JB-TB-TC5109 control panel manual Ver3.3
JB-TB-TC5109 control panel manual Ver3.3
CONTENTS
Preface.......................................................................................................................................................................................... 5
Section 1 Brief Introduction..........................................................................................................................................................6
1.1 Features.......................................................................................................................................................................... 6
1.2 Flexible Modularized Structure and Available Multifunction Configuration.................................................................6
1.3 Certification instructions................................................................................................................................................ 6
Section 2 Technical Features.........................................................................................................................................................8
2.1 Operating Voltage...........................................................................................................................................................8
2.2 Battery............................................................................................................................................................................ 8
2.3 Detection of Loop Parameters........................................................................................................................................8
2.4 Output Circuit Parameters..............................................................................................................................................8
2.5Communication Parameters...................。....................................................................................................................9
2.6 Current.........................................................................................................................................................................9
Section 3 Structure and Configuration Instructions...................................................................................................................10
3.1 Typical Components and Interior Construction........................................................................................................... 10
3.2 control panel Description............................................................................................................................................. 11
3.3 Interior Construction and Wiring................................................................................................................................. 15
3.4 Component................................................................................................................................................................... 17
3.5 Outside Devices............................................................................................................................................................ 19
Section 4 Installation and Commission...................................................................................................................................... 21
4.1 Open-case Inspection................................................................................................................................................... 21
4.2 Cabinet Installation.......................................................................................................................................................21
4.3 Start-up Check.............................................................................................................................................................. 22
4.4 Peripheral Devices Inspection...................................................................................................................................... 23
4.5 Connection and Setup.................................................................................................................................................. 23
4.6 Power Connection........................................................................................................................................................ 23
4.7 Commission.................................................................................................................................................................. 25
Section 5 General User Instructions...........................................................................................................................................25
5.1 Start-up, Shut-down and Self-test................................................................................................................................25
5.2 Keypad Operation Preparation.....................................................................................................................................26
5.3 Operation Level.............................................................................................................................................................27
5.4 Device Registration and Registration Inspection......................................................................................................... 27
5.5 Information Display and History Log............................................................................................................................ 30
5.6 Mute..............................................................................................................................................................................36
5.7 Fire alarm and fault handling....................................................................................................................................... 36
5.8 Disable and enable equipment.................................................................................................................................... 37
5.9 Offcable Programming..................................................................................................................................................39
5.10 Message Display Rules................................................................................................................................................40
5.11 Reset Function............................................................................................................................................................ 41
Chapter Six System Administrator Manual................................................................................................................................ 41
6.1 Time Setup....................................................................................................................................................................41
6.2 Print Setup.................................................................................................................................................................... 41
6.3 Language Setup............................................................................................................................................................ 42
6.4 Device Definition.......................................................................................................................................................... 42
6.5 Display Panel Setup...................................................................................................................................................... 44
China·Liaoning·Yingkou Tiancheng Fire Protection Equipment Co., Ltd. 3
Instruction Manual for Installation and Application of JB-TB-TC5109 Intelligent Fire Alarm control panel Ver. 3.3 2019.6
Preface
JB-TB-TC5109 Intelligent Fire Alarm control panel is a new generation of alarm control panel that is
designed and developed by our company through researching the fire-fighting market demand and
summarizing the fire engineering experience for many years.
This control panel adopts wall-mounted and modular design. And it has features of strong function,
high reliability and flexible configuration. The system adopts large screen and color LCD display. The printer
can print all system information, such as fire alarm, fault and so on. It is compatible with a series of TC
addressable products, which are intelligent detectors, sounder strobe, LCD repeater panel, etc. It is the best
option of fire protection engineering.
Refer to the corresponding installation manuals for detailed technical parameters and installation
instructions of detectors, modules and other accessory devices.
This manual should be in charge of specially-assigned personnel carefully in order to be uses in the
future.
1.1 Features
The CIE can have up to 48 zones, which can be distributed in one or more loops , with alarm and
fault/disable indicators.
1-4 loops can be selected, with a maximum of 255 addressable points for a single loop, Max
totaling 1020 addressable points including but not limited sounder strobe (TCSG5266) under
EN54-3, addressable heat detector (JTW-ZOM-TC5162) under EN54-5, addressable photoelectric
smoke detector (JTW-ZOM-TC5161) under EN54-7, manual call point (J-SAP-TCSB5264) under
EN54-11,I/O module (TCMK5263) under EN54-18 and loop isolator (TCMK5260) under EN54-17.
High-speed processor has been used in this control panel with faster data processing speed and
larger data capacity.
7-inch color LCD screen with display resolution of 800 × 480. Information is more visual.
Block terminals are all pluggable with clear marks, which is convenient for installation, commission
and maintaining.
Programming can be operated on the panel or by computer.
The loop has strong anti-interference performance and the system is stable and reliable,
convenient for field operating and commissioning.
Super data capability, available for 2000 pieces of information of each fire alarm, faults and etc.
Multi-operation levels have been applied on this control panel. Each level applies to variety
operations which are protected by passwords, with the second level password of three digits and
the third level password of six digits.
The control panel is capable of detecting faults from points (smoke detectors)as EN54-2 Clause 8.3.
The panel is formed up by various multifunctional modules which adopts plug-pull structure making
configuration flexible and convenient installation easy and system commission and later capacity expansion
with ease.
The JB-TB-TC5109 Intelligent Fire Alarm control panel complies with the basic requirements of
the standard EN54-2: 1997 +A1:2006 and EN54-4:1998. In addition to these basic requirements, the
JB-TB-TC5109 meets the following standard optional requirements.
