duct fan IB

This document provides a comprehensive manual for the installation and operation of a ventilating fan, emphasizing safety precautions and proper installation techniques. It outlines essential warnings, cautions, and detailed steps for installation, including required materials and methods. Additionally, it includes guidelines for electrical connections and maintenance to ensure safe and effective use of the fan.

Uploaded by

Nick Maung
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
9 views

duct fan IB

This document provides a comprehensive manual for the installation and operation of a ventilating fan, emphasizing safety precautions and proper installation techniques. It outlines essential warnings, cautions, and detailed steps for installation, including required materials and methods. Additionally, it includes guidelines for electrical connections and maintenance to ensure safe and effective use of the fan.

Uploaded by

Nick Maung
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 12

VENTILATING FAN

MODEL:

MANUAL AND INSTALLATION PROCEDURE

PRODUCT APPEARANCE
ADDITIONAL PART

SCREW (9 PCS)

REMARK : IS THE ALPHABET OF DEVELOPEMENT NUMBER

CAREFULLY READ INSTALLATION MANUAL AND THE PRODUCT


SHOULD BE INSTALLED BY THE SPECIALIZED TECHNICIAN.
ESSENTIAL SAFETY PRECAUTIONS

WARNING
FAILURE TO COMPLY DEATH OR BODILY INJURY MAY RESULT.
1. Do not use the ventilator when damages found on wire or other components. This may
cause fire and electric shock.
2. Do not switch on the ventilator when the assembling is not completed with all
components such as airguide and propeller as bodily injury may result.
3. Do not use the ventilator or its electrical components when they are wet as injury from
electric shock may result.
PROHIBITED 4. Do not contact the ventilator or its electrical components when your hands are wet.
5. Do not modify the ventilator as severe injury may result.
6. Be sure to unplug the ventilator from the main supply prior to cleaning or repairing the
ventilator.

CAUTIONS
FAILURE TO COMPLY BODILY INJURY OR PROPERTY DAMAGE MAY RESULT.
1. It is dangerous to insert fingers or object into the ventilator propeller or rotating component.
2. Do not use harsh cleaners or solvents on the ventilator as this may cause deforming on plastic
components and damaging other components.
3. Do not install the ventilator at the location of heat source such as gas/electric fire nearby; location of
high humidity, location of solvent dampness, as fan damage or fire may result.
4. The appliance is not intended for use by young children or infirm persons unless they been adequately
supervised by a responsible person to ensure that can use the appliance safety.

INSTALLATION

INSTALLATION CAUTIONS
1. Before installation and assembling the Ventilator, please study the manual.
2. The installation might be suggestion from Service Center or Sales Agency.
3. To be install with stable ceiling to bear the weight and vibration of Ventilator.
4. To be installed metal pipe by do not install metal parts contact with conductive material which
be coated on the wooden.
5. The Accessory pipe hood more available to protect insect or bird and rains.
6. Do not install the ventilator and control switch in bathroom or high humidity area may cause electric
short-circuit.
7. Do not install the fan in:
- Area containing high amount of oil, chemical, dust.
- The back-flow of gases into the room the open fuel of gas or other open fire appliances.
8. The Installation area might be stable ceiling to bear the weight of ventilator in each model as;

Kg Kg
Kg Kg
Kg Kg
Kg
In case of installation at high temperature area, the Should inclined install smoke pipe by additional duct
capacity of insulator parts such as motor, capacity higher than smoke pipe on the wall
might drop and be cause of electric leakage. 1mm/100mm to protect the rain water.
Moreover, not well-done lubricated shaft might be
hotter as well as motor. To protect those conditions
do not install the product at the high temperature
area.
WALL
Should avoid pipe bending as belows:
Watch out!!
It’s Electric leaking SHARP BENDS MANY BENDS BEND RIGHT BY VERY NARROW
THE AIR OUTLET CONNECTION

In the closed building or unable to exhaust the


air area, the hole should be installed to drain in The installed
the fresh air. ceiling should be
easy to check
OPENED GAP
from opened gap.

