20comm
20comm
PRODUCT HIGHLIGHTS
Installation – The adapter mounts internal
to the drive to save valuable panel space, and
is field installable. If an external connection
is needed, the adapter can also be installed
in a DPI External Communications Kit
(20-XCOMM-DC-BASE).
Configuration Switches – The adapter has
configuration switches for setting the MAC
address (addressable up to node 127), and
enabling/disabling the termination and
bias resistors.
Supported Data Rates – The adapter can
“autoband” out-of-the-box or be set to one
of four selectable baud rates (9600, 19200,
38400 or 76800 bps), and can be configured
using a parameter.
Multiple Configuration Tool Options – A User Configurable Fault Responses – Selects the action that the adapter and
number of configuration tools can be used to drive will take for the following two conditions:
configure the adapter and the connected
• Idle Fault Action – the scanner is idle (controller in program mode)
drive. These tools include the PowerFlex DPI
HIM, or drive-configuration software such as • Comm Fault Action – network communications have become disrupted
DriveExplorer™ or DriveExecutive™. Available actions include:
DPI Routing – Allows DriveExplorer to • Fault – the drive is faulted and stopped
connect to a PowerFlex drive using a 1203-SSS • Stop – the drive is stopped using the current deceleration rate and is not faulted
or 1203-USB converter and then route over • Zero Data – the adapter zeros the I/O data transmitted to the drive
BACnet MS/TP to access other Allen-Bradley®
• Hold Last – the adapter continues sending the I/O data prior to the fault and the
drives. This eliminates the need for a separate
network connection and interface. drive continues in its present state
• Send Fault Configuration – the user specifies the Logic Command, Reference, and
BACnet Objects – Unlike other PowerFlex Datalink data that is sent to the drive, allowing complete flexibility in
drive communication adapters, BACnet
MS/TP adapters use network objects to view configuring a fault action
logic status, speed feedback and monitor Diagnostics – Built-in diagnostics allow drive-side troubleshooting of the network
parameter values, and to send logic control, connection using a PowerFlex DPI HIM, DriveExplorer or DriveExecutive. View
speed reference and change parameter
values. The following objects are supported actual Logic Command/Speed Reference, Logic Status/Speed Feedback and Datalink
by the adapter: data being transmitted to and from the controller.
• Analog Input (AI) Flash Upgradeable – The adapter can be flash updated in the field using
• Analog Output (AO)
DriveExplorer, DriveExecutive or ControlFLASH to take advantage of new firmware
• Analog Value (AV)
• Binary Input (BI) features as they become available.
• Binary Output (BO)
• Binary Value (BV)
20-COMM-B_PP_10_4.qxd:Layout 1 11/1/06 11:40 AM Page 2
PARAMETERS SPECIFICATIONS
No. Name Description Communications Network Protocol BACnet MS/TP
01 Reset Module Resets the adapter or sets the adapter parameters to factory default. Data Rates 9600, 19200, 38400 or 76800 bps
02 Comm Loss Action Sets the action that the adapter and drive will take if the adapter Drive Protocol DPI
detects a network failure. Data Rates 125 or 500 Kbps
03 Comm Loss Time Sets the communication loss timeout period (in seconds). Electrical Consumption Drive (DPI) 150 mA at 5 VDC
04 Flt Cfg Logic Sets the data that is sent to the drive if Parameter 02 – [Comm Loss Action] Network None
05 Flt Cfg Ref is set to “Send Flt Cfg” and the adapter times out. Regulatory BACnet BTL (BACnet Testing Laboratories)
06 Baud Rate Cfg Sets the baud rate (kilobits per second) at which the adapter communicates. approval pending
07 Baud Rate Act Displays the baud rate (kilobits per second) actually used by the adapter. UL UL508C
08 MAC Address Displays the actual address selected by the MAC address switches cUL CAN/CSA C22.2 No. 14-M91
SW1 – SW7 on the adapter.
CE EN50178 and EN61800-3
09 Max Master Sets the maximum MAC address for any device in the BACnet
CTick EN61800-3
MS/TP token ring.
10 Max Info Frames Sets the maximum number of messages that the adapter can transmit
while it owns the token.
11 Device Instance Sets the device instance number used by the adapter.
LD
LD
SH
SH
SH
+B
+B
+B
-A
-A
-A
1 2 3 4 5 6 7 8
1 2 3 4
Laptop or Desktop PC
with DriveExplorer
RK RK RK
D1 D1 D1
J2 J2 J2
RK
1 1 1
D2
RK
FRN AS SHIPPED: V 1.001 FRN AS SHIPPED: V 1.001 FRN AS SHIPPED: V 1.001
D3
20-COMM-B SERIAL NUMBER: 402D9423 20-COMM-B SERIAL NUMBER: 402D9423 20-COMM-B SERIAL NUMBER: 402D9423
RK SERIES A DEVICE: 5VDC 250mA SERIES A DEVICE: 5VDC 250mA SERIES A DEVICE: 5VDC 250mA
D4 D4 D4
LISTED
N223 LISTED
N223 LISTED
N223
IND.CONT.EQ. IND.CONT.EQ. IND.CONT.EQ.
966X 966X 966X
R5 R5 R5
R6 R6 R6
2 2 2
TERMS
TERMS
MAC
MODE
MAC
MODE
MAC
MODE
+BIAS
+BIAS
+BIAS
-BIAS
-BIAS
-BIAS
RSRV
RSRV
RSRV
1 2 3 4 1 2 3 4 5 6 7 1 2 3 4 1 2 3 4 5 6 7 1 2 3 4 1 2 3 4 5 6 7
1203-USB or 1203-SSS
Converter
Drive Cable
Use DriveExplorer Lite or Full to configure a single Use DriveExplorer Full to route through DPI and configure
drive and its installed BACnet adapter. drives connected directly on BACnet (Up to 127 drives!)
Publication 20COMM-PP001F-EN-P – May 2008 Copyright ©2008 Rockwell Automation, Inc. All Rights Reserved. Printed in USA.
20-COMM-C_PP_NL_8_2:Layout 1 8/23/06 8:04 AM Page 1
PRODUCT HIGHLIGHTS
Internal Mount – The adapter mounts
internal to the drive to save panel space, and
is field installable.
Configuration Switches – The adapter has
rotary switches for setting the node address.
Alternatively, the switches can be disabled,
allowing the node address to be set using a
configuration parameter.
Redundancy – The adapter provides a
redundant media connection for improved
media reliability. The adapter also supports
multicast and redundant owner/hot backup.
Multiple Configuration Tool Options – A
number of configuration tools can be used
to configure the adapter and the connected User Configurable Fault Responses – Selects the action that the adapter and
drive. These tools include the PowerFlex DPI drive will take for the following two conditions:
HIM, or drive configuration software such as • Idle Fault Action – the scanner is idle (controller in program mode)
DriveExplorer™ or DriveExecutive™. • Comm Fault Action – network communications have become disrupted
DPI Routing – Allows DriveExplorer to connect Available actions include:
to a PowerFlex drive using a 1203-SSS or • Fault – the drive is faulted and stopped
1203-USB converter and then route over • Stop – the drive is stopped using the current deceleration rate and is not faulted
ControlNet to access other Allen-Bradley • Zero Data – the adapter zeros the I/O data transmitted to the drive
drives. This eliminates the need for a separate • Hold Last – the adapter continues sending the I/O data prior to the fault and the
network tap and interface. drive continues in its present state
I/O Messaging (Scheduled) – I/O messaging • Send Fault Configuration – the user specifies the Logic Command, Reference,
is used to transfer time-critical data, such as and Datalink data that is sent to the drive, allowing complete flexibility in
data that controls the drive. The following configuring a fault action
data can be sent and received by the adapter: Diagnostics – Built-in diagnostics allow drive-side troubleshooting of the network
• Logic Command/Reference connection using a PowerFlex DPI HIM, DriveExplorer or DriveExecutive. View
• Logic Status/Feedback actual Logic Command/Reference, Logic Status/Feedback and Datalink data being
• Datalinks – read and write up to 8 parameters transmitted to and from the controller.
Explicit Messaging (Unscheduled) – Flash Upgradeable – The adapter can be flash updated in the field using
Explicit messaging involves non time-critical DriveExplorer, DriveExecutive or ControlFLASH to take advantage of new firmware
information that is typically triggered by the features as they become available.
application (ladder program in a controller,
etc.). The adapter supports the reading/
writing of parameters, etc. in the drive and
any connected DPI peripheral(s).
20-COMM-C_PP_NL_8_2:Layout 1 8/23/06 8:04 AM Page 2
PARAMETERS SPECIFICATIONS
No. Name Description Communications Network Protocol ControlNet
01 DPI Port Displays the port to which the adapter is connected. Data Rate 5 Mbps
02 DPI Data Rate Displays the data rate (kilobits per second) used by the drive. Drive Protocol DPI
03 CN Addr Cfg Configures the ControlNet node address if the Node Address Data Rates 125 or 500 Kbps
Switches are set to “00.” Electrical Consumption Drive (DPI) 275 mA at 5 VDC
04 CN Addr Act Displays the ControlNet node address actually used by the adapter. Network None
05 CN Rate Cfg Configures the ControlNet data rate (megabits per second) Regulatory UL UL508C
at which the adapter communicates.
Compliance cUL CAN/CSA C22.2 No. 14-M91
06 CN Rate Act Displays the ControlNet data rate (megabits per second)actually used
by the adapter. CE EN50178 and EN61800-3
07 Ref/Fdbk Size Displays the size of the Reference/Feedback words. CTick EN61800-3
08 Datalink Size Displays the size of each Datalink word.
09 Reset Module Used to reset the adapter or set defaults.
10 Comm Flt Action Sets the action that the adapter will take if it detects a network failure.
EXAMPLE I/O IMAGE
11 Idle Flt Action Sets the action that the adapter will take if the adapter detects that
the scanner is idle.
ControlNet DPI
12 CN Active Cfg Displays the source from which the adapter node address is taken. Controller Scanner Adapter PowerFlex Drive
Word and I/O
13 DPI I/O Cfg Selects the I/O that is transferred through the adapter. 0 Logic Command Logic Command
Output
14 DPI I/O Active Displays the I/O that the adapter is actively transmitting. Image 1 Reference Reference
15 Flt Cfg Logic Sets the data that is sent to the drive if any of the following is true: (Write) 2 Datalink In A1 Data In A1
3 Datalink In A2 Data In A2
16 Flt Cfg Ref 4 Datalink In B1 Data In B1
17 Flt Cfg A1 • Parameter 10 - [Comm Flt Action] is set to 5 Datalink In B2 Data In B2
“Send Flt Cfg” and communications are disrupted. 6 Datalink In C1 Data In C1
18 Flt Cfg A2
7 Datalink In C2 Data In C2
19 Flt Cfg B1 • Parameter 11 - [Idle Flt Action] is set to “Send Flt Cfg” and the scanner is idle. 8 Datalink In D1 Data In D1
20 Flt Cfg B2 9 Datalink In D2 Data In D2
21 Flt Cfg C1 Input 0 Pad Word (1)
22 Flt Cfg C2 Image 1 Pad Word (1)
(Read) 2 Logic Status Logic Status
23 Flt Cfg D1
3 Feedback Feedback
24 Flt Cfg D2 4 Datalink Out A1 Data Out A1
25 M-S Input Selects the data produced by the scanner and consumed by the adapter. 5 Datalink Out A2 Data Out A2
6 Datalink Out B1 Data Out B1
26 M-S Output Selects the data produced by the adapter and consumed by the scanner. 7 Datalink Out B2 Data Out B2
27 Ref Adjust Sets the percent scale factor for the Reference from the network. 8 Datalink Out C1 Data Out C1
9 Datalink Out C2 Data Out C2
10 Datalink Out D1 Data Out D1
EDS FILES 11 Datalink Out D2 Data Out D2
EDS files can be created on-line using RSNetWorx for ControlNet or Message Message Message
Handler Buffer Handler
downloaded from: http://www.ab.com/drives/eds.html
Publication 20COMM-PP001F-EN-P – May 2008 Copyright ©2008 Rockwell Automation, Inc. All Rights Reserved. Printed in USA.
Supersedes Publication 20COMM-PP001E-EN-P – July 2006
20-COMM-D_PP_NL_8_14:Layout 1 8/23/06 7:29 AM Page 1
PRODUCT HIGHLIGHTS
Internal Mount – The adapter mounts
internal to the drive to save panel space, and
is field installable.
Configuration Switches – The adapter has
configuration switches for setting the node
address and network data rate. Alternatively,
the switches can be disabled, allowing these
settings to be configured using parameters.
Multiple Configuration Tool Options – A
number of configuration tools can be used
to configure the adapter and the connected
drive. These tools include the PowerFlex DPI
HIM, or drive-configuration software such as
DriveExplorer™ or DriveExecutive™.
DPI Routing – Allows DriveExplorer to connect
to a PowerFlex drive using a 1203-SSS or
1203-USB converter and then route over
DeviceNet to access other Allen-Bradley
drives. This eliminates the need for a separate 700H and 700S AC drives operating as "followers". The "master" can send control
network connection and interface. and speed reference data along with up to two parameter values.
I/O Messaging – I/O messaging is used to Automatic Device Replacement (ADR) Support – Allows a scanner to upload
transfer time-critical data, such as data that and store the adapter and drive configuration settings. Upon replacing a faulty
controls the drive. The following data can be drive with a new unit, the scanner can automatically download the configuration
sent and received by the adapter: data and set the node address.
• Logic Command/Reference User Configurable Fault Responses – Selects the action that the adapter and
• Logic Status/Feedback drive will take for the following two conditions:
• Datalinks - read and write up to 8 parameters • Idle Fault Action – the scanner is idle (controller in program mode)
Polled, Change-of-State (COS) and Cyclic I/O • Comm Fault Action – network communications have become disrupted
methods are supported.