The control panel meets the standard EN54-2 with the following options:
Voltage: AC230V
Frequency: 50HZ
Current: 1A
Recommended wiring: Fire cable not less than 1.5mm2
2.2 Battery
Loop output: Polarization signal cable from control panel connected to 255 addressable devices
Loop input: Polarization signal cable returns control panel
Output voltage: 18V ~ 26.5V pulse
Output current: 0mA ~ 220mA
Cycle Type: A cycle
Recommended cable: Fireproof cable, connecting cable cross-sectional zone≥1.0mm2; cable length≤
1000m.All LPCB approved fireproof cables
See Fig. 3-7 Terminal block diagram. The detailed wiring instructions for Fig. 3.3.2
Loop resistance, number of isolators: loop resistance <50Ω, isolator <20 pcs
Recommended cable: Twisted pair, connecting cable cross-sectional zone ≥ 1.0mm2; cable length ≤
1000m.All LPCB approved fireproof cables
See Fig. 3-7 Terminal block diagram. The detailed wiring instructions for Fig. 3.3.2.
Recommended cable: Twisted pair, connecting cable cross-sectional zone ≥ 1.0mm2; cable length ≤
1000m.All LPCB approved fireproof cables
2.5.2 RS485 interface(A1 B1,A2 B2)
Recommended cable: Twisted pair, connecting cable cross-sectional zone ≥ 1.0mm2; cable length ≤
1000m.All LPCB approved fireproof cables
2.6 Current
JB-TB-TC5109 control panel is wall-mounted, and the typical components include: main panel,
zone/FPE display panel, power supply, etc. This control panel sets the function of fire alarm and linkage in
one, which can not only alarm if there is any fire, but also start or stop the connected outside devices.
The appearance sketch diagram of JB-TB-TC5109 control panel is shown in Fig. 3-1:
Fig. 3-1
The sketch diagram of the control panel’s panel is shown in Fig. 3-1: display-operation zone and zone /
FPE display panel.
1) Display-operation zone
It is shown as in Fig. 3-2.
Fig. 3-2
The display-operation zone consists of LCD, LED indicators, keypad and printer. The descriptions of
LEDs are as follows:
Fire: Red. This indicator is on, indicating that the control panel detects that the field detectors or
manual call point is in a fire alarm state. For details, see the LCD display. After the fire alarm is removed,
press the “Reset” button to clear the fire alarm state, and the indicator will be removed at the same
time.
Fault: Yellow. It illuminates when control panel detects a fault of connected peripheral devices
(detector, module, or manual call point etc.) or itself; refer to specific information on LCD screen. After
fault is removed, the fault indicator goes out.
Active: Red. This indicator is on when the FPE device is active. This indicator goes out when there is no
FPE action.
Feedback: Red. When this indicator is on, the control panel receives the FPE device action feedback
signal. This indicator goes out when there is no feedback.
Power: Green. It illuminates when control panel is powered by main power or battery or both.
Main power fault: Yellow. It illuminates when no main power or PSE is damaged. After the main power
returns normal, this LED goes out.
Battery fault: Yellow. It illuminates when the battery has a fault. After the fault is removed, this LED
goes out.
Disable: Yellow. It illuminates when a loop device is disabled.
Sounder strobe fault: Yellow. It illuminates when there is any fault on the sounder strobe. After the
fault is removed, this LED goes out.
Sounder strobe disable: Yellow. It illuminates when sounder strobe is disabled.
Zone fault: Yellow. It flash when a point of a zone is in fault. After the fault is removed, this LED goes
out.
Zone disable: Yellow. It illuminates when all the points of a zone is disabled.
FPE fault: Yellow. It illuminates when there is any fault on FPE devices. After the fault is removed, this
LED goes out.
FPE disable: Yellow. It illuminates when FPE device is disabled.
Mute: Yellow. It illuminates when press Mute key, the buzzer stops. When there is a new alarm, the
LED goes out, and the control panel sounds again.
System fault: Yellow. It illuminates when there is a system fault. After the fault is removed, this LED
goes out.
Backup indicator: reserve 5 spare indicators. The indicator is shown in Figure 3-3.
Fig. 3-3
2) ZONE and FPE indication panel
It is shown as in Fig. 3-4.
Fig. 3-4
Description of ZONE and FPE indication panel:
1: Zone indicator panel: The panel displays 48 zone indicators. Each zone contains a fire alarm indicator
and a disable/fault indicator.
“Fire” indicator: red. When the zone detector or manual call point is in the fire alarm state, the
indicator illuminates; when the fire is removed and control panel is reset, the indicator goes out.
“Disable/Fault” indicator: yellow. When all the detectors and manual call points in the zone are
disabled, this indicator illuminates. when any detector or manual call point in fault, the indicator
flash. This indicator goes out when the detector or manual call point fault is removed.
2: FPE indicator panel: The panel displays 24 FPE status indicators, which display the FPE action
indicator and FPE feedback indicator and a label.
Label : Users can put the FPEdevice name on the label ;
“Active” indicator: Red. When the FPE device is activated, this indicator illuminates;
“Feedback” indicator: Red. When the FPE device feedback, this indicator illuminates;
3) Key-pad Description
China·Liaoning·Yingkou Tiancheng Fire Protection Equipment Co., Ltd. 13
Instruction Manual for Installation and Application of JB-TB-TC5109 Intelligent Fire Alarm control panel Ver. 3.3 2019.6
Fig. 3-5
press this button to manual register. When the control panel is in the printer setup operation
interface, press this button to set the printer status. When the control panel is in the FPE
setting interface, press this button to continue setting the FPE. When the control panel is in
the linkage programming interface, press this button to edit the next one.
