SHORT-CIRCUIT-CALCULATION

The document details the short circuit calculations for a utility system at 13.2 kV, including the Thevenin equivalent impedance and transformer impedance. It provides fault current calculations for various segments of the electrical distribution system, specifying resistance and inductance values for different cable sizes and lengths. The calculated fault currents range from 293.206A to 46,377.67A across multiple pathways from the service entrance to various load points.

Uploaded by

iversoncabadin3
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
4 views

SHORT-CIRCUIT-CALCULATION

The document details the short circuit calculations for a utility system at 13.2 kV, including the Thevenin equivalent impedance and transformer impedance. It provides fault current calculations for various segments of the electrical distribution system, specifying resistance and inductance values for different cable sizes and lengths. The calculated fault currents range from 293.206A to 46,377.67A across multiple pathways from the service entrance to various load points.

Uploaded by

iversoncabadin3
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
You are on page 1/ 24

SHORT CIRCUIT CALCULATION

Utility Impedance
Fault Duty at Point Connection at 13.2 kV (Assumed)
Maximum 3-Φ MVA Fault Duty = 100
Thevenin Equivalent Impedance

X/R = 10
Zth (ohms, Ref to 230V) = 𝑘𝑉 2 𝑀𝑉𝐴 = (0.23) 2 100 = 0.000529 Ω
Rth (ohms, Ref to 230V) = Zpu * cos (tan-1 (X/R)) = (0.000529) * (cos
(tan-1 (10))) = 0.0000526 Ω
Xth (ohms, Ref to 230V) = = Zpu * sin (tan-1 (X/R)) = (0.000529) * (sin
(tan-1 (10))) = 0.0005264 Ω

Transformer Impedance
kVA: 3-225 kVA, 3-phase, 60Hz
Primary Voltage Rating: 19.92kV
Secondary Voltage Rating: 230V
Percent Z (%Z): 5
MVABASE = 100
MVATR = 0.675
X/R ratio = 2.8

Zpu =
%Z∗ ( MVAtrans
MVA
) = 5∗( 100
675 ) = 7.407 Ω
100 100

2 2
kV 0.23
Z referred to 230V = Zpu* = 7.407 * = 0.003918 Ω
MVA 100
R referred to 230V = Zpu * cos (tan-1 (X/R)) = (0.003918) * (cos (tan-1 (2.8))) = 0.001318Ω
X referred to 230V = Zpu * sin (tan-1 (X/R)) = (0. 003918) * (sin (tan-1 (2.8))) = 0.003690Ω
FORMULA USED:

Fault Current:
230
If 3-Φ =
√(Rth+ Rref + Rtotal )2+(X th+ X ref + X total)2

Total Resistance:
R L
=( ( )
¿ of∥¿ ¿ 305

Total Inductance:
X L
=( ( )
¿ of∥¿ ¿ 305

qwertyuioasdfhjlzxcnm
From Service Entrance to MDP
Used: 5 sets of 325mm2 THW
L = 15 m
R = 0.0250 Ω/ 305m
X = 0.0480 Ω/ 305m
Total Resistance
0.0250 15
=( ¿( ) = 0.000246Ω
5 305
Total Inductance
0.04 8 15
=( ¿( ) = 0.000472Ω
5 305

Fault Current:
230
If 3-Φ = =
√(0.0000526+ 0.001318+0.000246)2 +(0.0005264 +0.003690+ 0.000472)2
46,377.67A
From MDP to MCB1
Used: 2 sets of 150mm2 THW
L = 25 m
R = 0.0450 Ω/ 305m
X = 0.0510Ω/ 305m

Total Resistance
0. 0450 25
=( ¿( ) = 0.001844Ω
2 305
Total Inductance
0. 0510 25
=( ¿( ) = 0.002090Ω
2 305

Fault Current:
230
If 3-Φ = =
√(0.0000526+ 0.001318+0.001844)2 +(0.0005264+0.003690+ 0.00 2090)2
32,493.029A

From MCB1 to LPP 1-A


Used: 1 set of 50mm2 THW
L = 23 m
R = 0.1200Ω / 305m
X = 0.0550Ω / 305m

Total Resistance
0.1200 23
=( ¿( ) = 0.009049Ω
1 305
Total Inductance
0. 055 0 2 3
=( ¿( ) = 0.004148Ω
1 305
Fault Current:
230
If 3-Φ = =
√(0.0000526+ 0.001318+0.009049)2+(0.0005264 +0.003690+0.004148)2
17,213.56A