Available actions include:
Explicit Messaging – Explicit messaging involves • Fault – the drive is faulted and stopped
non time-critical information that is typically • Stop – the drive is stopped using the current deceleration rate and is not faulted
triggered by the application (ladder program • Zero Data – the adapter zeros the I/O data transmitted to the drive
in a controller, etc.). The adapter supports the • Hold Last – the adapter continues sending the I/O data prior to the fault and
reading/writing of parameters, etc. in the the drive continues in its present state
drive and to any connected DPI peripheral(s). • Send Fault Configuration – the user specifies the Logic Command, Reference, and
UnConnected Message Manager (UCMM) Datalink data that is sent to the drive, allowing complete flexibility in
Support – The adapter supports DeviceNet configuring a fault action
Group 3 services, which allows the adapter to Diagnostics – Built-in diagnostics allow drive-side troubleshooting of the network
speak for itself (a scanner is not required to connection using a PowerFlex DPI HIM, DriveExplorer or DriveExecutive. View
'proxy' for the adapter). This allows a software actual Logic Command/Reference, Logic Status/Feedback and Datalink data being
tool, PanelView, another 20-COMM-D, etc. to transmitted to and from the controller.
communicate directly with the adapter, without
burdening the scanner and affecting throughput. Flash Upgradeable – The adapter can be flash updated in the field using
DriveExplorer, DriveExecutive or ControlFLASH to take advantage of new firmware
Peer-to-Peer Capability – Allows a features as they become available.
PowerFlex drive to operate as a "master" and
communicate with other PowerFlex 70, 700,
20-COMM-D_PP_NL_8_14:Layout 1 8/23/06 7:29 AM Page 2
PARAMETERS SPECIFICATIONS
No. Name Description Communications Network Protocol DeviceNet
01 DPI Port Displays the port to which the adapter is connected. Data Rates 125, 250, and 500 Kbps
02 DPI Data Rate Displays the data rate (kilobits per second) used by the drive. Drive Protocol DPI
03 DN Addr Cfg Configures the DeviceNet node address if the Data Rate switch is set to Data Rates 125 or 500 Kbps
“PGM” (Program). Electrical Consumption Drive (DPI) 150 mA at 5 VDC
04 DN Addr Act Displays the DeviceNet node address actually used by the adapter. Network 60 mA at 24 VDC
05 DN Rate Cfg Configures the DeviceNet data rate if the data rate switch is set to Regulatory UL UL508C
“PGM” (Program).
Compliance cUL CAN/CSA C22.2 No. 14-1791
06 DN Rate Act Displays the DeviceNet data rate actually used by the adapter.
CE EN50178 and EN61800-3
07 Ref/Fdbk Size Displays the size of the Reference/Feedback words.
CTick EN61800-3
08 Datalink Size Displays the size of each Datalink word.
09 Reset Module Used to reset the adapter or set defaults.
10 Comm Flt Action Sets the action that the adapter will take if it detects a network failure. EXAMPLE I/O IMAGE
11 Idle Flt Action Sets the action that the adapter will take if the adapter detects that
the scanner is idle.
12 DN Active Cfg Displays the source from which the adapter node address and data rate are taken.
DeviceNet DPI
13 DPI I/O Cfg Selects the I/O that is transferred through the adapter.
Controller Scanner Adapter PowerFlex Drive
14 DPI I/O Act Displays the I/O that the adapter is actively transmitting. Word and I/O
15 Flt Cfg Logic Sets the data that is sent to the drive if any of the following is true: Output 0 Logic Command Logic Command
16 Flt Cfg Ref • Parameter 10 - [Comm Flt Action] is set to “Send Flt Cfg” Image 1 Reference Reference
(Write) 2 Datalink In A1 Data In A1
17 Flt Cfg A1 In and communications are disrupted.
3 Datalink In A2 Data In A2
18 Flt Cfg A2 In • Parameter 11 - [Idle Flt Action] is set to “Send Flt Cfg” and the scanner is idle. 4 Datalink In B1 Data In B1
5 Datalink In B2 Data In B2
19 Flt Cfg B1 In • Parameter 34 - [Peer Flt Action] is set to “Send Flt Cfg” and 6 Datalink In C1 Data In C1
20 Flt Cfg B2 In communications are disrupted. 7 Datalink In C2 Data In C2
8 Datalink In D1 Data In D1
21 Flt Cfg C1 In 9 Datalink In D2 Data In D2
22 Flt Cfg C2 In
Input 0 Pad Word (1)
23 Flt Cfg D1 In Image 1 Pad Word (1)
(Read) 2 Logic Status Logic Status
24 Flt Cfg D2 In
3 Feedback Feedback
25 M-S Input Selects the data produced by the scanner and consumed by the adapter. 4 Datalink Out A1 Data Out A1
26 M-S Output Selects the data produced by the adapter and consumed by the scanner. 5 Datalink Out A2 Data Out A2
6 Datalink Out B1 Data Out B1
27 COS Status Mask Configures the mask for the 16-bit Logic Status word. If a bit is not masked 7 Datalink Out B2 Data Out B2
and it changes, it is reported as a change in the Change of State operation. 8 Datalink Out C1 Data Out C1
28 COS Fdbk Change Configures the hysteresis band to determine how much the Feedback word can 9 Datalink Out C2 Data Out C2
change before it is reported as a change in the Change of State operation. 10 Datalink Out D1 Data Out D1
11 Datalink Out D2 Data Out D2
29 COS/Cyc Interval Displays the amount of time that a scanner will wait to check for data in the adapter.
Message Message Message
30 Peer A Input Handler Buffer Handler
Configures the destination in the drive of the Peer I/O Input.
31 Peer B Input
32 Peer Cmd Mask Configures the mask for the Logic Command word when it is received
through peer input. EDS FILES
33 Peer Ref Adjust Scales the Reference received from a peer. EDS files can be created on-line using RSNetWorx for DeviceNet
34 Peer Flt Action Sets the action that the adapter and drive take if the adapter detects that or downloaded from: http://www.ab.com/drives/eds.html
communications with a peer have been disrupted.
35 Peer Node to Inp Configures the node address of the node producing the peer I/O.
36 Peer Inp Timeout Configures the time-out for a Change of State peer-to-peer connection.
37 Peer Inp Enable Determines if Peer I/O input is on or off.
38 Peer Inp Status Displays the status of the consumed peer input connection.
39 Peer A Output Selects the source of the Peer I/O output data.
40 Peer B Output The adapter transmits this data to the network.
41 Peer Out Enable Determines if Peer I/O output is on or off.
42 Peer Out Time Configures the minimum time that an adapter will wait when transmitting
data to a peer.
43 Peer Out Skip Configures the maximum time that an adapter will wait when transmitting
data to a peer.
Publication 20COMM-PP001F-EN-P – May 2008 Copyright ©2008 Rockwell Automation, Inc. All Rights Reserved. Printed in USA.
Supersedes Publication 20COMM-PP001E-EN-P – July 2006
20-COMM-E_PP_NL_8_14:Layout 1 8/23/06 7:16 AM Page 1
PRODUCT HIGHLIGHTS
Internal Mount – The adapter mounts internal to
the drive to save panel space, and is field installable.
Multiple Configuration Tool Options – A number
of configuration tools can be used to configure the
adapter and the connected drive. These tools include
the PowerFlex DPI HIM, or drive-configuration
software such as DriveExplorer™ or DriveExecutive™.
DPI Routing – Allows DriveExplorer to connect to a
PowerFlex drive using a 1203-SSS or 1203-USB
converter and then route over EtherNet/IP to access
other Allen-Bradley drives. This eliminates the need
for a separate network connection and interface.
I/O Messaging – I/O messaging is used to transfer
time-critical data, such as data that controls the
drive. The following data can be sent and received
by the adapter:
• Logic Command/Reference
• Logic Status/Feedback Peer-to-Peer Capability - Allows a PowerFlex drive to operate as a "master" and communicate
• Datalinks – read and write up to 8 parameters with other PowerFlex 70, 700, 700H and 700S AC drives operating as "followers". The "master"
Explicit Messaging – Explicit messaging involves can send control and speed reference data along with up to two parameter values.
non time-critical information that is typically User Configurable Fault Responses – Selects the action that the adapter and drive will take
triggered by the application (ladder program in a for the following two conditions:
controller, etc.). The adapter supports the reading/ • Idle Fault Action – the scanner is idle (controller in program mode)
writing of parameters, etc. in the drive and to any • Comm Fault Action – network communications have become disrupted
connected DPI peripheral(s).
Available actions include:
Web Interface – Use a web browser such as • Fault – the drive is faulted and stopped
Microsoft® Internet Explorer™ to access the drive • Stop – the drive is stopped using the current deceleration rate and is not faulted
over the Intranet or Internet. • Zero Data – the adapter zeros the I/O data transmitted to the drive
• TCP/IP Configuration - View TCP/IP configuration • Hold Last – the adapter continues sending the I/O data prior to the
data and Ethernet diagnostic information. fault and the drive continues in its present state
• Email Notification - Configure email notification if • Send Fault Configuration – the user specifies the Logic Command, Reference, and
a specific fault or alarm occurs, if any fault or Datalink data that is sent to the drive, allowing complete flexibility in configuring a
alarm occurs, or if the drive is reset. fault action
• DPI Backplane Browse - View every DPI device,
including the drive and connected peripherals. Diagnostics – Built-in diagnostics allow drive-side troubleshooting of the network connection
Provides general device information, diagnostics, using a PowerFlex DPI HIM, DriveExplorer or DriveExecutive. View actual Logic Command/Reference,
events and alarm information. Logic Status/Feedback and Datalink data being transmitted to and from the controller.
• Online User Manuals – Link to view the user manual Flash Upgradeable – The adapter can be flash updated in the field using DriveExplorer,
online over the Internet. DriveExecutive or ControlFLASH to take advantage of new firmware features as they
• Software Tools Web Site – Link to the DriveExplorer become available.
and DriveExecutive Internet web sites.
• Launch Drive Software Tools – Directly launch
DriveExplorer or DriveExecutive software already
on your PC, and have the tool automatically
connect to the drive.
20-COMM-E_PP_NL_8_14:Layout 1 8/23/06 7:16 AM Page 2
PARAMETERS PARAMETERS
No. Name Description No. Name Description
01 DPI Port Displays the port to which the adapter is connected. 41 Peer Flt Action Sets the action that the adapter and drive take if the adapter detects that the
02 DPI Data Rate Displays the data rate (kilobits per second) used by the drive. EtherNet/IP communications with a peer have been disrupted.
03 BOOTP Enables or disables using a BOOTP server to set the IP address, subnet mask, 42 Peer Inp Addr 1 Sets the bytes in the IP address (Addr1.Addr2.Addr3.Addr4) that specifies the
and gateway address. 43 Peer Inp Addr 2 device from which the adapter receives (consumes) Peer I/O data.
04 IP Addr Cfg 1 Sets the respective bytes in the IP address, where the represented address is: 44 Peer Inp Addr 3
05 IP Addr Cfg 2 Cfg1.Cfg2.Cfg3.Cfg4 45 Peer Inp Addr 4
06 IP Addr Cfg 3 46 Peer Inp Timeout Configures the time-out for a peer connection.
07 IP Addr Cfg 4 47 Peer Inp Enable Determines if Peer I/O input is on or off.
08 Subnet Cfg 1 Sets the bytes of the subnet mask, where the represented mask is: 48 Peer Inp Status Displays the status of the consumed peer input connection.
09 Subnet Cfg 2 Cfg1.Cfg2.Cfg3.Cfg4 49 Peer A Output Selects the source of the Peer I/O output data. The adapter transmits
10 Subnet Cfg 3 50 Peer B Output this data to the network.
11 Subnet Cfg 4 51 Peer Out Enable Determines if Peer I/O output is on or off.
12 Gateway Cfg 1 Sets the bytes of the gateway address, where the represented address is: 52 Peer Out Time Determines the minimum time that an adapter will wait when transmitting
13 Gateway Cfg 2 Cfg1.Cfg2.Cfg3.Cfg4 data to a peer.
14 Gateway Cfg 3 53 Peer Out Skip Determines the maximum time that an adapter will wait when transmitting
data to a peer.
15 Gateway Cfg 4
54 Access Control Determines the access to the Web interface and Web-configurable features
16 EN Rate Cfg Configures the network data rate at which the adapter communicates. such as e-mail notification.
17 EN Rate Act Displays the data rate actually used by the adapter. 55 Web Enable Only available for Series B (v3.xxx or higher) adapters. Displays the setting
18 Ref/Fdbk Size Displays the size of the Reference/Feedback words. of the Web Pages Switch (SW2) on the adapter when the adapter was
last reset.
19 Datalink Size Displays the size of each Datalink word.
56 Web Features Only available for Series B (v3.xxx or higher) adapters. Sets access to the
20 Reset Module Used to reset the adapter or set defaults. Web interface and Web-configurable features.
21 Comm Flt Action Sets the action that the adapter will take if it detects anetwork failure.
22 Idle Flt Action Sets the action that the adapter and drive take if theadapter detects that
the scanner is idle.
23 DPI I/O Cfg Selects the I/O that is transferred through the adapter.
24 DPI I/O Act Displays the I/O that the adapter is actively transmitting.
25 Flt Cfg Logic Sets the Logic Command data that is sent to the drive if any of
26 Flt Cfg Ref the following is true:
27 Flt Cfg A1 In • Parameter 21 - [Comm Flt Action] is set to “Send Flt Cfg” and
28 Flt Cfg A2 In communications are disrupted.
29 Flt Cfg B1 In • Parameter 22 - [Idle Flt Action] is set to “Send Flt Cfg” and the scanner is idle.
30 Flt Cfg B2 In
31 Flt Cfg C1 In • Parameter 41 - [Peer Flt Action] is set to “Send Flt Cfg” and
32 Flt Cfg C2 In communications are disrupted.
33 Flt Cfg D1 In
34 Flt Cfg D2 In
35 M-S Input Selects the data produced by the scanner and consumed by the adapter.
36 M-S Output Selects the data produced by the adapter and consumed by the scanner.
37 Ref Adjust Sets the percent scale factor for the Reference from the network.
38 Peer A Input
Configures the destination in the drive of the Peer I/O input.
39 Peer B Input
40 Peer Cmd Mask Configures the mask for the Logic Command word when it is received
through peer input.
20-COMM-E_PP_NL_8_14:Layout 1 8/23/06 7:16 AM Page 3
SPECIFICATIONS
Communications Network Protocol EtherNet/IP
Data Rates 10/100 Mbps, Half/Full Duplex
Drive Protocol DPI
Data Rates 125 or 500 Kbps
Electrical Consumption Drive 370 mA at 5 VDC
Network N/A
Regulatory UL UL508C
Compliance cUL CAN/CSA C22.2 No. 14-1791
CE EN50178 and EN61800-3
CTick EN61800-3
AUTO-REFRESH
PROCESS DISPLAY
EXAMPLE FAULT
NOTIFICATION EMAIL
Publication 20COMM-PP001F-EN-P – May 2008 Copyright ©2008 Rockwell Automation, Inc. All Rights Reserved. Printed in USA.
Supersedes Publication 220COMM-PP001E-EN-P – July 2006
20-COMM-H_PP_NL_5_27_08:Layout 1 5/27/08 3:31 PM Page 1
PRODUCT HIGHLIGHTS
Internal Mount – The adapter mounts internal to
the drive to save panel space, and is field installable.
Configuration Switches – The adapter has rotary
switches for setting the node address (01-99) and
protocol (RTU/N2/P1). Alternatively, the switches
can be disabled (00 setting), allowing the node
address to be set using a configuration parameter.
Multiple Configuration Tool Options – A
number of configuration tools can be used to
configure the adapter and the connected drive.
These tools include the PowerFlex DPI HIM,
or drive-configuration software such as
DriveExplorer™ or DriveExecutive™.
Three HVAC Protocols – Three HVAC protocols
are provided in one adapter: User Configurable Fault Responses – Selects the action that the adapter and drive will
take for the following two conditions:
Modbus RTU Protocol – • Idle Fault Action – the scanner is idle (controller in program mode)
• Utilizes familiar I/O control bits and words • Comm Fault Action – network communications have become disrupted
(Logic Command/Reference, Logic Status/
Feedback and Datalinks A-D) Available actions include:
• Includes 8 configurable User Input words and • Fault – the drive is faulted and stopped
8 configurable User Output words • Stop – the drive is stopped using the current deceleration rate and is not faulted
• Drive parameters are directly mapped to • Zero Data – the adapter zeros the I/O data transmitted to the drive
Modbus addresses for complete parameter • Hold Last – the adapter continues sending the I/O data prior to the fault and the drive
read/write access continues in its present state
• Supports Modbus broadcast address “0” for • Send Fault Configuration – the user specifies the Logic Command, Reference, and
global Start, Stop, Reference, etc. Individual Datalink data that is sent to the drive, allowing complete flexibility in configuring a
nodes can scale their Reference (0-200%) from fault action
the global Reference command Diagnostics – Built-in diagnostics allow drive-side troubleshooting of the network connection
Metasys N2 Protocol – using a PowerFlex DPI HIM, DriveExplorer or DriveExecutive. View actual Logic Command/Reference,
• Utilizes familiar I/O control bits and words Logic Status/Feedback and Datalink data being transmitted to and from the controller.
(Logic Command/Reference, Logic Status/ Flash Upgradeable – The adapter can be flash updated in the field using DriveExplorer,
Feedback and Datalinks A-B) DriveExecutive or ControlFLASH to take advantage of new firmware features as they
• Includes 4 configurable User Input words and become available.
2 configurable User Output words
Siemens P1 Protocol –
• Siemens Application Note 2718
• Utilizes familiar I/O control words (Logic
Command/Reference, Logic Status/Feedback
and Datalinks A-D.) in addition to common
Siemens network points
• Includes 1 configurable User Input word and
1 configurable User Output word
20-COMM-H_PP_NL_5_27_08:Layout 1 5/29/08 4:28 PM Page 2
PARAMETERS SPECIFICATIONS
No. Name Description Communications Network Protocol Modbus RTU, Metasys N2
or Siemens P1 FLN
01 DPI Port Displays the port to which the adapter is connected.
Data Rates RTU: 4800 - 38400 bps
02 DPI Data Rate Displays the data rate (kilobits per second) used by the drive.
N2: 9600 bps
03 Net Addr Cfg Configures the network node address if the network switches on the adapter P1: 4800 or 9600 bps
are set to “00.”
Drive Protocol DPI
04 Net Addr Act Displays the network address actually used by the adapter.
Data Rates 125 or 500 Kbps
05 Net Rate Cfg Configures the network data rate at which the adapter communicates.
Electrical Consumption Drive 150 mA at 5 VDC
06 Net Rate Act Displays the network data rate actually used by the adapter.
Network N/A
07 Net Parity Cfg Configures the network parity.
Regulatory UL UL508C
08 Net Parity Act Displays the actual network parity used by the adapter.
Compliance cUL CAN/CSA C22.2 No. 14-1791
09 Stop Bits Act Displays the actual number of stop bits used by the selected protocol.
CE EN50178 and EN61800-3
10 Net Chksum Type Displays the type of checksum used by the selected protocol.
CTick EN61800-3
11 Network Timeout Configures the time in seconds to be used to detect network communication loss.
12 Ref/Fdbk Size Displays the size of the Reference/Feedback words.
13 Datalink Size Displays the size of each Datalink word.
CONNECTOR TERMINALS
14 Reset Module Used to reset the adapter or set defaults. Terminal Signal Function
15 Comm Flt Action Sets the action that the adapter will take if it detects a network failure. TERM Termination Signal RC Termination
16 DPI I/O Cfg Selects the I/O that is transferred through the adapter. A Signal A TxRxDx -
17 DPI I/O Active Displays the I/O that the adapter is actively transmitting. B Signal B TxRxDx +
18 Flt Cfg Logic Sets the data that is sent to the drive if Parameter 15 - [Comm Flt Action] COM Common Signal Common
19 Flt Cfg Ref is set to “Send Flt Cfg” and the adapter times out. SHIELD Shield Shield RC Termination
20 Flt Cfg A1 In GND Ground Shield Ground Termination
21 Flt Cfg A2 In
22
23
Flt Cfg B1 In
Flt Cfg B2 In
WIRING DIAGRAM
24 Flt Cfg C1 In Node 1 Node 2 Node “n”
25 Flt Cfg C2 In
G LD
G LD
G LD
M
M
RM
RM
RM
D
D
IE
IE
IE
N
N
N
O
O
SH
SH
SH
TE
TE
TE
A
A
A
B
C
C
B
B
26 Flt Cfg D1 In
27 Flt Cfg D2 In
28 Clear Counters Clears the network diagnostic counters.
29 N2 Ref Scale Only used if Metasys N2 protocol is selected. Determines the engineering
unit sent over DPI for the Reference when 100% is set for AO#2.
30 Stop Bits Cfg Sets the number of stop bits used by the adapter when the network protocol
switch is set to “Modbus RTU”. SUPPORTED MODBUS RTU COMMANDS
31 RTU Ref. Adjust Sets the percent scale factor for the Reference from the network when the net
Function Code Description
work protocol switch is set to “Modbus RTU,” and broadcast messages
(Modbus address “0”) are sent. 01 Read Coil Status
02 Read Input Status
03 Read Holding Registers
04 Read Input Registers
PROTOCOL SELECTION 05 Force Single Coil
06 Write Single Register
08 Diagnostics/Loop-back
16 Write Multiple Registers
20-COMM-H
SERIES A
FRN AS SHIPPED: V 1.001
SERIAL NUMBER: 402D9423
23 Read/Write 4x Registers
DEVICE: 5VDC 150mA
LISTED
IND.CONT.EQ. N223
COMPATIBLE PRODUCTS
966X
RTU
NODE ADDRESS
N2
Publication 20COMM-PP001F-EN-P – May 2008 Copyright ©2008 Rockwell Automation, Inc. All Rights Reserved. Printed in USA.
Supersedes Publication 20COMM-PP001E-EN-P – July 2006
20-COMM-I_PP_NL_8_14:Layout 1 8/23/06 8:16 AM Page 1
PRODUCT HIGHLIGHTS
Internal Mount – The adapter mounts
internal to the drive to save panel space, and
is field installable.
Multiple Configuration Tool Options – A
number of configuration tools can be used
to configure the adapter and the connected
drive. These tools include the PowerFlex DPI
HIM, or drive configuration software such as
DriveExplorer™ or DriveExecutive™.
I/O Messaging – I/O messaging is used to
transfer time-critical data, such as data that
controls the drive. The following data can be
sent and received by the adapter:
• Logic Command/Reference
• Logic Status/Feedback
Available actions include:
• Datalinks - read and write up to 7 parameters
• Fault – the drive is faulted and stopped
Up to 9 words of input data and 9 words of • Stop – the drive is stopped using the current deceleration rate and is not faulted
output data can be mapped to the network. • Zero Data – the adapter zeros the I/O data transmitted to the drive
PCP Communications – PCP messages are • Hold Last – the adapter continues sending the I/O data prior to the fault and the
used for explicit messaging, which involves drive continues in its present state
non time-critical information that is typically • Send Fault Configuration – the user specifies the Logic Command, Reference, and
triggered by the application (ladder program Datalink data that is sent to the drive, allowing complete flexibility in
in a controller, etc.). The adapter supports: configuring a fault action
• Reading/writing of drive parameters
• Reading the drive fault queue Diagnostics – Built-in diagnostics allow drive-side troubleshooting of the network
• Reading/writing of adapter parameters connection using a PowerFlex DPI HIM, DriveExplorer or DriveExecutive. View
• Reading of adapter events actual Logic Command/Reference, Logic Status/Feedback and Datalink data being
transmitted to and from the controller.
Compliance Tested – Certificate No. 373
issued by INTERBUS Club Deutschland E.V. Flash Upgradeable – The adapter can be flash updated in the field using
User Configurable Fault Responses – DriveExplorer, DriveExecutive or ControlFLASH to take advantage of new firmware
Selects the action that the adapter and drive features as they become available.
will take for the following two conditions:
• Idle Fault Action – the scanner is idle
(controller in program mode)
• Comm Fault Action – network
communications have become disrupted
20-COMM-I_PP_NL_8_14:Layout 1 8/23/06 8:17 AM Page 2
PARAMETERS PARAMETERS
No. Name Description No. Name Description
01 DPI Port Displays the port to which the adapter is connected. 46 PODD W4 Cfg Configured Process Output Data Description for Word 4.
02 DPI Data Rate Displays the data rate (kilobits per second) used by the drive. 47 PODD W4 Actual Actual Process Output Data Description for Word 4.
03 Ref/Feedback Size Displays the size of the Reference/Feedback words. 48 PODD W5 Cfg Configured Process Output Data Description for Word 5.
04 Datalink Size Displays the size of each Datalink word. 49 PODD W5 Actual Actual Process Output Data Description for Word 5.
05 Reset Module Used to reset the adapter or set defaults. 50 PODD W6 Cfg Configured Process Output Data Description for Word 6.
06 Comm Flt Action Sets the action that the adapter will take if it detects a network failure. 51 PODD W6 Actual Actual Process Output Data Description for Word 6.
07 Reserved 52 PODD W7 Cfg Configured Process Output Data Description for Word 7.
08 DPI I/O Config Selects the I/O that is transferred through the adapter. 53 PODD W7 Actual Actual Process Output Data Description for Word 7.
09 DPI I/O Active Displays the I/O that the adapter is actively transmitting. 54 PODD W8 Cfg Configured Process Output Data Description for Word 8.
10 Flt Cfg Logic Sets the data that is sent to the drive if Parameter 06 - [Comm Flt Action] is 55 PODD W8 Actual Actual Process Output Data Description for Word 8.
11 Flt Cfg Ref set to Send Flt Cfg and communications are disrupted. 56 PCP Comm Cfg Enables or disables PCP communications.
12 Flt Cfg A1 57 PCP Comm Act Displays actual PCP Configuration status.
13 Flt Cfg A2
14 Flt Cfg B1
15 Flt Cfg B2 SPECIFICATIONS
16 Flt Cfg C1 Communications Network Protocol Interbus
17 Flt Cfg C2 Data Rate 500 Kbps
18 Flt Cfg D1 Drive Protocol DPI
19 Flt Cfg D2 Data Rates 125 or 500 Kbps
20 PIDD W0 Cfg Configured Process Input Data Description for Word 0 (default is Logic Status). Electrical Consumption Drive (DPI) 450 mA at 5 VDC
21 PIDD W0 Actual Actual Process Input Data Description for Word 0. Network N/A
22 PIDD W1 Cfg Configured Process Input Data Description for Word 1 (default is Feedback). Regulatory UL UL508C
23 PIDD W1 Actual Actual Process Input Data Description for Word 1. Compliance cUL CAN/CSA C22.2 No. 14-1791
24 PIDD W2 Cfg Configured Process Input Data Description for Word 2. CE EN50081-2 and EN61000-6-2
25 PIDD W2 Actual Actual Process Input Data Description for Word 2. CTick AS/NZS 2064, Group 1, Class A
26 PIDD W3 Cfg Configured Process Input Data Description for Word 3.
27 PIDD W3 Actual Actual Process Input Data Description for Word 3.
28 PIDD W4 Cfg Configured Process Input Data Description for Word 4. EXAMPLE I/O IMAGE
29 PIDD W4 Actual Actual Process Input Data Description for Word 4.
Interbus DPI
30 PIDD W5 Cfg Configured Process Input Data Description for Word 5.
Controller Scanner Adapter PowerFlex Drive
31 PIDD W5 Actual Actual Process Input Data Description for Word 5. Word and I/O
Output 0 Logic Command Logic Command
32 PIDD W6 Cfg Configured Process Input Data Description for Word 6.
Image 1 Reference Reference
33 PIDD W6 Actual Actual Process Input Data Description for Word 6. (Write) 2 Datalink In A1 Data In A1
34 PIDD W7 Cfg Configured Process Input Data Description for Word 7. 3 Datalink In A2 Data In A2
4 Datalink In B1 Data In B1
35 PIDD W7 Actual Actual Process Input Data Description for Word 7. 5 Datalink In B2 Data In B2
36 PIDD W8 Cfg Configured Process Input Data Description for Word 8. 6 Datalink In C1 Data In C1
7 Datalink In C2 Data In C2
37 PIDD W8 Actual Actual Process Input Data Description for Word 8.
8 Datalink In D1 Data In D1
38 PODD W0 Cfg Configured Process Output Data Description for Word 0 (default is Logic Command).
39 PODD W0 Actual Actual Process Output Data Description for Word 0.
M0/M1 PCP Communications Message
40 PODD W1 Cfg Configured Process Output Data Description for Word 1 (default is Reference). Handler
Files
41 PODD W1 Actual Actual Process Output Data Description for Word 1.
42 PODD W2 Cfg Configured Process Output Data Description for Word 2. Input 0 Logic Status Logic Status
Image 1 Feedback Feedback
43 PODD W2 Actual Actual Process Output Data Description for Word 2.
(Read) 2 Datalink Out A1 Data Out A1
44 PODD W3 Cfg Configured Process Output Data Description for Word 3. 3 Datalink Out A2 Data Out A2
45 PODD W3 Actual Actual Process Output Data Description for Word 3. 4 Datalink Out B1 Data Out B1
5 Datalink Out B2 Data Out B2
6 Datalink Out C1 Data Out C1
7 Datalink Out C2 Data Out C2
8 Datalink Out D1 Data Out D1
M0/M1 Message
PCP Communications
Handler
Files
Publication 20COMM-PP001F-EN-P – May 2008 Copyright ©2008 Rockwell Automation, Inc. All Rights Reserved. Printed in USA.
Supersedes Publication 20COMM-PP001E-EN-P – July 2006
20-COMM-K_8_14.qxd:Layout 1 8/23/06 7:30 AM Page 1
PRODUCT HIGHLIGHTS
Internal Mount – The adapter mounts
internal to the drive to save panel space, and Compliance Tested – Certificate No. CiA200407-301V402/20-0036 issued by CAN in
is field installable. Automation GmbH.
Configuration Switches – The adapter has User Configurable Fault Responses – Selects the action that the adapter and
configuration switches for setting the node drive will take for the following two conditions:
address and network data rate. Alternatively, • Idle Fault Action – the scanner is idle (controller in program mode)
the switches can be disabled, allowing these • Comm Fault Action – network communications have become disrupted
settings to be configured using parameters. Available actions include:
Multiple Configuration Tool Options – A • Fault – the drive is faulted and stopped
• Stop – the drive is stopped using the current deceleration rate and is not faulted
number of configuration tools can be used to
• Zero Data – the adapter zeros the I/O data transmitted to the drive
configure the adapter and the connected
• Hold Last – the adapter continues sending the I/O data prior to the fault and the
drive. These tools include the PowerFlex DPI drive continues in its present state
HIM, or drive-configuration software such as • Send Fault Configuration – the user specifies the Logic Command, Reference,
DriveExplorer™ or DriveExecutive™. and Datalink data that is sent to the drive, allowing complete flexibility in
I/O Messaging – I/O messaging is used to configuring a fault action
transfer time-critical data, such as data that Diagnostics – Built-in diagnostics allow drive-side troubleshooting of the network
controls the drive. The following data can be connection using a PowerFlex DPI HIM, DriveExplorer or DriveExecutive. View
sent and received by the adapter: actual Logic Command/Reference, Logic Status/Feedback and Datalink data being
• Logic Command/Reference transmitted to and from the controller.
• Logic Status/Feedback Flash Upgradeable – The adapter can be flash updated in the field using
• Datalinks - read and write up to 8 parameters DriveExplorer, DriveExecutive or ControlFLASH to take advantage of new firmware
features as they become available.
20-COMM-K_8_14.qxd:Layout 1 8/23/06 7:30 AM Page 2
PARAMETERS SPECIFICATIONS
No. Name Description Communications Network Protocol CANopen
01 DPI Port Displays the port on the host drive which the adapter is connected. Data Rates 10 Kbps – 1 Mbps
02 DPI Data Rate Displays the data rate used by the DPI drive. This data rate is set in the drive, Drive Protocol DPI
and the adapter autobauds to it. Data Rates 125 or 500 Kbps
03 COPN Addr Cfg Configures the CANopen node address if the Data Rate switch is set to “PGM” Electrical Consumption Drive (DPI) 500 mA at 5 VDC
(Program). Network None
04 COPN Addr Actual Displays the CANopen node address actually used by the adapter. Regulatory UL UL508C
05 COPN Rate Cfg Configures the CANopen data rate if the data rate switch is set to“PGM” Compliance cUL CAN/CSA C22.2 No. 14-1791
(Program). CE EN50081-2 and EN61000-6-2
06 COPN Rate Actual Displays the CANopen data rate actually used by the adapter. CTick AS/NZS 2064, Group 1, Class A
07 Ref/Fdbk Size Displays the size of the Speed Reference/Feedback words which is determined
by the drive. The adapter automatically uses the correct size.
08 Datalink Size Displays the size of each Datalink word which is determined by the drive.
09 Reset Module
The adapter automatically uses the correct size.
Resets the adapter or sets the adapter parameters to factory default.
EXAMPLE I/O IMAGE
10 Comm Flt Action Sets the action that the adapter will take if it detects that communications. CANopen DPI
11 Idle Flt Action Sets the action that the adapter will take if it detects that the scanner is idle.
Controller Scanner Adapter PowerFlex Drive
12 DPI I/O Config Selects the I/O that is transferred through the adapter. Word and I/O
13 DPI I/O Active Displays the I/O that the adapter is actively transmitting.
Output 0 Logic Command Logic Command
14 Flt Cfg Logic Sets the data that is sent to the drive if any of the following is true: 1 Reference Reference
Image
15 Flt Cfg Ref (Write) 2 Datalink In A1 Data In A1
16 Flt Cfg A1 In • Parameter 09 - [Comm Flt Action] is set to Send Flt Cfg and communications 3 Datalink In A2 Data In A2
17 Flt Cfg A2 In are disrupted. 4 Datalink In B1 Data In B1
18 Flt Cfg B1 In 5 Datalink In B2 Data In B2
19 Flt Cfg B2 In • Parameter 10 - [Idle Flt Action] is set to Send Flt Cfg and the scanner is
6 Datalink In C1 Data In C1
put into Program mode.
20 Flt Cfg C1 In 7 Datalink In C2 Data In C2
21 Flt Cfg C2 In 8 Datalink In D1 Data In D1
22 Flt Cfg D1 In 9 Datalink In D2 Data In D2
23 Flt Cfg D2 In
24 PDO1 Trigger Sets the transmission type for TPDO1 (Status/Feedback) if transmission type 0 Input 0 Logic Status Logic Status
or 254 is configured. Image 1 Feedback Feedback
25 COS Status Mask Configures the mask for the 16-bit Logic Status word. If a bit is not masked and (Read) 2 Datalink Out A1 Data Out A1
it changes, it is reported as a change in the Change of State operation. 3 Datalink Out A2 Data Out A2
26 COS Fdbk Change Configures the hysteresis band to determine how much the Feedback word can 4 Datalink Out B1 Data Out B1
change before it is reported as a change in the Change of State operation. 5 Datalink Out B2 Data Out B2
27 Cyc Interval Time between transfers used for cyclic tranmissions if transmission type 0 or 6 Datalink Out C1 Data Out C1
254 is configured and Parameter 24 – [PDO1 Trigger] is set to “1 = Cyclic”. 7 Datalink Out C2 Data Out C2
8 Datalink Out D1 Data Out D1
9 Datalink Out D2 Data Out D2
CANopen EDS FILE Message Message Message
The CANopen EDS file is provided on 3.5” disk with the adapter and Handler Buffer Handler
Publication 20COMM-PP001F-EN-P – May 2008 Copyright ©2008 Rockwell Automation, Inc. All Rights Reserved. Printed in USA.
20-COMM-L_PP_NL_8_14:Layout 1 8/23/06 8:17 AM Page 1
PRODUCT HIGHLIGHTS
Internal Mount – The adapter mounts
internal to the drive to save panel space, and
is field installable.
Multiple Configuration Tool Options – A
number of configuration tools can be used
to configure the adapter and the connected
drive. These tools include the PowerFlex DPI
HIM, or drive-configuration software such as
DriveExplorer™ or DriveExecutive™.
LonMark Functional Profile: “Variable
Speed Motor Drive: 6010” Support – The
adapter supports the standard functional
profile used by the HVAC industry for drives,
which provides a common set of system network User Configurable Fault Responses – Selects the action that the adapter and
variables and configuration properties. drive will take for the following two conditions:
Additional “Manufacturer Defined” • Idle Fault Action – the node is taken offline
• Comm Fault Action – network communications have become disrupted
network variables – Additional
“Manufacturer Defined” network variables Available actions include:
are also provided: • Fault – the drive is faulted and stopped
• Datalinks • Stop – the drive is stopped using the current deceleration rate and is not faulted
• Parameter Read/Write • Zero Data – the adapter zeros the I/O data transmitted to the drive
• Metering • Hold Last – the adapter continues sending the I/O data prior to the fault and the
drive continues in its present state
• Configuration
• Send Fault Configuration – the user specifies the Logic Command, Reference,
Resource Files – The following resource files and Datalink data that is sent to the drive, allowing complete flexibility in
are included on 3.5” disk with the adapter: configuring a fault action
• XIF file Diagnostics – Built-in diagnostics allow drive-side troubleshooting of the network
• Type File (TYP) connection using a PowerFlex DPI HIM, DriveExplorer or DriveExecutive. View
• Format File (FMT) actual Logic Command/Reference, Logic Status/Feedback, Datalink, etc. data being
• Language File (ENU) transmitted to and from the controller.
• Functional Profile Template (FPT) Flash Upgradeable – The adapter can be flash updated in the field using
The resource files can also be downloaded at: DriveExplorer, DriveExecutive or ControlFLASH to take advantage of new
http://www.ab.com/drives/20-comm/ firmware features as they become available.
20-comm-l
20-COMM-L_PP_NL_8_14:Layout 1 8/23/06 8:17 AM Page 2
PARAMETERS SPECIFICATIONS
No. Name Description Communications Network Protocol LonWorks
01 DPI Port Displays the port to which the adapter is connected. Data Rates 78 Kbps
02 DPI Data Rate Displays the data rate (kilobits per second) used by the drive. Drive Protocol DPI
03 Ref/Fdbk Size Displays the size of the Reference/Feedback words. Data Rates 125 or 500 Kbps
04 Datalink Size Displays the size of each Datalink word. Electrical Consumption Drive (DPI) 200 mA at 5 VDC
05 Reset Module Used to reset the adapter or set defaults. Network N/A
06 Comm Flt Action Sets the action that the adapter will take if it detects that network Regulatory UL UL508C
communications have been disrupted. Compliance cUL CAN/CSA C22.2 No. 14-1791
07 RcvHrtBeat Time Sets the time used as a Receive Heartbeat timer and is used to trigger the CE EN50081-2 and EN61000-6-2
fault action in Parameter 6 - [Comm Flt Action].
CTick AS/NZS 2064, Group 1, Class A
08 Idle Flt Action Sets the action that the adapter will take during offline/disable occurrences.
09 DPI I/O Config Selects the I/O that is transferred through the adapter.
10 DPI I/O Active Displays the I/O that the adapter is actively transmitting.
11 Flt Cfg Logic Sets the data that is sent to the drive if Parameter 6 - [Comm Flt Action] VARIABLE SPEED MOTOR DRIVE PROFILE
12 Flt Cfg Ref is set to Send Flt Cfg and communications are disrupted.
13 Flt Cfg A1 In
14 Flt Cfg A2 In Variable Speed Motor
Drive: 6010
15 Flt Cfg B1 In
Mandatory
16 Flt Cfg B2 In nv1
nviDrvSpeedStpt Network nv3
nvoDrvSpeed
SNVT_switch SNVT_lev_percent
Variables
17 Flt Cfg C1 In
nvoDrvCurnt
nv4
18 Flt Cfg C2 In SNVT_amp
Optional nv5
nvoDrvVolt
Network
32 MinSpeedParam Sets the PowerFlex drive parameter number to be used with nciMinSpeed. Variables
33 RampUpTmParam Sets the PowerFlex drive parameter number to be used with nciRampUpTm.
nvoDatalinkA1
nv12
34 RampDownTmParam Sets the PowerFlex drive parameter number to be used with nciRampDownTm. nv21
nviDatalinkA1
UNVT_DATALINK
UNVT_DATALINK
nvoDatalinkA2
nviDatalinkA2 nv13
nv22 UNVT_DATALINK
UNVT_DATALINK
nvoDatalinkB1
nviDatalinkB1 nv14
nv23 UNVT_DATALINK
UNVT_DATALINK
nviDatalinkB2 nvoDatalinkB2
nv24 nv15
UNVT_DATALINK UNVT_DATALINK
nviDatalinkC1 nvoDatalinkC1
nv25 nv16
UNVT_DATALINK UNVT_DATALINK
nviDatalinkC2
nv26 nvoDatalinkC2
UNVT_DATALINK nv17
UNVT_DATALINK
nviDatalinkD1
nv27
UNVT_DATALINK nvoDatalinkD1
nv18
UNVT_DATALINK
nviDatalinkD2
nv28
UNVT_DATALINK nvoDatalinkD2
nv19
UNVT_DATALINK
Manufacturer- Defined
Configuration Properties
ncRA1 nciParRdAdr
ncRA2 nciParWriAdr
ncRA3 nciParWriData
Publication 20COMM-PP001F-EN-P – May 2008 Copyright ©2008 Rockwell Automation, Inc. All Rights Reserved. Printed in USA.
Supersedes Publication 20COMM-PP001E-EN-P – July 2006
20-COMM-M_PP.qxd:Layout 1 2/28/07 2:02 PM Page 1
PRODUCT HIGHLIGHTS
Installation – The adapter mounts internal to
the drive to save valuable panel space, and is field
installable. If an external connection is needed, the
adapter can also be installed in a DPI External
Communications Kit (20-XCOMM-DC-BASE).
