Eh Price Flow Factors
Eh Price Flow Factors
Page No. Date: Supercedes: Page 1 Sept. 15, 1998 June 1, 1994
Index
Section A A-1 A-2 A-3 A-4 A-5 A-6 Section B B-1 B-2 B-3 B-4 B-5 Section C C-1 C-2 C-3 C-4 C-5 C-6 C-7 C-8 C-9 C-10 C-11 C-12 C-13 C-14 C-15 C-16 C-17 C-18 Section D D-1 D-2 D-3 D-4 D-5 D-6 D-7 D-8 Section E E-1 E-2 E-3 E-4 E-5 E-6 Linear Diffuser & Grilles SDS SDA / SDAI LBP / LBPH LBMH LV1 LV2 Ceiling Component Diffusers TBD3 Series TBD4 Series TBD7 Series TBD8 Series LT Series Light Troffers Ceiling Diffusers SCD / ASCD SCDA / ASCDA SPD / ASPD PDN / PDNE PDF / PDFE PDDR / PDDRE PDS PDR PE / PL SMD / AMD SMD / AMD Return SMDA / AMDA SMCD / AMCD CVD (1 & 2 Way Blow) CVD (3 & 4 Way Blow) RCD / RCDA RCDE RID Grilles & Registers Supply Grilles Return Grilles MSLG / MSLGH HCD ATG STG MSPG 10 Series Medical / Cleanroom RFD LFD AMDC RVDC HORD HORD June 1, 1994 June 1, 1994 June 1, 1994 June 1, 1994 June 1, 1994 June 1, 1994 June 1, 1994 June 1, 1994 June 1, 1994 June 1, 1994 June 1, 1994 June 1, 1994 June 1, 1994 June 1, 1994 June 1, 1994 June 1, 1994 June 1, 1994 June 1, 1994 June 1, 1994 June 1, 1994 June 1, 1994 June 1, 1994 June 1, 1994 June 1, 1994 June 1, 1994 June 1, 1994 June 1, 1994 June 1, 1994 June 1, 1994 June 1, 1994 June 1, 1994 June 1, 1994 June 1, 1994 Sept. 15, 1998 Sept. 15, 1998 Sept. 15, 1998 Sept. 15, 1998 June 1, 1994 June 1, 1994 Sept. 15, 1998 Sept. 15, 1998 Sept. 15, 1998 Sept. 15, 1998
SDS 75
SDS 100
H = Horizontal Pattern
Model 1 SDR 50 SDR 75 SDR 100 .033 .039 .044
V = Vertical Pattern
RETURN No. of Slots 2 .066 .078 .088 3 .099 .117 .132 4 .132 .156 .176 5 .165 .195 .220 6 .190 .234 .264 7 .231 .273 .308 8 .264 .312 .352
Note:
SDS 50, 75, 100 Slot Diffuser with SDA or SDAI Plenum Assembly
Procedure: 1. Place velometer probe 14 inches from each and of slot and against the slot edge opposite the inlet as shown. 2. Record and average two velocity readings for each slot. 3. The Flow Rate in CFM = Flow Factor x Average Velocity. Flow Factors
No. of Slots Pattern 3 1 2 3 4 H H H H .070 .125 .185 .245 SDS 50 Nom. Length (ft) 4 .088 .183 .268 .330 5 .112 .215 .320 .420 3 .078 .185 .223 .292 SDS 75 Nom. Length (ft) 4 .106 .221 .286 .454 5 .133 .239 .380 .600 3 .094 .177 .260 .330 SDS 100 Nom. Length (ft) 4 .111 .231 .350 .460 5 .155 .300 .440 .580
.031 .026 .034 .031 .035 .030 .039 .035 .026 .022 .031 .028
.047 .040 .049 .044 .055 .046 .056 .050 .045 .039 .048 .042
.065 .056 .065 .057 .074 .064 .075 .065 .066 .057 .067 .058
.083 .070 .082 .072 .096 .080 .093 .082 .088 .075 .086 .073
.102 .090 .099 .083 .116 .103 .113 .095 .110 .094 .105 .090
.122 .103 .117 .100 .139 .118 .133 .114 .133 .114 .127 .105
.157 .135 .152 .130 .179 .154 .173 .148 .177 .150 .167 .140
.194 .165 .186 .158 .221 .188 .212 .180 .222 .190 .210 .180
Note:
For sizes greater than 6" the flow factor in ft2 / ft of length may be calculated by the following equation: Flow Factor ft. of Length = (W - 0.75) x Flow Factor Coef. W = Listed Width in inches
.027 .023 .031 .028 .030 .026 .035 .031 .030 .025 .032 .028
.043 .036 .044 .039 .049 .041 .050 .045 .049 .042 .048 .042
.059 .056 .059 .051 .067 .064 .067 .058 .071 .060 .066 .058
.078 .067 .072 .062 .089 .077 .082 .071 .095 .080 .085 .073
.098 .082 .087 .073 .111 .094 .099 .083 .114 .098 .106 .090
.116 .100 .105 .089 .132 .114 .120 .102 .135 .115 .125 .105
.152 .128 .135 .115 .173 .146 .154 .131 .180 .152 .165 .140
.190 .160 .165 .140 .216 .182 .188 .160 .225 .193 .210 .180
Note:
For sizes greater than 6" the flow factor in ft2 / ft of length may be calculated by the following equation: Flow Factor ft. of Length = (W - 0.75) x Flow Factor Coef. W = Listed Width in inches
Flow Factors
(A) These factors apply when the diffuser has integral straightening vanes or dampers. (B) These factors apply when the diffuser has no integral straightening vanes or dampers. (C) These factors apply with diffuser when used as a return intake.
