BEE Module Transformer 24 25
BEE Module Transformer 24 25
• The magnetic circuit stores energy in its field while the electric circuit immediately
releases its energy as heat
• Coil C is wound on limb L and carries a current I. The total magnetic flux produced in
limb L divides at point P; some flux passes along limb M and the remaining along
limb N. These two parts join again at Q. There is no break or discontinuity in any of
the lines of flux at P and Q then
22-12-2024 Basic Electrical Engineering, Payal Shah, SPIT 5
Kirchhoff’s Laws for magnetic circuit
• Kirchhoff’s Magnetomotive Force Law (KML): In a closed magnetic circuit, the
algebraic sum of the product of the magnetic field strength and the length of each
part of the circuit is equal to the resultant magnetomotive force.
• If HL is the magnetic field strength required for limb L and lL is the length of the
circuit from Q via L to P, and HM and lM are the corresponding values for limb M and
HN and lN are those for the limb extending from P via N to Q then
• This property of the coil of capability of inducing an emf in itself by changing the
current flowing through it is known as self inductance
• e=Ldi/dt ; L=inductance
• For linear inductor rate of change of current with respect to time is constant hence
• Also, and
✓ Conductive
✓ Electrostatic
✓ Electromagnetic
R12 is the mutual resistance C is the mutual capacitor A part of magnetic flux produced
between circuit 1 and 2 by a coil in one circuit interlinks
with the coil in other circuit. Energy
may be transferred from one circuit
to the other through the medium
of magnetic flux that is common to
both circuits. When current in one
circuit changes, the flux linking
with the other circuit changes
hence there is an induced emf in
the other coil known as mutually
induced emf e2
• Mutual inductance is a property; which is associated with two or more coils that are
physically close together.
• Similarly,
• If flux and current are linearly related, then and
• Thus mutual inductance between two coils is ratio of weber turns of one coil to the current
through the other coil
• Also due to reciprocity,
• i.e
• Dot convention is a convenient way of determining the sign of mutual voltage without
going into the physical construction of the two coils
• A current entering the dotted terminal of one coil produces an open circuit voltage which is
positively sensed at the dotted terminal of the second coil.
• Transformers electrical energy from one circuit to another without any change in frequency
• Small size are used in communication circuits, radio and TV circuits, telephone circuits,
instrumentation and control systems.
• If one coil is connected to a source of alternating voltage, an alternating flux is set up in the
laminated core, most of which is linked with the other coil in which it produces mutually-
induced e.m.f. (according to Faraday’s Laws of Electromagnetic Induction e = MdI/dt). If the
second coil circuit is closed, a current flows in it and so electric energy is transferred
(entirely magnetically) from the first coil to the second coil.
✓ where the two electric circuits are in mutual inductive influence of each other.
• 1. The permeability of the magnetic circuit (core) is infinite. i.e. the magnetic circuit has
zero reluctance so that no mmf is needed to set up the flux in the core
• 3. The resistance of its windings is zero, i.e. no I2R losses in the winding
• 4. Entire flux in the core links both windings, i.e. there is no leakage flux.
• As per the law of electromagnetic induction, the induced emf in a winding of N turns is given by
• K=V2/V1=E2/E1=N2/N1
• K>1=>Step-up
• K<1=>Step-down
• The side of transformer with the larger no. of turns has the smaller current
• In step up transformer would have a primary with few turns of thick wire (Small voltage, large
current) and the secondary would have many turns of thin wire
• Also
• If ideal transformer has N1 and N2 turns in its primary and secondary windings and a load impedance
ZL is connected across its secondary, then an equivalent impedance Zeq is defined at its primary.
• If the transformer is ideal then primary current would be also zero, but in practice there
does flow a no-load current I0 in the primary.
• The copper loss in secondary is I22R2. This loss is supplied by primary which takes a current
of I1. Hence if R2′ is the equivalent resistance in primary which would have caused the same
loss as R2 in secondary,
• secondary resistance has been transferred to primary side leaving secondary circuit
resistanceless. The resistance R1 + R2′ = R1 + R2/K2 is known as the equivalent or effective
resistance of the transformer as referred to primary (R01)
• All the flux linked with primary does not link the secondary but part of it i.e.ΦL1 completes its
magnetic circuit by passing through air rather than around the core
• This leakage flux is produced when the m.m.f. due to primary ampere-turns existing between points a
and b, acts along the leakage paths. Hence, this flux is known as primary leakage flux and is
proportional to the primary ampere-turns alone because the secondary turns do not link the
magnetic circuit of ΦL1
• The flux ΦL1 is in time phase with I1. It induces an e.m.f. eL1 in primary but not in secondary.
