The document is a home inspection report by Kirwynd Real Estate Services detailing findings from an inspection conducted on January 23, 2018. It outlines various deficiencies categorized into Maintenance Items, Recommendations, and Significant Defects across different areas of the property, including HVAC, plumbing, electrical, and roofing. The report emphasizes the importance of addressing these issues to ensure the safety and functionality of the home.

Uploaded by

epic4111
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
2 views

Sample Report!! 2

The document is a home inspection report by Kirwynd Real Estate Services detailing findings from an inspection conducted on January 23, 2018. It outlines various deficiencies categorized into Maintenance Items, Recommendations, and Significant Defects across different areas of the property, including HVAC, plumbing, electrical, and roofing. The report emphasizes the importance of addressing these issues to ensure the safety and functionality of the home.

Uploaded by

epic4111
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 45

KIRWYND REAL ESTATE SERVICES

902-848-1033
[email protected]
http://www.kirwynd.com

DEFAULT TEMPLATE
1234 Main St.
South Farmington NS B0P1W0
Buyer Name
01/23/2018 9:00AM

Inspector Agent
Wayne Thurber Agent Name
Certified Master Inspector 555-555-5555
902-848-1033 [email protected]
[email protected]
1234 Main St. Buyer Name

Table of Contents

Table of Contents 2
SUMMARY 4
1: EXTERIOR 6
2: ROOFING 11
3: GARAGE 16
4: STRUCTURE 19
5: ATTIC AND INSULATION 22
6: INTERIOR 24
7: BATHROOMS 28
8: APPLIANCES 30
9: HVAC 34
10: ELECTRICAL 38
11: PLUMBING 43

Kirwynd Real Estate Services Page 2 of 45


1234 Main St. Buyer Name

SCOPE OF THE INSPECTION:


Kirwynd Real Estate Services endeavours to perform all inspections in substantial compliance with the
Standards of Practice of the International Association of Certified Home Inspectors (InterNACHI). As such, we
inspect the readily accessible, visually observable, installed systems and components of a home as designated
in the InterNACHI Standards of Practice. When systems or components designated in the InterNACHI
Standards of Practice are present but are not inspected, the reason(s) the item was not inspected is identified
within the “Limitations” tab of this report. This report contains observations of those systems and
components that, in the professional judgement of the inspector, are not functioning properly, significantly
deficient, unsafe, or are near the end of their service lives. If the cause for the deficiency is not readily
apparent, the suspected cause or reason why the system or component is at or near end of expected service
life is reported, and recommendations for correction or monitoring are made as appropriate.

USE OF PHOTOS:
Your report includes many photographs. Some pictures are informational and of a general view, to help you
understand where the inspector has been, what was looked at and the condition of the item or area at the
time of the inspection. Some of the pictures may be of problem areas, these are to help you better
understand what is documented in this report and to help you see areas or items that you normally would not
see. Not all problem areas or conditions will be supported with photos.

CATEGORIES:
This report divides deficiencies into three categories; Maintenance Items (colored in blue), Recommendations
(in orange), and Significant Defects (in red).

MAINTENANCE ITEMS: Include components that were found to be in need of recurring or basic general
maintenance to protect either a the component or the occupants. Also included in this section are items that
were beginning to show signs of wear, but were, in the opinion of the inspector, still functional at the time of
inspection. Typically these items are considered to represent a less significant immediate cost than those
listed in the following two categories.

RECOMMENDATIONS: Include comments of a deficiency, a latent defect or a suggested improvement of a


system which may have appeared functional at the time of inspection, however some benefit may be
achieved by adhering to the recommendation.

SIGNIFICANT DEFECTS: Will denote a brief comment of a significantly deficient component or a condition
which, will require a relatively short term correction and/or expense. These will typically fall into one of the
following four categories:

1. Major defects. An example of this would be a structural failure.


2. Things that may lead to major defects, such as a small roof-flashing leak, for example.
3. Things that may hinder your ability to finance, legally occupy, or insure the home
4. Safety hazards, such as an exposed, live buss bar at the electrical panel.

Anything in these categories should be addressed. Often, a serious problem can be corrected inexpensively
to protect both life and property (especially in categories 2 and 4).

This categorization is the opinion of the inspector and is based on what was observed at the time of
inspection. It is not intended to imply that items documented in any one category are not in need of
correction. Maintenance items or latent defects left unrepaired can soon become significant defects. It should
be considered very likely there will be other issues you personally may consider deficient, and you should
add these as desired. There may also be defects that you feel belong in a different category, and again, you
should feel free to consider the importance you believe they hold and act accordingly.

Please review the report in its entirety. It is ultimately up to your discretion to interpret its findings and to act
accordingly. This report does not offer an opinion as to whom among the parties to this transaction should
take responsibility for addressing any of these concerns. As with all aspects of your transaction, you should
consult with your Realtor® for further advice regarding the contents of this report. Any repairs should be
performed by the applicable licensed and bonded tradesman or qualified professional who will provide
copies of all receipts, warranties and applicable permits for any repairs that are carried out.