Address Configuration – The adapter's IP
address can be configured using software
parameters or a BOOTP server.
Supported Data Rates – The adapter
can automatically negotiate a baud rate of
10 Mbps or 100 Mbps when connected to
a Modbus/TCP network.
Supported Modbus Function Codes – Unlike most drive communication adapters,
Multiple Configuration Tool Options – Modbus/TCP adapters use Function Codes to view logic status, feedback and parameter
A number of configuration tools can be used values, send logic control, reference, and change parameter values. The following Function
to configure the adapter and connected drive. Codes are supported by the adapter:
These tools include the PowerFlex DPI HIM, • 01 - Read Coils
or drive-configuration software such as • 02 - Read Discrete Inputs
DriveExplorer™ or DriveExecutive™. • 03 - Read Holding Registers
• 05 - Write Single Coil
DPI Routing – Allows DriveExplorer to connect • 06 - Write Single Register
to a PowerFlex drive using a 1203-SSS or • 15 - Write Multiple Coils
1203-USB converter and then route over • 16 - Write Multiple Registers
Modbus/TCP to access other Allen-Bradley® • 23 - Read/Write Multiple Registers
drives. This eliminates the need for a separate • 43 - Read Device Identification
network connection and interface.
User Configurable Fault Response – Selects the action that the adapter and drive will take
Advanced Built-in Web Interface – Use a web for a Comm Fault Action (network communications have become disrupted) condition
browser such as Microsoft® Internet Explorer™ to
access the drive over the Intranet or Internet. Available actions include:
• TCP/IP Configuration - View TCP/IP • Fault – the drive is faulted and stopped
configuration data and Modbus/TCP • Stop – the drive is stopped using the current deceleration rate and is not faulted
diagnostic information. • Zero Data – the adapter zeros the I/O data transmitted to the drive
• Email Notification - Configure email • Hold Last – the adapter continues sending the I/O data prior to the fault and the
notification if a specific fault or alarm drive continues in its present state
occurs, if any fault or alarm occurs, or if • Send Fault Configuration – the user specifies the Logic Command, Reference, and
the drive is reset. Datalink data that is sent to the drive, allowing complete flexibility in
• DPI Backplane Browse - View every DPI configuring a fault action
device, including the drive and connected
peripherals. Provides general device Diagnostics – Built-in diagnostics allow drive-side troubleshooting of the network
information, diagnostics, events, and connection using a PowerFlex DPI HIM, DriveExplorer or DriveExecutive. View actual
alarm information. Logic Status/Feedback, Logic Command/Reference, and Datalink data being transmitted
• Online User Manuals – Link to view the to and from the controller.
user manual online over the Internet. Flash Upgradeable – The adapter can be flash updated in the field using DriveExplorer,
• Software Tools Web Site – Link to the DriveExecutive or ControlFLASH to take advantage of new firmware features as they become available.
DriveExplorer and DriveExecutive Internet
web sites.
• Launch Drive Software Tools – Directly launch
DriveExplorer or DriveExecutive software
already on your PC, and have the tool
automatically connect to the drive.
20-COMM-M_PP.qxd:Layout 1 2/28/07 2:02 PM Page 2
PARAMETERS PARAMETERS
No. Name Description No. Name Description
01 DPI Port Displays the port to which the adapter is connected. 38 Indirect Par #1 Sets the Indirect Parameter value used to point to a device (drive or any of its
02 DPI Data Rate Displays the data rate (kilobits per second) used by the drive. 39 Indirect Par #2 connected peripherals) to read or write values with specific Modbus Function Codes.
03 BOOTP Enables or disables using a BOOTP server to set the IP address, subnet mask, 40 Indirect Par #3
and gateway address. 41 Indirect Par #4
04 IP Addr Cfg 1 Sets the respective bytes in the IP address, where the represented address is: 42 Indirect Par #5
05 IP Addr Cfg 2 Cfg1.Cfg2.Cfg3.Cfg4
43 Indirect Par #6
06 IP Addr Cfg 3 44 Indirect Par #7
07 IP Addr Cfg 4 45 Indirect Par #8
08 Subnet Cfg 1 Sets the bytes of the subnet mask, where the represented mask is: 46 Indirect Par #9
09 Subnet Cfg 2 Cfg1.Cfg2.Cfg3.Cfg4
47 Indirect Par #10
10 Subnet Cfg 3 48 Indirect Par #11
11 Subnet Cfg 4 49 Indirect Par #12
12 Gateway Cfg 1 Sets the bytes of the gateway address, where the represented address is: 50 Indirect Par #13
13 Gateway Cfg 2 Cfg1.Cfg2.Cfg3.Cfg4
51 Indirect Par #14
14 Gateway Cfg 3 52 Indirect Par #15
15 Gateway Cfg 4 53 Indirect Par #16
16 EN Rate Cfg Configures the network data rate at which the adapter communicates.
17 EN Rate Act Displays the data rate actually used by the adapter.
18
19
Modbus/TCP Port
Msg I/O Timer
Sets the TCP port used to transport Modbus/TCP messages.
Sets the communication loss timeout period in seconds.
SPECIFICATIONS
20 Ref/Fdbk Size Displays the size of the Reference/Feedback, which is determined by the drive. Communications Network Protocol Modbus/TCP
21 Datalink Size Displays the size of the Datalinks, which is determined by the drive. Data Rates 10/100 Mbps, Half/Full Duplex
22 Reset Module Used to reset the adapter or set defaults. Drive Protocol DPI
23 Comm Flt Action Sets the action that the adapter will take if it detects a network failure. Data Rates 125 or 500 Kbps
24 DPI I/O Cfg Selects the I/O that is transferred through the adapter. Electrical Consumption Drive 350 mA at 5 VDC
25 DPI I/O Act Displays the I/O that the adapter is actively transmitting. Network N/A
26 Flt Cfg Logic Sets the Logic Command data that is sent to the drive if Parameter 23 – Regulatory UL UL508C
[Comm Flt Action] is set to "Send Flt Cfg" and communications are disrupted.
27 Flt Cfg Ref Compliance cUL CAN/CSA C22.2 No. 14-M91
28 Flt Cfg A1 In CE EN50178 and EN61800-3
29 Flt Cfg A2 In CTick EN61800-3
30 Flt Cfg B1 In
31 Flt Cfg B2 In
32 Flt Cfg C1 In
33 Flt Cfg C2 In
34 Flt Cfg D1 In
35 Flt Cfg D2 In
36 Web Enable Displays the setting of the Web Pages Switch (SW2) on the adapter when the
adapter was last reset.
37 Web Features Sets access to the Web interface and Web-configurable features.
20-COMM-M_PP.qxd:Layout 1 2/27/07 1:57 PM Page 3
AUTO-REFRESH
PROCESS DISPLAY
EXAMPLE FAULT
NOTIFICATION EMAIL
NETWORK ROUTING EXAMPLE PowerFlex 70 Drives with
20-COMM-M Adapters (Port 5)
Laptop or Desktop PC
with DriveExplorer 1
J2
RK
RK
RK
D1
D2
1
J2
RK
RK
RK
D1
D2
RK
RK
D1
D2
LISTED
N223 LISTED
N223 LISTED
N223
IND.CONT.EQ. IND.CONT.EQ.
IND.CONT.EQ. 966X 966X
966X
R5 R5
R5 R6 R6
R6 2 2
2
1203-USB or 1203-SSS
Converter
Modbus/TCP Network
Drive Cable
Use DriveExplorer Lite or Full to configure a single Use DriveExplorer Full to route through DPI and configure
drive and its installed Modbus/TCP adapter drives connected directly on Modbus/TCP
Publication 20COMM-PP001F-EN-P – May 2008 Copyright ©2008 Rockwell Automation, Inc. All Rights Reserved. Printed in USA.
Supersedes Publication 20COMM-PP001E-EN-P – July 2006
20-COMM-P_PP_NL_8_14:Layout 1 8/23/06 8:00 AM Page 1
PRODUCT HIGHLIGHTS
Internal Mount – The adapter mounts
internal to the drive to save panel space, and
is field installable.
Configuration Switches – The adapter has
rotary switches for setting the node address
(01-99). Alternatively, the switches can be
disabled (00 setting), allowing the node address
to be set using a configuration parameter.
Multiple Configuration Tool Options – A
number of configuration tools can be used
to configure the adapter and the connected
drive. These tools include the PowerFlex DPI
HIM, or drive-configuration software such as User Configurable Fault Responses – Selects the action that the adapter and
DriveExplorer™ or DriveExecutive™. drive will take for the following two conditions:
I/O Messaging – I/O messaging is used to • Idle Fault Action – the scanner is idle (controller in program mode)
• Comm Fault Action – network communications have become disrupted
transfer time-critical data, such as data that
controls the drive. The following data can be Available actions include:
sent and received by the adapter: • Fault – the drive is faulted and stopped
• Logic Command/Reference • Stop – the drive is stopped using the current deceleration rate and is not faulted
• Logic Status/Feedback • Zero Data – the adapter zeros the I/O data transmitted to the drive
• Datalinks - read and write up to 8 parameters • Hold Last – the adapter continues sending the I/O data prior to the fault and the
drive continues in its present state
Explicit Messaging – Explicit messaging • Send Fault Configuration – the user specifies the Logic Command and Reference
involves non time-critical information that data that is sent to the drive, allowing complete flexibility in configuring a
is typically triggered by the application fault action
(ladder program in a controller, etc.). Diagnostics – Built-in diagnostics allow drive-side troubleshooting of the network
The adapter supports: connection using a PowerFlex DPI HIM, DriveExplorer or DriveExecutive. View
• Reading/writing of drive parameters actual Logic Command/Reference and Logic Status/Feedback data being transmitted
• Reading the drive fault queue to and from the controller.
• Reading/writing of adapter or other Flash Upgradeable – The adapter can be flash updated in the field using
peripheral parameters DriveExplorer, DriveExecutive or ControlFLASH to take advantage of new firmware
Compliance Tested – Certificate No. Z00652 features as they become available.
issued by PROFIBUS Nutzerorganisation E.V.
20-COMM-P_PP_NL_8_14:Layout 1 8/23/06 8:00 AM Page 2
PARAMETERS SPECIFICATIONS
No. Name Description Communications Network Protocol PROFIBUS DP
01 DPI Port Port to which the adapter is connected. Data Rates 9600 bps - 12 Mbps (autobauds)
02 DPI Data Rate Displays the data rate (kilobits per second) used by the drive. Drive Protocol DPI
03 P-DP Addr Cfg Configures the node address to use if the Node address switches are set to “00”. Data Rates 125 or 500 Kbps
04 P-DP Addr Actual Displays the node address actually used by the adapter. Electrical Consumption Drive (DPI) 370 mA at 5 VDC
05 P-DP Rate Actual Displays the data rate actually used by the adapter. Network N/A
06 Ref/Fdbk Size Displays the size of the Reference/Feedback words. Regulatory UL UL508C
07 Datalink Size Displays the size of each Datalink word. Compliance cUL CAN/CSA C22.2 No. 14-1791
08 Reset Module Used to reset the adapter or set defaults. CE EN50081-2 and EN61000-6-2
09 Comm Flt Action Sets the action that the adapter will take if it detects that communications CTick AS/NZS 2064, Group 1, Class A
have been disrupted.
10 Idle Flt Action Sets the action that the adapter will take if it detects that the scanner is idle.
11 DPI I/O Config Selects the I/O that is transferred through the adapter.
12 DPI I/O Active Displays the I/O that the adapter is actively transmitting.
EXAMPLE I/O IMAGE
13 Flt Cfg Logic Sets the data that is sent to the drive if any of the following is true: PROFIBUS DPI
14 Flt Cfg Ref • Parameter 09 - [Comm Flt Action] is set to Send Flt Cfg and Controller Scanner Adapter PowerFlex Drive
Word and I/O
15 Flt Cfg A1 In communications are disrupted. Output 0 Logic Command Logic Command
Image 1 Reference Reference
16 Flt Cfg A2 In • Parameter 10 - [Idle Fault Action] is set to Send Flt Cfg and the (Write) 2 Datalink In A1 Data In A1
17 Flt Cfg B1 In scanner is put into Program mode. 3 Datalink In A2 Data In A2
4 Datalink In B1 Data In B1
18 Flt Cfg B2 In 5 Datalink In B2 Data In B2
6 Datalink In C1 Data In C1
19 Flt Cfg C1 In 7 Datalink In C2 Data In C2
20 Flt Cfg C2 In 8 Datalink In D1 Data In D1
9 Datalink In D2 Data In D2
21 Flt Cfg D1 In 10 Parameter Access Word 1
11 Parameter Access Word 2 Message
22 Flt Cfg D2 In 12 Parameter Access Word 3 Handler
13 Parameter Access Word 4
23 Parameter Mode Sets the format used when performing explicit messages:
• Par Prot (Parameter Protocol) is used to read or write single parameters. 0 Logic Status Logic Status
Input
• DPI Par Prot is reserved for future use. Image 1 Feedback Feedback
(Read) 2 Datalink Out A1 Data Out A1
24 P-DP State Displays the state of the PROFIBUS controller. 3 Datalink Out A2 Data Out A2
4 Datalink Out B1 Data Out B1
5 Datalink Out B2 Data Out B2
Publication 20COMM-PP001F-EN-P – May 2008 Copyright ©2008 Rockwell Automation, Inc. All Rights Reserved. Printed in USA.
Supersedes Publication 20COMM-PP001E-EN-P – July 2006
20-COMM-Q_PP_NL_8_14:Layout 1 8/23/06 8:06 AM Page 1
PRODUCT HIGHLIGHTS
Internal Mount – The adapter mounts
internal to the drive to save panel space,
and is field installable.
Configuration Switches – The adapter has
rotary switches for setting the node address.
Alternatively, the switches can be disabled,
allowing the node address to be set using a
configuration parameter.
Redundancy – The adapter provides a
redundant media connection for improved
media reliability. The adapter also supports
multicast and redundant owner/hot backup.