In case of loosen
AIR DRAIN IN GAP installation, It’s
might occur
vibration or loud
noise.
INSTALLATION
TO SELECT INSTALLATION AREA AND WALL FOR DRILLING THE AIR-EXHAUSTED HOLE
To Install duct from the air-exhausted hole to DUCT
additional duct by fixing it with ceiling to protect the
overload. Diameter of duct is 100 mm(VD-10/15) or
150 mm (VD-18/20/23) made from vinyl chloride,
aluminium, steel. Before Installation Please carefully
read Installation of caution. WALL
Figure.

VENTILATING FAN INSTALLATION


There are two methods to install the product.
To prevent the contact with the propeller, install the ventilating fan above 2.3 m from the floor.

A. Fixed by beam BEAM

(A1) To make a frame with beam and sub beam as


Figure.2 and dimension in Table 1.
Table.1
Model Dimension A Dimension B Model Dimension A Dimension B SUB BEAM

Figure.

Unit : mm.
(A2) To take off additional duct as the arrow (A3) To install the wing of additional duct under sub
direction as Figure.3 beam and fix additional duct with main duct. Then
fix additional duct with sub beam at “A” position with
ADDITIONAL DUCT
screw as Figure.4
Remark
In case of vinyl chloride duct, the inclination from the
product to ended-duct should not greater than 7 degree.

ADDITIONAL
BODY Push up DUCT

Figure.
BEAM
(A4) To install the product with additional duct and
push product until lock point of additional duct
lock hook of product as Figure.5 LETTER “A”
HOLE
Figure. SCREW
To lock
product with (A5) To check the completeness and install
upper product with beam by screwing with 8 screws.
additional duct. as Figure.6
ADDITIONAL
DUCT
BODY

To lock product
with lower
additional duct WALL
Figure. as picture. SCREW

B. The installation by using hook nut. Figure.


SCREW
There are two methods, using L fix plate, and sub frame (LETTER “A” HOLE)

(B1) L fix plate method


(B1.1) To set hook nut with ceiling and install L fix plate with the product as the Figure.7, 8 and 9

Model : Model :

L fix plate
SCREW
SCREW
L fix plate

Q.14UL3)BEEJUJPOBM!QBSU* Q.16UL)BEEJUJPOBM!QBSU*

Figure. Figure.
Table shown dimension of position of “L” Fix plate
each model as followed

MODEL Dimension Dimension Dimension


A B C

Unit:mm.
As shown at Figure.9

L fix plate
Figure.

SCREW
P-08TK (ADDITIONAL PART)

L FIX PLATE HOOK NUT


(B1.2) To fix the product with hook nut and
horizontal install the product as right NUT
picture. as Figure.10
WASHER

RUBBER
(B2) To use SUB FRAME WASHER
Figure.
(B2.1) Install HOOK NUT with the ceiling and
install sub frame with the Body.
The sub frame of model
The sub frame of model
Figure.12
Figure.11

Caution
2 Central holes to be use.
HOLE

Figure.

HOLE Table shown each SUB FRAME model dimension


Dimension Dimension Dimension Dimension
MODEL SUB FRAME
A B C D

Unit :mm.
Figure.

Unit:mm.
(B2.2) To set 2 wooden parts with sub frame (B2.3) To Install sub frame to ceiling with Hook nut as
by using screws as the Figure.13 the Figure.14
Caution :Do not obstruct hook nut-hole on sub frame. HOOK-NUT

SUB FRAME

Figure.
SCREW
Figure.
(B2.5) To set the product by turning the front to open air hole to
exhaust the air from the wall and fix the additional duct
with sub frame by screwing through “A” letter hole as
SUB FRAME
Figure.16
WOODEN
ADDITIONAL DUCT HOOK NUT
as Figure.15.
WOODEN
ADDITIONAL
DUCT

SCREW
PUSH UP
SUB FRAME

Figure.
BODY
Figure.

(B2.6) To set the product with additional duct with as Figure.18


hook of product and additional duct Figure.17
SUGGESTION

ADDITIONAL
DUCT
WOODEN
SUB FRAME ADDITIONAL DUCT

BODY

Figure. Figure.
SCREW
(B2.9) After installed ceiling board, to hammer from the
as Figure.19 inside for protecting the slide of sub frame and
ceiling as Figure.20
SUB FRAME SUB FRAME
WOODEN

MODEL NAME BEAM

TAPE
NAIL NAIL
Figure. SUB FRAME

Figure.
Unit:mm.
TO INSTALL PIPE FROM BODY TO WELL EXHAUST PIPE
To adhere aluminium tape at connecting point
TAPE
between exhaust pipe and additional duct to
protect air leakage as Figure.21 DUCT

Figure.

