PLC Connection Guide

MODBUS Server (COM/Ethernet)

HMI Setting:
Parameters Recommended Options Notes
PLC type MODBUS Server (COM/Ethernet)
PLC I/F RS232 RS232, RS485
9600~115200 Ethernet supports UDP or TCP/IP
Baud rate 9600
Ethernet protocol
Data bits 8 8
Parity Even Even, Odd,
Stop bits 1 None
1
PLC sta. no. 1 1-31 HMI Modbus Station No.
Port no. 502

Online simulator YES Extend address mode NO


Broadcast command NO

If HMI is Modbus Server, connecting two or more Modbus Servers with one Modbus RTU
via RS485 4W is not supported. To do so, use RS485 2W instead.
PLC Connection Guide

PLC Setting:
Communication mode Modbus RTU protocol

Modbus Server UDP Protocol Setting:


MODBUS Server (Ethernet) supports UDP communication protocol. To use UDP mode,
go to [System Parameter Settings] in editing software, in [Device list] click [New], for [PLC
type] select “Modbus Server”, [PLC I/F] set to [Ethernet], and select [Use UDP (User
Datagram Protocol)] to finish setting.

Modbus Server Port No. can be changed by clicking [Settings].

Modbus Server Port No. can not be set identically to HMI Port No. When doing so, the
warning message below will be shown requesting users to change setting.
PLC Connection Guide

Note:
A maximum of 64 Clients can be connected simultaneously.
Modbus Server Port No. can’t be identical to HMI Port No.

Modbus Server TCP/IP Protocol Setting:


MODBUS Server (Ethernet) supports TCP/IP communication protocol. Go to [System
Parameter Settings] in editing software, in [Device list] click [New], for [PLC type] select
“Modbus Server”, [PLC I/F] set to [Ethernet] to finish setting.
PLC Connection Guide
For Modbus Server TCP/IP, HMI Port No. is the same as Modbus Server Port No. To
change Prot No. go to [System Parameter Settings] / [Model], the default Port No. is
“8000”, and it is allowed to change Modbus Server Port No. here.

MODBUS TCP/IP Gateway:

By adding MODBUS Server with [Ethernet] interface, the [MODBUS TCP/IP Gateway] feature

can be enabled by selecting the [Enable] check box.

Note the following two points when enabling the [MODBUS TCP/IP Gateway]:
a. The original mapping between the MODBUS Server and the HMI address will be
canceled.
b. The SCADA cannot read from or write in the addresses defined in different Address
Mapping Table at one time.
For more information about this, see “Chapter37 MODBUS TCPIP Gateway”.
PLC Connection Guide

Device Address:
Bit/Word Device type Format Range Memo
B LB dddd 0 ~ 9998 Mapping to 0x/1x 1 ~ 9999
W LW dddd 0 ~ 9998 Mapping to 3x/4x 1 ~ 9999
W RW ddddd 0 ~ 55536 Mapping to 3x/4x 10000 ~ 65536

LB0 = 0x0001, LB1 = 0x0002, LW0 = 3x0001, LW1 = 3x0002

Modbus Server Function Code:


0x 0x01 Read coil 0x05 write single coil
0x_multi_coils 0x01 Read coil 0x0f write multiple coils
1x 0x02 Read discrete input N/A for write operation
3x 0x04 Read input register N/A for write operation
4x 0x03 Read holding register 0x10 write multiple registers

Modbus Server Error Code:


Error Code Definition Condition
01 Incorrect function code The function code is not supported.
02 Incorrect read address The read address is not within the range.
The data read is incorrect, for example, the
03 Incorrect data
data length is 0.
Read/Write exceeding number of words
251 Incorrect data
from/to the register of the Modbus device.
252 Incorrect data Modbus device replies incorrect data format.
253 Incorrect data Modbus device checksum error.
PLC Connection Guide

Wiring Diagram:
RS232 (Diagram 1 ~ Diagram 3)
Diagram 1
cMT Series cMT3071 / cMT3072 / cMT3090 / cMT3103 / cMT3151

eMT Series eMT3070 / eMT3105 / eMT3120 / eMT3150

MT-iE MT8073iE / MT8102iE

MT-XE MT8092XE

MT-iP MT6103iP / MT8102iP

HMI PLC
COM1 COM3
RS232 RS232 RS232
9P Female 9P Female
Rx 2 8 TXD
Tx 3 7 RXD
GND 5 5 GND
RTS
CTS
PLC Connection Guide

Diagram 2
cMT Series cMT-SVR / cMT-G01 / cMT-G02 / cMT-HDM / cMT-FHD

mTV mTV

MT-iE MT8070iE / MT6070iE / MT8100iE / MT8121iE / MT8150iE /


MT8071iE / MT6071iE / MT8072iE / MT6072iE / MT8073iE /
MT8101iE / MT8102iE / MT8103iE
MT-XE MT8121XE / MT8150XE / MT8090XE

