlike RTDs, 2-wire measurements are adequate.
For more information about the signal conditioning requirements of a thermistor, refer
to Signal Conditioning Requirements for Thermistors and RTDs.
Related concepts:
• Current Excitation—Because RTDs and thermistors are resistive devices, your DAQ
system must provide a current excitation source to measure a voltage across the
device. This current source must be constant and precise.
• 2-, 3-, and 4-Wire Configurations (RTDs only)—RTDs come in 2-, 3-, and 4-wire
configurations. Therefore, your system must support the type of RTD you choose.
Thermistors are typically 2-wire devices because they have higher resistance
characteristics, thus eliminating lead resistance considerations.
• Linearization —Neither RTD nor thermistor output voltage is linear with
temperature. Therefore, your system must perform linearization either in hardware
or software.
622 ni.com
Measurement Fundamentals
Related concepts:
• 2-Wire Resistance
• 3-Wire Resistance
• 4-Wire Resistance
Thermocouples
A thermocouple is created when two dissimilar metals touch and the contact point
produces a small open-circuit voltage that corresponds to temperature. This
thermoelectric voltage is known as Seebeck voltage and is nonlinear with respect to
temperature. Thermocouples require signal conditioning.
Temperature Range
Temperature Range (°C) for
Thermocouple Positive Negative (°C) for Inverse
Polynomial Coefficients or
Type Conductor Conductor Polynomial
for Table Conversion
Coefficients
J Iron Constantan -210 to 1200 -210 to 1200
K Chromel Alumel -270 to 1372 -200 to 1372
N Nicrosil Nisil -270 to 1300 -200 to 1300
Platinum-13%
R Platinum -50 to 1768 -50 to 1768
Rhodium
Platinum-10%
S Platinum -50 to 1768 -50 to 1768
Rhodium
T Copper Constantan -270 to 400 -200 to 400
B Platinum Rhodium 0 to 1820 250 to 1820
E Chromel Constantan -270 to 1000 -200 to 1000
Use the temperature ranges for polynomial coefficients when converting temperature
to voltage. For most thermocouples, the equation used for converting temperature to
voltage is the following:
n
i
VR = ci t 90
i=0
where E is the voltage in millivolts, t90 is the temperature in degrees Celsius, and ci is
the coefficient.
Use the temperature ranges for inverse polynomial coefficients when converting
voltage to temperature. For most thermocouples, the equation for converting voltage
to temperature is the following:
n
i
t 90 = Di E
i=0
where t90 is the temperature in degrees Celsius, E is the voltage in millivolts, and Di is
the coefficient.
Note For coefficients to use with each thermocouple type, visit the NIST
ITS-90 thermocouple database available at nist.gov.
Related concepts:
Related information:
• nist.gov
624 ni.com
Measurement Fundamentals
accurately with a standard 12-bit measurement device. Alternatively, you can use a
measurement device with a high-resolution ADC. NI recommends a device with 16
bits of resolution and amplification capabilities or a device with 24 bits of
resolution.
• Cold-Junction Compensation—Thermocouples require some form of temperature
reference to compensate for unwanted parasitic thermocouples. A parasitic
thermocouple is created when you connect a thermocouple to an instrument.
Because the terminals on the instrument are made of a different material than the
thermocouple wire, voltage is created at the junctions, called cold junctions, which
changes the voltage output by the actual thermocouple.
T1
Isothermal
Region Ice Bath
Temp = 0° C
Copper
Metal 1
Metal 2
LVDTs
LVDTs operate on the principle of a transformer and consist of a stationary coil
LVDTs require special electronics designed for the sensor. LVDTs typically have a delay
of approximately 10 ms caused by filtering in the signal conditioner.
LVDTs typically come in 4-wire, or open wire, and 5-wire, or ratiometric wire,
configurations. Wires from the sensor connect to a signal conditioning circuit that
translates the output of the LVDT to a measurable voltage. The method of signal
conditioning used on the signals from the first and second secondaries differentiate
the 4-wire and 5-wire configurations. In the 4-wire configuration, the sensor only
measures the voltage difference between the two secondaries.
The benefit of using a 4-wire configuration is that you require a simpler signal
conditioning system. However, temperature changes can alter the efficiency of the
magnetic induction of the LVDT. Because the 4-wire scheme is also sensitive to phase
changes between the primary and the resulting secondary voltage, long wires or a
poor excitation source also can cause problems.
The 5-wire configuration is less sensitive to both temperature changes and phase
differences between the primary and the secondaries. The device determines phase
information at the signal conditioning circuitry without needing to reference the phase
of the primary excitation source. Therefore, you can use longer wires between the
LVDT and the signal conditioning circuitry.
LVDTs are extremely rugged, operate over wide temperature ranges, and are
insensitive to moisture and dirt. LVDTs are a preferred sensor in harsh environments,
where very long life is needed because there are no moving parts in contact or where
very low friction is required. Also, LVDT technology lends itself well to applications
requiring accurate measurements less than 0.1 in., such as measuring the thickness of
sheet material. The main advantage of the LVDT transducer over other types of
displacement transducer is the high degree of robustness. Because there is no physical
contact across the sensing element, there is no wear in the sensing element.