Multiple Configuration Tool Options – A
number of configuration tools can be used
to configure the adapter and the connected
drive. These tools include the PowerFlex DPI
HIM, or drive configuration software such as User Configurable Fault Responses – Selects the action that the adapter and
DriveExplorer™ or DriveExecutive™. drive will take for the following two conditions:
DPI Routing – Allows DriveExplorer to • Idle Fault Action – the scanner is idle (controller in program mode)
connect to a PowerFlex drive using a 1203-SSS • Comm Fault Action – network communications have become disrupted
or 1203-USB converter and then route over Available actions include:
ControlNet to access other Allen-Bradley • Fault – the drive is faulted and stopped
drives. This eliminates the need for a separate • Stop – the drive is stopped using the current deceleration rate and is not faulted
network tap and interface. • Zero Data – the adapter zeros the I/O data transmitted to the drive
I/O Messaging (Scheduled) – I/O messaging • Hold Last – the adapter continues sending the I/O data prior to the fault and the
is used to transfer time-critical data, such as drive continues in its present state
data that controls the drive. The following • Send Fault Configuration – the user specifies the Logic Command, Reference,
data can be sent and received by the adapter: and Datalink data that is sent to the drive, allowing complete flexibility in
• Logic Command/Reference configuring a fault action
• Logic Status/Feedback Diagnostics – Built-in diagnostics allow drive-side troubleshooting of the network
• Datalinks - read and write up to 8 parameters connection using a PowerFlex DPI HIM, DriveExplorer or DriveExecutive. View
Explicit Messaging (Unscheduled) – actual Logic Command/Reference, Logic Status/Feedback and Datalink data being
Explicit messaging involves non time-critical transmitted to and from the controller.
information that is typically triggered by the Flash Upgradeable – The adapter can be flash updated in the field using
application (ladder program in a controller, DriveExplorer, DriveExecutive or ControlFLASH to take advantage of new
etc.). The adapter supports the reading/ firmware features as they become available.
writing of parameters, etc. in the drive and
any connected DPI peripheral(s).
20-COMM-Q_PP_NL_8_14:Layout 1 8/23/06 8:06 AM Page 2
PARAMETERS SPECIFICATIONS
No. Name Description Communications Network Protocol ControlNet
01 DPI Port Displays the port to which the adapter is connected. Data Rates 5 Mbps
02 DPI Data Rate Displays the data rate (kilobits per second) used by the drive. Drive Protocol DPI
03 CN Addr Cfg Configures the ControlNet node address if the Node Address Switches are set to “00.” Data Rates 125 or 500 Kbps
04 CN Addr Act Displays the ControlNet node address actually used by the adapter. Electrical Consumption Drive (DPI) 275 mA at 5 VDC
05 CN Rate Cfg Configures the ControlNet data rate (megabits per second) at which the Network N/A
adapter communicates. Regulatory UL UL508C
06 CN Rate Act Displays the ControlNet data rate (megabits per second) actually used by Compliance cUL CAN/CSA C22.2 No. 14-M91
the adapter.
CE EN50178 and EN61800-3
07 Ref/Fdbk Size Displays the size of the Reference/Feedback words.
CTick EN61800-3
08 Datalink Size Displays the size of each Datalink word.
09 Reset Module Used to reset the adapter or set defaults.
10 Comm Flt Action Sets the action that the adapter will take if it detects a network failure. EXAMPLE I/O IMAGE
11 Idle Flt Action Sets the action that the adapter will take if the adapter detects that the
scanner is idle. ControlNet DPI
12 CN Active Cfg Displays the source from which the adapter node address is taken. Controller Scanner Adapter PowerFlex Drive
13 DPI I/O Cfg Selects the I/O that is transferred through the adapter.
Word and I/O
Output 0 Logic Command Logic Command
14 DPI I/O Act Displays the I/O that the adapter is actively transmitting. Image 1 Reference Reference
15 Flt Cfg Logic Sets the data that is sent to the drive if any of the following is true: (Write) 2 Datalink In A1 Data In A1
3 Datalink In A2 Data In A2
16 Flt Cfg Ref
4 Datalink In B1 Data In B1
17 Flt Cfg A1 In • Parameter 10 - [Comm Flt Action] is set to “Send Flt Cfg” and 5 Datalink In B2 Data In B2
18 Flt Cfg A2 In communications are disrupted. 6 Datalink In C1 Data In C1
7 Datalink In C2 Data In C2
19 Flt Cfg B1 In • Parameter 11 - [Idle Flt Action] is set to “Send Flt Cfg” and the 8 Datalink In D1 Data In D1
20 Flt Cfg B2 In scanner is idle. 9 Datalink In D2 Data In D2
21 Flt Cfg C1 In Input 0 Pad Word (1)
22 Flt Cfg C2 In Image 1 Pad Word (1)
(Read) 2 Logic Status Logic Status
23 Flt Cfg D1 In
3 Feedback Feedback
24 Flt Cfg D2 In 4 Datalink Out A1 Data Out A1
25 M-S Input Selects the data produced by the scanner and consumed by the adapter. 5 Datalink Out A2 Data Out A2
26 M-S Output Selects the data produced by the adapter and consumed by the scanner. 6 Datalink Out B1 Data Out B1
7 Datalink Out B2 Data Out B2
27 Ref Adjust Sets the percent scale factor for the Reference from the network. 8 Datalink Out C1 Data Out C1
9 Datalink Out C2 Data Out C2
10 Datalink Out D1 Data Out D1
11 Datalink Out D2 Data Out D2
Publication 20COMM-PP001F-EN-P – May 2008 Copyright ©2008 Rockwell Automation, Inc. All Rights Reserved. Printed in USA.
Supersedes Publication 20COMM-PP001E-EN-P – July 2006
20-COMM-R_PP_NL_8_14:Layout 1 8/23/06 8:23 AM Page 1
PRODUCT HIGHLIGHTS
Internal Mount – The adapter mounts
internal to the drive to save panel space, and
is field installable.
Configuration Switches – The adapter has
rotary switches for setting the node address
(0-77) and DIP switches for setting the network
data rate (57.6 Kbps/115.2 Kbps/230.4 Kbps),
rack size, group number, and last group in
rack. Alternatively, the switches can be
disabled to allow these settings to be
configured using parameters.
Multiple Configuration Tool Options – A
number of configuration tools can be used
to configure the adapter and the connected
drive. These tools include the PowerFlex DPI User Configurable Fault Responses – Selects the action that the adapter and
HIM, or drive-configuration software such as drive will take for the following two conditions:
DriveExplorer™ or DriveExecutive™. • Idle Fault Action – the scanner is idle (controller in program mode)
• Comm Fault Action – network communications have become disrupted
I/O Messaging – I/O messaging is used to
transfer time-critical data, such as data that Available actions include:
controls the drive. The following data can • Fault – the drive is faulted and stopped
be sent and received by the adapter: • Stop – the drive is stopped using the current deceleration rate and is not faulted
• Logic Command/Reference • Zero Data – the adapter zeros the I/O data transmitted to the drive
• Logic Status/Feedback • Hold Last – the adapter continues sending the I/O data prior to the fault and the
• Datalinks - read and write up to 8 parameters drive continues in its present state
• Send Fault Configuration – the user specifies the Logic Command, Reference,
Explicit Messaging – Explicit messaging and Datalink data that is sent to the drive, allowing complete flexibility in
involves non time-critical information that is configuring a fault action
typically triggered by the application (ladder
program in a controller, etc.). The adapter Diagnostics – Built-in diagnostics allow drive-side troubleshooting of the network
supports the reading/writing of parameters, connection using a PowerFlex DPI HIM, DriveExplorer or DriveExecutive. View
etc. in the drive and to any connected DPI actual Logic Command/Reference, Logic Status/Feedback and Datalink data being
peripheral(s). transmitted to and from the controller.
Rack Size – Two rack sizes can be configured: Flash Upgradeable – The adapter can be flash updated in the field using
• 1/4 Rack - Logic Command/Status DriveExplorer, DriveExecutive or ControlFLASH to take advantage of new firmware
• 1/2 Rack - Logic Command/Reference and features as they become available.
Logic Status/Feedback
Block Transfer is always enabled and is also
used for I/O messaging.
20-COMM-R_PP_NL_8_14:Layout 1 8/23/06 8:23 AM Page 2
PARAMETERS SPECIFICATIONS
No. Name Description Communications Network Protocol Remote I/O
01 DPI Port Displays the port to which the adapter is connected. Data Rates 57.6, 115.2 or 230.4 Kbps
02 DPI Data Rate Displays the data rate (kilobits per second) used by the drive. Drive Protocol DPI
03 RIO Addr Cfg Sets the node address if dipswitches 7 and 8 are ON. Data Rates 125 or 500 Kbps
04 RIO Addr Act Displays the node address actually used by the adapter. Electrical Consumption Drive (DPI) 250 mA at 5 VDC
05 RIO Rate Cfg Sets the data rate (kilobits per second) that the adapter communicates Network N/A
at when dipswitches 7 and 8 are ON. Regulatory UL UL508C
06 RIO Rate Act Displays the data rate (kilobits per second) actually used by the adapter. Compliance cUL CAN/CSA C22.2 No. 14-1791
07 Ref/Fdbk Size Displays the size of the Reference/Feedback words. CE EN50178 and EN61800-3
08 Datalink Size Displays the size of each Datalink word. CTick EN61800-3
09 Reset Module Used to reset the adapter or reset defaults.
10 Comm Flt Action Sets the action that the adapter will take if it detects that communications
have been disrupted.
EXAMPLE I/O IMAGE –1/4 RACK
Remote I/O DPI
11 Idle Flt Action Sets the action that the adapter will take if the adapter detects that
the scanner is idle. Controller Scanner Adapter PowerFlex Drive
12 DPI I/O Config Selects the I/O that is transferred through the adapter. Discrete I/O
Output 0 BT Control
Word
Logic Command
13 DPI I/O Active Displays the I/O that the adapter is actively transmitting. Image 1 Logic Command
Reference
14 Flt Cfg Logic Sets the data that is sent to the drive if Parameter 10 - [Comm Flt Action] Block Transfer I/O
15 Flt Cfg Ref is set to “Send Flt Cfg” and communications are disrupted. Data 0-1 Reference
Files 2-3 Datalink A1 Data In A1
4-5 Datalink A2 Data In A2
16 Flt Cfg A1 In 6-7 Datalink B1 Data In B1
Word
24 Switches Displays the status of the dipswitch settings. 6-7 Datalink B1 Data Out B1
Word
25 Start RIO Group Sets the starting module group if dipswitches 7 and 8 are ON. 10 - 11 Datalink C1 Data Out C1
Data Out C2
12 - 13 Datalink C2
Data Out D1
26 Last RIO Rack Enables or disables the last physical group within a rack address if 14 - 15 Datalink D1
Data Out D2
16 - 17 Datalink D2
dipswitches 7 and 8 are ON.
Data Block Message
27 Rack Size Sets the rack size if dipswitches 7 and 8 are ON. Files Transfer Messages Handler
The adapter uses the following parameters instead of switches: Image 1 Logic Status Logic Status
3 - [RIO Addr Cfg] for the rack address 2 - 3 Feedback Feedback
5 - [RIO Rate Cfg] for the baud rate
25 - [Start RIO Group] for the starting module group Block Transfer I/O
26 - [Last RIO Rack] for the last physical rack Data 0-1 Feedback (2)
27 - [Rack Size] for the rack size Files 2-3 Datalink A1 Data Out A1
4-5 Datalink A2 Data Out A2
6-7 Datalink B1 Data Out B1
Word
(1) Not used in 1/2 rack. The space is reserved so the Datalinks occupy the same Block Transfer I/O
locations regardless of 1/4 or 1/2 rack configuration.
(2)
Feedback is transmitted in both Discrete I/O and Block Transfer I/O.
Publication 20COMM-PP001F-EN-P – May 2008 Copyright ©2008 Rockwell Automation, Inc. All Rights Reserved. Printed in USA.
Supersedes Publication 20COMM-PP001E-EN-P – July 2006
20-COMM-S_PP_NL_8_14:Layout 1 8/23/06 8:23 AM Page 1
PRODUCT HIGHLIGHTS
Internal Mount – The adapter mounts
internal to the drive to save panel space, and
is field installable.
Configuration Switches – The adapter
has rotary switches for setting the node
address and the network data rate.
Alternatively, the switches can be disabled,
allowing the node address to be set using
a configuration parameter.
User Configurable Fault Responses – Selects the action that the adapter and
Multiple Configuration Tool Options – A
drive will take for the following two conditions:
number of configuration tools can be used to
• Idle Fault Action – the scanner is idle (controller in program mode)
configure the adapter and the connected
• Comm Fault Action – network communications have become disrupted
drive. These tools include the PowerFlex DPI
HIM, or drive-configuration software such as Available actions include:
DriveExplorer™ or DriveExecutive™. • Fault – the drive is faulted and stopped
• Stop – the drive is stopped using the current deceleration rate and is not faulted
DPI Routing – Allows DriveExplorer to
• Zero Data – the adapter zeros the I/O data transmitted to the drive
connect to a PowerFlex drive using a 1203-SSS
• Hold Last – the adapter continues sending the I/O data prior to the fault and the
or 1203-USB converter and then route over the
drive continues in its present state
network to access other Allen-Bradley drives.
• Send Fault Configuration – the user specifies the Logic Command, Reference,
DF1 Messaging – DF1 Messaging can be and Datalink data that is sent to the drive, allowing complete flexibility in
used by Allen-Bradley controllers to transfer configuring a fault action
data to and from the drive, including control
Diagnostics – Built-in diagnostics allow drive-side troubleshooting of the network
data. The following data can be sent and received
connection using a PowerFlex DPI HIM, DriveExplorer or DriveExecutive. View
by the adapter using N40:/N41: file addressing:
actual Logic Command/Reference, Logic Status/Feedback and Datalink data being
• Logic Command/Reference
transmitted to and from the controller.