ADDITIONAL PART(NOT INCLUDE ON PRODUCT)

“L” fix plate, Sub frame, Duct (Iron, plastic, Aluminium, Stainless steel), Hood.

TO INSTALL LEAD WIRE SHOULD BE DONE AS NECESSARY

LEAD WIRE INATALLATION CAUTION

1.Fan and lead wire installation should be suggested by service center or specialize
technician.
2.Before installation and Assembling the fan please read installation manual carefully.
3.Installation leadwire carefully, in case missing occure may cause circuit-shorten.
4.Installing lead wire in pipe should be use the standard piping accesories (available from
hardware store),and then connect to the terminal.

TERMINAL DIAGRAM AND LEAD WIRE CONNECTION


Separate each model group as followed

VENTILATOR MAIN UNIT VENTILATOR MAIN UNIT VENTILATOR MAIN UNIT

Thermal Thermal
Thermal fuse
fuse fuse

WALL WALL WALL


SWITCH * SWITCH * SWITCH*
VVF VVF VVF
LEAD WIRE LEAD WIRE LEAD WIRE
1.6 mm or 1.6 mm or 1.6 mm or
2.0 mm CIRCUIT 2.0 mm CIRCUIT 2.0 mm CIRCUIT
BREAKER BREAKER BREAKER

Figure.
VENTILATOR MAIN UNIT HOOK
Thermal
fuse 157

SLIDE COVER
*WALL SWITCH is obtained from hardware store.
Remark :
VVF 1. Installation location of circuit breaker should be easy
LEAD WIRE to operation and shut off.
1.6 mm or 2. The circuit breaker shall have a contact separation in
2.0 mm all poles and provide full disconnection under
overvoltage category III condition in accordance
WALL with the wiring rules.
SWITCH *
CIRCUIT CONDUCTOR
BREAKER
Figure. Continue

CAUTION
Pay attention to connect the wire,1 wire
from power supply especially common
wire connect with the “N(COM)” terminal.
Insert the tip of the flathead
Leadwire size for installation screwdriver here.
2 2 Figure.
1. Must use indoor wiring VVF cable Ø1.6 mm or Ø2.0 mm
2. In case of install ground wiring must install ground at least
1.0 mm2 and must install to Industrial Standard CAUTION
Ground Rod by specialized technician. Do not connect the ground wire to Gas duct, Water pipe
Lightning rod or Telephone line because may
occur electric shock.
General connector and electric line procedure
SCREW
To peel off lead wire 10 mm.
To pull wiring approx. 150 mm from the product.
TERMINAL
To separate wiring from connecting board, then push LEAD WIRE COVER
red button on connecting board and pull each wiring
with Screw Driver.
STRIPPED WIRE
Lead wire connector method
Model : (as Figure. ) TERMINAL
GROUND
(1) Remove screw and unlock cover, weave VVF (Ø1.6, Ø2.0) TERMINAL
through rubber button until it can be completely passed.
(2) The product is used in high humidity area, the ground wiring Figure.
should be installed.
(3) To lock the cover and fix to screw. SCREW
TERMINAL
COVER
Model : as Figure.
LEAD WIRE
(1) Remove screw and unlock cover, weave VVF (Ø1.6, Ø2.0) STRIPPED WIRE
through rubber button until it can be completely passed.
(2) The product is used in high humidity area, the ground wiring
should be installed. GROUND TERMINAL
(3) To lock the cover and fix to screw. TERMINAL

Figure.
TERMINAL
Model: as Figure. COVER
SCREW
(1) Remove screw and unlock cover, weave VVF (Ø1.6, Ø2.0)
through rubber button until it can be completely passed.
(2) The product is used in high humidity area, the ground wiring
should be installed. LEAD WIRE
(3) To lock the cover and fix to screw. GROUNDING
TERMINAL
STRIPPED WIRE

Figure.