626 ni.com
Measurement Fundamentals
Because the device relies on the coupling of magnetic flux, an LVDT can have infinite
resolution. Therefore, suitable signal conditioning hardware can detect the smallest
fraction of movement, and only the resolution of the data acquisition system
determines the resolution of the transducer.
RVDTs
RVDTs are the rotational version of LVDTs and generally operate over an angular range
of ±30°–70°. They are available in servo-mount and can rotate through 360° without
stopping.
RVDTs require special electronics designed for the sensor. RVDTs typically have a delay
of 10 ms caused by required filtering in the signal conditioner. They are extremely
rugged and operate over wide temperature ranges. In environments characterized by
extremes in temperature and shock, an RVDT is the clear choice for rotational
applications when you need more than 70° of measurement range.
Related concepts:
• LVDTs
• A TEDS can reside in embedded memory, typically an EEPROM, within the sensor.
To download a TEDS from the sensor, you need TEDS-supported hardware such as
the BNC-2096 or the SCXI-1314T. You can then download the TEDS in MAX to use in
your application. Refer to the Measurement & Automation Explorer Help
Use the Write TEDS Data function/VI to write data to a TEDS sensor. The TEDS data
must be in a virtual TEDS file or in a bitstream constructed according to the IEEE 1451.4
specification.
National Instruments provides a LabVIEW library for viewing and editing TEDS
bitstreams and virtual TEDS files. You can download the TEDS Library for LabVIEW at
How Do I Install the TEDS Library into LabVIEW?.
Related concepts:
Some TEDS sensors include a PROM, to which you can write data one time. When you
write TEDS data, you can choose to write basic TEDS data to the PROM or to the
EEPROM. Basic TEDS data includes the manufacturer ID, model number, serial
number, version number, and version letter. If you write basic TEDS data to the PROM,
the Write TEDS Data function/VI returns an error if you later attempt to write basic
TEDS data to the EEPROM.
Control Overview
In a typical control application, there are one or more process variables that you want
to control, such as temperature. Sensors measure the process variable in the dynamic
system and provide the data to the control application. The set point is the value you
want for the process variable. A comparator determines if a difference exists between
the process variable and the set point. If a difference exists and if the control system
628 ni.com
Measurement Fundamentals
deems the difference large enough, the compensator processes the data and
determines the desired actuator output to drive the system closer to the set point.
Comparator
Actuator System
Set Point + – Compensator
Output (Plant)
Process
Variable
Measurement
Related concepts:
• Proportional-Integral-Derivative (PID)
• Real Time
• Loop Cycle Time
• Jitter Overview for Control Applications
• Event Response
Proportional-Integral-Derivative (PID)
The Proportional-Integral-Derivative (PID) algorithm is the most common control
algorithm used in industry. Often, people use PID to control processes that include
heating and cooling systems, fluid level monitoring, flow control, and pressure control.
In PID control, you must specify a process variable and a setpoint. The process variable
is the system parameter you want to control, such as temperature, pressure, or flow
rate, and the setpoint is the desired value for the parameter you are controlling. A PID
controller determines a controller output value, such as the heater power or valve
position. The controller applies the controller output value to the system, which in
turn drives the process variable toward the setpoint value.
Real Time
Real time means that responses occur in time, or on time. With non-real-time systems,
there is no way to ensure that a response occurs within any time period, and
operations may finish much later or earlier than expected. In other words, real-time
systems are deterministic, which guarantees that operations occur within a given time.
Real-time systems are predictable.
For a system to be a real-time system, all parts of it need to be real time. For instance,
even though a program runs in a real-time operating system, it does not mean that the
program behaves with real-time characteristics. The program may rely on something
that does not behave in real-time such as file I/O, which then causes the program to
not behave in real-time.
Related concepts:
630 ni.com
Measurement Fundamentals
Jitter
5
Loop Iteration
Time
Loop Period
In real-time systems, jitter is bounded. For instance, air bags must deploy within
fractions of a second after a critical impact and are thus bound to a maximum jitter. In
non-real-time systems, jitter is unbounded—or very large. Waiting for a bus is an
example. Suppose that according to the schedule, the bus is supposed to arrive at
11:00 a.m. but actually arrives at 11:05 a.m. one day, 11:30 a.m. the next day, and has a
flat tire the day after that. There is no bound on how late the bus could arrive.
Related concepts:
Event Response
Event response applications require a response to a stimulus in a determined amount
of time. An example is monitoring the temperature of an engine. When the
temperature rises too high, the engine is slowed down. The event, in this case, is the
temperature rising above a predetermined level, and the response is the engine
slowing down. Another example comes from manufacturing. In a manufacturing line, a
system senses when a part is in front of a station (the event) and takes a reading or
manipulates the part (the response). If the system does not sense and respond to the
presence of that part in a set amount of time, the manufacturing line creates defective
parts.