“F2/down” key: it is for the loop state. When the system is in the fire alarm interface, you can
press the page to view the information. When the control panel is in the setup language
interface, press this button to set the control panel language. When the control panel is in the
device registration operation interface, press this button to manual cancel. When the control
panel is in the printer setup operation interface, press this button to set the printer status.
When the control panel is in the linkage programming interface, press this button to delete
the program.
“Silence” key: it is used to silence the sounder when it starts to sound. This feature requires
AL2. When the control panel is in the linkage programming interface, press this button to
enter "(".
“Resound” button: It is used to initiate sounder strobe that has been silenced. This feature
requires AL2. When the control panel is in the linkage programming interface, press this
button to enter ")".
"Operation Level" key: used to set the operating level of the system.
The arrow keys: They are used to move up and down to view each message. When the fire
alarm and fault are displayed on a screen, you can switch Windows by right key.
4) Printer description
The indicator (green) on the printer interface is to show the printer’s status. If the printer is
ready for printing, the indicator is on. If the printer is lack of paper, the indicator flashes. Key:
paper loading key (LF) and setting key (SET).
3.3.1 Construction
Fig. 3-6
1. Keyboard 2. Printer 3. Mainboard 4. Indicator board 5. zone and FPE indication board
6.Loop board 7. Loop base board 8.power supply board 9. Battery 10. Filter board 2
11. Filter board 1
relay is opened.)
CANL,CANH: control panel’s networking CAN bus, polarity-sensitive; Not to be used.
A1, B1: RS485 terminal, to connect CRT, polarity-sensitive; Not to be used.
A2, B2: RS485 terminal, as backup; Not to be used.
RGND: not to be used;
DC24V, GND: The output DC24V is used for FPEs or sounder strobes.
3.4 Component
operations.
Loop base board:
The loop board is installed inside the control panel cabinet. The power supply equipment and
battery are connected to the loop base board via a cable. The loop base board is the signal
connector of control panel, including the detection output connector, the loop connector, 485
loop connector and CAN loop connector, which set the devices on fields and control panel in one
as a complete fire alarm system.
Loop board
The loop card is installed on the loop board in a pluggable way, which can be connected with 255
addressable devices.
Zone and FPE indication board
The Zone and FPE indication board is installed on the back of the front panel of the control panel
and connected to the control panel board through a cable. The Zone and FPE indication board can
display the fire alarm, fault, disabled status of a zone and FPE action and feedback.
Indicator board
The indicator board is installed on the back of the front interface of the control panel, which is
connected to the mainboard through a cable for indication.
Keyboard
The keyboard is installed on the back of the front interface of the control panel, which is
connected to the mainboard through a cable.
Power supply equipment (PSE)
The power supply unit contains a power supply board that supplies power to the loop base board,
loop board, zone and FPE indicator board, printer, and so on. When the main power is lost, the
backup battery can provide power to the entire system to prevent loss of information due to
power loss.
Filter board 2
The filter board 1 is installed in the control panel cabinet, and is connected with the loop base
board through the cable to increase the anti-interference ability of the loop bus, and provides an
field bus interface of loop (3, 4).
Filter board 1
The filter board 2 is installed in the control panel cabinet, and is connected with the loop base
board through the cable to increase the anti-interference ability of the loop bus, and provides
field loop (1, 2) bus, RS485 bus and CAN bus interface, field fire output, field fault output, and
field output 24V.
3.4.2 Optional Component
Printer
The printer is installed on the back of the front interface of the control panel, consisted of a front
cover, a chassis, a print-head, a roll axis, and printing paper. There is also a paper loading key (LF),
setting key (SET) and an indicator.
RS 485 board
RS 485 board is pin-mounted on the main board of control panel, which is connected with CRT by
RS 485 communication.
CAN board
CAN board is pin-mounted on the main board of control panel, which is netted with other control
panel by CAN communication.
Fig.4-1
Control panel dimensions (length × width × height): 420mm × 140mm ×560mm. The control panel is
mounted on the wall through 4 mounting holes, the dimensions of the mounting holes are shown in Figure
4-1. The right side of the control panel has 8 wiring holes, which are easy for wiring between the control
panel and field devices.There are also 5 knock holes at the top, if the holes on the right side are not
enough.
4.2.2 Mounting conditions
Operating temperature: 0 ℃~ +40 ℃
Relative humidity ≤95%, non-condensing
Wall-mounted
The control panel should be powered in field in the state of power-on. The checking contents include:
Check LCD screen, digital tubes and LED indicators.
Check if the control panel can self-test. Check if LED indicators and digital tubes illuminate. And check if
the buzzer can give three loud alarm sounds.
Check if the control panel has power fault, all keys are normal, and the printer is normal.
China·Liaoning·Yingkou Tiancheng Fire Protection Equipment Co., Ltd. 22
Instruction Manual for Installation and Application of JB-TB-TC5109 Intelligent Fire Alarm control panel Ver. 3.3 2019.6
After checking the control panel and peripheral devices, if all checks meet with requirements, please
refer to Chapter 2 to connect peripheral devices to the control panel and set direct control panel and loop
control panel.
Fig. 4-2
4.6.2 Battery Connection
Please refer to the battery calculation part for the needed capacity of the battery. According to Fig. 4-3,
connect batteries and link the battery terminals.
Fig. 4-3
Note:
1. please do not connect the battery before the connection is completed.