TERMINAL
Model: as Figure. SCREW COVER
(1) Remove screw and unlock cover, weave VVF (Ø1.6, Ø2.0)
through rubber button until it can be completely passed.
(2) The product is used in high humidity area, the ground wiring
should be installed.
(3) To lock the cover and fix to screw. GROUNDING
LOW
TERMINAL
HIGH
STRIPPED WIRE
COM

Figure.

TO INSTALL CEILING BOARD AND CEILING


Figure.
Caution
To leave a gap between the product and BEAM
ceiling board approx. 2-3 mm. CEILING
To prevent the contact with the propeller,
install the ventilating fan above 2.3 m from
2-3 mm. More than 2.3 m
the floor. from the floor.
FLOOR.

TO INSTALL GRILLE

To hold grille’s spring of both side and insert to ELLIPTICAL


elliptical hole of product then, release spring and HOLE

push cover to fix with the product as Figure.29.

Remarks:
Grille of VD-10Z4T -C, VD-15Z4T -C, VD-18Z4T ,
VD-20Z4T , VD-20ZP4T , VD-23Z4T , VD-23ZP4T SPRING

can be reverse 90 ° by changing SPRING. GRILLE


Figure.
Spring grille assembling
MODEL
MODEL MODEL

Put SPRING in SPRING


Insert
SPRING Twist to CLOSE
Insert PIN locking with PLIERS
Figure. PLIERS
CATCH
USAGE
For VD-10Z4T , VD-10Z4T -C, VD-15Z4T , VD-15Z4T -C, VD-15ZP4T .
CAUTION USAGE
In case of installed in restroom having hot bathtub, Various parts are made from plastic material, do not
after draining the hot water, please cover bathtub bring flammable objects to be near them that they
to prevent the evaporation of hot stream. might possibly be deformed or melted.

Be Quick
Close it
Yep

Figure. Figure.

OPERATING PROCEDURE
Switch boarded exclude the product, Use switch which be sold generally.

Remark : Installation location


START TO EXHAUST THE AIR STOP TO EXHAUST THE AIR
of switch should be easy to
operate and shut off. Switch on the wall. Switch on the wall.

OFF ON OFF ON

Air volume selector is available SET THE AIR VOLUME SELECTOR SET THE AIR VOLUME SELECTOR
Only this followed model SWITCH TO “HIGH.” SWITCH TO “LOW.”
VD-20ZP4T2,VD23Z4T2,VD-23ZP4T2

LOW HIGH LOW HIGH

MAINTENANCE
1. Be always turn switch off or pull the circuit breaker down before cleaning and
musn’t wet the motor or other electrical parts.
2. Cleaning the dirty part with water/neutral detergent damped-cloth to protect
water driping into electrical part, and then wipe with a dry cloth.
3. Do not use any chemical to clean the plastic part it may cuase damage to
product.
4. In case of intensive dirt on the grille, the air blow will be less causing loud
noise. To protect such condition, should often clean the grille.
5. To remove the grille, pull the grille, then squeeze the spring and take it from
the elliptical hole of fix spring as Figure.29 in page 9.
6. Disconnect the power when not in use.
REPAIRING PRODUCT
1. This product must not be assembled under any circumstances. Only authorized repair technicians are
qualified to conduct diassembly and repairs.
(Failure to heed this warning may result infire, electric shock or injury.)
2. Must use genuine spare part from Service center or Sales Agency.
3. Do not modify any electric part, if failure to heed this warning may cause injury.

DIMENSIONS
NPEFM!;
HOLE FOR FIX
SCREW(8POINT)

LEAD WIRE
Unit : mm. INSERT HOLE

NPEFM!;

HOLE FOR FIX


SCREW(8POINT)

LEAD WIRE
Unit : mm. INSERT HOLE

NPEFM!;

HOLE FOR FIX


SCREW(8POINT)
Unit : mm.
LEAD WIRE
Dimension table was shown INSERT HOLE
at Page.12
TABLE: Each part dimension of

PART NAME
MODEL
No. PART NAME PICTURE
PLASTIC METAL
ADDITIONAL
ALL MODEL
DUCT

BODY ALL MODEL

PROPELLER
FAN

AIR GUIDE

ORIFICE

GRILLE

REMARK : NOT HAVE ORIFICE (No. 5) IN THIS FOLLOWED MODEL

K0588N41401