From MCB1 to LPP 1-B


Used: 1 set of 50mm2 THW
L = 30 m
R = 0.1200Ω / 305m
X = 0.0550Ω / 305m

Total Resistance
0.1200 30
=( ¿( ) = 0.01180Ω
1 305
Total Inductance
0. 055 0 30
=( ¿( ) = 0.00541Ω
1 305

Fault Current:
230
If 3-Φ = =
√(0.0000526+ 0.001318+0.01180)2 +(0.0005264+0.003690+ 0.00541)2
14,098.7A

From MCB1 to LPP 1-C


Used: 1 set of 8mm2 THW
L = 10 m
R = 0.7800Ω / 305m
X = 0.0650Ω / 305m

Total Resistance
0.7800 10
=( ¿( ) = 0.02557 Ω
1 305
Total Inductance
0.0650 10
=( ¿( ) = 0.002131 Ω
1 305

Fault Current:
230
If 3-Φ = =
√(0.0000526+ 0.001318+0. 02557)2+(0.0005264 +0.003690+0. 002131)2
8,309.775A

From MCB1 to LPP 1-D


Used: 1 set of 8mm2 THW
L = 35 m
R = 0.7800Ω / 305m
X = 0.0650Ω / 305m

Total Resistance
0.7800 35
=( ¿( ) = 0.08950 Ω
1 305
Total Inductance
0.0650 35
=( ¿( ) = 0.007459 Ω
1 305

Fault Current:
230
If 3-Φ = =
√(0.0000526+ 0.001318+0. 08950)2+(0.0005264+ 0.003690+0. 007459)2
2,510.435A

From MCB1 to LPP 1-E


Used: 1 set of 22mm2 THW
L = 15 m
R = 0.3100 Ω / 305m
X = 0.0600 Ω / 305m
Total Resistance
0.3100 15
=( ¿( ) = 0.01525 Ω
1 305
Total Inductance
0. 0600 15
=( ¿( ) = 0.002951 Ω
1 305

Fault Current:
230
If 3-Φ = =
√(0.0000526+ 0.001318+0. 01525)2+(0.0005264+ 0.003690+0. 002951)2
12,408.41A
From MCB1 to LPP 1-F
Used: 1 set of 8mm2 THW
L = 12 m
R = 0.7800Ω / 305m
X = 0.0650Ω / 305m

Total Resistance
0.7800 12
=( ¿( ) = 0.03069 Ω
1 305
Total Inductance
0.0650 12
=( ¿( ) = 0.002557 Ω
1 305

Fault Current:
230
If 3-Φ = =
√(0.0000526+ 0.001318+0. 03069)2+(0.0005264+ 0.003690+0. 002557)2
7,018.98 A

From MCB1 to LPP 1-G


Used: 1 set of 8mm2 THW
L = 24 m
R = 0.7800Ω / 305m
X = 0.0650Ω / 305m

Total Resistance
0.7800 24
=( ¿( ) = 0.06138 Ω
1 305
Total Inductance
0.0650 24
=( ¿( ) = 0.005115 Ω
1 305

Fault Current:
230
If 3-Φ = =
√(0.0000526+ 0.001318+0. 0 6138)2 +(0.0005264+ 0.003690+0. 005115)2
3,625.44 A

From MCB1 to LPP 1-H


Used: 1 set of 22mm2 THW
L = 36 m
R = 0.3100 Ω / 305m
X = 0.0600 Ω / 305m

Total Resistance
0.3100 36
=( ¿( ) = 0.03659 Ω
1 305
Total Inductance
0. 0600 36
=( ¿( ) = 0.007082 Ω
1 305

Fault Current:
230
If 3-Φ = =
√(0.0000526+ 0.001318+0. 03659)2+(0.0005264+ 0.003690+0. 007082)2
5807.15 A

From MCB1 to LPP 1-I


Used: 1 set of 8mm2 THW
L = 10 m
R = 0.7800Ω / 305m
X = 0.0650Ω / 305m

Total Resistance
0.7800 10
=( ¿( ) = 0.02557 Ω
1 305
Total Inductance
0.0650 10
=( ¿( ) = 0.002131 Ω
1 305