HMI PLC
COM1
RS232 RS232
9P Female
Rx 2 TXD
Tx 3 RXD
GND 5 GND
RTS
CTS

Diagram 3
MT-iE MT8050iE / MT8053iE

MT-iP MT6051iP / MT8051iP / MT6071iP / MT8071iP

HMI PLC
COM1
RS232 RS232
9P Female
Rx 9 TXD
Tx 6 RXD
GND 5 GND
RTS
CTS
PLC Connection Guide
RS485 4W (Diagram 4 ~ Diagram 7)
Diagram 4
cMT Series cMT3151

eMT Series eMT3070 / eMT3105 / eMT3120 / eMT3150

MT-iE MT8070iE / MT6070iE / MT8100iE / MT8121iE / MT8150iE

MT-XE MT8121XE / MT8150XE

HMI PLC
COM1
RS485 4W RS485 4W
9P Male
Rx- 1 TX-
Rx+ 2 TX+
Tx- 3 RX-
TX+ 4 RX+
GND 5 GND

Diagram 5
cMT Series cMT-SVR / cMT-G01 / cMT-G02 / cMT-HDM / cMT-FHD

mTV mTV

HMI PLC
COM2
RS485 4W RS485 4W
9P Female
Rx- 7 TX-
Rx+ 6 TX+
Tx- 9 RX-
TX+ 8 RX+
GND 5 GND
PLC Connection Guide

Diagram 6
cMT Series cMT3071 / cMT3072 / cMT3090 / cMT3103

MT-iE MT8071iE / MT6071iE / MT8072iE / MT6072iE / MT8073iE /


MT8101iE / MT8102iE / MT8103iE
MT-XE MT8090XE / MT8092XE

MT-iP MT6071iP / MT8071iP / MT6103iP / MT8102iP

HMI PLC
COM2
RS485 4W RS485 4W
9P Male
Rx- 1 TX-
Rx+ 2 TX+
Tx- 3 RX-
TX+ 4 RX+
GND 5 GND

Diagram 7
MT-iE MT8050iE / MT8053iE

MT-iP MT6051iP / MT8051iP

HMI PLC
COM1
RS485 4W RS485 4W
9P Female
Rx- 1 TX-
Rx+ 2 TX+
Tx- 3 RX-
TX+ 4 RX+
GND 5 GND
PLC Connection Guide

RS485 2W (Diagram 8 ~ Diagram 13)


Diagram 8
cMT Series cMT3151

eMT Series eMT3070 / eMT3105 / eMT3120 / eMT3150

HMI PLC
COM1 COM3
RS485 2W RS485 2W RS485 2W
9P Male 9P Male
Data- 1 6 D-
Data+ 2 9 D+
GND 5 5 GND

Diagram 9
cMT Series cMT-SVR / cMT-G01 / cMT-G02 / cMT-HDM / cMT-FHD

mTV mTV

HMI PLC
COM2 COM3
RS485 2W RS485 2W RS485 2W
9P Female 9P Female
Data- 7 4 D-
Data+ 6 1 D+
GND 5 5 GND
PLC Connection Guide

Diagram 10
MT-iE MT8070iE / MT6070iE / MT8100iE / MT8121iE / MT8150iE

MT-XE MT8121XE / MT8150XE

HMI PLC
COM1 COM3
RS485 2W RS485 2W RS485 2W
9P Male 9P Male
Data- 1 7 D-
Data+ 2 8 D+
GND 5 9 GND

Diagram 11
cMT Series cMT3071 / cMT3072 / cMT3090 / cMT3103

MT-iE MT8071iE / MT6071iE / MT8072iE / MT6072iE / MT8073iE /


MT8101iE / MT8102iE / MT8103iE
MT-XE MT8090XE / MT8092XE

MT-iP MT6103iP / MT8102iP

HMI PLC
COM2 COM3
RS485 2W RS485 2W RS485 2W
9P Male 9P Male
Data- 1 6 D-
Data+ 2 9 D+
GND 5 5 GND
PLC Connection Guide

Diagram 12
MT-iE MT8050iE / MT8053iE

MT-iP MT6051iP / MT8051iP

HMI PLC
COM1 COM3
RS485 2W RS485 2W RS485 2W
9P Female 9P Female
Data- 1 7 D-
Data+ 2 8 D+
GND 5 5 GND

Diagram 13
MT-iP MT6071iP / MT8071iP

HMI PLC
COM2
RS485 2W RS485 2W
9P Female
Data- 1 D-
Data+ 2 D+
GND 5 GND
Note: Setting more than one Modbus Server in HMI Device List is of no effect.

Diagram 14
Ethernet cable: