820-series-instruction-manual
820-series-instruction-manual
Instruction Manual
Part Number IM-82
Revision J, August 2022
Table of Contents Series 820 Instruction Manual
CORPORATE HEADQUARTERS
5 Harris Court, Building L Monterey, CA 93940
Phone (831) 373-0200 www.sierrainstruments.com
EUROPE HEADQUARTERS
Bijlmansweid 2 1934RE Egmond aan den Hoef The Netherlands
Phone +31 72 5071400
ASIA HEADQUARTERS
Second Floor Building 5, Senpu Industrial Park
25 Hangdu Road Hangtou Town
Pu Dong New District, Shanghai, P.R. China
Postal Code 201316
Phone: + 8621 5879 8521
TRADEMARKS
Top-TrakTM and Cal-Bench TM is a Registered Trademark of Sierra Instruments, Inc. Other product
and company names listed in this manual are trademarks or trade names of their respective manu-
facturers.
Series 820 Instruction Manual Table of Contents
Table of Contents
Chapter 1 Introduction
Introduction ............................................................................ 1-1
Using this Manual............................................................. 1-1
Safety Information ............................................................ 1-2
Receipt of System Components ....................................... 1-2
Technical Assistance ........................................................ 1-2
Top Trak Features................................................................... 1-3
The 820 Series Flow Sensing Principle .................................. 1-4
Chapter 2 Installation
Installation Overview.............................................................. 2-1
Installing the Transducer ........................................................ 2-2
Compression Fittings ........................................................ 2-2
VCO Fittings .................................................................... 2-2
VCR Fittings .................................................................... 2-3
All 1/2-inch Size Connections .......................................... 2-3
Wiring the Transducer ............................................................ 2-4
Standard 0-5 VDC Output Signal Wiring ........................ 2-5
Optional 4-20 mA Output Signal Wiring ......................... 2-5
Remote Display Installation ................................................... 2-6
Chapter 3 Operation
Transducer Operation ............................................................. 3-1
Transducer Accuracy ........................................................ 3-1
Referencing the Transducer to Non-Standard Conditions .... 3-2
Transducer Over-Ranging ................................................ 3-2
Zero and Span Adjustments ............................................. 3-3
Totalizer Option ................................................................ 3-4
IM-82 0-3
Table of Contents Series 820 Instruction Manual
List of Figures
1-1. Top-Trak Features (Typical) ....................................... 1-3
1-2. Flow Paths through the Transducer ............................ 1-4
1-3. Flow Measuring Principle ........................................... 1-4
2-1. Piping Requirements for 1/2-inch Size Connections ... 2-3
2-2. Transducer D-Connector Pin Assignments ................. 2-4
2-3. Standard 0-5 VDC Output Signal Wiring................... 2-5
2-4. Single Transducer Current Loop Connection.............. 2-5
2-5. Multiple Transducer Current Loop Connections ........ 2-6
2-6. Mounting the Remote Display .................................... 2-6
4-1. Model 822/824 Flow Components ............................. 4-2
4-2. Correct LFE Position................................................... 4-3
4-3. Model 826/827 Flow Components .............................. 4-4
4-4. Low Flow Transducer LFE Cleaning ......................... 4-5
4-5. Medium Flow Transducer LFE Cleaning ................... 4-6
4-6. High Flow Transducer LFE Cleaning......................... 4-7
4-7. Printed Circuit Board Component Locations .............. 4-11
0-4 IM-82
Series 820 Instruction Manual Table of Contents
Cautions
Caution! When using toxic or corrosive gases, purge the unit thoroughly
with inert dry gas before disconnecting from the gas line.
IM-82 0-5
Series 820 Instruction Manual Chapter 1 Introduction
Chapter 1 Introduction
This instruction manual covers the installation, operation and
maintenance of Sierra’s 820 Series product line including the fol-
lowing Top-Trakª Models:
• 822 Mass Flow Meter with display (nylon flow body)
• 824 Mass Flow Meter without display (nylon flow body)
• 826 Hi-Flow Meter with display (aluminum flow body)
• 827 Hi-Flow without display (aluminum flow body)
• 822-S Mass Flow Meter with display (stainless steel flow body)
• 824-S Mass Flow Meter without display (stainless steel flow body)
IM-82 1-1
Chapter 1 Introduction Series 820 Instruction Manual
Safety Information
Caution and warning statements are used throughout this book to
draw your attention to important information.
Warning! Caution!
This statement appears with information that This statement appears with information that is
is important to protect people and equip ment important for protecting your equipment and
from damage. Pay very clo se attention to all performance. Read and follow all cautions that
warnings that apply to your application. apply to your application.
Technical Assistance
If you encounter a problem with your transducer, review the confi-
guration information for each step of the installation, operation and
set up procedures. Verify that your settings and adjustments are
consistent with factory recommendations. Refer to Chapter 4,
Troubleshooting, for specific information and recommendations.
1-2 IM-82
Series 820 Instruction Manual Chapter 1 Introduction
Top-Trak Features
Standard Top-Trak Mass Flow Meters require a 12 to 15 VDC ex-
ternal power source (24 VDC input power optional). The transduc-
er’s 0 to 5 VDC output signal allows for flow recording, data-logging
or control. A 4 to 20 mA output signal is optionally available. Input
power and output signal connections are made via the 9-pin sub-
type D-connector located on the side of the transducer. An addi-
tional input power jack is located just below the D-connector. (It is
important to connect input power at only one location.)
IM-82 1-3
Chapter 1 Introduction Series 820 Instruction Manual
1-4 IM-82
Series 820 Instruction Manual Chapter 2 Installation
Chapter 2 Installation
Installation Overview
To ensure a successful installation, inlet and outlet tubing should be clean
and free from burrs or rims caused by cutting prior to plumbing the transduc-
er into the system. The protective caps covering the inlet/outlet fittings
should not be removed until immediately prior to installation.
1. Make sure the installation site meets the specific operating parameters
recorded on the transducer’s nameplate. Each transducer is factory-
configured for a specific gas and flow range. If the operating pressure is
more than 50 psi (3.4 bar) away from the calibration pressure, it is advis-
able to return the unit to the factory for re-calibration. (Adjusting zero
may be sufficient to remain within specification.)
3. For 1/2-inch size inlet/outlet process connections on models 826 and 827
make sure the location meets the minimum number of recommended pipe
diameters upstream and downstream of the transducer. A minimum of 5
inches (127 mm) upstream and 2-1/2 inches (64 mm) downstream is al-
ways recommended. (not necessary for other models)
5. If the gas contains any particulate matter, install an in-line filter prior to
the transducer. Recommended filter size: 15 micron for flows of 10
sccm to 30 slpm, 30 micron for above 30 slpm.
6. If a potential over-flow condition exists, insert a valve or critical orifice
in the line to limit flow to approximately 25 percent above the full scale
range of the meter.
7. Confirm that the transducer o-ring material is compatible with the gas to
be measured.
8. For remote displays, confirm the supplied cable is of sufficient length to
connect the components.
IM-82 2-1
Chapter 2 Installation Series 820 Instruction Manual
Compression Fittings
1. Position the transducer with the flow direction arrow pointing
downstream in the direction of flow.
2. Verify the position of the front
and back ferrule. Insert the
tubing into the fitting. Make
sure that the tubing rests firmly
on the shoulder of the fitting
and that the nut is finger tight.
(Do not mix or interchange
parts of tube fittings made by different manufactur- ers.)
3. Hold the body steady with a backup wrench. For 1/2-inch size,
tighten the nut 1-1/4 turns from finger tight. For 1/8-inch, 1/4- inch
and 3⁄8-inch sizes, tighten only 3/4 turn from finger tight. Do not
over-tighten!
4. Check the system’s entire flow path thoroughly for leaks. (Do not
use liquid leak detectors, instead monitor pressure decay. Over-
exposing the transducer to leak detector fluid may damage the unit.)
VCO Fittings
1. Position the transducer with the flow direction arrow pointing
downstream in the direction of flow.
2. Install new o-rings compatible with the gas to be used. (Do not mix
or interchange parts of tube fittings made by different manu-
facturers.)
3. Hold the body steady with a backup wrench. Tighten the nut
finger tight and then 1/4 turn tighter with a wrench. Do not over-
tighten!
4. Check the system’s entire flow path thoroughly for leaks. (Do not use
liquid leak detectors, instead monitor pressure decay. Over- exposing
the transducer to leak detector fluid may damage the unit.)
2-2 IM-82
Series 820 Instruction Manual Chapter 2 Installation
1. Position the transducer with the flow direction arrow pointing in the di-
rection of flow.
2. Use a good quality paste pipe thread sealant. Apply to pipe threads.
3. Tighten the pipe no more than 1 turn past hand-tight. Caution! Do not
over-tighten. Damage to the instrument may result.
2. Position the transducer with the flow direction arrow pointing down-
stream in the direction of flow.
3. Tighten fittings until leak tight (refer to published standards for specific
recommendations).
4. Check the system’s entire flow path thoroughly for leaks. (Do not use liq-
uid leak detectors, instead monitor pressure decay. Over-exposing the
transducer to leak detector fluid may damage the unit.)
Figure 2-1 Piping Requirements for all 1/2-Inch Size Process Connections
IM-82 2-3
Chapter 2 Installation Series 820 Instruction Manual
2-4 IM-82
Series 820 Instruction Manual Chapter 2 Installation
IM-82 2-5
Chapter 2 Installation Series 820 Instruction Manual
2-6 IM-82-E
Series 820 Instruction Manual Chapter 2 Installation
IM-82 2-7
Series 820 Instruction Manual Chapter 3 Operation
Chapter 3 Operation
The output signal of the transducer is either 0-5 VDC (standard) or
4-20 mA (optional). The output signal is linear and proportional to
the gas mass flow rate. For example, for a 0-5 VDC output signal,
5.00 VDC is the output signal for the full scale listed on the trans-
ducer’s nameplate, 2.50 VDC is for one-half of full scale, and 0.00
VDC is for zero flow. For a 4-20 mA output signal, 20.00 mA is
the output signal for the full scale, 12.00 mA is for one-half of full
scale, and 4.00 mA is for zero flow.
Transducer Operation
When the transducer is installed and the system has undergone a
complete leak check:
1. Apply power. The output signal will be at a high level for the
first 10 to 20 seconds while the sensor warms up to its normal
operating temperature range. Assuming zero flow, the output
signal will then drop to zero (or 4 mA, depending on output
configuration). Allow at least thirty minutes of warm-up time.
Transducer Accuracy
The standard accuracy of Top-Trak is ±1.5% of full scale. The
±1.5% of full scale accuracy means that the 0-5 VDC output sig-
nal is accurate to within ±.075 VDC. The 4-20 mA output is ac-
curate to within ±0.24 mA.
For example, the output signal for zero flow can be as much as
±.075 VDC or +0.24 mA. If the transducer has an output signal at
zero flow, as long as it is within either of these two ranges, it does
not mean it is malfunctioning.
IM-82 3-1
Chapter 3 Operation Series 820 Instruction Manual
Transducer Over-Ranging
If the flow rate exceeds the full scale value listed on the transducer
nameplate, the output signal and digital display (if so equipped)
will read a higher value. The transducer is not calibrated for over-
ranged flows and will probably be both non-linear and inaccurate.
Over-range conditions are indicated by the display and/or output
signal going to a level above the full scale range. When the over-
range condition is removed, it may take several seconds for the
transducer to recover and resume normal operation.
3-2 IM-82
Series 820 Instruction Manual Chapter 3 Operation
2. Connect a digital multimeter to Pin 3 (0-5 Out) or, Pin 9 (4-20 Out)
and Pin 7 (Power Common). Check the reading. If it does not
indicate 0± .05 VDC, (or 4.0± .016mA) adjust the zero poten-
tiometer.
IM-82 3-3
Chapter 3 Operation Series 820 Instruction Manual
Screens:
The totalizer display has three screens which are accessed by
pressing the button circled in the photo below:
Totalizer:
A total of 8 digits can be shown by the totalizer ranging from
.0000001 to 99999999. The decimal point will automatically shift
position as the total increases. Upon reaching the maximum count
(99999999), the totalizer will “roll-over”--be cleared and begin
counting from zero again.
3-4 IM-82
Series 820 Instruction Manual Chapter 4 Maintenance and Repair
Transducer Cleaning
Due to transducer design variations, separate cleaning instructions
are given in this chapter for each of the following models:
IM-82 4-1
Chapter 4 Maintenance and Repair Series 820 Instruction Manual
4-14 IM-82
Series 820 Instruction Manual Chapter 4 Maintenance and Repair
3. The LFE has a slightly tapered shape with the larger diameter
on the upstream (inlet) side. To remove, use a blunt object
which does not mar the flow channels to push the LFE from the
outlet side to the inlet side. A 3/8-inch (9 mm) nut driver works
well.
IM-82 4-3
Chapter 4 Maintenance and Repair Series 820 Instruction Manual
3. To remove the LFE, use a blunt object which does not mar
the flow channels to push the LFE from the flow body.
4-4 IM-82
Series 820 Instruction Manual Chapter 4 Maintenance and Repair
.
and unscrewing the LFE with a medium flat-tipped screwdriv-
er.
3. Remove the LFE assembly taking care not to bend the inlet
screen. Inspect the sealing O-ring and replace if necessary. In-
spect the inlet screen and replace if corroded or damaged. Light
to medium particulate contamination can be cleaned by back
washing with a suitable solvent. Air dry thoroughly.
IM-82 4-5
Chapter 4 Maintenance and Repair Series 820 Instruction Manual
3. Remove the LFE assembly taking care not to bend the inlet
screen. Inspect the sealing O-ring and replace if necessary. In-
spect the inlet screen and replace if corroded or damaged. Light
to medium particulate contamination can be cleaned by back
washing with a suitable solvent. Air dry thoroughly.
4-6 IM-82
Series 820 Instruction Manual Chapter 4 Maintenance and Repair
IM-82 4-7
Chapter 4 Maintenance and Repair Series 820 Instruction Manual
Caution! When usin g toxic or 1. Remove the transducer from the system. Remove the two sock-
corrosive gases, purge the unit et head access port plugs with a 1Ú4-inch Allen wrench. Visual-
thoroughly with inert dry gas
before disconnecting from the ly inspect the sensing ports and sensor.
gas line.
1. Use a hemostat or tweezers to
push the cleaning wire into the
downstream opening of the
sensor tube. Do not force the
cleaning wire, move it back and
forth–DO NOT TWIST OR
ROTATE.
4-8 IM-82-E
Series 820 Instruction Manual Chapter 4 Maintenance and Repair
3. Blow dry all parts with dry nitrogen and re-assemble. When the
transducer is installed in the system, leak test the connection.
Re-zero the transducer (see Chapter 3).
Transducer Calibration
Calibration of Sierra’s flow meters requires a calibration standard
of at least four times the accuracy of the transducer. Sierra’s Cal-
Caution! Bench Automated Primary Calibration System is the preferred me-
It is important that this
transducer be calibrated
thod of calibration and is used at the factory for all calibrations
only by qualified personnel. from 10 sccm up to 50 slpm. Most calibrations can be performed
with a digital voltmeter (DVM) or multimeter with 0.25% accuracy
and four digits, dry nitrogen and the K-factor tables included in this
manual. Flow meters require a metering valve for setting a constant
flow rate.