• Logic Status/Feedback
• Datalinks - read and write up to 8 parameters Flash Upgradeable – The adapter can be flash updated in the field using
• Explicit Messaging - read/write drive DriveExplorer, DriveExecutive or ControlFLASH to take advantage of new firmware
parameters using Block Transfer Emulation features as they become available.
20-COMM-S_PP_NL_11_1:Layout 1 11/1/06 11:48 AM Page 2
PARAMETERS SPECIFICATIONS
No. Name Description Communications Network Protocol DF1
01 DPI Port Displays the port to which the adapter is connected. Data Rates 1200 - 38400 bps
02 DPI Data Rate Displays the data rate (kilobits per second) used by the drive. Drive Protocol DPI
03 DF1 Addr Cfg Sets the node address if the Data Rate switch is set to “PGM” (Program). Data Rates 125 or 500 Kbps
04 DF1 Addr Act Displays the node address actually used by the adapter. Electrical Consumption Drive (DPI) 150 mA at 5 VDC
05 DF1 Rate Cfg Sets the data rate (kilobits per second) at which the adapter Network N/A
communicates when the Data Rate switch is set to “PGM” (Program). Regulatory UL UL508C
06 DF1 Rate Act Displays the data rate (bits or kilobits per second) actually used Compliance cUL CAN/CSA C22.2 No. 14-1791
by the adapter.
CE EN50178 and EN61800-3
07 Ref/Fdbk Size Displays the size of the Reference/Feedback words.
CTick EN61800-3
08 Datalink Size Displays the size of each Datalink word.
09 Reset Module Used to reset the adapter or reset defaults.
10 Comm Flt Action Sets the action that the adapter will take if it detects that communications CONNECTOR TERMINALS
have been disrupted. Terminal Signal Function
11 Active Cfg Displays the source from which the adapter node address and data rate are TERM Termination Signal RC Termination
taken (switches or parameters). A Signal A TxRxDx -
12 DPI I/O Cfg Selects the I/O that is transferred through the adapter. B Signal B TxRxDx +
COM Common Signal Common
13 DPI I/O Act Displays the I/O that the adapter is actively transmitting. SHIELD Shield Shield RC Termination
14 Flt Cfg Logic Sets the data that is sent to the drive if Parameter 10 - [Comm Flt Action] GND Ground Shield Ground Termination
15 Flt Cfg Ref is set to “Send Flt Cfg” and communications are disrupted.
16 Flt Cfg A1 In Node 1 Node 2 Node “n”
17 Flt Cfg A2 In
G LD
G LD
G LD
M
M
RM
RM
RM
D
D
IE
IE
IE
N
N
O
O
SH
SH
SH
TE
TE
TE
A
A
B
B
18 Flt Cfg B1 In
C
C
19 Flt Cfg B2 In
20 Flt Cfg C1 In
21 Flt Cfg C2 In
22 Flt Cfg D1 In
23 Flt Cfg D2 In
24 CRC/BCC Cfg Sets the method for error detection (BBC or CRC) in data communications. N-FILE SUMMARY
25 CRC/BCC Act Displays the actual error detection method (BBC or CRC)used for Data Category N-File Address Description
data communications. Explicit Messaging N40:0-63 Block Transfer Emulation
26 Dup Msg Detect Determines if the adapter ignores duplicate messages. I/O Messaging N41:0 Logic Command/Status
N41:1-2 Reference/Feedback
EXAMPLE SYSTEM DPI Port Config
N41:3-18
N42:3
Datalinks A-D
Comms Time-Out Value
Laptop or Desktop PC
with DriveExplorer 20-COMM-S
SERIES A
FRN AS SHIPPED: V 1.001
SERIAL NUMBER: 402D9423
DEVICE: 5VDC 150mA
20-COMM-S
SERIES A
FRN AS SHIPPED: V 1.001
SERIAL NUMBER: 402D9423
DEVICE: 5VDC 150mA
20-COMM-S
SERIES A
FRN AS SHIPPED: V 1.001
SERIAL NUMBER: 402D9423
DEVICE: 5VDC 150mA
LISTED
IND.CONT.EQ.
966X
N223 LISTED
IND.CONT.EQ.
966X
N223 LISTED
IND.CONT.EQ.
966X
N223
1203-USB or 1203-SSS
Converter
Drive Cable
Use DriveExplorer Lite or Full to configure a single Use DriveExplorer Full to route through DPI and configure
drive and its installed RS485 DF1 adapter drives connected directly on RS485 DF1 (Up to 254 drives!)
Publication 20COMM-PP001F-EN-P – May 2008 Copyright ©2008 Rockwell Automation, Inc. All Rights Reserved. Printed in USA.
Supersedes Publication 20COMM-PP001E-EN-P – July 2006
1203-SSS_PP_NL_8_14:Layout 1 8/23/06 8:21 AM Page 1
PRODUCT HIGHLIGHTS
External Connection – The module connects
externally and is powered by the drive.
DPI Routing – Allows DriveExplorer to
connect to a PowerFlex drive using a 1203-SSS
serial converter and then route out over
EtherNet/IP™, ControlNet™, DeviceNet™, or
RS-485 DF1 to access other Allen-Bradley
drives (1-to-many connection). This
eliminates the need for a separate network
connection and interface.
Legacy SCANport Connectivity – Use the
1203-SSS with DriveExplorer or DriveManager™
to connect with 1305 and 1336 PLUS II drives,
ACCESSORIES
and other SCANport-based host products. Do you have a PC with only a USB connection? Use a USB to Serial adapter, such as
an Allen-Bradley 9300-USBS, to connect to the RS232 side of the 1203-SSS. The
Use the 1203-SFC cable (supplied with the adapter is a small, portable unit with no AC power required. It has also been tested
1203-SSS) to connect directly to 1203-GU6 with Allen-Bradley DriveExplorer and DriveExecutive software tools.
DeviceNet, 1203-CN1 ControlNet, or 1203-EN1
EtherNet/IP modules, and route over the Do you want to connect to a drive without having to open the enclosure door? Use
network to access other Allen-Bradley drives. a GracePort™ interface, such as a P-A19-B3 (Nema 4/12 interface) or P-A19-F3R0
(NEMA 4/12 interface with AC outlet), available from Grace Engineered Products
DriveExplorer Lite Included – A Inc. (http://www.grace-eng.com).
DriveExplorer Lite CD is included with the
1203-SSS. DriveExplorer Lite is freeware
and can also be downloaded at:
http://www.ab.com/drives/driveexplorer/f
ree_download.html
Flash Upgradeable – The module can be
flash updated in the field using DriveExplorer,
DriveExecutive or ControlFLASH, to take
advantage of new firmware features as they
become available. The module is also the
primary connection mechanism for flashing
drives and other peripherals.
1203-SSS_PP_NL_8_14:Layout 1 8/23/06 8:21 AM Page 2
PARAMETERS SPECIFICATIONS
No. Name Description Communications Network Protocol DF1
01 Adapter Port Displays the port to which the adapter is connected. Data Rates 9600 - 38400 bps
02 DF1 Addr Cfg Configures the DF1 address used for the serial converter. Drive Protocol DPI or SCANport
03 DF1 Rate Cfg Configures the data rate used for the serial port. Data Rates 125 or 500 Kbps (DPI only)
04 Comm Flt Action Sets the action that the module will take if it detects that communications Electrical Consumption Drive (DPI) 130 mA at 12 VDC
have been disrupted. Network N/A
05 Reset Module Used to reset the adapter or reset defaults. Regulatory UL UL508C
06 Clear DF1 Counts Used to clear the DF1 statistical parameters (7-15). Compliance cUL CAN/CSA C22.2 No. 14-1791
07 DF1 Packets Sent Displays the number of DF1 packets sent by the serial converter. CE EN50178 and EN61800-3
08 DF1 Packets Rcvd Displays the number of DF1 packets received by the serial converter. CTick AS/NZS 2064, Group 1, Class A
09 Undelivered Msgs Displays the number of DF1 packets sent by the serial converter and
not acknowledged.
10 ENQs Sent Displays the number of ENQs sent by the serial converter.
11 ENQs Received Displays the number of ENQs received by the serial converter.
DriveExplorer LITE
12 NAKs Received Displays the number of NAKs received by the serial converter.
13 NAK Bad Packet Displays the number of NAKs received by the serial converter because of
bad packets.
14 NAK No Memory Displays the number of NAKs received by the serial converter because of
insufficient buffer memory.
15 Duplicate Msgs Displays the number of duplicate messages sent by the serial converter.
16 Interface Mode Selects whether the serial converter will autodetect DPI or SCANport devices
and use the appropriate protocol.
17 DPI Data Rate Displays the data rate (kilobits per second) used by the drive.
18 DF1 Addr Act Displays the actual DF1 address used by the serial converter.
19 DF1 Rate Act Displays the actual data rate used by the serial converter.
20 Ref/Fdbk Size Displays the size of the Reference/Feedback words.
21 Datalink Size Displays the size of each Datalink word.
ROUTING DIAGRAM
PowerFlex 70 Drives with 20-COMM-C, 20-COMM-D,
20-COMM-E or 20-COMM-S Adapters (Port 5)
Laptop or Desktop PC
with DriveExplorer 20-COMM-S
SERIES A
FRN AS SHIPPED: V 1.001
SERIAL NUMBER: 402D9423
DEVICE: 5VDC 150mA
20-COMM-S
SERIES A
FRN AS SHIPPED: V 1.001
SERIAL NUMBER: 402D9423
DEVICE: 5VDC 150mA
20-COMM-S
SERIES A
FRN AS SHIPPED: V 1.001
SERIAL NUMBER: 402D9423
DEVICE: 5VDC 150mA
LISTED
IND.CONT.EQ.
966X
N223 LISTED
IND.CONT.EQ.
966X
N223 LISTED
IND.CONT.EQ.
966X
N223
1203-USB or 1203-SSS
Converter
Network
Drive Cable
Use DriveExplorer Lite to connect to a single drive Use DriveExplorer Full to route through DPI to drives connected
and configure its installed communication adapter directly on ControlNet, DeviceNet, EtherNet/IP or RS485 DF1
Publication 20COMM-PP001F-EN-P – May 2008 Copyright ©2008 Rockwell Automation, Inc. All Rights Reserved. Printed in USA.
Supersedes Publication 20COMM-PP001E-EN-P – July 2006
1769-SM_PP_NL_8_14:Layout 1 8/23/06 8:44 AM Page 1
PRODUCT HIGHLIGHTS
1769 Platform Connectivity –The module
can be used in 1769-based systems, such as:
• MicroLogix 1500 controllers
• CompactLogix controllers
• Remote 1769-Based node adapters
(1769-ADN DeviceNet, etc.)
Three DPI/SCANport Channels – Three
channels are provided, allowing any
combination of up to three PowerFlex 70,
700, 700H and 700S drives (DPI) and/or
SCANport (1305, 1336 PLUSII, etc.) devices
User Configurable Fault Responses – Selects the action that the adapter and
to be connected per module.
drive will take for the following two conditions:
I/O Messaging – I/O messaging is used to • Idle Fault Action – the controller or scanner is idle (controller in program mode)
transfer time-critical data, such as data that • Comm Fault Action – network communications have become disrupted
controls the drive. The following data can
be sent and received by the adapter: Available actions include:
• Logic Command/Reference • Fault – the drive is faulted and stopped
• Logic Status/Feedback • Stop – the drive is stopped using the current deceleration rate and is not faulted
• Datalinks - read and write up to 8 parameters • Zero Data – the adapter zeros the I/O data transmitted to the drive
• Hold Last – the adapter continues sending the I/O data prior to the fault and the
Explicit Messaging – Explicit messaging drive continues in its present state
involves non time-critical information that
• Send Fault Configuration – the user specifies the Logic Command, Reference,
is typically triggered by the application
and Datalink data that is sent to the drive, allowing complete flexibility in
(ladder program in a controller, etc.).
configuring a fault action
The adapter supports the reading/writing
of parameters, etc. in the drive and to Diagnostics – Built-in diagnostics allow drive-side troubleshooting of the network
any connected DPI peripheral(s). connection using a PowerFlex DPI HIM, DriveExplorer or DriveExecutive. View
Multiple Configuration Tool Options – A actual Logic Command/Reference, Logic Status/Feedback and Datalink data being
number of configuration tools can be used to transmitted to and from the controller.
configure the adapter and the connected Flash Upgradeable – The adapter can be flash updated in the field using
drive. These tools include the PowerFlex DPI DriveExplorer, DriveExecutive or ControlFLASH to take advantage of new firmware
HIM, or drive-configuration software such as features as they become available.
DriveExplorer™ or DriveExecutive™.
