Manual supplement 7340
Manual supplement 7340
This supplement contains information necessary to ensure the accuracy of the above manual.
Change #1
On page 12, after the last bullet in the Environmental Conditions section, add:
Note
The Product can show some control sensitivity to moderate or severe electromagnetic fields
or conducted interference of certain frequencies. In the presence of radiated EM
disturbances, with frequencies of 250 MHz to 400 MHz and with amplitude >1 V/m to a
maximum of 3 V/m, add 0.0025 °C to the stability specification. Stability is not guaranteed if
amplitude is >3 V/m. When subject to conducted disturbances of 8 MHz to 80 MHz, and
amplitude >3 V, add 0.005 °C to the stability specification.
From: R-507
To: R-410A
9/22 1
Manual Supplement 7340 Users
On page 36, in Figure 5. Controller Operation Flow, under Operating Parameters Menu, delete the
options remove:
Cutout Reset Mode and Adj. Cutout Reset Mode.
On page 46, under 9.10 Cutout, replace the 2nd and 3rd paragraph with:
If the cutout is activated because of excessive bath temperature, power to the heater is shut off
and the bath cools and the display flashes . The display continues to flash between the
actual temperature and until the temperature falls below the reset temperature and the
cutout is reset.
On page 48, in section 9.13 Operating Parameters change the last paragraph to:
Press “UP” to enter the menu. The operating parameters menu contains the cooling mode and
hot gas bypass mode.
On page 48, remove section 9.13.1 Cutout Reset Mode.
On page 61, in the table remove the section for Operating Parameters Menu, (including Read cutout
mode, Set cutout mode, Set cutout to be reset manually,and Set cutout to be reset automatically).
On page 68, under Maintenance replace the last bullet with
• The over-temperature cutout should be checked every 6 months to see that it is working
properly. In order to check the user selected cutout, follow the controller directions in Section
9.2, Reset Cutout, for setting the cutout. Set the bath temperature higher than the cutout. Check
to see if the display flashes cutout and if the temperature is decreasing.
Note: When checking the over-temperature cutout, be sure that the temperature limits of the
bath fluid are not exceeded. Exceeding the temperature limits of the bath fluid could cause
harm to the operator, lab, and instrument.
On page 69, replace second item in the table with:
Problem Causes and Solutions
The controller display The display will flash alternately with the process temperature.
flashes and the • If the process temperature displayed seems grossly in error, consult the
heater does not
problem: The display flashes and an incorrect process temperature.
operate
• Normally, the cutout disconnects power to the heater when the bath
temperature exceeds the cutout set-point causing the temperature to drop
back down to a safe value. The heater only comes on again when the
temperature is reduced and the cutout is manually reset by the operator, see
Section 9.10, Cutout. Check that the cutout set-point is adjusted to 10 °C or
20°C above the maximum bath operating temperature.
• If the cutout activates when the bath temperature is well below the cutout set-
point or the cutout does not reset when the bath temperature drops and it is
manually reset, then the cutout circuitry or the cutout thermocouple sensor
may be faulty or disconnected. Contact an Authorized Service Center (see
Section 1.3 Authorized Service Centers) for assistance.
2 9/22
7340 Users Guide Manual Supplement
9/22 3