SGP_1
SGP_1
Course Outcomes
2. Asymmetrical Faults:
LG Fault: It occurs due to flashover of insulator or
sometimes the failure of the insulator.
1.Selectivity
2.Speed
3.Sensitivity
4.Disrimination
5.Stability
6.Reliability
7.Economics
1.Selectivity
• This is ability of protective device to isolate the
faulty section from the power system network. In this
case, main objective is the outage area that should be
minimum and at the same time, the interruption of
power or duration of interruption of power that is
also minimum.
• The possibility to failure and failure of protective
relays and circuit breaker that has to be considered in
determining the selectivity of whole system or whole
network.
Selectivity
Absolute Relative
Selectivity Selectivity
2. Speed
• It is apparent that quick disconnection of faulted area
or the elements can significantly improve the stability
of power system, reduce the outage duration and at
the same time, it also minimizes the damage to the
equipment. Therefore when a fault occurs, the
protective relays should identify the fault and operate
as fast as possible.
• The total time to remove the fault is determined as
the sum of the operation time of relays and circuit
breakers.
• Typically, a high speed relay can operate in the range
of 10 to 30 msec.
3. Sensitivity
• It is the ability of protective device to operate
correctly for any fault or abnormal condition inside
the zone of protection.
• It is related to the minimum level of fault current at
which your protective device operates.
• Protective device with good sensitivity can sense any
faults within the zone of protection.
• Protective device with good sensitivity can sense any
type of fault in the protective system. Sensitivity is
usually given by the factor known as sensitivity
factor which depends on the parameters of protected
elements and operating conditions of power system.
4. Discrimination
• Discrimination is defined as the capability or ability
of the protective device to discriminate between fault
and loading condition even when magnitude of fault
current is lower than the maximum full load current.
5. Stability
• Stability means a protective system should be able to
distinguish between fault and loading condition when
the minimum fault current is less than the maximum
full load current.
6. Reliability
• It is the ability of protective device to operate
correctly or accurately during the whole lifespan of
the device.
• Reliability can be categorized as Dependability and
Security
• Dependability - It is the ability of the system that
operates correctly for any abnormal condition or if
any fault occurs inside the system, your system
should be capable to operate for that event.
• Security- It means your system or protective device
should remain stable for any mal-operation.
7. Economics
Consider total cost of system = %
Unit Protection
• Unit protection scheme is a scheme that operates for
a fault within its own zone.
• Here zone of protection is decided on the basis of
current transformers and it includes each and every
point inside the CT’s, where measurement of current
is carried out.
• This type of scheme is widely used in generators,
transformers, and induction motors. e.g. Differential
protection
Non- Unit Protection
• A scheme that achieves protection using successive
grading of relays is known as non unit protection
scheme.
e.g. Over current and distance relays
Relay Backup
In relay backup, the separate or duplicate primary relays, CTs,
PTs, all are there. So, if any one relay fails, then the other
relay will provide backup. However, this type of scheme is not
used in actual practice because we need to require all the
relays, CTs, PTs doubled than the actual requirement, which
increases the cost.
Breaker Backup
In breaker backup scheme, whenever a fault occurs on a
feeder, on which the breaker is installed and if that feeder
breaker fails to operate, then that fault virtually becomes the
bus bar fault. So in this case, a time delay relay is operated by
the main relay due to which all the breakers emanating from
the bus bar that is installed on all the feeders, those are going
to trip if the main breaker fails to operate in this situation.
Remote Backup
In this scheme, the backup is achieved by the bus
located towards source end. So any relay located near
the load end, if that relay fails to operate for fault in
its own job, then the other relay which is located
towards the next bus, towards the source, that relay
will act as a backup and that will be taken care, fault
will be taken care by that relay. So, this is all about
the primary and the backup scheme of the protective
system.
Tripping mechanism of relay