Kirwynd Real Estate Services Page 3 of 45


1234 Main St. Buyer Name

SUMMARY

☐ HVAC - Propane Supply: Gas Line Bonding


☐ HVAC - Air Exchanger: Clean Filters
☐ HVAC - Air Exchanger: The condensate drain of the HRV should be looped in order to properly form a
trap seal
☐ HVAC - Heating System: Discharge Tube Too Short
☐ HVAC - Heating System: Have Unit Serviced
☐ Appliances - Dishwasher: No High Loop
☐ Appliances - Ranges, Ovens, Cooktops: Burner Inoperable
☐ Garage - Garage Door Opener(s): Inoperable Safety Reverse
☐ Garage - Garage Door(s): Rust
☐ Garage - Exterior: Deteriorated Block
☐ Garage - Exterior: Low Area
☐ Garage - Exterior: Protect Material Changes
☐ Garage - Exterior: Add Extensions
☐ Plumbing - Water Heater: Past Design Life
☐ Plumbing - Water Heater: TPR Tubing Too Short
☐ Plumbing - Fixtures: Winterized
☐ Electrical - Carbon Monoxide Detectors: No CO Alarms
☐ Electrical - Smoke Detectors: Old Detectors
☐ Electrical - GFCI Protection: Did Not Trip
☐ Electrical - Lighting, Fixtures, Outlets & Switches: Receptacle in Cabinet
☐ Electrical - Lighting, Fixtures, Outlets & Switches: Missing Cover
☐ Electrical - Branch Wiring: Leaking Conduit
☐ Electrical - Sub Panel: Lock Device Cover
☐ Bathrooms - Toilet(s): Loose Toilet
☐ Interior - Walls & Ceilings: Missing Trim
☐ Interior - Stairways and Railings: Missing Handrail
☐ Interior - Doors: Missing Hardware
☐ Interior - Windows: Screens Removed
☐ Interior - Windows: Minor Corrosion
☐ Structure - Foundation: No Capillary Break
☐ Roofing - Roof Covering: Defective Shingles
☐ Roofing - Roof Covering: Lichen Growth
☐ Roofing - Roof Drainage System: Damaged Downspout
☐ Roofing - Roof Drainage System: Clear Debris
☐ Roofing - Roof Drainage System: Leaking at Joints
☐ Exterior - Vegetation Affecting: Siding Contact
☐ Exterior - Window/Door Frames & Trim: Paint Sills
☐ Exterior - Grading & Surface Drainage: Low Area with Basement

Kirwynd Real Estate Services Page 4 of 45


1234 Main St. Buyer Name

☐ Exterior - Stoop, Steps: Wood/Mulch Contact

Kirwynd Real Estate Services Page 5 of 45


1234 Main St. Buyer Name

1: EXTERIOR
Information

Driveway: OK
No deficiencies were observed in the overall condition of the driveway, at the time of the inspection. Inspection
of the driveway typically includes review of the surface condition for any functional defects or safety hazards and
any conditions which may adversely affect the home structure where applicable.

Walkways: OK
No deficiencies were observed in the condition of the home walkways at the time of the inspection.

Stoop, Steps: Mostly OK


At the time of the inspection, few deficiencies were observed in the condition of the verandah. Notable
exceptions will be listed in this report. Inspection of this area typically includes evaluation of the visible
foundation, general structure, attachment to the home, walking surface and stair components.

Stoop, Steps: Mostly OK


At the time of the inspection, few deficiencies were observed in the condition of the front step. Notable
exceptions will be listed in this report. Inspection of this area typically includes evaluation of the visible
foundation, general structure, attachment to the home, walking surface, stair components and applicable
guardrails assemblies.

Kirwynd Real Estate Services Page 6 of 45


1234 Main St. Buyer Name

Stoop, Steps: Moderate Planking Deterioration


Deck planking (the walking surface) had moderate wear or deterioration visible at the time of the inspection.
Routine maintenance will improve its lifespan.

Doors: OK
At the time of the inspection, no deficiencies were observed in the condition of door exteriors. Inspection of door
exteriors typically includes examination of the exterior surface condition, weather-stripping condition, presence
of an effective sweep (sweeps are gaskets which seal the area between the bottom of a door and the threshold),
jamb condition, threshold condition and moisture-intrusion integrity.

Cladding: OK
No deficiencies were observed in the condition of wood shingles covering exterior walls at the time of the
inspection. Inspection of wood shingle wall coverings typically includes visual examination for excessive splitting,
shingle distortion (cupping, curling, etc.), proper installation, missing shingles, damaged shingles, fungal growth
and vegetative growth.

Eaves, Soffit, Fascia & Trim: OK


The homes soffit, fascia and exterior trim were inspected and found to be in serviceable condition. No defects
were observed on the day of inspection.

Kirwynd Real Estate Services Page 7 of 45


1234 Main St. Buyer Name

Window/Door Frames & Trim: OK


At the time of the inspection, no deficiencies were observed in the condition of the window/door frames and
trim.

Grading & Surface Drainage: Mostly OK


The exterior drainage appeared to generally slope away from foundation. Notable exceptions will be listed in this
report.

Limitations

Stoop, Steps
NOT VISIBLE
The deck substructure inspection was excluded due to limited access
because of low height or obstructions.

Kirwynd Real Estate Services Page 8 of 45


1234 Main St. Buyer Name

Limitations
A representative sample of exterior components were inspected rather than every occurrence of
components. When present, seasonal accessories, recreational facilities, outbuildings and fences are not
inspected unless specifically agreed upon and documented in this report. A home inspection does not
include an assessment of geological, geotechnical, or hydrological conditions or environmental hazards.

Recommendations

1.3.1 Stoop, Steps Maintenance Item


WOOD/MULCH CONTACT
SOUTH
Bark mulch was in contact with the wood beam supporting the deck structure. Whether treated or not, it is
important to keep wood free of debris that retains moisture and will cause eventual decay. Recommend
clearing mulch so there is at least 6 of space between wood and mulch or soil below.
Recommendation
Contact a qualified landscaper or gardener.

1.7.1 Window/Door Frames & Trim Maintenance Item


PAINT SILLS
UPPER LEVEL NORTH WINDOWS
As part of routine maintenance, re-staining areas of deteriorated
finish coating at wood window sills is advised to help protect frames
from wood decay resulting from exposure to moisture and sunlight.
All exterior painted wood surfaces should be annually examined and
sealed, re-caulked and re-stained as needed.
Recommendation
Contact a qualified painter.

1.10.1 Grading & Surface Drainage Recommendation


LOW AREA WITH BASEMENT
SOUTHEAST

Kirwynd Real Estate Services Page 9 of 45


1234 Main St. Buyer Name

There were low spots visible near the foundation wall which will
collect water and can increase the potential for foundation seepage.
Recommend filling or re-grading the affected areas as needed in
order to create the proper slope away from the home while
maintaining adequate clearances from the top of the foundation
wall.
Recommendation
Contact a qualified landscaper or gardener.

1.11.1 Vegetation Affecting Maintenance Item


SIDING CONTACT
EAST
Overgrown shrubs were in contact with the structure at the exterior of the home. Vegetation too close to
the structure can potentially cause harm through decay by increasing moisture retention from reducing
light and airflow, damage to screens and siding from branches abrading surfaces and leaves providing a
path for moisture and insects into the home. Shrubs and bushes should maintained at a distance of at
least 18-inches from the structure. In many cases, it may be more practical to relocate shrubs to a different
area or simply remove them.
Recommendation
Contact a qualified landscaper or gardener.