Fault Current:
230
If 3-Φ = =
√(0.0000526+ 0.001318+0. 02557)2+(0.0005264 +0.003690+0. 002131)2
8,309.775A

From MDP to MCB2


Used: 2 sets of 150mm2 THW
L = 29 m
R = 0.4900 Ω/ 305m
X = 0.0640 Ω/ 305m

Total Resistance
0.4900 2 9
=( ¿( ) = 0.0466 Ω
2 305
Total Inductance
0.0640 2 9
=( ¿( ) = 0.0061 Ω
2 305

Fault Current:
230
If 3-Φ = =
√(0.0000526+ 0.001318+0.0466)2 +(0.0005264 +0.003690+ 0.0061)2
4,687.43A

From MCB2 to LPP 2-A


Used: 1 set of 8mm2 THW
L=5m
R = 0.7800 Ω / 305m
X = 0.0650 Ω / 305m
Total Resistance
0.7800 5
=( ¿( ) = 0.0128 Ω
1 305
Total Inductance
0.0650 5
=( ¿( ) = 0.0011 Ω
1 305

Fault Current:
230
If 3-Φ = =
√(0.0000526+ 0.001318+0.0128)2+(0.0005264 +0.003690+0.0011)2
15,196.50A

From MCB2 to LPP 3-A


Used: 1 set of 8mm2 THW
L = 10 m
R = 0.7800 Ω / 305m
X = 0.0650 Ω / 305m

Total Resistance
0.7800 10
=( ¿( ) = 0.0256 Ω
1 305
Total Inductance
0.0650 10
=( ¿( ) = 0.0021 Ω
1 305

Fault Current:
230
If 3-Φ = =
√(0.0000526+ 0.001318+0.0256)2 +(0.0005264 +0.003690+ 0.0021)2
293.206A

From MDP to MCB3


Used: 2 sets of 150mm2 THW
L = 33 m
R = 0.0450 Ω/ 305m
X = 0.0510 Ω/ 305m

Total Resistance
0. 0450 33
=( ¿( ) = 0.0024 Ω
2 305
Total Inductance
0. 0510 33
=( ¿( ) = 0.0028 Ω
2 305

Fault Current:
230
If 3-Φ = =
√(0.0000526+ 0.001318+0.0024)2 +(0.0005264+0.003690+ 0.0028)2
28,874.95A

From MDP to MCB4


Used: 2 sets of 150mm2 THW
L = 37 m
R = 0.0450 Ω/ 305m
X = 0.0510 Ω/ 305m

Total Resistance
0. 0450 37
=( ¿( ) = 0.00273 Ω
2 305
Total Inductance
0. 0510 3 7
=( ¿( ) = 0.003093 Ω
2 305

Fault Current:
230
If 3-Φ = =
√(0.0000526+ 0.001318+0. 00273)2+(0.0005264+ 0.003690+0. 003093)2
27,442.81A
From MDP to MCB5
Used: 2 sets of 150mm2 THW
L = 41 m
R = 0.0450 Ω/ 305m
X = 0.0510 Ω/ 305m

Total Resistance
0. 0450 41
=( ¿( ) = 0.003025 Ω
2 305
Total Inductance
0. 0510 41
=( ¿( ) = 0.003428 Ω
2 305

Fault Current:
230
If 3-Φ = =
√(0.0000526+ 0.001318+0. 003025)2+(0.0005264+ 0.003690+0. 003428)2
51,730.457A

From MDP to MCB6


Used: 2 sets of 150mm2 THW
L = 45 m
R = 0.0450 Ω/ 305m
X = 0.0510 Ω/ 305m
Total Resistance
0. 0450 4 5
=( ¿( ) = 0.00332 Ω
2 305
Total Inductance
0. 0510 4 5
=( ¿( ) = 0.003762 Ω
2 305
Fault Current:
230
If 3-Φ = =
√(0.0000526+ 0.001318+0. 00332)2 +(0.0005264+ 0.003690+0. 003762)2
24,851.204A
Note: THE SHORT CIRCUIT IN EACH DWELLING ROOM IS SAME IN EVERY FLOOR (FOUR
FLOORS, MCB3, MCB4, MCB5, MCB6) SINCE THEY ARE SYMMETRICAL
From MCB3 to LPP 4-K / MCB4 to LPP 5-K / MCB5 to LPP 6-K /
MCB6 to LPP 7-K
Used: 1 set of 8mm2 THW
L = 14 m
R = 0.4900 Ω / 305m
X = 0.0640 Ω / 305m
Total Resistance
0.4900 14
=( ¿( ) = 0.0161 Ω
1 305
Total Inductance
0.0640 14
=( ¿( ) = 0.0021 Ω
1 305

