classification_karlsen_pp
classification_karlsen_pp
CLASSIFICATION OF DP SYSTEMS
Development, present focus areas and future directions
MTS DP 2013 Luncheon presentation
Aleks Karlsen
Houston October 2013
Agenda
Background
DNV Rule development process
DNV Rules and Standards related to DP
Development within DP rules
Present challenges influencing DP rule development
Possible future rule development
Present focus areas, incl. power systems operating with closed bus-ties
Summary
Cooperation
- Industry
- Authorities
- Universities and other research institutions
Manageable pace:
- Not to fast DNV Rules for
classification
- Not to slow of ships
No single fault shall cause a loss of position or heading (to avoid catastrophic events)
Never exceed vessel’s sub failure capabilities, which is to be continuously monitored by the automatic DP
control system Consequence Analysis
Capable certified personnel and higher focus on operational aspects
Designated workstations for DP operations
FMEA, generally to a higher standard and often based on more than one “technical system operational
mode” with inherent different integrity towards loss of position
Withstand the worst case relevant failure mode
Systems split in more than two redundancy groups
More complex power systems
Desire to operate with closed bus-ties
No failure to full thrust allowed for any propeller (RPM control is the state of the art and the failure mode is
easier mitigated on these thrusters as compared to CPP)
(At least) Three position references: All on line
Redundant DP control system + Joystick + Manual levers
Back-up non-redundant DP control system for DP class 3
DYNPOS
DPS
(DNV main DP notations)
(IMO Minimum ER
requirements)
Enhanced Reliability
ISDS
(DNV new DP principles)
(Integrated Software
Enhanced
Dependent Systems)
System verification
RP for DP design
(HIL-IS and HIL-DS)
RP for DP Operations
RP for FMEA
of redundant systems
Growth
- Both in high-end and low-end
- High-end set very strong requirements on class
- Other parts of the market are more focused on “getting the certificate”
Main Class
FMEA
IEC 61508
HIL
ISO 17894
FSA - Risk
CMMI - RP Product
Risk based ver
Process
Performance
ISDS
Safety case
MBE SCM
12
= =
=
FThrusters = FA + FB + FC + FD = Fweather
FThrusters = FA + FB + FC + FD = Fweather
DP-2 Variable U
1A1
0%
Transient under voltage The FMEA must analyse the effect of transient voltage dips in the system and identify measures necessary to
(short circuit ride through): avoid problems with:
(In electrical systems •unintended tripping of frequency converters
transient voltage dips may •unintended deselecting of thrusters from DP control (e.g. loss of ready signal from drives to DP control system)
occur, e.g. due to short •unintended tripping of motors and other important components, like auxiliary system pumps (tripping of motor
circuits and subsequent starters and/or contactors)
intended opening of feeder •unintended activation of under voltage protection systems
or bus-tie breakers for •DC control power systems, e.g. dual feeding through diodes or automatic change-over
disconnection of the faulty In relation with the above items, functionality must be checked in order to verify the potential effect of this failure
equipment. In connection mode.
with operation with closed The requirement is that the equipment DP-3: Live short
not belonging circuitsgroup
to the redundancy must beaffected
directly introduced
by the failure
bus such transients will shall ride through the transient periodatandthebe main switchboard
immediately level.
available, without Short
operator circuit
intervention, when the
affect the whole connected system voltage is re-established. tests may be required for all power systems
distribution system.) Measures must be implemented as found (AC,necessary
DC, UPS) through
if analysis.
these are crossing the
No “short circuit test”-requirements to verify the conclusions.
redundancy groups:
(Additionally, or as an alternative, verification of the above mentioned items may also be based on testing. Such
• Short circuit 3-phase
testing should be based upon non-destructive methods for simulating the transient low voltage period in the
system. ) • Short circuit 1-phase
© Det Norske Veritas AS. All rights reserved.
• Earth faults
More additional DP-3 failure modes:
Examples of failure modes to consider can be found in DNV FMEA RP-D102:
www.dnv.com