Kirwynd Real Estate Services Page 10 of 45


1234 Main St. Buyer Name

2: ROOFING
Information

Roof Covering: Method of Roof Covering: Approximate Age Roof Penetrations: OK


Inspection 16 Years Roof penetrations appeared
Viewed from Ladder at the Eaves functional and properly flashed.

Chimney: Type
Metal Vent, Insulated Metal
Chimney

Roof Covering: Material


Laminated Fiberglass Asphalt Shingles

Kirwynd Real Estate Services Page 11 of 45


1234 Main St. Buyer Name

Roof Covering: Last Third


The roof covering material appeared to be in the last third of its life cycle. It would be prudent to begin to budget
for replacement of the roof covering. With proper maintenance and spot repairs, the need to replace these
shingles should be expected to arise within the next 3 +/- years.

Flashings: OK
A representative number of areas were checked for flashing. No deficiencies were observed in the condition of
roof flashing.

Chimney: OK
No deficiencies were observed in the condition of the portion of the chimney that extended above the roof.
Inspection of this portion of the chimney includes evaluation of the chimney exterior, cap, spark arrestor, visible
flue, cricket, penetration flashing and counter-flashing and location on the roof.

Roof Drainage System: Mostly OK


The roof drainage system appeared to be in generally serviceable condition at the time of inspection. Notable
exceptions will be listed in this report. Inspection of the roof drainage system typically includes examination of
gutters (condition and configuration), downspouts and extensions (condition and configuration).

Roof Drainage System: Monitor Drainage


There were downspout connected to underground drainage lines. A couple of times a year, check the connection
between the downspouts and the underground pipes in a heavy rain storm to be sure that the water is going into
the pipe and not backing up and overflowing near the house. If backup is noted, the pipe will need to be cleaned
out to remove the obstruction. Basement moisture can often be attributed to the overflow from this type of
drainage system when it becomes clogged. Running strong stream of water from a garden hose can both test the
ability of the water to flow through the system and be of assistance in pushing debris out of inaccessible portions
of the downspouts and sub surface drains.

Kirwynd Real Estate Services Page 12 of 45


1234 Main St. Buyer Name

Limitations

Limitations
ACCESSIBILITY
Roof was visually inspected from accessible points on the interior and/or exterior. If a roof is too high, is
too steep, is wet, is slippery or is composed of materials which can be damaged if walked upon, the roof is
not mounted. Therefore, client is advised that this is a limited review and a qualified roofer should be
contacted if a more detailed report is desired.

Recommendations

2.2.1 Roof Covering Maintenance Item


LICHEN GROWTH
EAST
Portions of the asphalt shingles covering the roof of the home had
lichens growing on them. Lichens are plant-like organisms that may
do long-term, very mild damage to shingles. They are generally
considered to be a cosmetic concern only. Efforts to remove them
may result in granule loss where they were attached to shingles. For
this reason, removal should be performed by qualified professionals.

2.2.2 Roof Covering Significant Defect


DEFECTIVE SHINGLES
Accelerated deterioration of the roof covering material appeared to be the result of a manufacturing
defect. These shingles appeared to be approaching the end of their useful service life, and will require
replacement long before their rated lifespan rating. Some areas appeared to be in need of replacement at
this time (most notably below the south dormer valleys) in order to reduce the risk of damage to the home
that may result from leaking. You are advised to have the roof covering reviewed by a qualified roofing
contractor in order to to determine whether a pro-rated manufacturers warranty may be applicable and
to provide a quote and estimated time line for replacement.
Recommendation
Contact a qualified roofing professional.

Kirwynd Real Estate Services Page 13 of 45


1234 Main St. Buyer Name

2.6.1 Roof Drainage System Maintenance Item


CLEAR DEBRIS
Debris visible in the gutters at the time of the inspection should be
removed to encourage proper drainage. Recommend having the
gutters cleaned now and at least once a year thereafter in order to
ensure proper drainage and to help limit the potential for moisture
back up and ice damming.
Recommendation
Contact a handyman or DIY project

2.6.2 Roof Drainage System Maintenance Item


LEAKING AT JOINTS
NORTHWEST, SOUTHWEST, SOUTHEAST CORNERS
The gutters were leaking at various areas and needed maintenance such as the application of an
appropriate sealant. All work should be performed by a qualified contractor.
Recommendation
Contact a qualified handyman.

Kirwynd Real Estate Services Page 14 of 45


1234 Main St. Buyer Name

2.6.3 Roof Drainage System Recommendation


DAMAGED DOWNSPOUT
NORTHEAST HOUSE, NORTHEAST GARAGE
A downspout designed to discharge roof drainage was damaged or in
disrepair and may limit its ability to function as designed.
Recommend repair to help protect the home structure.
Recommendation
Contact a qualified professional.

Kirwynd Real Estate Services Page 15 of 45


1234 Main St. Buyer Name

3: GARAGE
Information

Garage Floor: OK
At the time of the inspection, no deficiencies were observed in the condition of the garage floor.

Garage Door(s): Mostly OK


At the time of the inspection, few deficiencies were observed in the condition of the overhead vehicle door(s).
Notable exceptions will be listed in this report.

Garage Door Opener(s): OK


The automatic overhead door opener(s) responded appropriately to wall mounted operator controls.

Exterior: Information
Out buildings are not considered to be part of a general home inspection, however as a courtesy, some general
notes have been taken.

Recommendations

3.3.1 Garage Door(s) Recommendation


RUST
ALL FOUR DOORS
Weathered/rusted garage door panels were observed. This is not uncommon for age and location.
Recommend maintenance be performed to help protect the panels from further deterioration.
Recommendation
Contact a qualified painter.

Kirwynd Real Estate Services Page 16 of 45


1234 Main St. Buyer Name

3.4.1 Garage Door Opener(s) Recommendation


INOPERABLE SAFETY REVERSE
NORTH & SOUTH GARAGE DOORS
An automatic-reverse photoelectric sensor at an overhead garage
door was inoperable. Photoelectric sensors are devices installed to
prevent injury by raising the vehicle door if the sensor detects a
VIDEO
person on a position in which they may be injured by the descending
door. Installation of photo sensors in new homes has been required
by building codes since 1993. Correction of this condition is advised.
Recommendation
Contact a qualified garage door contractor.

3.5.1 Exterior Maintenance Item


ADD EXTENSIONS
NORTHEAST, SOUTHEAST
Downspouts discharged roof drainage in close proximity to the
foundation. This condition can result in excessively high moisture
levels in soil at the foundation and can cause damage related to
soil/foundation movement. Recommend the installation of
downspout extensions to discharge roof drainage a minimum of 3
feet from the foundation wall.
Recommendation
Contact a qualified handyman.

3.5.2 Exterior Maintenance Item


DETERIORATED BLOCK
SOUTHWEST
One damaged/deteriorated mounting block was observed.
Replacement of the affected accessory is advised.
Recommendation
Contact a qualified handyman.

Kirwynd Real Estate Services Page 17 of 45


1234 Main St. Buyer Name

3.5.3 Exterior Maintenance Item


LOW AREA
EAST WALL
There were low spots visible near the foundation wall which will
collect moisture. This condition can result in excessively high
moisture levels in soil at the foundation which may cause damage
related to soil/foundation movement. Proper filling and re-grading of
the area to divert water away from the foundation is recommended.
The ground should slope away from the structure a minimum of one-
inch per foot for a distance of at least six feet from the foundation.
Recommendation
Contact a qualified landscaper or gardener.

3.5.4 Exterior Maintenance Item


PROTECT MATERIAL CHANGES
No flashing was installed above exterior mounting blocks as is
required by good building practice, leaving gaps through which
moisture may penetrate the wall assembly or damage exposed end
grain. At minimum, the application of an appropriate sealant is
advised to help prevent moisture intrusion until such a time as the
mounting blocks are replaced in the future. Because sealants will
eventually dry, shrink and crack, all sealant-dependant areas should
be inspected on an annual basis and sealant re-applied as necessary.
Recommendation
Contact a handyman or DIY project

Kirwynd Real Estate Services Page 18 of 45


1234 Main St. Buyer Name

4: STRUCTURE
Information

Foundation: Type Floor Structure: Material Ceiling & Roof Structure: OK


Unfinished Basement I-Joists, Plywood Subfloor No deficiencies were observed
during inspection of the roof
structure.

Foundation: Material
Poured Concrete

Foundation: OK
At the time of the inspection, no deficiencies were observed in the condition of the visible portions of the
foundation.

Foundation: No Visible Leaking


No leaks were observed during the course of the inspection. Although no active moisture penetration was noted,
it is advised that you consider any basement as wet until experience proves it dry.

Foundation Floor: OK
At the time of the inspection, no deficiencies were observed in the condition of the visible portions of the
concrete floor slab. All concrete floor slabs are expected to experience some degree of cracking due to shrinkage
in the drying process.

Kirwynd Real Estate Services Page 19 of 45


1234 Main St. Buyer Name

Floor Structure: OK
At the time of the inspection, no deficiencies were observed in the condition of the visible floor structure.
Inspection of the floor structure typically includes examination of the condition and proper installation of the
floor joists, joist supporting structures and members, connections and fasteners and the floor sheathing.

Ceiling & Roof Structure: Material


I-Joist, Plywood Sheathing, Common Rafters, Dimensional Lumber

Limitations

Wall Structure
NOT VISIBLE
The exterior wall structure was not visible to inspect. The general home inspection does not include
evaluation of structural components hidden behind finishing materials, but is visual and non-invasive only.

Limitations
A representative sample of the visible structural components were inspected. Full inspection of all
structural components (posts/girders, foundation walls, sub flooring, and/or framing) is not possible in
areas/rooms where there are finished walls, ceilings and floors. Engineering or architectural services such
as calculation of structural capacities, adequacy, or integrity are not part of a home inspection.

Recommendations

4.1.1 Foundation Maintenance Item


NO CAPILLARY BREAK
SMALL AREA AT STAIRWELL LANDING
Insulation in the basement was improperly installed in contact with the exterior foundation wall without
the use of a moisture barrier or capillary break. In certain cases, this can allow moisture to transfer from
the cool/damp foundation walls to the insulation, increasing the potential for moisture damage and
microbe growth within the wall cavity. You should discuss this condition with a qualified carpenter, prior to
further finishing walls in the basement, in order to determine whether correction is justified.
Recommendation
Contact a qualified handyman.

Kirwynd Real Estate Services Page 20 of 45


1234 Main St. Buyer Name

Kirwynd Real Estate Services Page 21 of 45


1234 Main St. Buyer Name

5: ATTIC AND INSULATION


Information

Access: Method of Inspection Insulation: Insulation Depth Insulation: R-Value


Walked Accessible Areas 10 to 12 Inches 36 ±

Ventilation: Source
Soffit Inlet Vents, Ridge Exhaust
Venting

Access: Attic Maintenance


All attic areas should be reviewed at least twice per year to ensure ventilation openings are clear and to ensure
development of mould is kept in check. While there may be very little or no evidence of mould build-up in the
attic at time of inspection, it can reproduce and spread rapidly should conditions allow it to. Mould can be
potentially hazardous and will spread when moisture enters the attic cavity and is not vented to the exterior. Any
area of suspected mould should be reviewed by a qualified contractor for analysis and removal.

Access: Insulated Hatch


The attic access appeared functional with an insulated hatch cover installed.

Insulation: Energy Efficiency


In the average home, 50 to 70% of the total energy used is for heating and cooling. In Nova Scotia we have a
"heating climate" . Most of our energy is used for heating in the winter and therefore adequate insulation of the
building envelope is very important to minimizing energy costs. The minimum recommended "R-value" for newly
constructed homes in our province is R-49.2. While it is highly unlikely that older homes will achieve this level of
efficiency; it is intended to be used as a reference point in order to help determine whether insulation
improvements should be considered in your specific situation.

Insulation: Material
Blown-in Cellulose

Ventilation: OK
There were no signs of adverse conditions resulting from inadequate ventilation observed within the attic
space on the day of inspection.

Kirwynd Real Estate Services Page 22 of 45


1234 Main St. Buyer Name

Vent Piping: OK
No deficiencies were observed in the condition of the visible portions of the vent piping throughout the attic
space.

Kirwynd Real Estate Services Page 23 of 45


1234 Main St. Buyer Name

6: INTERIOR
Information

Door Bell: OK
The doorbell operated normally
when tested.

Floor Surfaces: OK
At the time of the inspection, no deficiencies were observed in the condition of floors in the home. Cosmetic
defects are not noted except where a functional concern exists.

Walls & Ceilings: OK


At the time of inspection, no deficiencies were observed in the condition of the interior walls and
ceilings. Inspection of the walls and ceilings typically includes examination for functional defects in the wall and
ceiling coverings, window and door casings, baseboards and other installed mouldings.

Doors: Mostly OK
At the time of the inspection, few deficiencies were observed in the condition or operation of the interior doors.
Notable exceptions will be listed in this report.

Stairways and Railings: Mostly OK


Few deficiencies were observed in the condition of interior stairs. Notable exceptions will be listed in this report.
Inspection of staircases typically includes a visual examination of the treads and risers, landings, the angle of the
staircase, handrails, guardrails, lighting, headroom and windows.

Cabinets & Vanities: OK


At the time of the inspection, no deficiencies were observed in the condition of the kitchen and bathroom
cabinets. Inspection of installed cabinetry typically includes inspection of installation hardware, door and drawer
operation, hardware function and countertops. Areas of cosmetic damage are not noted.

Kirwynd Real Estate Services Page 24 of 45


1234 Main St. Buyer Name

Limitations

Limitations
INTERIOR
Assessing the quality and condition of interior finishes is highly subjective. Issues such as cleanliness,
cosmetic flaws, quality of materials, architectural appeal and color are outside the scope of this inspection.
Comments will be general, except where functional concerns exist. Furniture, area rugs, storage,
appliances and/or wall hangings are not moved to permit inspection and may block defects. Carpeting,
window treatments, central vacuum systems, household appliances, screening, recreational facilities, paint,
wallpaper, and other finish treatments are not inspected unless otherwise noted in this report.
Recommend thorough review of interior areas during final walk-through inspection prior to closing.

Recommendations

6.3.1 Walls & Ceilings Maintenance Item


MISSING TRIM
BASEMENT LANDING
Missing trim was noted at a finished area of the home. Replace
missing trim as desired to improve appearance.
Recommendation
Contact a qualified handyman.

Kirwynd Real Estate Services Page 25 of 45


1234 Main St. Buyer Name

6.4.1 Doors Maintenance Item


MISSING HARDWARE
SOUTHEAST MAIN LEVEL BEDROOM
There were doors that had missing hardware needed for the door to
properly latch. You should have appropriate hardware installed.
Recommendation
Contact a handyman or DIY project

6.5.1 Windows Maintenance Item


SCREENS REMOVED
There were screens missing from the majority of windows
throughout the home. A large group of screens were located in
storage. You should ask to have the screens installed for the pre-
closing walk-through. This allows the opportunity to verify screens
were present at all of the windows, that they fit properly, and were all
in acceptable condition.

Kirwynd Real Estate Services Page 26 of 45


1234 Main St. Buyer Name

6.5.2 Windows Maintenance Item


MINOR CORROSION
NORTH
As is typical of homes with significant exposure to salt air. A small
area of rust staining was visible at metal window operator hardware.
Keeping these components well lubricated will help to extend their
useful lifespan and resist deterioration.
Recommendation
Recommended DIY Project

6.6.1 Stairways and Railings Recommendation


MISSING HANDRAIL
BASEMENT
Although a staircase had more than two risers, no handrail was
installed. Recommend a handrail be installed to comply with modern
safety standards.
Recommendation
Contact a qualified carpenter.

Kirwynd Real Estate Services Page 27 of 45


1234 Main St. Buyer Name

7: BATHROOMS
Information

Tub(s): OK
At the time of the inspection, no deficiencies were observed in the condition of bathtub components. Inspection
of the tub includes testing for functional flow, functional drainage and operational shut-off valves, faucet, and
diverter valve.

Shower(s): OK
All shower components appeared to be in serviceable condition at the time of the inspection. Inspection of the
shower typically includes evaluation of functional flow, functional drainage, proper operation of shut-off, diverter
valves and faucet; and moisture intrusion of walls and pan.

Toilet(s): OK
All toilet components operated in a manner consistent with their intended use, on the day of inspection.

Ventilation: OK
All bathrooms had an operable source of ventilation at the time of the inspection.

Kirwynd Real Estate Services Page 28 of 45


1234 Main St. Buyer Name

A Word About Caulking: Maintain Caulking


Water intrusion from bathtubs and shower enclosures is a common cause of damage behind walls, sub floors
and ceilings below bathrooms. As such, periodic re-caulking of shower areas, the tub lip, tub spouts and faucet
trim plates is an ongoing maintenance task which should not be neglected

Recommendations

7.3.1 Toilet(s) Recommendation


LOOSE TOILET
NORTH BATHROOM
A loose toilet was observed. The wax ring seal inside the unit must
have a snug, secure fit in order to keep from leaking. Properly
resealing and re-securing this toilet is advised to prevent water
VIDEO
leakage and damage to the sub-flooring beneath the fixture. Repairs
may involve re-setting the toilet on a new wax seal.
Recommendation
Contact a qualified plumbing contractor.

Kirwynd Real Estate Services Page 29 of 45


1234 Main St. Buyer Name

8: APPLIANCES
Information

Kitchen Ventilation: Source


Range Hood, Vented to Exterior

Dishwasher: OK
The dishwasher was operated through one cycle and appeared to be in working order at time of inspection.

Ranges, Ovens, Cooktops: Oven OK


The oven operated when tested. Inspection of ranges is limited to basic functions, such as testing of the
bake/broil features of the oven. Self-cleaning and convection features (if present) were not tested.

Kitchen Ventilation: OK
The over the range fan and lights functioned and operated normally when tested.

Microwave: OK
No deficiencies were observed in the condition or operation of the built-in microwave oven. The unit was tested
and appeared to be serviceable at time of inspection. Built-in microwave ovens are tested using normal operating
controls. Microwave leak and/or efficiency testing is beyond the scope of this inspection. If concerned, you should
seek further evaluation by qualified appliance technician.

Kirwynd Real Estate Services Page 30 of 45


1234 Main St. Buyer Name

Refrigerator: OK
The refrigerator was operational, at time of inspection. The efficiency of the appliance was not tested.

Central Vac: OK
The central vac blower operated when powered. Hoses, accessories and ports are not inspected as part of a
general home inspection. Ensure all accessories are present and functional at your final walk-through, if included
as part of your purchasing agreement.

Limitations

Dryer Vent
NOT VISIBLE
The transition ducting behind the dryer was not visible to inspect. It
should be verified that it meets UL2158A standard and the pipe to its
termination be properly cleaned.

Kirwynd Real Estate Services Page 31 of 45


1234 Main St. Buyer Name

Limitations
APPLIANCES
Appliances are checked for general functionality by turning them on for a short period of time using basic
operating modes. Thermostats, timers, clocks, self-cleaning features and other specialized functions are
not tested during this inspection. Appliances are not inspected for cosmetic flaws, performance or the
ability/accuracy of heating, cooling, etc. They are not inspected to ascertain whether the proper racks
and/or accessories are present or in working order. Laundry appliances (and other portable appliances)
are not moved and are outside the scope of this inspection; any comments are included for information
purposes only. Water supply valves are not operated for liability reasons. It is further recommended that
appliances be operated once again during the final walk through inspection prior to closing. Finally,
product recalls and consumer product safety alerts occur almost daily. To best address your specific
concerns, visit www.cpsc.gov or www.recalls.gov. Items, brand names, and model numbers will be required
for proper identification.

Recommendations

8.1.1 Dishwasher Maintenance Item


NO HIGH LOOP
The dishwasher had no high loop installed in the drain line at the time of the inspection. The high loop is
designed to prevent wastewater from contaminating the dishwasher. Recommend having the drain
properly secured to the underside of the counter top.
Recommendation
Contact a handyman or DIY project

Kirwynd Real Estate Services Page 32 of 45


1234 Main St. Buyer Name

8.3.1 Ranges, Ovens, Cooktops Recommendation


BURNER INOPERABLE
There were that burners did not operate properly when tested.
Recommend repair by a qualified appliance technician.
Recommendation
Contact a qualified appliance repair professional.
VIDEO

Kirwynd Real Estate Services Page 33 of 45


1234 Main St. Buyer Name

9: HVAC
Information

Propane Supply: Location of Fuel Propane Supply: Fuel Thermostat(s): Location


Shut-off Distribution Entrance, Each Bedroom With a
At the Tank, At the Appliance Copper, Corrugated Stainless Heater, Livingroom, Bathroom(s)
Steel Tubing (CSST), Black Steel

Heating System: Primary Heating System: Rated Output Heating System: Year of
Heating Source Capacity Manufacture
Electric Boiler, Electric Baseboard 68000 BTU 2011
Heaters

Air Exchanger: OK
The air exchanger operated
using normal controls at the time
of inspection.

Propane Supply: Information


Evaluation of propane tanks lies beyond the scope of the general Home Inspection. The propane tanks can be
evaluated by the contractor supplying the home with propane.

Heating System: Electric Boiler Mostly OK


At the time of the inspection, few deficiencies were observed in the condition and operation of the boiler.
Notable exceptions will be listed in this report. Inspection of the boiler typically includes examination of the
cabinet interior and exterior, circulation pumps, the pressure relief valve and overflow pipe, fluid temperature
and pressure, general component condition and response to the thermostat(s).

Heating Distribution: Method of Distribution


In Slab Piping, In Joist Piping, Baseboard Heaters

Solid Fuel Heating: Wood Stove


Living Room
The home contained a wood stove, the inspection of which lies beyond the scope of the General Home
Inspection. For a full inspection to more accurately determine the condition of the fireplace and to ensure that
safe conditions exist, it is advised that you have the fireplace inspected by a WETT certified technician Find a
WETT-certified inspector near you at https://www.wettinc.ca/search.cfm

Kirwynd Real Estate Services Page 34 of 45


1234 Main St. Buyer Name

Gas Fireplace(s): OK
Master Bedroom
At the time of the inspection, no deficiencies were observed in the condition of the propane-fueled fireplace.

Limitations

Limitations
HEATING
Adequacy, efficiency, or the balanced distribution of air throughout the home are not performed as part of
a home inspection. These calculations are typically performed by designers to determine the required size
of HVAC systems.

Recommendations

9.1.1 Propane Supply Recommendation


GAS LINE BONDING

Kirwynd Real Estate Services Page 35 of 45


1234 Main St. Buyer Name

There was no "visible" bonding of the propane supply line. Any metal components which may become
energized are required to be bonded to the grounding system. Recommend correction by a licensed
electrician.
Recommendation
Contact a qualified electrical contractor.

9.3.1 Heating System Recommendation


DISCHARGE TUBE TOO SHORT
The temperature pressure relief valve's discharge tube was too short. This safety valve releases water (and
thus relieves pressure) if either the temp or pressure in the tank gets too high. The TPR valve discharge
tube must terminate within 6" above the floor in order to ensure any potential blow-off is directed away
from occupants. Recommend extending TPR discharge tube with 3/4" copper pipe to within 6" off the floor.
Recommendation
Contact a qualified plumbing contractor.

9.3.2 Heating System Recommendation


HAVE UNIT SERVICED
Evidence of a past over temperature or pressure event was evident by staining on the basement floor
below the TPRV discharge tube, while this may have occurred during the life of the previous boiler, a
bucket below the tube indicates some leaking may still occur and may need to be addressed. Signs of past
leaking and corrosion were also noted at the air vent and and one fitting. It is advised that the boiler and
associated components/fittings be reviewed, serviced and repaired as necessary as part of good
maintenance practices to help prevent the potential for damage from leaking.
Recommendation
Contact a qualified plumbing contractor.