1769-SM_PP_NL_8_14:Layout 1 8/23/06 8:45 AM Page 2
PARAMETERS SPECIFICATIONS
No. Name Description Communications Drive Protocol DPI or SCANport
01 Config Mode Displays the module’s configuration mode. Data Rates 125 or 500 Kbps (DPI only)
02 Reset Module Used to reset the module or set defaults. Electrical Consumption Module 280 mA at 5 VDC
03 Port ID 1 Displays the port number to which CH1 is connected. Channel (each) 60 mA at 12 VDC
04 Data Rate 1 Displays the data rate (kilobits per second) used by the CH1 drive. Regulatory UL UL508C
05 Ref/Fbk Size 1 Displays the size of the Reference/Feedback words for the CH1 drive. Compliance cUL CAN/CSA C22.2 No. 14-1791
06 Datalink Size 1 Displays the size of each Datalink word for the CH1 drive. CE EN50081-2 and EN61000-6-2
07 I/O Config 1 Selects the I/O that is transferred through the module to the CH1 drive. CTick AS/NZS 2064, 1997, Group 1, Class A
08 I/O Actual 1 Displays the I/O actively transmitted by the module for the CH1 drive.
09 Idle Action 1 Sets the action that the module and CH1 drive will take if it detects that the controller was switched to
Program or Test mode. EXAMPLE I/O IMAGE
10 Flt Cfg Logic 1 Sets the data that is sent to the CH1 drive if Parameter 09 - [Idle Action 1] is set to
11 Flt Cfg Ref 1 “Send Flt Cfg” and the controller is put into Program or Test mode. (POWERFLEX 70/700 STANDARD)
12 Flt Cfg A1 In1 Output Input Word
13 Flt Cfg A2 In1 Image Image CH1 CH2 CH3
14 Flt Cfg B1 In1 Channel Enable Channel Status 0 4 8
15 Flt Cfg B2 In1 Logic Command Logic Status 1 5 9
Reference(LSW) Feedback (LSW) 2 6 10
16 Flt Cfg C1 In1 Reference(WSW) Feedback (MSW) 3 7 11
17 Flt Cfg C2 In1 Datalink In A1 (low) Datalink Out A1 (low) 12 16 20
18 Flt Cfg D1 In1 Datalink In A1 (high) Datalink Out A1 (high) 13 17 21
Datalink In A2 (low) Datalink Out A2 (low) 14 18 22
19 Flt Cfg D2 In1 Datalink In A2 (high) Datalink Out A2 (high) 15 19 23
20 Port ID 2 Displays the port number to which CH2 is connected. Datalink In B1 (low) Datalink Out B1 (low) 24 28 32
Datalink In B1 (high) Datalink Out B1 (high) 25 29 33
21 Data Rate 2 Displays the data rate (kilobits per second) used by the CH2 drive.
Datalink In B2 (low) Datalink Out B2 (low) 26 30 34
22 Ref/Fbk Size 2 Displays the size of the Reference/Feedback words for the CH2 drive. Datalink In B2 (high) Datalink Out B2 (high) 27 31 35
23 Datalink Size 2 Displays the size of each Datalink word for the CH2 drive. Datalink In C1 (low) Datalink Out C1 (low) 36 40 44
Datalink In C1 (high) Datalink Out C1 (high) 37 41 45
24 I/O Config 2 Selects the I/O that is transferred through the module to the CH2 drive. Datalink In C2 (low) Datalink Out C2 (low) 38 42 46
25 I/O Actual 2 Displays the I/O actively transmitted by the module for the CH2 drive. Datalink In C2 (high) Datalink Out C2 (high) 39 43 47
26 Idle Action 2 Sets the action that the module and CH2 drive will take if it detects that the controller was switched to Datalink In D1 (low) Datalink Out D1 (low) 48 52 56
Program or Test mode. Datalink In D1 (high) Datalink Out D1 (high) 49 53 57
Datalink In D2 (low) Datalink Out D2 (low) 50 54 58
27 Flt Cfg Logic 2 Sets the data that is sent to the CH1 drive if Parameter 26 - [Idle Action 2] is set to Datalink In D2 (high) Datalink Out D2 (high) 51 55 59
28 Flt Cfg Ref 2 “Send Flt Cfg” and the controller is put into Program or Test mode.
29 Flt Cfg A1 In2
30 Flt Cfg A2 In2
EXAMPLE SYSTEMS
31 Flt Cfg B1 In2
MicroLogix 1500 Controller PowerFlex 70 Drives
32 Flt Cfg B2 In2
Allen-Bradley Allen-Bradley Allen-Bradley
38 Data Rate 3 Displays the data rate (kilobits per second) used by the CH3 drive. CH3
39 Ref/Fbk Size 3 Displays the size of the Reference/Feedback words for the CH3 drive.
CompactLogix Controller PowerFlex 70 Drives
40 Datalink Size 3 Displays the size of each Datalink word for the CH3 drive. Allen-Bradley
PowerFlex 70
© 2000
Allen-Bradley
PowerFlex 70
© 2000
Allen-Bradley
PowerFlex 70
© 2000
41 I/O Config 3 Sets the I/O that is transferred through the module to the CH3 drive.
MOD MOD MOD
42 I/O Actual 3 Displays the I/O actively transmitted by the module for the CH3 drive.
43 Idle Action 3 Sets the action that the module and CH3 drive will take if it detects that the controller was switched to CH1
Program or Test mode. CH2
44 Flt Cfg Logic 3 Sets the data that is sent to the CH3 drive if Parameter 43 - [Idle Action 3] is set to “Send CH3
45 Flt Cfg Ref 3 Flt Cfg” and the controller is put into Program or Test mode.
46 Flt Cfg A1 In3 DeviceNet PowerFlex 70 Drives
Allen-Bradley Allen-Bradley Allen-Bradley
Publication 20COMM-PP001F-EN-P – May 2008 Copyright ©2008 Rockwell Automation, Inc. All Rights Reserved. Printed in USA.
Supersedes Publication 20COMM-PP001E-EN-P – July 2006
DPI WIM PP_8_14:Layout 1 8/23/06 7:14 AM Page 1
PRODUCT HIGHLIGHTS
Multiple Enclosure Styles – The DPI WIM
is offered in two different form-factors to
meet your environment needs:
• NEMA 1 (cat. no. 20-WIM-N1) (shown left)
• NEMA 4 (cat. no. 20-WIM-N4S) (shown right)
Versatile Mounting – The NEMA 1 DPI
WIM can be installed in a NEMA 1 DPI HIM
bezel (20-HIM-B1) mounted on the front of
an enclosure door, or it can be installed in the
HIM cradle on the front of the drive (Port 1).
The NEMA 4 DPI WIM is designed for NEMA 4 Security – Use the security mode parameter to limit access to qualified personnel.
and permanent-mount applications. This safety feature prevents unintended drive configuration and/or machine operation.
Multiple Tool Options – A number of tools User Configurable Fault Response – Selects the action that the WIM and drive
can be used to configure and communicate will take for the following condition:
with the WIM and connected drive. These • Comm Fault Action – network communications have become disrupted
tools include the PowerFlex DPI HIM, or Available actions include:
drive-configuration software such as Pocket • Fault – the drive is faulted and stopped
DriveExplorer™ for Pocket PC, DriveExplorer™ • Stop – the drive is stopped using the current deceleration rate and is not faulted
or DriveExecutive™. • Zero Data – the WIM zeros the I/O data transmitted to the drive
DPI Routing – Connect point-to-point to a • Hold Last – the WIM continues sending the I/O data prior to the fault and
PowerFlex 7-Class drive using the DPI WIM the drive continues in its present state
and then route out over EtherNet/IP™, Diagnostics – Built-in diagnostics allow drive-side troubleshooting of the network
ControlNet™, DeviceNet™ or RS-485 DF1 to connection using Pocket DriveExplorer for Pocket PC, DriveExplorer or
access other Allen-Bradley drives (1-to-many DriveExecutive. View actual Logic Command/Speed Reference and Logic Status/
connection). This eliminates the need for a Speed Feedback data being transmitted to and from the controller.
separate network connection and interface for
Flash Upgradeable – The DPI WIM can used to flash update its own firmware, and
each drive.
the firmware of other connected DPI products such as PowerFlex 7-Class drives and
Legacy SCANport Connectivity – Use the peripherals through Pocket DriveExplorer for Pocket PC, DriveExplorer or DriveExecutive
DPI WIM with Pocket DriveExplorer for to take full advantage of new firmware features as they become available.
Pocket PC, DriveExplorer or DriveExecutive to
connect with 1305 and 1336 PLUS II drives,
and other SCANport-based host products.
DPI WIM PP_8_14:Layout 1 8/23/06 7:14 AM Page 2
PORT PORT
0.00 Hz 0.00 Hz
MOD MOD
2.5 Cans/Sec 2.5 Cans/Sec
NET A NET A
STS STS
Allen-Bradley
PowerFlex 70
© 2000
PORT
MOD
NET A
STS
NET B
Publication 20COMM-PP001F-EN-P – May 2008 Copyright ©2008 Rockwell Automation, Inc. All Rights Reserved. Printed in USA.
Supersedes Publication 20COMM-PP001E-EN-P – July 2006
DPI X_COMM PP_5_11_07.QXD:Layout 1 5/31/07 8:10 AM Page 1
PRODUCT HIGHLIGHTS
Multiple Network Connectivity –
Provides a secondary network connection
for DPI-based PowerFlex 70, 700, and 700S
AC drives. One connection can be dedicated
for drive control (for example, start, stop)
while additional connections may be used
for software tools (for example,
DriveExplorer™, DriveExecutive™),
data collection, etc.
Comm Kits Enclosure Cover
Comm Kits (with adapter mounted inside)
Enclosure Base
installed in the kit for applications that require additional general-purpose network
I/O that a controller can use. The drive and I/O devices are handled as one node
Internal Interface Cable
(connects power supply board on the network, saving network node count and increasing network throughput.
in enclosure base to adapter)
Versatile Power Connections – Connect either a 24 VDC power source to the kit's
The kit is for use with only the following convenient removable terminal block, or use the Allen-Bradley AC power adapter
Allen-Bradley communication adapters (20-XCOMM-AC-PS1, purchased separately) that comes with interchangeable region
(sold separately): plugs (US, UK, Europe, and Australia). The kit can also be daisy-chained to provide
• 20-COMM-B BACnet® MS/TP power for additional kits.
• 20-COMM-C ControlNet™ (coax)
• 20-COMM-D DeviceNet™ (series B or later) EXAMPLE SYSTEM OVERVIEW
• 20-COMM-E EtherNet/IP™
Computer with
• 20-COMM-K CANopen® PanelView Plus Ethernet Connection
1500
• 20-COMM-M Modbus/TCP
• 20-COMM-Q ControlNet™ (fiber)
Universal Mounting – Direct panel, DIN Ethernet Network
Adapter (Port 5)
NET B
PORT
MOD
External DPI
Increased System I/O – Allows for the Communications Kit
NET A
NET B
with 20-COMM-E
installation of additional I/O. An optional Remote I/O Network Adapter (Port 2)
I/O board (20-XCOMM-IO-OPT1) can be
DPI X_COMM PP_8_14.QXD:Layout 1 8/23/06 10:25 AM Page 2
DAISY-CHAINING KITS
You can power additional external communication kits
by daisy-chaining them together.
Comm Kits
(20-XCOMM-DC-BASE)
AC-to-DC Converter
(20-XCOMM-AC-PS1)
Publication 20COMM-PP001F-EN-P – May 2008 Copyright ©2008 Rockwell Automation, Inc. All Rights Reserved. Printed in USA.
Supersedes Publication 20COMM-PP001E-EN-P – July 2006
1203-USB_8_14.qxd:Layout 1 9/20/06 3:09 PM Page 1
PRODUCT HIGHLIGHTS
External Connection – The converter
connects externally and is powered by the
connected drive. No additional power source
is required.
DPI Routing Support – When connected to
a PowerFlex Architecture-Class drive, use
DriveExplorer with a 1203-USB converter to
route over BACnet MS/TP EtherNet/IP™, DriveExplorer Lite/USB Drivers Included – A CD with DriveExplorer Lite and USB
ControlNet™, DeviceNet™, or RS-485 DF1 to drivers is included with the 1203-USB converter. DriveExplorer Lite is freeware and can
access other Allen-Bradley drives (1-to-many also be downloaded at: http://www.ab.com/drives/driveexplorer/free_download.html
connection). This eliminates the need for a
separate network connection and interface. Flash Upgradeable – The 1203-USB converter can be flash updated in the field
using DriveExplorer, DriveExecutive or ControlFLASH to take advantage of new
DSI Routing Support – When connected to firmware features as they become available. The converter is also the primary
a PowerFlex Component-Class drive, use connection mechanism for flashing drives and other peripherals.
DriveExplorer with a 1203-USB converter to
route over EtherNet/IP™, ControlNet™, or ACCESSORIES
DeviceNet™ to access other Allen-Bradley Do you want to connect to a drive without having to open the enclosure door?
drives (1-to-many connection). Like the 22- The following GracePort™ interface options provide this capability:
SCM-232 module, the converter also has an
RTU Master mode. This mode provides DPI/SCANport Products
connectivity for up to 31 drives via their built- • P-A19-B3 (NEMA 4/12 interface with 8-pin mini-DIN connector)
in RS-485 ports. This eliminates the need for • P-A19-F3R0 (same as above plus convenience AC outlet)
a separate network connection and interface.
DSI Products
Legacy SCANport Connectivity – Use the
1203-USB converter with DriveExplorer or • P-A20-B3 (NEMA 4/12 interface with RJ45 connector)
DriveTools SP (DriveExecutive and • P-A20-F3R0 (same as above plus convenience AC outlet)
DriveObserver) to connect with 1305 and For more information about these and other related products, please visit
1336 PLUS II drives, and other SCANport- Grace Engineered Products Inc. at http://www.grace-eng.com
based host products.
1203-USB_8_14.qxd:Layout 1 9/20/06 3:09 PM Page 2
08 Ref/Fdbk Size
and the converter autobauds to it.
Displays the size of the Speed Reference/Feedback words which is determined
SPECIFICATIONS
by the drive. The converter automatically uses the correct size.
Communications Network Protocol USB
09 Datalink Size Displays the size of each Datalink word which is determined by the drive.
The converter automatically uses the correct size. Data Rate 115.2 Kbps
Drive Protocol DPI
NETWORK EXAMPLE
PowerFlex 70 Drives Route through DPI to drives connected on
with 20-COMM-* BACnet MS/TP (20-COMM-BControlNet (20-COMM-C),
PORT PORT
0.00 Hz 0.00 Hz
MOD MOD
2.5 Cans/Sec 2.5 Cans/Sec
NET A NET A
or DF1 (20-COMM-S)
STS STS
Laptop or Desktop PC
with DriveExplorer or DriveExecutive
22-HIM-H10 (included)
Publication 22COMM-PP001F-EN-P – May 2008 Copyright ©2008 Rockwell Automation, Inc. All Rights Reserved. Printed in USA.
20Comm Cover_NL_8_14.qxd:Layout 1 8/22/06 11:44 AM Page 3
7-CLASS CONNECTIVITY
PowerFlex 7-Class
Communication 70 700
700H 700S 7000
Adapter / Module Protocol/Platform Std. EC Std VC
Publication 20COMM-PP001F-EN-P – May 2008 Copyright ©2008 Rockwell Automation, Inc. All Rights Reserved. Printed in USA.
Supersedes Publication 20COMM-PP001E-EN-P – July 2006