Flow Factors
Size 6.25 7.75 9.25 10.75 12.25 Supply 0.103 0.156 0.210 0.267 0.328 Return 0.090 0.130 0.170 0.210 0.250
The factors apply to all LV2 diffusers, both with and without straightening vanes and / or dampers. Alnor Probe 6070P Locations
TBD & TBDI 350, 375, 3100 Ceiling Diffusers for Steel T-Bar
Procedure: 1. Set pattern controllers for the pattern required either horizontal or vertical. 2. Take velocity readings at slot of diffuser with Alnor 6070P probe at the locations shown above.Two readings for one slot diffusers and four readings for two slot diffusers. Average the velocity readings. 3. Select flow factor for diffuser length and pattern and calculate air flow from the equation CFM = Flow Factor x Average Velocity Flow Factors
Diffuser Length 2' 0" Pattern TBD 350 1 Slot H V H V H V H V .039 .045 .050 .059 .079 .100 .100 .130 2 Slot .078 .096 .100 .125 .160 .210 .200 .270 1 Slot .054 .066 .069 .085 .112 .145 .140 .185 TBD 375 2 Slot .109 .140 .137 .185 .222 .320 .280 .410 TBD 3100 1 Slot .068 .085 .086 .110 .139 .185 .175 .240 2 Slot .137 .185 .175 .235 .280 .400 .350 .520
5'0"
TBD & TBDI 475 / 4100 / 4150 High Capacity Diffusers for Steel T-Bar
Procedure: 1. Place probe at locations shown. 2. Record and average velocity readings (2 per slot). 3. Flow Rate in CFM = Flow Factor & Average Velocity. Flow Factors
Diffuser Length 2' - 0" 2' - 6" 3' - 0" 4' - 0" 5' - 0" TBD 475 1 Slot 2 Slot .064 .080 .098 .130 .164 .128 .161 .195 .261 .328 TBD 4100 1 Slot 2 Slot .073 .093 .112 .150 .188 .146 .185 .223 .300 .376 TBD 4150 1 Slot 2 Slot .107 .136 .164 .220 .276 .166 .208 .252 .338 .425
LTF / LTA 10-4 LTF / LTA 14, LTF / LTA 24 LTF / LTA 10-3 LTF / LTA 13, LTF / LTA 23 LTF / LTA 33 LTF / LTA 10-2 LTF / LTA 12, LTF / LTA 22
5 5
.033 .062
12 x 12 0.22 -
16 x 16 0.32 0.40 -
1.5"
.031 .047 .063 .078 .094 .109 .125 .141 .156 .172 .188 .203 .219 .234 .250 .266 .281 .297 .313
3"
.063 .094 .125 .156 .188 .219 .250 .281 .313 .344 .375 .406 .438 .469 .500 .531 .563 .594 .625
4.5"
.141 .187 .234 .281 .328 .375 .422 .469 .516 .563 .610 .656 .703 .750 .797 .844 .891 .938
6"
7.5"
9"
10.5"
12"
13.5"
15"
16.5"
18"
19.5"
21"
22.5"
24"
25.5"
27"
28.5"
30"
.250 .313 .375 .438 .500 .563 .625 .688 .750 .813 .875 .938 1.000 1.060 1.125 1.190 1.250 .390 .469 .547 .625 .703 .781 .859 .938 1.015 1.090 1.170 1.250 1.330 1.410 1.480 1.560 .560 .656 .750 .844 .938 1.030 1.125 1.220 1.310 1.410 1.500 1.590 1.690 1.780 1.875 .766 .875 .984 1.100 1.200 1.310 1.420 1.530 1.640 1.750 1.860 1.970 2.080 2.190 1.000 1.130 1.250 1.380 1.500 1.630 1.750 1.880 2.000 2.130 2.250 2.380 2.500 1.270 1.410 1.550 1.690 1.830 1.970 2.110 2.250 2.390 2.530 2.670 2.810 .156 1.720 1.875 2.030 2.190 2.340 2.500 2.660 2.810 2.970 3.125 1.890 2.060 2.230 2.410 2.580 2.750 2.920 3.090 3.270 3.440 2.250 2.440 2.62 2.810 3.000 3.190 3.375 3.560 3.750 2.640 2.840 3.050 3.250 3.450 3.660 3.860 4.060 3.060 3.280 3.500 3.720 3.940 4.160 4.375 3.520 3.750 3.980 4.220 4.450 4.690 4.000 4.250 4.500 4.750 5.000 4.520 4.780 5.050 5.310 5.060 5.340 5.625 5.640 5.940 6.250
Flow Factors
Duct Area (ft2) 0.25 0.30 0.35 0.40 0.45 0.50 0.60 0.70 0.80 0.90 1.00 Flow Factor (Ak) 0.150 0.120 0.135 0.152 0.167 0.184 0.216 0.242 0.268 0.300 0.320 Duct Area (ft2) 1.10 1.20 1.30 1.40 1.50 1.60 1.80 2.00 2.20 2.40 2.60 Flow Factor (Ak) 0.360 0.390 0.415 0.440 0.465 0.490 0.535 0.580 0.630 0.680 0.730 Duct Area (ft2) 2.80 3.00 3.20 3.40 3.60 3.80 4.00 4.59 5.00 5.50 6.00 Flow Factor (Ak) 0.770 0.810 0.855 0.900 0.940 0.980 1.020 1.110 1.210 1.330 1.440
1.5"
.031 .047 .063 .078 .094 .109 .125 .141 .156 .172 .188 .203 .219 .234 .250 .266 .281 .297 .313
3"
.063 .094 .125 .156 .188 .219 .250 .281 .313 .344 .375 .406 .438 .469 .500 .531 .563 .594 .625
4.5"
.141 .187 .234 .281 .328 .375 .422 .469 .516 .563 .610 .656 .703 .750 .797 .844 .891 .938
6"
7.5"
9"
10.5"
12"
13.5"
15"
16.5"
18"
19.5"
21"
22.5"
24"
25.5"
27"
28.5"
30"
.250 .313 .375 .438 .500 .563 .625 .688 .750 .813 .875 .938 1.000 1.060 1.125 1.190 1.250
.390 .469 .547 .625 .703 .781 .859 .938 1.015 1.090 1.170 1.250 1.330 1.410 1.480 1.560
.560 .656 .750 .844 .938 1.030 1.125 1.220 1.310 1.410 1.500 1.590 1.690 1.780 1.875
.766 .875 .984 1.100 1.200 1.310 1.420 1.530 1.640 1.750 1.860 1.970 2.080 2.190
1.000 1.130 1.250 1.380 1.500 1.630 1.750 1.880 2.000 2.130 2.250 2.380 2.500
1.270 1.410 1.550 1.690 1.830 1.970 2.110 2.250 2.390 2.530 2.670 2.810
.156 1.720 1.875 2.030 2.190 2.340 2.500 2.660 2.810 2.970 3.125
1.890 2.060 2.230 2.410 2.580 2.750 2.920 3.090 3.270 3.440
5.640 5.940
6.250
2 Way
Width 4 6 8 10 12 14 16 18 20 24 No. of Vanes 4 6 10 12 14 18 20 22 26 30 K-Factor .0064 .0110 .0210 .0260 .0310 .0400 .0450 .0500 .0600 .0700
Note:
Note:
1.312 1.750 2.187 2.625 3.062 3.500 3.937 4.375 5.250 6.625 6.625
Flow Factors
Neck Diam (in.) 10 12 14 16 18 20 24
Flow Factor 0.66 0.58 0.51 0.70 0.60 0.52 0.78 0.83 0.68 0.72 0.87 0.92
13 13 13 13 13 13
Note:
Procedure: 1. Take a number of readings at grille face with Alnor 6070P probe at center of equal areas. Spacing of probe location not to exceed 6 inches in either direction. Do not take readings directly in front of blade supports. 2. Average the velocity readings. 3. Obtain core area from calculation (in square feet). 4. Core Area (ft2) = [Nominal Duct Width (inches) - X] x [Nominal Duct Height (inches) - X] 144 Where X = Core undersizing listed below. 5. Flow Rate in CFM is obtained from following equation: CFM = (Ak / Ac factor) (Core Area, ft2) (Average Velocity, fpm) Flow Factors
Core Style 530/630/730 535/655/735 60 70 80 90 91 95 96 97 98 Deflection (degrees) 45 45 45 45 0 0 45 0 45 0 45 x Flow Factor
0.312 0.309 0.309 0.343 0.470 0.477 0.341 0.555 0.482 0.470 0.300
Note:
Probe locations on face of grille. Less than 1sq. ft., use 9 to 12 readings spaced evenly. For areas of more than 1 sq. ft., use 12 to 16 readings spaced evenly. Distance between readings not to exceed 6". Core Area in sq. ft. W x H is listed in inches. a) ATG - Core Area b) ATG1A - Core Area c) ATG1B - Core Area d) ATG1BF - Core Area e) ATG1C - Core Area = (W - 0.75) = (W - 0.75) = (W - 0.78) = (W - 0.78) = (W - 1.78) (H - 0.75) / 144 (H - 0.75) / 144 (H - 0.78) / 144 (H - 0.78) / 144 (H - 0.78) / 144