2. Thermistors must be installed between the battery clip and the battery.
4.7 Commission
4.7.1 Connect wires to the control panel, check circuit and insulation resistance. When the resistance
between loop wires is about more than 5kΩ (loop is full-load) in a state of power off, measure whether the
insulation resistance between loop and ground is more than 20M. (Before measuring, connect two loop
wires in parallel, or it will destroy the loop devices.)
4.7.2 Install bases of detectors, modules, manual call point etc. and connect wires.
4.7.3 Encode the loop devices and install them on the bases.
4.7.4 Register loop devices and check. There should be no inaccurate information of the registration. If
there is a large loss, firstly check output power and loop isolator in each floor. And then check individual
device and register it again and then observe whether they are registered completely.
4.7.5 Write configuration program and linkage program.
4.7.6 Check detector’s fire alarm function, note text and field situation.
4.7.7 Automatic linkage test. If automatic linkage is abnormal, check manually modules first. If circuit and
module are normal, check the logical expression and peripheral devices.
4.7.8 Train the operator to use correct operating method. After the devices pass the acceptance inspection,
plunge the project into usage.
Fig. 5-1
① system time ②operation level
You can look through information one by one by pressing ▲ and ▼ or pressing “F1” (page up) or “F2”
(page down). Press “Cancel” key to exit to the upper level operation menu or system running screen.
The control panel has three operation levels, including “Level I”, “Level II” and “Level III”. When the
control panel is powered, the factory default is “Level I”. And at this time, you can press Mute key, Query
key and menu of Query setup to operate the control panel, and it will display “Operation level: I” on the
blow of the LCD screen. You can press User setup key, Self-test key, Reset key, Start key, Stop key, Disable key,
Enable key, Linkage mode key, Sounder strobe start/stop key and Spray control key to operate the control
panel by Level II. And you can operate the menus of System setup, Network setup and Linkage setup by
Level III.
Press Operation level key and then press number key to choose operation level, and the screen will
show Input password. So at this time, input the correct password and press Enter key, and then it will enter
the corresponding operation level to gain corresponding operating authority. If there is no operation in 30s,
it will be automatically back to Level I.
Fig. 5-2
On this page, press the number key 1, the system displays the number of registrations, bus current and
reference voltage of the 4 loops (Figure 5-2).
Fig. 5-3
For details on each loop, press the corresponding number keys “1”, “2”, “3”, “4” to enter the
corresponding loop information page (as shown in Figure 5-3).
Fig. 5-4
On the page shown in Figure 5-4, press the “F1” key to query the loop device information. The loop
device information page display includes: the device's own code, registration type, 2nd code, setting type,
device attribute and Chinese character comment information (The details please go for Device Definition
Chapter One). Press “▲” or “▼” to execute the previous and next query operations. The registration
type is the front-end bus device type; the device attribute is a type defined for the input module, including:
three types: fire alarm, feedback, and supervision.
On the page in Figure 5-4, press the “F2” key to browse the loop status and display the response
current of the bus device on this loop. According to this status table, it can be judged whether the loop
working status is normal.
5.4.3 Check the Information of Networking control panel
In the page shown in Figure 5-2, press the number key “2” to display the display networking
information with the control panel, which is convenient for the user to view. This operation is a level I
operation. As shown in Figure 5-5.
Fig. 5-5
Fig. 5-6
The first fire alarm information is “The First Fire Alarm”, which is always displayed on the front of the
China·Liaoning·Yingkou Tiancheng Fire Protection Equipment Co., Ltd. 30
Instruction Manual for Installation and Application of JB-TB-TC5109 Intelligent Fire Alarm control panel Ver. 3.3 2019.6
window. The last fire alarm information is displayed at the bottom of the fire alarm window. Press “▲”
or “▼” key to query each fire alarm information. Please click Enter to enter a zone for detailed fire
location information, press F1 (upward) and F2 (downward) to query by page.
The yellow bar displays fault information. The fault information categories are: zone fault, loop fault,
power fault,FPE fault system fault and sounder fault. The fault bar displays the last fault message at
the bottom. Press “▲” or “▼” key to query each fault information, or press F1 (upward) and F2
(downward) to query by page.
You can switch between the fire alarm status and the fault inquiry status by pressing the “▶” key.
Figure 5-7
The illustrations of example shown in Figure 5-7:
1. Fire Zone Sum: 0003:3 zones were hit by fire.
2.1st Zone-21: ZONE 21 is the first fire zone
3.0001 Zone-21 Sum 001: This fire alarm indicates that there is a fire in Zone 21, the fire alarm point in the
zone is No. 1, the fire time (hours, minutes) occurs, and then press the “enter” button to display the alarm
device in the zone (It displays: the 2nd code, loop, address, comment information). If it displays the page is
full, press F1 (up) or F2 (down) to query the former or latter page. The last message is displayed at the
bottom of each page.
4. Last Zone-23 Sum 001: This bar shows that the last fire in the fire alarm column is a fire in Zone 23.
China·Liaoning·Yingkou Tiancheng Fire Protection Equipment Co., Ltd. 31
Instruction Manual for Installation and Application of JB-TB-TC5109 Intelligent Fire Alarm control panel Ver. 3.3 2019.6
5. Fault Zone-06 Sum: 001 Total: This bar shows that there is a fault in Zone 6, and the number of points
in the zone is 1.
6.0001 FPE Sum 002: This fault indicates that the FPE device has failed, the number of FPE faults is 2,
and the fault time (hours, minutes). Then press the “enter” button to display the faulty FPE (the 2nd code,
loop, address, comment information). If it displays the page is full, press F1 (up) or F2 (down) to query the
former or latter page. The last message is displayed at the bottom of each page.