Kirwynd Real Estate Services Page 36 of 45


1234 Main St. Buyer Name

9.6.1 Air Exchanger Maintenance Item


THE CONDENSATE DRAIN OF THE HRV SHOULD BE LOOPED IN
ORDER TO PROPERLY FORM A TRAP SEAL
Recommendation
Recommended DIY Project

9.6.2 Air Exchanger Maintenance Item


CLEAN FILTERS
The air exchanger filters were in need of cleaning in order to
guarantee efficient operation of the ventilation system. Recommend
inspection and cleaning of these filters with every change of season.
Recommendation
Contact a handyman or DIY project

Kirwynd Real Estate Services Page 37 of 45


1234 Main St. Buyer Name

10: ELECTRICAL
Information

Service Equipment: Service Service Equipment: Main Service Equipment: Over


Entrance Cables Disconnect Rating Current Protection
Not Visible 200 Amp Breakers

Sub Panel: Rating Sub Panel: Over Current Branch Wiring: Wire Sheathing
100 Amps Protection Nylon Jacket PVC Insulated Non-
Breakers Metallic Sheathed Cable "Romex"

Branch Wiring: Conductor GFCI Protection: Locations Smoke Detectors: Locations


Material Exterior, Bathroom(s) Main Level, Upper Level,
Copper, Multi-Strand Aluminum Basement
(OK)

Service Drop: OK
At the time of the inspection, the Inspector observed no deficiencies in the condition of the service drop.
Components inspected included the service conductors, splice, drip loop, and point of attachment to the home.

Service Equipment: OK
No deficiencies were observed at the electrical service panel at the time of the inspection. Inspection of the main
service panel typically includes examination of the panel interior and exterior condition, panel amperage rating,
main disconnect amperage rating and condition, main conductor amperage ratings, branch conductor types,
amperage rating and condition, visible wiring materials types, condition and connections, circuit breaker types,
amperage ratings and condition, label information, service and equipment grounding and bonding of service
equipment.

Kirwynd Real Estate Services Page 38 of 45


1234 Main St. Buyer Name

Sub Panel: OK
No deficiencies were observed at the electrical service panel at the time of the inspection. Inspection of the main
service panel typically includes examination of the panel interior and exterior condition, panel amperage rating,
main disconnect amperage rating and condition, main conductor amperage ratings, branch conductor types,
amperage rating and condition, visible wiring materials types, condition and connections, circuit breaker types,
amperage ratings and condition, label information, service and equipment grounding and bonding of service
equipment.

Branch Wiring: Mostly OK


At the time of the inspection, few deficiencies were observed in the condition of the visible branch wiring.
Notable exceptions will be listed in this report. Home branch circuit wiring consists of wiring distributing
electricity to devices such as switches, receptacles, and appliances. Most conductors are hidden behind floor, wall
and ceiling coverings and cannot be evaluated. Cover plates are not removed, limiting the inspection to wiring
visible in unfinished areas, within the electric panel and by proper response to testing of switches and a
representative number of electrical receptacles.

Lighting, Fixtures, Outlets & Switches: Mostly OK


At the time of the inspection, few deficiencies were observed in the condition or operation of electrical
receptacles, switches and light fixtures. Notable exceptions will be listed in this report. In accordance with the
Standards of Practice, a representative number of accessible outlets were tested.

GFCI Protection: Information


A Ground Fault Circuit Interrupter (GFCI) is an electrical safety device that cuts power to the individual outlet
and/or entire circuit when as little as .005 amps is detected leaking; this is faster than a person's nervous system
can react! At minimum; bathrooms, whirlpools, exterior circuits, hot-tubs and pools need to be GFCI protected. In
addition, homes constructed or substantially renovated after 2005 have been required to have GFCI protection at
receptacles located within 5' of all water sources (ie. kitchen and laundry room sinks). At the time this house was
built, the latter may not have been required protection. Nonetheless, you should consider adding GFCI protection
to these locations as a preventative safety measure against electrical shock. All GFCI protected devices should be
tested monthly using the "Test" button to ensure proper operation.

Kirwynd Real Estate Services Page 39 of 45


1234 Main St. Buyer Name

GFCI Protection: Mostly OK


Some areas of installed ground fault circuit interrupter (GFCI) protection responded to testing in a satisfactory
manner at the time of the inspection. Notable exceptions found will be listed in this report.

Smoke Detectors: OK
Smoke detector placement appeared to be adequate. Smoke detectors are not tested as part of a general home
inspection. Recommend all detectors be checked upon occupancy to confirm batteries and alarm are
operational.

Carbon Monoxide Detectors: Information


Carbon monoxide is a colorless, odorless toxic gas produced by fuel-fired appliances during the combustion
process. This gas is especially dangerous because its presence can only be detected by specialized instruments.
You can't see it or smell it. Inefficient combustion, such as that caused by automobiles, furnaces, boilers or wood
stoves with components that are dirty or out of adjustment can create elevated levels of carbon monoxide in
exhaust gasses. Carbon monoxide can cause sickness, debilitating injury, and even death. Electronic detectors
are inexpensive, and under current standards, should be installed in homes in which fuel-fired appliances are
installed and in homes with an attached garage. Detectors should not be placed next to heating appliances like
furnaces and boilers, but should be placed in the immediate vicinity of the bedrooms to protect living and
sleeping areas. Choose carbon monoxide detectors that are certified by the Canadian Standards Association
(CSA) or the Underwriters Laboratories of Canada (ULC). Read the installation manual for each detector for
placement and maintenance directions. Consult Health Canada for further specifics.

Limitations

Limitations
ELECTRICAL
Load calculation are not performed to determine service capacity adequacy. The inspection does not
involve any electrical stress tests on the system to determine if a breaker trips properly. Labeling of electric
circuit locations on electrical panel are not checked for accuracy. Electrical components concealed behind
finished surfaces are not visible to be inspected. Determination of the type of branch circuit wiring used in
this home was made by inspection of the electric panels only. Inspection of the wiring in or at the
receptacles, switches, fixtures, junction boxes, walls, ceiling, floors, etc., is beyond the scope of a home
inspection and were not inspected. The inspection does not include remote control devices, alarm systems
and components, low voltage wiring, systems, and components, ancillary wiring, systems, and other
components which are not part of the primary electrical power distribution system.

