Product data sheet
Specifications
High power contactor, TeSys Giga,
3 pole (3NO), AC-3 <=440V 225A,
standard version, 100…250V wide
band AC/DC coil
LC1G225KUEN
Main
Range TeSys
Range of product TeSys Giga
Product or component type Contactor
Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Device short name LC1G
Contactor application Power switching
Motor control
Utilisation category AC-1
AC-3
AC-3e
AC-4
AC-5a
AC-5b
AC-6a
AC-6b
AC-8a
AC-8b
DC-1
DC-3
DC-5
Poles description 3P
[Ue] rated operational voltage <= 1000 V AC 50/60 Hz
<= 460 V DC
[Ie] rated operational current 330 A (at <40 °C) at <= 1000 V AC-1
225 A (at <60 °C) at <= 440 V AC-3
[Uc] control circuit voltage 100...250 V AC 50/60 Hz
100...250 V DC
Control circuit voltage limits Operational: 0.8 Uc Min...1.1 Uc Max (at <60 °C)
Drop-out: 0.1 Uc Max...0.45 Uc Min (at <60 °C)
Complementary
[Uimp] rated impulse withstand 8 kV
voltage
overvoltage category III
[Ith] conventional free air thermal 330 A (at 40 °C)
current
Rated breaking capacity 2050 A at 440 V
[Icw] rated short-time withstand 1.8 kA - 10 s
current 1.0 kA - 30 s
0.85 kA - 1 min
0.56 kA - 3 min
0.44 kA - 10 min
Associated fuse rating 250 A aM at <= 440 V for motor
200 A aM at <= 690 V for motor
400 A gG at <= 690 V
List Price displayed is VAT EXCLUSIVE.
Feb 5, 2025 1
Average impedance 0.00015 Ohm
[Ui] rated insulation voltage 1000 V
Power dissipation per pole 20 W AC-1 - Ith 330 A
8 W AC-3 - Ith 225 A
Compatibility code LC1G
Pole contact composition 3 NO
Auxiliary contact composition 1 NO + 1 NC
Motor power kW 55 kW at 230 V AC 50/60 Hz (AC-3e)
110 kW at 400 V AC 50/60 Hz (AC-3e)
110 kW at 415 V AC 50/60 Hz (AC-3e)
132 kW at 440 V AC 50/60 Hz (AC-3e)
132 kW at 500 V AC 50/60 Hz (AC-3e)
160 kW at 690 V AC 50/60 Hz (AC-3e)
132 kW at 1000 V AC 50/60 Hz (AC-3e)
55 kW at 230 V AC 50/60 Hz (AC-3)
110 kW at 400 V AC 50/60 Hz (AC-3)
110 kW at 415 V AC 50/60 Hz (AC-3)
132 kW at 440 V AC 50/60 Hz (AC-3)
132 kW at 500 V AC 50/60 Hz (AC-3)
160 kW at 690 V AC 50/60 Hz (AC-3)
132 kW at 1000 V AC 50/60 Hz (AC-3)
55 kW at 230 V AC 50/60 Hz (AC-4)
110 kW at 400 V AC 50/60 Hz (AC-4)
110 kW at 415 V AC 50/60 Hz (AC-4)
129 kW at 440 V AC 50/60 Hz (AC-4)
132 kW at 500 V AC 50/60 Hz (AC-4)
132 kW at 690 V AC 50/60 Hz (AC-4)
110 kW at 1000 V AC 50/60 Hz (AC-4)
Motor power hp 60 hp at 200/208 V 60 Hz
75 hp at 230/240 V 60 Hz
150 hp at 460/480 V 60 Hz
150 hp at 575/600 V 60 Hz
Irms rated making capacity 2720 A at 440 V
Coil technology Built-in bidirectional peak limiting
Safety reliability level B10d = 400000 cycles contactor with nominal load conforming to EN/ISO 13849-1
B10d = 3000000 cycles contactor with mechanical load conforming to EN/ISO
13849-1
Mechanical durability 8 Mcycles
inrush power in VA (50/60 Hz, AC) 540 VA
inrush power in W (DC) 380 W
hold-in power consumption in VA 12.4 VA
(50/60 Hz, AC)
hold-in power consumption in W 7.8 W
(DC)
Operating time 40...70 ms closing
15...50 ms opening
Maximum operating rate 600 cyc/h AC-3
600 cyc/h AC-3e
300 cyc/h AC-1
150 cyc/h AC-4
Connections - terminals Power circuit: bar 2 - busbar cross section: 25 x 6 mm
Power circuit: lugs-ring terminals 1 185 mm²