• Similarly, secondary ampere-turns (or m.m.f.) acting across points c and d set up leakage flux ΦL2
which is linked with secondary winding alone (and not with primary turns). This flux ΦL2 is in time
phase with I2 and produces a self-induced e.m.f. eL2 in secondary (but not in primary).
22-12-2024 Basic Electrical Engineering, Payal Shah, SPIT 42
Magnetic leakage
• The leakage flux links one or the other winding but not both, hence it in no way contributes
to the transfer of energy from the primary to the secondary winding.
• The primary voltage V1 will have to supply reactive drop I1X1 in addition to I1R1. Similarly E2
will have to supply I2R2 and I2X2.
• When a transformer is loaded with a constant primary voltage, the secondary voltage
decreases(power factor is lagging) because of its internal resistance and leakage reactance.
• Efficiency is based on power output in watts and not in volt-amperes, although losses are proportional to
VA. Hence, at any volt-ampere load, the efficiency depends on power factor, being maximum at a power
factor of unity.
• Efficiency can be computed by determining core loss from no-load or open-circuit test and Cu loss from
the short-circuit test.
• With normal voltage applied to the primary, normal flux will be set up in the core, hence
normal iron losses will occur which are recorded by the wattmeter.
• As the primary no-load current I0 (as measured by ammeter) is small (usually 2 to 10% of
rated load current), Cu loss is negligibly small in primary and nil in secondary (it being open).
Hence, the wattmeter reading represents practically the core loss under no-load condition
which is the same for all loads
(i) Equivalent impedance (Z01 or Z02), leakage reactance (X01 or X02) and total resistance (R01 or
R02) of the transformer as referred to the winding in which the measuring instruments are
placed.
(ii) Cu loss at full load (and at any desired load), which is used in calculating the efficiency of the
transformer.
(iii) Knowing Z01 or Z02, the total voltage drop in the transformer as referred to primary or
secondary can be calculated and hence regulation of the transformer determined.
• A low voltage (usually 5 to 10% of normal primary voltage) is applied to the primary and is cautiously
increased till full-load currents are flowing both in primary and secondary (as indicated by the
respective ammeters)
• Since, the applied voltage is a small percentage of the normal voltage, the mutual flux Φ produced is
also a small percentage of its normal value. Hence, core losses are very small with the result that the
wattmeter reading represent the full-load Cu loss or I2R loss for the whole transformer i.e. both primary
Cu loss and secondary Cu loss
• If Vsc is the voltage required to circulate rated load currents, then Z01 = Vsc/I1
• In (a), AB is primary winding having N1 turns and BC is secondary winding having N2 turns.
Neglecting iron losses and no-load current.
• The current in section CB is vector difference of I2 and I1. But as the two currents are practically
in phase opposition, the resultant current is (I2 − I1) where I2 is greater than I1.
22-12-2024 Basic Electrical Engineering, Payal Shah, SPIT 63
Three Phase Transformer
Three identical single-phase transformers can be connected to form a 3-phase bank. Primary and
secondary sides of the bank can be connected in star/delta with various possible arrangements as
– star/star
– delta/delta
– star/delta or delta/star
But three phase transformer has following advantages over 3 single phase transformers, hence
popularly used.
✓Occupies less floor space for equal rating
✓Weighs less
✓Costs about 15% less
✓Only one unit is to be handled and connected.
• The three cores are 120° apart and their empty legs are shown in contact with each other. The center
leg, formed by these three, carries the flux produced by the three phase currents IR, IY and IB. As at any
instant IR + IY + IB = 0, hence the sum of three fluxes is also zero.
• Therefore, it will make no difference if the common leg is removed. In that case any two legs will act as
the return for the third just as in a 3-phase system any two conductors act as the return for the current
in the third conductor
• In finding voltages and currents in a 3-phase transformer along with the ratio of transformation
between the coupled windings, the line and phase relationship of star/delta connections with the
assumption that the transformer is feeding a balanced load needs to be used
• Voltage transformer: used for metering and protection purpose in high voltage circuits
• Resonant transformer: uses leakage inductance of secondary winding with external capacitor to create
one or more resonant circuits