Fault Current:
230
If 3-Φ = =
√(0.0000526+ 0.001318+0.0161)2+(0.0005264+ 0.003690+0.0021)2
12,380.65A

From MCB3 to LPP 4-P / MCB4 to LPP 5-P / MCB5 to LPP 6-P / MCB6
to LPP 7-P
Used: 1 set of 8mm2 THW
L = 30 m
R = 0.4900 Ω / 305m
X = 0.0640 Ω / 305m
Total Resistance
0.4900 30
=( ¿( ) = 0.0482 Ω
1 305
Total Inductance
0.0640 30
=( ¿( ) = 0.0063 Ω
1 305
Fault Current:
230
If 3-Φ = =
√(0.0000526+ 0.001318+0.0482)2+(0.0005264+ 0.003690+0.0063)2
4,538.83A

From MCB3 to LPP 4-A / MCB4 to LPP 5-A / MCB5 to LPP 6-A /
MCB6 to LPP 7-A
Used: 1 set of 8mm2 THW
L = 18 m
R = 0.4900 Ω / 305m
X = 0.0640 Ω / 305m

Total Resistance
0.4900 18
=( ¿( ) = 0.0289 Ω
1 305
Total Inductance
0.0640 18
=( ¿( ) = 0.0038 Ω
1 305

Fault Current:
230
If 3-Φ = =
√(0.0000526+ 0.001318+0.0289)2+(0.0005264 +0.003690+0.0038)2
7,344.93A

From MCB3 to LPP 4-F / MCB4 to LPP 5-F / MCB5 to LPP 6-F / MCB6
to LPP 7-F
Used: 1 set of 8mm2 THW
L = 33 m
R = 0.4900 Ω / 305m
X = 0.0640 Ω / 305m

Total Resistance
0.4900 33
=( ¿( ) = 0.0530 Ω
1 305
Total Inductance
0.0640 33
=( ¿( ) = 0.0069 Ω
1 305

Fault Current:
230
If 3-Φ = =
√(0.0000526+ 0.001318+0.0530)2+(0.0005264 +0.003690+0.0069)2
7,344.93A
From MCB3 to LPP 4-G / MCB4 to LPP 5-G / MCB5 to LPP 6-G /
MCB6 to LPP 7-G
Used: 1 set of 22mm2 THW
L = 12 m
R = 0.3100 Ω / 305m
X = 0.0600 Ω / 305m
Total Resistance
0.3100 12
=( ¿( ) = 0.0122 Ω
1 305
Total Inductance
0.0600 12
=( ¿( ) = 0.0024 Ω
1 305
Fault Current:
230
If 3-Φ = =
√(0.0000526+ 0.001318+0.0122)2+(0.0005264+ 0.003690+0.0024)2
15,234.20A

From MCB3 to LPP 4-I / MCB4 to LPP 5-I / MCB5 to LPP 6-I / MCB6
to LPP 7-I
Used: 1 set of 22mm2 THW
L=9m
R = 0.3100 Ω / 305m
X = 0.0600 Ω / 305m
Total Resistance
0.3100 9
=( ¿( ) = 0.0091 Ω
1 305
Total Inductance
0.0600 9
=( ¿( ) = 0.0018 Ω
1 305
Fault Current:
230
If 3-Φ = =
√(0.0000526+ 0.001318+0.0091)2+(0.0005264+ 0.003690+0.0018)2
19,046A
From MCB3 to LPP 4-H / MCB4 to LPP 5-H / MCB5 to LPP 6-H /
MCB6 to LPP 7-H
Used: 1 set of 22mm2 THW
L = 34 m
R = 0.3100 Ω / 305m
X = 0.0600 Ω / 305m

Total Resistance
0.3100 34
=( ¿( ) = 0.0346 Ω
1 305
Total Inductance
0.0600 34
=( ¿( ) = 0.0067 Ω
1 305

Fault Current:
230
If 3-Φ = =
√(0.0000526+ 0.001318+0.0346)2 +(0.0005264 +0.003690+ 0.0067)2
6,118.55A

