UNIT 5 - Transformer Protection
UNIT 5 - Transformer Protection
The principal relays and systems used for transformer protection are :
Advantages
(i) It is the simplest form of transformer protection.
(ii) It detects the incipient faults at a stage much earlier than is
possible with other forms of protection.
Disadvantages
(i) It can only be used with oil immersed transformers equipped
with conservator tanks.
(ii) The device can detect only faults below oil level in the
transformer. Therefore, separate protection is needed for
connecting cables.
The three leads of the primary winding of power transformer are taken through the
core of a current transformer which carries a single secondary winding. The
operating coil of a relay is connected to this secondary. Under normal conditions
(i.e. no fault to earth), the vector sum of the three phase currents is zero and there is
no resultant flux in the core of current transformer no matter how much the load is
out of balance. Consequently, no current flows through the relay and it remains
inoperative. However, on the occurrence of an earth-fault, the vector sum of three
phase currents is no longer zero. The resultant current sets up flux in the core of the
C.T. which induces e.m.f. in the secondary winding. This energises the relay to trip
the circuit breaker and disconnect the faulty transformer from the system.
Fig. above shows Merz-Price circulating-current scheme for the protection of a 3- phase
delta/delta power transformer against phase-to ground and phase-to-phase faults. Note that
CTs on the two sides of the transformer are connected in star. This compensates for the
phase difference between the power transformer primary and secondary. The CTs on the two
sides are connected by pilot wires and one relay is used for each pair of CTs. During normal
operating conditions, the secondaries of CTs carry identical currents. Therefore, the currents
entering and leaving the pilot wires at both ends are the same and no current flows through
the relays. If a ground or phase-to-phase fault occurs, the currents in the secondaries of CTs
will no longer be the same and the differential current flowing through the relay circuit will
clear the breaker on both sides of the transformer. The-protected zone is limited to the region
between CTs on the high-voltage side and the CTs on the low-voltage side of the power
transformer.
10/29/2024 ENG. KELVIN KAMALONI 19
Differential Protection of Transformers
Example
A 3-phase transformer of 220/11,000 line volts is
connected in star/delta. The protective
transformers on 220 V side have a current ratio of
600/5. What should be the CT ratio on 11,000 V
side ?
Solution
Solution