Probe locations on face of grille. Less than 1sq. ft., use 9 to 12 readings spaced evenly. For areas of more than 1 sq. ft., use 12 to 16 readings spaced evenly. Distance between readings not to exceed 6". Core Area in sq. ft. W x H is listed in inches. a) STG1 - Core Area b) STG1A - Core Area c) STG1B - Core Area d) STG1BF - Core Area = (W - 0.75) = (W - 0.75) = (W - 0.78) = (W - 0.78) (H - 0.75) / 144 (H - 0.75) / 144 (H - 0.78) / 144 (H - 0.78) / 144
Air Flow
Air Flow
Module Size 48 x 12 48 x 24 24 x 24
16"
16"
IN THE UNITED STATES US Head Office, Laboratory & Testing Facilities, Manufacturing Facilities & Distribution Warehouse in Atlanta, Georgia US Representatives in most major cities
2975 Shawnee Ridge Court Suwanee, Georgia USA 30024 Ph: 770.623.8050 Fax: 770.623.6404 IN THE UNITED STATES
Manufacturing Facilities & Distribution Warehouse in Casa Grande, Arizona 999 North Thornton Road Casa Grande, Arizona USA 85222-3809 Fax: 520.423.0517 IN CANADA Head Office, Export Sales Office, Laboratory & Testing Facilities, Manufacturing Facilities & Distribution Warehouse in Winnipeg, Manitoba Canadian Sales Offices in most major cities US Representatives in most major cities
638 Raleigh Street Winnipeg, Manitoba Canada R2K 3Z9 Ph: 204.669.4220 Fax: 204.663.2715
The founding principles of our company have never changed business integrity, first class service and a commitment to people. Price manufacturing endeavours arose from our belief that we could supply superior products and services at a reasonable price. Our mission is to become the worldwide supplier of preference for air distribution products and services. You can rely on Price our products and services with confidence.
Product Improvement is a continuing endeavour at Price. Therefore, specifications are subject to change without notice.
Consult your Price sales representative for current specifications or more detailed information.
Warranty: The Company warrants and guarantees that all goods within this catalog that have been manufactured by the Company have been manufactured in accordance with the specifications published herein and will be free from defects in material and workmanship for a period of twelve (12) months from the date of Bill of Lading issued by the Company. The Company will replace defective product at its option, but will not be responsible for labor or material charges in replacing product or consequential damages. Any installation not conforming with the Company's specifications, manuals, bulletins or instructions or any misuse or any modification not authorized by the Company voids this warranty. This warranty is in lieu of all Provincial, State, and Federal statutory warranties and the conditions herein are in substitution and replacement of such warranties, statutory or otherwise.