7. Last Zone-06 Sum: 001: This clause shows that the last fault message in the fault column is faulty in
Zone 6.
5.5.2 Disable Information Display
Press the “Query” button to press the number key “3. Disable” on each information page to enter the
disabled information query. The disabled information can be displayed: disable zone, disable point,
disabled sounder, disabled FPE, etc. To view each disabled information, press “▲” or “▼” to query by
bar, or press F1 (up) and F2 (down) to query by page. As shown in Figure 5-7 below:
Fig. 5-7
The Illustrations of the example shown in Figure 5-7:
1. Disable Zone Sum: 00001: This bar shows the total number of zone disabled is 1.
2. 0001 17/11/12 15:27 Zone-01 Sum 001 ALL: This bar shows the disabled information in zone 1, the total
number of disabled zone, the time of the disable (year, month, day, hour, minute) and then press "enter"
key, which can display the disabled information of zone device (display: 2nd code, loop, address). When the
China·Liaoning·Yingkou Tiancheng Fire Protection Equipment Co., Ltd. 32
Instruction Manual for Installation and Application of JB-TB-TC5109 Intelligent Fire Alarm control panel Ver. 3.3 2019.6
display page is full, you can press F1 (up), F2 (down) to query the information page by page. The last
message is displayed on the bottom of each page.
3. 0001 17/11/12 15:27 FPE Sum 002: This bar shows that the total number of FPE devices blocked is 2,
disabled time (year, month, day, hour, minute). Then press the “enter” button to display the disabled
information of FPE device (display: 2nd code, loop, address). When the display page is full, you can press F1
(up) and F2 (down) to query the information page by page. The last message is displayed at the bottom of
the page.
4. 0001 17/11/12 15:27 Sounder Sum 003: This bar shows that the total number of disabled sounders is 3,
disabled time (year, month, day, hour, minute). Then press the “enter” button to display the disabled
information of the sounder (display: 2nd code, loop, address). When the display page is full, you can press
F1 (upward) and F2 (downward) to query by page. The last message is displayed at the bottom of each
page.
5. Last 17/11/12 15:27 Sounder Sum 003: This item shows that the last message in the disabled information
bar is blocked by sounder.
Fig. 5-8
The illustrations of the example shown in Figure 5-9:
1. Start Sum: 0001: This bar shows the total number of linked device startups 1.
2. Feedback Sum: 0000: This bar shows the total number of feedbacks from the linkage device is 0.
3. 0001 02001046 01-46 In/Out 18:25 Room 104 ● : This bar shows the device type: single-input
single-out, Loop: 01, Address: 46, the 2nd code: 02001046, Note: Room 104, Status: Start.
5.5.4 View fire alarm history information
On the page shown in Figure 5-9, press the “1” button to select the fire alarm history and enter the
fire alarm history information page, as shown in Figure 5-10.
Fig. 5-9
Fig. 5-10
The system will display the fire alarm history information, and each piece of information includes the
time, loop, address, zone number, type, and Chinese character comment information of the recorded
information. Press “▲” or “▼” to view each fire history information.
5.5.5 View history
On the page in Figure 5-9, press the number “2” to select the history and enter the history information
page. The system will display the year/month/day/time of each message: system startup, system shutdown,
system reset, FPE startup, FPE Feedback, sound and indicator start, equipment failure, etc. Press “▲”,
“▼” to view each piece of history information.
5.5.6 View zone information
Press the “Menu” button to enter the main menu, and then press the number button “2” to enter the
setting query information interface. As shown in Figure 5-11.
Fig. 5-11
On the page shown in Figure 5-11, press the number “2” to select the zone information query and
enter the zone information display interface. You can press “ ◀” or “ ▶” to view the device information of
each zone. It can display the loop, address, type, 2nd code, comments and other information of each
device in each zone. Press “▲” or “▼” to execute the previous and next query device information
operations. As shown in Figure 5-12 below.
Fig. 5-12
5.5.7 FPE indicator query
On the page shown in Figure 5-11, press the number “4” to select the FPE information query and enter
the FPE information display interface to display the loop and address of each FPE device. Press “▲” or “▼”
to execute the previous and next query FPE device information operations. As shown in Figure 5-13 below
Fig. 5-13
5.6 Mute
When a fire or fault alarm occurs, the control panel's buzzer will sound a corresponding alarm. Press
the “mute” button, the buzzer will stop alarming, and the control panel LED panel will display the mute
indicator. If a new alarm occurs, the alarm sounds automatically again.
When there is a fire alarm signal, the control panel LED display panel fire alarm indicator is on, the
control panel buzzer sounds a fire alarm, and the corresponding indicator of the zone indication panel is
illuminated, and the control panel system displays the fire alarm information.
5.7.3 General treatment of fire alarms
When a fire occurs, first locate the location of the fire based on the information displayed on the
control panel and enter if a fire has occurred. If it is a false alarm, find out the cause and dispose of it as
appropriate; if it is entered that the fire has occurred, immediately organize the rescue work into the
following steps: The first step: enter the fire. Step 2: Evacuate the site personnel. Step 3: Call the fire
department. Step 4: Start the corresponding fire extinguishing device.
When an field device (detector, module, sounder) fails, it can be isolated, the control panel’s master
disable indicator, sounder’s disable indicator, FPE disable indicator, master zone disable indicator and the
disable indicators of zone (1-48) is indicated up. After all the equipment is restored by the enable function
after being repaired or replaced, the control panel’s master disable indicator, sounder’s disable indicator,
FPE disable indicator, master zone disable indicator and the disable indicators of zone are extinguished.