From MCB3 to LPP 4-J / MCB4 to LPP 5-J / MCB5 to LPP 6-J / MCB6
to LPP 7-J
Used: 1 set of 22mm2 THW
L = 33 m
R = 0.3100 Ω / 305m
X = 0.0600 Ω / 305m

Total Resistance
0.3100 3 3
=( ¿( ) = 0.0335 Ω
1 305
Total Inductance
0.0600 3 3
=( ¿( ) = 0.0065 Ω
1 305

Fault Current:
230
If 3-Φ = =
√(0.0000526+ 0.001318+0.0335)2+(0.0005264 +0.003690+0.0065)2
6,3O4.80A

From MCB3 to LPP 4-B / MCB4 to LPP 5-B / MCB5 to LPP 6-B /
MCB6 to LPP 7-B
Used: 1 set of 8mm2 THW
L = 21 m
R = 0.7800 Ω / 305m
X = 0.0650 Ω / 305m
Total Resistance
0.3100 21
=( ¿( ) = 0.0537 Ω
1 305
Total Inductance
0.0600 21
=( ¿( ) = 0.0045 Ω
1 305
Fault Current:
230
If 3-Φ = =
√(0.0000526+ 0.001318+0.0537)2 +(0.0005264 +0.003690+ 0.0045)2
4,125.1A
From MCB3 to LPP 4-C / MCB4 to LPP 5-C / MCB5 to LPP 6-C / MCB6
to LPP 7-C
Used: 1 set of 8mm2 THW
L = 21 m
R = 0.7800 Ω / 305m
X = 0.0650 Ω / 305m
Total Resistance
0.3100 21
=( ¿( ) = 0.0537 Ω
1 305
Total Inductance
0.0600 21
=( ¿( ) = 0.0045 Ω
1 305
Fault Current:
230
If 3-Φ = =
√(0.0000526+ 0.001318+0.0537)2 +(0.0005264 +0.003690+ 0.0045)2
4,125.1A

From MCB3 to LPP 4-D / MCB4 to LPP 5-D / MCB5 to LPP 6-D /
MCB6 to LPP 7-D
Used: 1 set of 8mm2 THW
L = 29 m
R = 0.7800 Ω / 305m
X = 0.0650 Ω / 305m
Total Resistance
0.3100 2 9
=( ¿( ) = 0.0742 Ω
1 305
Total Inductance
0.0600 2 9
=( ¿( ) = 0.0062 Ω
1 305
Fault Current:
230
If 3-Φ = = 3,015A
√(0.0000526+ 0.001318+0.0742)2+(0.0005264+ 0.003690+0.0062)2

From MCB3 to LPP 4-E / MCB4 to LPP 5-E / MCB5 to LPP 6-E / MCB6
to LPP 7-E
Used: 1 set of 8mm2 THW
L = 29 m
R = 0.7800 Ω / 305m
X = 0.0650 Ω / 305m

Total Resistance
0.3100 29
=( ¿( ) = 0.0742 Ω
1 305
Total Inductance
0.0600 29
=( ¿( ) = 0.0062 Ω
1 305

Fault Current:
230
If 3-Φ = = 3,015A
√(0.0000526+ 0.001318+0.0742)2+(0.0005264+ 0.003690+0.0062)2

From MCB3 to LPP 4-E / MCB4 to LPP 5-E / MCB5 to LPP 6-E / MCB6
to LPP 7-E
Used: 1 set of 8mm2 THW
L = 16 m
R = 0.7800 Ω / 305m
X = 0.0650 Ω / 305m
Total Resistance
0.3100 16
=( ¿( ) = 0.0409 Ω
1 305
Total Inductance
0.0600 16
=( ¿( ) = 0.0034 Ω
1 305

Fault Current:
230
If 3-Φ = =
√(0.0000526+ 0.001318+0.0409)2+(0.0005264 +0.003690+0.0034 )2
5,354.9A
From MCB3 to LPP 4-M / MCB4 to LPP 5-M / MCB5 to LPP 6-M /
MCB6 to LPP 7-M
Used: 1 set of 8mm2 THW
L = 16 m
R = 0.7800 Ω / 305m
X = 0.0650 Ω / 305m
Total Resistance
0.3100 16
=( ¿( ) = 0.0409 Ω
1 305
Total Inductance
0.0600 16
=( ¿( ) = 0.0034 Ω
1 305