Power circuit: bolted connection
Control circuit: push-in 1 0.2…2.5 mm² - cable stiffness: solid stranded without cable
end
Control circuit: push-in 1 0.25…2.5 mm² - cable stiffness: flexible with cable end
Control circuit: push-in 2 0.5…1.0 mm² with cable end
Control circuit: push-in 0.75…2.5 mm² - cable stiffness: solid stranded without cable
end
Control circuit: push-in 0.75…2.5 mm² - cable stiffness: flexible with cable end
Connection pitch 35 mm
2 Feb 5, 2025
Mounting support Plate
Standards EN/IEC 60947-4-1
EN/IEC 60947-5-1
UL 60947-4-1
CSA C22.2 No 60947-4-1
JIS C8201-4-1
JIS C8201-5-1
IEC 60335-1:Clause 30.2
IEC 60335-2-40:Annex JJ
UL 60335-1
UL 60335-2-40:Annex JJ
Product certifications CB Scheme
CCC
cULus
EAC
CE
UKCA
EU-RO-MR by DNV-GL
Tightening torque 18 N.m
Height 193 mm
Width 108 mm
Depth 193 mm
Product weight 3.6 kg
Environment
IP degree of protection IP2X front face with shrouds conforming to IEC 60529
IP2X front face with shrouds conforming to VDE 0106
Ambient air temperature for -25…60 °C
operation
Ambient air temperature for -60…80 °C
storage
Mechanical robustness Vibrations 5…300 Hz 2 gn contactor open
Vibrations 5…300 Hz 4 gn contactor closed
Shocks 10 gn 11 ms contactor open
Shocks 15 gn 11 ms contactor closed
Colour Dark grey
Protective treatment TH
Permissible ambient air -40…70 °C at Uc
temperature around the device
Packing Units
Unit Type of Package 1 PCE
Number of Units in Package 1 1
Package 1 Height 25.800 cm
Package 1 Width 17.500 cm
Package 1 Length 32.000 cm
Package 1 Weight 4.497 kg
Unit Type of Package 2 S06
Number of Units in Package 2 12
Package 2 Height 75.000 cm
Package 2 Width 60.000 cm
Package 2 Length 80.000 cm
Package 2 Weight 64.690 kg
Feb 5, 2025 3
Environmental Data
Schneider Electric aims to achieve Net Zero status by 2050 through supply chain partnerships, lower impact materials, and circularity
via our ongoing “Use Better, Use Longer, Use Again” campaign to extend product lifetimes and recyclability.
Environmental Data explained
How we assess product sustainability
Environmental footprint
Carbon footprint (kg.eq.CO2 per CR, Total Life cycle) 878
Environmental Disclosure Product Environmental Profile
Use Better
Materials and Substances
Packaging made with recycled cardboard Yes
Packaging without single use plastic No
SCIP Number 6fbdad13-bb7c-47d4-a6d6-d82dd6f54349
China RoHS Regulation China RoHS declaration
PVC free Yes
Use Again
Repack and remanufacture
Circularity Profile End of Life Information
Halogen content performance Halogen free plastic parts product
Take-back No
4 Feb 5, 2025
Product data sheet LC1G225KUEN
Installation
Installation Videos
TeSys Giga - How to install the auxiliary contact block
TeSys Giga - How to install and remove remote wear diagnosis module
TeSys Giga - How to install mechanical interlock kit
TeSys Giga - How to install cable memory kit
TeSys Giga - How to directly mount LR9G overload relay
TeSys Giga - How to replace control module
TeSys Giga - How to replace switching modules
TeSys Giga - How to assemble reverser solution
TeSys Giga - How to assemble change-over solution
Feb 5, 2025 5