5.8.1 Device disable
The device disable can be divided into point disable and zone disable. It can also block all sounders
and FPE equipment. Press the “Disable” button and enter the Level II password correctly, as shown in
Figure 5-15.
Fig. 5-15
5.8.1.1 For example: to isolate all devices in Zone 01, press the number key “1” on the interface of Figure
5-15 to enter the zone isolation operation interface, and follow the steps below:
Enter the zone code to be isolated;
Press “enter” button, the isolation information of the screen shows that the device in Zone 01 is
isolated, the panel in the control panel zone shows that the disable lamp in Zone 01 is lit, and the LED
panel shows that the disabled lamp in the main zone is lit.
China·Liaoning·Yingkou Tiancheng Fire Protection Equipment Co., Ltd. 37
Instruction Manual for Installation and Application of JB-TB-TC5109 Intelligent Fire Alarm control panel Ver. 3.3 2019.6
5.8.1.2 For example: to isolate the loop device of No. 001 of the 1 circuit, press the number key “1” on the
interface of Figure 5-15 to enter the point isolation operation interface, and follow the steps below:
Enter the circuit to isolate the device: 01, address: 001;
Press “Enter” to add the device to the screen's isolation information.
Sounder and FPE can also be isolated by input loop and address number through this option.
5.8.1.3 For example: Disable all sound and indicator alarms, press the number key “3” on the interface of
Figure 4-11 to enter the sound and indicator isolation operation interface, and follow the steps below:
Press “Enter”, the isolation information of the screen shows that all sound and indicator are isolated,
and the LED panel of the control panel shows that the sounder’s disable indicator is on.
5.8.1.4 For example: to block all FPEs, press the number key “4” on the interface of Figure 4-11 to enter the
FPE isolation operation interface, and follow the steps below:
Press “Enter”, the isolation information of the screen shows that all FPEs are isolated, and the control
panel LED panel shows that the FPE disable indicators are on.
5.8.2 Enable
Enable can be divided into two methods of point enable and zone enable, which can also enable all
sounders and disabled FPE device. Press the “Enable” button and enter the Level II password correctly, as
shown in Figure 5-16.
Fig. 5-16
5.8.2.1 For example: Enable all devices in the 01 zone, press the number key “1” on the interface of Figure
5-16 to enter the zone enable operation interface, and follow the steps below:
Enter the zone code for enable: 01;
Press “enter” button, the device corresponding to Zone 01 is enabled, the panel of the control panel
zone shows that the 01 zone indicator is off, and the LED panel shows that the zone’s disabled indicator is
off.
5.8.2.2 For example, the enabled device is a loop device with No. 001 of the first loop. Press the number
key “2” on the interface of Figure 5-16 to enter the address point enable operation interface. The following
steps should be taken:
Enter the circuit of the enable device: 01, address: 001;
Press “Enter” to unblock the device at the corresponding address point. The disable indicator is off.
The sounders and FPE can also be isolated by the input loop and address number by the option.
5.8.2.3 For example: Enable all sounders. Press the number key “3” on the interface of Figure 5-16 to enter
the sounder disabled operation interface. Follow the steps below:
Press “Enter”. Then all sounders are enabled and the sounder’s disabled indicator is off.
5.8.2.4 For example: To release all FPE disable, press the number key “4” on the interface of Figure 5-16 to
enter the FPE enable operation interface, and follow the steps below:
Press “Enter”, then all FPEs are enabled and the FPE disabled indicators are off.
Press the "Menu" button to enter "7. Linkage Program" → "2. Off-line Programming", the system
enters the off-line programming operation interface, the system displays "1. Download 2nd codes and
notes", "2. Download programming ", "3. Upload 2nd codes and notes ", "4. Upload programming ". The
numeric key and the third-level password can be input to download the linkage programming and the 2nd
code annotation to the control panel through the USB port, or the linkage programming and the 2nd code
annotation can be uploaded to the USB flash drive through the USB port.
The off-line programming file must be placed in the root directory of the USB flash drive. The 2nd code
comment file is named TCZS.txt or tczs.txt.
The data format of each piece of the 2nd code comment file is: serial number, loop, address 2nd code,
device type, device attribute ,sensitivity ,notes, as shown in Figure 5-17:
Fig. 5-17
For example, the 0244 in Figure 5-17 is the loop device 2nd code note 0244 01 240 08001240 001 0 1 HD
★ "0244" is the serial number (4 digits) 0001-9999
★ The data interval is “Delimiter”. Press “TAB” to enter. You cannot use space spacing. (All subsequent
intervals are the same).
★ "01" is 1 loop. Equipment circuit range 1-4
★ "240" is the address. Device address range 1-255
★ "08001240" is a 2nd code (8 digits): The first two digits of the 2nd code are the zone number.
★ "010" is the device type (3 digits), Type: 001 heat detector, 002 smoke detector, 003 combination
detector, 004 manual call point, 008 isolator, 010 FPE(IO module), 011 sounder.
★ "0" is the device attribute.
★ "1" is the sensitivity level, only the smoke detector can set its sensitivity level, with three levels of
sensitivity.1 is the most sensitive and 3 is the least sensitive.
★ "HD" is comment information, each comment can be up to 20 characters.
★ Each message must be entered with “Enter”.