Fault Current:
230
If 3-Φ = =
√(0.0000526+ 0.001318+0.0409)2+(0.0005264 +0.003690+0.0034 )2
5,354.9A

From MCB3 to LPP 4-N


Used: 1 set of 8mm2 THW
L = 25 m
R = 0.7800 Ω / 305m
X = 0.0650 Ω / 305m

Total Resistance
0.3100 25
=( ¿( ) = 0.0639 Ω
1 305
Total Inductance
0.0600 25
=( ¿( ) = 0.0053 Ω
1 305

Fault Current:
230
If 3-Φ = =
√(0.0000526+ 0.001318+0.0639)2+(0.0005264 +0.003690+0.0053)2
3,486.93A
From MCB3 to LPP 4-O / MCB4 to LPP 5-O / MCB5 to LPP 6-O /
MCB6 to LPP 7-O
Used: 1 set of 8mm2 THW
L = 25 m
R = 0.7800 Ω / 305m
X = 0.0650 Ω / 305m

Total Resistance
0.3100 25
=( ¿( ) = 0.0639 Ω
1 305
Total Inductance
0.0600 25
=( ¿( ) = 0.0053 Ω
1 305

Fault Current:
230
If 3-Φ = =
√(0.0000526+ 0.001318+0.0639)2+(0.0005264 +0.003690+0.0053)2
3,486.93A

From MCB3 to LPP 4-Q / MCB4 to LPP 5-Q / MCB5 to LPP 6-Q /
MCB6 to LPP 7-Q
Used: 1 set of 8mm2 THW
L=5m
R = 0.7800 Ω / 305m
X = 0.0650 Ω / 305m
Total Resistance
0.3100 5
=( ¿( ) = 0.0128 Ω
1 305
Total Inductance
0.0600 5
=( ¿( ) = 0.0011 Ω
1 305
Fault Current:
230
If 3-Φ = =
√(0.0000526+ 0.001318+0.0128)2+(0.0005264 +0.003690+0.0011)2
15,196.50A

From MDP to MCB7


Used: 1 set of 14mm2 THW
L = 49 m
R = 0.4900 Ω / 305m
X = 0.0640 Ω / 305m
Total Resistance
0. 4900 49
=( ¿( ) = 0.07872 Ω
1 305
Total Inductance
0. 0640 49
=( ¿( ) = 0.01028 Ω
1 305
Fault Current:
230
If 3-Φ = =
√(0.0000526+ 0.001318+0. 07872)2 +(0.0005264+ 0.003690+0. 01028)2
2825.8322A

From MCB7 to LPP 8-A


Used: 1 set of 15mm2 THW
L = 22.8 m
R = 0.4900 Ω / 305m
X = 0.0640 Ω / 305m
Total Resistance
0. 4900 22.8
=( ¿( ) = 0.03663 Ω
1 305
Total Inductance
0. 0640 22.8
=( ¿( ) = 0.00478 Ω
1 305
Fault Current:
230
If 3-Φ = =
√(0.0000526+ 0.001318+0. 03663)2+(0.0005264+ 0.003690+0. 00478)2
5889.7335 A

From MDP to MCB1A


Used: 2 set of 125mm2 THW
L = 10 m
R = 0. 0.0540 Ω / 305m
X = 0. 0.0520 Ω / 305m
Total Resistance
0. 0540 10
=( ¿( ) = 0.000885 Ω
2 305
Total Inductance
0. 0520 10
=( ¿( ) = 0.000852 Ω
2 305
Fault Current:
230
If 3-Φ =
√(0.0000526+ 0.001318+0. 000885)2+(0.0005264+ 0.003690+0. 000852)2
=41,459.003A
From MCB1A to PP1
Used: 2 set of 125mm2 THW
L = 40 m
R = 0. 0.0540 Ω / 305m
X = 0. 0.0520 Ω / 305m
Total Resistance
0. 0540 4 0
=( ¿( ) = 0.00354 Ω
2 305
Total Inductance
0. 0520 4 0
=( ¿( ) = 0.00341 Ω
2 305
Fault Current:
230
If 3-Φ =
√(0.0000526+ 0.001318+0. 00354)2 +(0.0005264 +0.003690+ 0.00341)2
=25,356.62A