5) Per Unit Analysis (1)
5) Per Unit Analysis (1)
Normally, in power system analysis the different quantities (voltage, current, power, impedance)
are expressed using the per-unit system. This provides the following advantages:
1- per unit data provides relative magnitude information.
2- simplifies the analysis of circuits containing transformers. The per unit impedance of a
transformer in three-phase system is the same, regardless of the type of the winding
connections (star-delta, delta-star, stat-star, or delta-delta). The per unit impedance of a
transformer is the same when referred to either the primary or the secondary side,
3- circuit parameter are in narrow ranges (around 1 p.u) and this makes error checking
easier.
4- Manufacturers usually specify the impedance of an equipment in per unit on the base of
its nameplate rating.
5- The per unit impedance values of various ratings of equipment lie in a narrow range,
(whereas the actual ohmic values may vary widely). Therefore when actual values are
unknown, a good approximate (typical) value of similar equipment can be used.
This method is suitable for systems with different voltage levels (sections connected with
transformers).
In this method base values are selected, and all the actual values are referred to their respective
base values, as:
actual value
value in p.u
base value
normally two base values, base VA, VAB and the base voltage, VB are chosen.
then for each section VB is found from the transformers ratios. then the base current I B and the
base impedance Z B are calculated for each section. the p.u values then are found.
- ZB
I B VAB
for practical cases the base VA is selected in MVA units or MVAB , and the base voltage is
selected in kV units or kV B , thus:
- the base current for each section is calculated as:
1000 xMVAB
IB
kV B
Or:
Solution:
MVAB ,new kV 2B ,old
X ( p.u ) new X ( p.u ) old .
MVAB ,old kV 2B ,new
100 18
2
if the primary voltage base is V1B and the secondary voltage is V2 B , thus:
V1B 1
(1)
V2 B a
thus:
I 1B
a (2)
I 2B
in this equation:
I 2,actual
I 2 ( pu ) (13)
I 2B
equation (16) represents a very simple equivalent circuit of the transformer in per unit, which is
only an impedance as shown below:
Solution:
For transformer T1 , as the p.u reactance is defined at the rating MVA, which is other than the
base MVA, thus
MVAB,new kV 2 B,old
Z T1 Z T1 ,old x x
MVAB,old kV 2 B,new
Or:
100 112
Z T1 j 0.1x x j 0.0667 p.u
150 112
Note that the voltage ratings of this transformer are the same as the base values.
For the transformer T2 , as the base MVA and the base voltage are the same as the transformers
ratings, thus:
ZT 2 j 0.08 p.u