For example: 0251 in Figure 5-17 is the zone comment: 0251 05 001 31002001 099 0 1 FLOOR1
China·Liaoning·Yingkou Tiancheng Fire Protection Equipment Co., Ltd. 39
Instruction Manual for Installation and Application of JB-TB-TC5109 Intelligent Fire Alarm control panel Ver. 3.3 2019.6
The linkage programming file is named TCLD.txt or tcld.txt. The data format of each linkage programming
file is: No., Disable or not, the linkage part expression = alarm part expression, as shown in Figure 5-18:
Fig. 5-18
For example, the first linkage relationship in Figure 5-18:
★ "0001" is the serial number (4 digits)
★ The data interval is “Delimiter”. Press “TAB” to enter. You cannot use space spacing. (All subsequent
intervals are the same).
★ “0” means enable, 1 means disable, and the linkage programming of disable is not processed.
★ "(01****** 011)" means all points where the first two digits of the second code are 01, 011 means
sound and indicator, and FPE is 010.
★ "=" means that the linkage starts.
★ "(01****** 002+01****** 001+01****** 004)" indicates the smoke detector in the Zone 1 or the heat
detector in the Zone 1 or the manual call point in the Zone 1. . “01******” means the device of the 01
zone, and the last three digits indicate the device type: smoke detector 002, heat detector 001, manual call
point 004. The symbol "+" indicates the meaning of “or”, and the "X" indicates the meaning of “and”.
★Note that there is a space between the 2nd code and the device type.
If there are multiple messages in the system, they are displayed in the following order: Fire Alarm >
Fault > Disable.
The system first displays the fire alarm information. When there is a new fault in the fire alarm state,
the LCD will display the screen separately. The upper window is the fire alarm information, and the
lower window is the fault information.
In any display, if there is no operation within 30 seconds, the system will display a higher priority
message.
Press 'reset' and input password to operate erase to control panel after alarm or fault eliminated. Reset
can realize listed functions:
Erase current alarm, fault and action display,
Reset all bus-mode loop devices and all indicators of under-control devices,
Erase all mute conditions.
Press “menu” key, enter into “4. User setup” → “1. Time Setup”. The screen will display a figure as
Fig.6-1. After edit and modification, there will be a new system time after conform.
Fig.6-1
Press the “Menu” button to enter “4. User Setup” → “2. Print Setup”, the LCD will display the print
setting menu (as shown in Figure 6-2): Press “F1” or “F2” to change the printer status, press the "enter"
button to save the changes.
Fig.6-2
No information can be printed under 'printer OFF' condition.
New occurred information can be printed under 'printer ON' condition.
Press the “Menu” button to enter “4. User Settings” → “3. Language Setup”, the LCD displays the
language print setting menu (as shown in Figure 6-3): Press the “F1” button to set the language to Chinese
or press the “F2” key setting language is English. Then press “Enter” to save the changes.
Fig. 6-3
Enter into ‘system setup’ then ‘2.Bus component setup’ shown as Fig.6-4.
China·Liaoning·Yingkou Tiancheng Fire Protection Equipment Co., Ltd. 42
Instruction Manual for Installation and Application of JB-TB-TC5109 Intelligent Fire Alarm control panel Ver. 3.3 2019.6
Fig. 6-4
6.4.1 Content and Procedures of Defined by Field Devices
Peripheral devices in field connected with the control panel include fire detectors, linkage module,
LCD repeater panel, etc. which needs to be encoded both original address and field address.
The device definition is to set the field code of a certain original encoding device, which is the third
item in the system setting menu. The defined device can be either registered on the control panel or not
registered on the control panel.
The “Original address” is consisted of device's loop No. and its address No. The Loop No. is
consecutively setting of 1 and 32. Press “enter” after coding completed.
The “2nd code of user” is a code consisted of eight digits from 0 to 9. This is a manual defined No. for
specified field address for the device which is easy for user to identify device address and relevant
information. Specifications for 2nd code of user:
The zone number of the device is corresponding to the first and second digits, in the range of 0-48.
The so-called zone number refers to a fire zone.
The third, fourth and fifth digits range 0-999. Corresponding circuit number, for example, 1 loop, can
be set to 001.
The sixth, seventh, and eighth recommendations correspond to the address number of the bus system
device.
“Device type” needs to input three numbers referring to device type from device type sheet.
“Device properties” can be used for setting up peripheral device as 'alarm', 'feedback' and
'supervisory' represented by 0, 1 and 2 respectively mainly for defining input module attribute.
"Note information" indicates the location of the device or other related information. This item can be
composed of up to 20 English letters.
Description:
1) In the device definition, only Arabic digits can be entered and the remaining characters are considered
illegal.
2) English letters can be capitalized, spaces are a letter
6.4.2 FPE Indicator Setup
Press the “Menu” button to enter “5. System Setup” as shown in Figure 6-4 → “3.FPE Indicator
Setup” Enter the third level password to enter the display panel fire alarm setting interface, as shown in
Figure 6-5.
Fig.6-5
Input the FPE device No. of FPE indicated zone and the registered address (24 points can be set) of the
corresponding FPE loop bus. When the loop bus FPE device is activated or fed back, the corresponding FPE
indicator zone indicator indicators. After the setting, press “Enter” to enter, then press “F1” to continue.
After the setting is completed, press the “Cancel” button to exit the setting.
For example, the FPE device FPE device 1-10 corresponds to the point 1 loop address 1-10 module.
The setting method is as follows:
FPE No. 01 to No. 10 corresponds to the machine. Circuit 01 address 001 to 010. Note: No. 010 is not
required to be filled in, and the control panel will automatically fill in the calculations.