Limitations
SECURITY SYSTEM
Due to the specialized nature of home security alarm systems, recommend you review this system with the
seller. Security systems are beyond the scope of a home inspection.

Recommendations

10.3.1 Sub Panel Significant Defect


LOCK DEVICE COVER
Although not a requirement of the Canadian Electrical Code; using a
zip tie to lock the access cover to the gutter containing the main
panel and sub panel feeders is advised in order to reduce the
potential for children to access to these high ampacity, exposed
terminations.
Recommendation
Recommended DIY Project

Kirwynd Real Estate Services Page 40 of 45


1234 Main St. Buyer Name

10.4.1 Branch Wiring Recommendation


LEAKING CONDUIT
The conduit through which the feeders powering the electric service
panel were housed, has filled with water and began leaking into the
basement interior. Recommend repair as necessary to help prevent
the potential for damage to the home or its contents which may arise
from moisture intrusion.
Recommendation
Contact a qualified electrical contractor.

10.5.1 Lighting, Fixtures, Outlets & Switches Maintenance Item


MISSING COVER
BASEMENT
Missing outlet cover plates were observed. This condition leaves
energized electrical components exposed to touch, creating a
potential shock hazard. Recommend all cover plates be installed for
personal safety.
Recommendation
Recommended DIY Project

10.5.2 Lighting, Fixtures, Outlets & Switches Recommendation


RECEPTACLE IN CABINET
SOUTHEAST LIVING ROOM
A receptacle was located within a cabinet. This is typically not an
approved installation, unless it is intended to serve a specific
appliance which is intended for such an application. You should
consider properly terminating the receptacle if this is not the case.
Recommendation
Contact a qualified electrical contractor.

10.6.1 GFCI Protection Significant Defect


DID NOT TRIP
EXTERIOR NORTH WALL, NORTH GARAGE WALL
There were receptacles installed at wet locations that did not
properly respond to trip testing. There is the potential for a shock

Kirwynd Real Estate Services Page 41 of 45


1234 Main St. Buyer Name

hazard from unprotected receptacles at wet locations. Recommend


correction by a licensed electrician.
Recommendation
Contact a qualified electrical contractor.

10.8.1 Smoke Detectors Maintenance Item


OLD DETECTORS
ALL LEVELS
There were smoke detectors which were older and may not be
functional. Although testing of smoke detectors lies beyond the
scope of the General Home Inspection, it is recommended that you
have any older smoke detectors tested and maintained, upgraded or
replaced as needed.
Recommendation
Recommended DIY Project

10.9.1 Carbon Monoxide Detectors Recommendation


NO CO ALARMS
There were no visible carbon monoxide detectors in the home. At a minimum, put an alarm within 15-feet
of the entrance to bedrooms in your home.
Recommendation
Recommended DIY Project

Kirwynd Real Estate Services Page 42 of 45


1234 Main St. Buyer Name

11: PLUMBING
Information

Water Supply: Water Source Water Supply: Service Piping Water Supply: Shut-Off Location
Private Water Supply Material Basement
Acrylonitrile-Butadiene-Styrene
(ABS)

Distribution Piping: Material Drain, Waste & Vent Piping: Sewage Disposal: System
Cross-Linked Polyethylene (PEX) Material Private Onsite Wastewater
Acrylonitrile-Butadiene-Styrene Handling
(ABS)

Water Heater: Description Water Heater: Date of Water Heater: Water heaters
Electric, 60 Gal Manufacture have a typical life expectancy of
2001 11
15 years.

Water Heater: Operational


The water heater was
operational at the time of
inspection.

Water Supply: OK
At the time of the inspection, no deficiencies were observed in the condition of the visible portion of main water
supply line or shut-off valve. The valve was not operated due to the potential for leakage but was visually
inspected.

Distribution Piping: OK
On the day of inspection, no deficiencies were observed in the condition of the visible water distribution pipes.

Water Flow & Pressure: OK


The water supply exhibited functional flow at the time of the inspection. This was determined by running water at
the bathroom sink and shower while the toilet was flushed.

Kirwynd Real Estate Services Page 43 of 45


1234 Main St. Buyer Name

Fixtures: OK
The sinks were visually inspected and faucet valves operated with no deficiencies observed at the time of
inspection.

Drain, Waste & Vent Piping: OK


At the time of the inspection, no deficiencies in the condition of the visible drain, waste and vent pipes.

Limitations

Sewage Disposal
SEPTIC SYSTEM
This inspection did not access the septic tank. Evaluation of the septic sewage system is beyond the scope
of a home inspection. Septic tanks should be pumped a minimum of every five (5) years. Recommend tank
be pumped, by a licensed septic company, if it has not been done within the last year.

Limitations
Water quantity and water quality are not tested unless explicitly contracted for and discussed in this or a
separate report. The sections of the plumbing system concealed by finishes and/or storage (below sinks,
etc.), below the structure, or beneath the ground surface are not inspected. Overflow backup is not tested
due to the possibility of damage from water leakage. This is necessary due to the fact that that aged
gaskets may fail and leak.

Recommendations

11.4.1 Fixtures Maintenance Item


WINTERIZED
WEST EXTERIOR
An exterior hose bib was turned off at an interior shut-off and was
not able to be tested. You should have the shut off valve turned on
and test for to ensure it is functioning.

11.8.1 Water Heater Recommendation


PAST DESIGN LIFE
The water heater was past its typically expected life span. Some
corrosion was observed within the unit near the element. As water
heaters may fail at any time, and often without any warning, it is
advised that the water heater be replaced at this time, prior to it's
failure. The client should be aware that significant flooding can occur
if the water heater fails. If replacement is put aside until a later time,
it is recommended that a catch pan with drain, or a water alarm be
installed by a qualified person to help prevent damage in the case of
water leaks.
Recommendation

Kirwynd Real Estate Services Page 44 of 45


1234 Main St. Buyer Name

Contact a qualified plumbing contractor.

11.8.2 Water Heater Recommendation


TPR TUBING TOO SHORT
Recommend extending TPR discharge tube with 3/4" copper pipe to
within 6" off the floor.
Recommendation
Contact a qualified plumbing contractor.

Kirwynd Real Estate Services Page 45 of 45