Step 1. Warm Up
Plug in the unit to be calibrated and allow at least 30 minutes warm
up time before attempting any adjustments.
Step 2. Zero Adjust
Slide open the zero and span access doors. Connect a DVM or
multimeter to the transducer output pins. Adjust the zero potenti-
ometer for 0.0 volts (4 mA) at zero flow.
Step 3. Check Full Scale
Generate full scale flow using a metering valve in-line with the unit
under test. Compare the indicated flow rate with the flow standard
reading. If they agree to within ±10%, adjust the span po-
tentiometer for exact agreement. If the readings do not agree with-
in ±10%, attempt to determine the cause of disagreement. Possibil-
ities are:
• leaks in the system or in the transducer
• wrong or improper use of K-factor
• wrong or improper correction for temperature and pressure
• partially clogged or dirty sensor tube
IM-82 4-9
Chapter 4 Maintenance and Repair Series 820 Instruction Manual
2. Remove the two Phillips head screws from the top of the trans-
ducer enclosure. Remove the two Phillips head screws from the
back of the transducer enclosure. Pull the enclosure panels off.
4-10 IM-82
Series 820 Instruction Manual Chapter 4 Maintenance and Repair
Transducer Troubleshooting
When you suspect that the transducer is not operating correctly,
there are a few simple checks that can be made before taking the
unit out of service:
2. Check that all cables are connected and are in good condition.
IM-82 4-11
Chapter 4 Maintenance and Repair Series 820 Instruction Manual
Unit will not zero Gas leak Find and correct leaks
Application requires high pres- Re-zero transducer
sure and non-horizontal mounting (see Chapter 3)
PCB defective Return to factory for repair
4-12 IM-82
Series 820 Instruction Manual Chapter 4 Maintenance and Repair
The following information will help you return your instrument to Sierra
Instruments' Factory Service Center and will ensure that your order is
processed promptly. Prices may vary depending on the flow range, type of
gas and operating pressure of your unit. To request a rough estimate of the
pricing, contact your local Sierra Instruments distributor or contact one of
our offices directly. A detailed quote will be provided following a full
evaluation of your instrument.
Please follow these easy steps to return your instrument for fac-
tory service:
1. Obtain a Return Materials Authorization (RMA) number from the
Sierra Instruments website at
http://www.sierrainstruments.com/rma/login.php
IM-82 4-13
Chapter 4 Maintenance and Repair Series 820 Instruction Manual
4-14 IM-82
Series 820 Instruction Manual Appendix A
If your transducer has a flow rate reading of 10.00 slm and was cali-
brated at standard conditions of 70°F (21°C) and 1 atmosphere (14.7
psia), and if you wish to convert this reading to standard conditions of
32°F (0°C) and 1 atmosphere, then you would use Equation (1) as
follows:
14.7 460 + 32
Q2 = (10.0) = 9.28 slm
14.7 460 + 70
The flow rate referenced to 0°C will be approximately 7% lower than
when referenced to standard conditions of 21 °C.
IM-82 A-1
Appendix A Series 820 Instruction Manual
Where:
H = µC p T2
(2)
A-2 IM-82
Series 820 Instruction Manual Appendix A
Where:
µ = ρQ (3)
Where:
ΔT = aE (4)
where:
a = a constant.
If we combine equations (3) and (4), insert them into equation (2),
and solve for Q, we get
Q = (bN/ρCp) (5)
where:
b = H/aE = a constant if the output voltage is constant.
IM-82 A-3
Appendix A Series 820 Instruction Manual
For our purposes, we want the ratio of the flow rate, Q1 , for an ac-
tual gas to the flow rate of a reference gas, Q2 , which will produce
the same output voltage in a particular mass flow meter or control-
ler. We get this by combining equations (1) and (5):
A-4 IM-82
Series 820 Instruction Manual Appendix A
Where:
Cp = F1 Cp1 + F2 Cp2
Where:
IM-82 A-5
Series 820 Instruction Manual Appendix A