Press the “Menu” button, enter “5. System Setup” → “4. Display Panel Setup”, enter the three-level
password to enter the fire alarm setup interface of display panel. In order to set range of the fire display
panel, the corresponding fire display panel needs to connect on the relative loop bus, then transmit the
information to the fire display panel, including: loop No., address number and 2nd code.
Press "Menu" button, enter "5. System Settings" → "5. Display Panel Setup" Enter the three-level
password to enter the simulated fire alarm setting interface, input the device circuit number and address
number, press F1 to indicator the device fire alarm indicator, press F2 to extinguish equipment’s fire
indicators, which can be used for equipment location entrance.
The main interface of the system setting is shown in Figure 6-4. Press the number key “8”, the system
enters the power setup editing interface. Press “F1” to set the internal resistance of the battery, press “F2”
to query the internal resistance of the battery as shown in Figure 6 -6 below.
Fig. 6-6
Battery internal resistance test value: measure battery internal resistance value in real time. When it
gets damage, the value will change and system will report battery internal resistance fault.
Note: the battery internal resistance value has been set before delivered from the manufacturer, so it
needs no modification. The user can set the value again when the battery is changed from the field panel.
Fig. 6-7
Display the current local address;
After changing the local address, press “Enter” to save the currently set local address, and press
“Cancel” to exit the setting.
6.8.2 Networking Mode
Press “Menu” button, enter “6. Network Setup” → “1. Network Mode” and input the three-level
password to enter the local address setting interface as shown in Figure 6-8.
Fig. 6-8
The control panel displays the current networking mode, and can reset the control panel networking
mode: 0. Slave mode, 1. Host mode, independent mode, you can enter the number keys “0”, “1”, “2” to
change the mode.
The control panel currently displays whether to accept fire alarm, fault, disable, linkage and send
information. Enter the number keys “0” and “1”. Choose yes or no to send or not the information of
fire, fault, disable and linkage.
After setting, press “Enter” to save, press “Cancel” to exit this setting.
Fig. 6-9
Press “F1” to clear all the field programming data, including: linkage programming, 2nd code setting,
registration information.
Press “F2” to clear all data in the FPE indication zone.
Note: After the information is removed, it cannot be recovered, so you need to enter and then operate.
Press “Cancel” to exit the setup.
China·Liaoning·Yingkou Tiancheng Fire Protection Equipment Co., Ltd. 47
Instruction Manual for Installation and Application of JB-TB-TC5109 Intelligent Fire Alarm control panel Ver. 3.3 2019.6
Field device refers to devices connected to loop control panel through non-polarized two bus system.
The panel offers max 32 loops with 255 points each loop and each device occupies one address. These
devices include fire detectors (e.g. rate of rise and fixed temperature heat detector, photoelectric smoke
detector, etc.), input modules (e.g. fire hydrant module, flow detector input interface module, etc.),
input/output modules (e.g. fire resisting damper, fire hydrant pump control module, etc.), customized
burglar alarms, etc. Direct control panel and loop controlled gas fire-extinguishing control panel
manufactured by TC can be connected to the loop to realize integral monitoring.
6.10.1 Linkage Formula Format
Linkage formula is used to define linkage logic expression between alarm device and controlled device in
the system. When status of detecting device or controlling module condition changed, the control panel
can operate automatically the start and stop of the device through logic formula. Linkage formula is
consisted of two parts between the equal mark, former part is consisted of linkage devices made up of user
code and device type, latter part is consisted of user code, device type and relational operator.
eg.1: Y(01010001 011)=(01010*** 004)_2
Means: when No. 01010001 manual call point gives out an alarm, the No. 01010001 sounder strobe will
activate immediately.
Note:
1) When “=” represents automatic “part permitted” or “all permitted” in the system and linkage
requirement is met, device will be activated. When “=X” represents automatic “part permitted” or “all
permitted” in the system and requirement is met, device will stop.
2) When “==” represents automatic “all permitted” in the system and linkage requirement is met,
device will be activated. When “==X” represents automatic “all permitted” in the system and requirement
is met, device will stop.
3) Devices at both sides of the linkage formula need to be made up of user code and device type
which type cannot be omitted.
4) Relation mark includes “and” and “or”. “+” represents “or” and “X” represents “and”.
5) Wildcard allowed to use '*' can represent any number from 0 to 9 in a linkage formula. The wildcard
can be part of the formula requirement or part of the linkage part to simplify the linkage formula rationally.
When it exists in the requirement, it implies an “or” relation between a series of devices, e.g. 0*001315
represents:
01001315+02001315+03001315+04001315+05001315+06001315+07001315+08001315+09001315+00001
315, while it represents a group of devices in linkage part.
6) There can be only one equal mark or fully equal mark representing cause and effect in a linkage
formula.
6.10.2 Linkage Formula Programming
Press “7” at main menu page to enter into linkage program page(AL3). The screen will show up linkage
formula editing menu (shown as Fig.6-10).
Fig. 6-10
6.11 About
The user presses the “Menu” button to enter the system main menu interface, enter “8. About” →
enter the interface, query the manufacturer, execute the standard software version and hardware code,
system capacity and other related information.
7.1Common Troubleshooting
Take regular test on devices: print paper is perishable articles, which needs to be replaced when
insufficient.
China·Liaoning·Yingkou Tiancheng Fire Protection Equipment Co., Ltd. 50
Instruction Manual for Installation and Application of JB-TB-TC5109 Intelligent Fire Alarm control panel Ver. 3.3 2019.6
WEEE Information
⭐ Note: it is advised that during alarm test on manual call point and detectors, module related linkage program of each
detector and manual call point shall be disabled to prevent losses from module actions.