Sample Report!! 2
Sample Report!! 2
902-848-1033
[email protected]
http://www.kirwynd.com
DEFAULT TEMPLATE
1234 Main St.
South Farmington NS B0P1W0
Buyer Name
01/23/2018 9:00AM
Inspector Agent
Wayne Thurber Agent Name
Certified Master Inspector 555-555-5555
902-848-1033 [email protected]
[email protected]
1234 Main St. Buyer Name
Table of Contents
Table of Contents 2
SUMMARY 4
1: EXTERIOR 6
2: ROOFING 11
3: GARAGE 16
4: STRUCTURE 19
5: ATTIC AND INSULATION 22
6: INTERIOR 24
7: BATHROOMS 28
8: APPLIANCES 30
9: HVAC 34
10: ELECTRICAL 38
11: PLUMBING 43
USE OF PHOTOS:
Your report includes many photographs. Some pictures are informational and of a general view, to help you
understand where the inspector has been, what was looked at and the condition of the item or area at the
time of the inspection. Some of the pictures may be of problem areas, these are to help you better
understand what is documented in this report and to help you see areas or items that you normally would not
see. Not all problem areas or conditions will be supported with photos.
CATEGORIES:
This report divides deficiencies into three categories; Maintenance Items (colored in blue), Recommendations
(in orange), and Significant Defects (in red).
MAINTENANCE ITEMS: Include components that were found to be in need of recurring or basic general
maintenance to protect either a the component or the occupants. Also included in this section are items that
were beginning to show signs of wear, but were, in the opinion of the inspector, still functional at the time of
inspection. Typically these items are considered to represent a less significant immediate cost than those
listed in the following two categories.
SIGNIFICANT DEFECTS: Will denote a brief comment of a significantly deficient component or a condition
which, will require a relatively short term correction and/or expense. These will typically fall into one of the
following four categories:
Anything in these categories should be addressed. Often, a serious problem can be corrected inexpensively
to protect both life and property (especially in categories 2 and 4).
This categorization is the opinion of the inspector and is based on what was observed at the time of
inspection. It is not intended to imply that items documented in any one category are not in need of
correction. Maintenance items or latent defects left unrepaired can soon become significant defects. It should
be considered very likely there will be other issues you personally may consider deficient, and you should
add these as desired. There may also be defects that you feel belong in a different category, and again, you
should feel free to consider the importance you believe they hold and act accordingly.
Please review the report in its entirety. It is ultimately up to your discretion to interpret its findings and to act
accordingly. This report does not offer an opinion as to whom among the parties to this transaction should
take responsibility for addressing any of these concerns. As with all aspects of your transaction, you should
consult with your Realtor® for further advice regarding the contents of this report. Any repairs should be
performed by the applicable licensed and bonded tradesman or qualified professional who will provide
copies of all receipts, warranties and applicable permits for any repairs that are carried out.
SUMMARY
1: EXTERIOR
Information
Driveway: OK
No deficiencies were observed in the overall condition of the driveway, at the time of the inspection. Inspection
of the driveway typically includes review of the surface condition for any functional defects or safety hazards and
any conditions which may adversely affect the home structure where applicable.
Walkways: OK
No deficiencies were observed in the condition of the home walkways at the time of the inspection.
Doors: OK
At the time of the inspection, no deficiencies were observed in the condition of door exteriors. Inspection of door
exteriors typically includes examination of the exterior surface condition, weather-stripping condition, presence
of an effective sweep (sweeps are gaskets which seal the area between the bottom of a door and the threshold),
jamb condition, threshold condition and moisture-intrusion integrity.
Cladding: OK
No deficiencies were observed in the condition of wood shingles covering exterior walls at the time of the
inspection. Inspection of wood shingle wall coverings typically includes visual examination for excessive splitting,
shingle distortion (cupping, curling, etc.), proper installation, missing shingles, damaged shingles, fungal growth
and vegetative growth.
Limitations
Stoop, Steps
NOT VISIBLE
The deck substructure inspection was excluded due to limited access
because of low height or obstructions.
Limitations
A representative sample of exterior components were inspected rather than every occurrence of
components. When present, seasonal accessories, recreational facilities, outbuildings and fences are not
inspected unless specifically agreed upon and documented in this report. A home inspection does not
include an assessment of geological, geotechnical, or hydrological conditions or environmental hazards.
Recommendations
There were low spots visible near the foundation wall which will
collect water and can increase the potential for foundation seepage.
Recommend filling or re-grading the affected areas as needed in
order to create the proper slope away from the home while
maintaining adequate clearances from the top of the foundation
wall.
Recommendation
Contact a qualified landscaper or gardener.
2: ROOFING
Information
Chimney: Type
Metal Vent, Insulated Metal
Chimney
Flashings: OK
A representative number of areas were checked for flashing. No deficiencies were observed in the condition of
roof flashing.
Chimney: OK
No deficiencies were observed in the condition of the portion of the chimney that extended above the roof.
Inspection of this portion of the chimney includes evaluation of the chimney exterior, cap, spark arrestor, visible
flue, cricket, penetration flashing and counter-flashing and location on the roof.
Limitations
Limitations
ACCESSIBILITY
Roof was visually inspected from accessible points on the interior and/or exterior. If a roof is too high, is
too steep, is wet, is slippery or is composed of materials which can be damaged if walked upon, the roof is
not mounted. Therefore, client is advised that this is a limited review and a qualified roofer should be
contacted if a more detailed report is desired.
Recommendations
3: GARAGE
Information
Garage Floor: OK
At the time of the inspection, no deficiencies were observed in the condition of the garage floor.
Exterior: Information
Out buildings are not considered to be part of a general home inspection, however as a courtesy, some general
notes have been taken.
Recommendations
4: STRUCTURE
Information
Foundation: Material
Poured Concrete
Foundation: OK
At the time of the inspection, no deficiencies were observed in the condition of the visible portions of the
foundation.
Foundation Floor: OK
At the time of the inspection, no deficiencies were observed in the condition of the visible portions of the
concrete floor slab. All concrete floor slabs are expected to experience some degree of cracking due to shrinkage
in the drying process.
Floor Structure: OK
At the time of the inspection, no deficiencies were observed in the condition of the visible floor structure.
Inspection of the floor structure typically includes examination of the condition and proper installation of the
floor joists, joist supporting structures and members, connections and fasteners and the floor sheathing.
Limitations
Wall Structure
NOT VISIBLE
The exterior wall structure was not visible to inspect. The general home inspection does not include
evaluation of structural components hidden behind finishing materials, but is visual and non-invasive only.
Limitations
A representative sample of the visible structural components were inspected. Full inspection of all
structural components (posts/girders, foundation walls, sub flooring, and/or framing) is not possible in
areas/rooms where there are finished walls, ceilings and floors. Engineering or architectural services such
as calculation of structural capacities, adequacy, or integrity are not part of a home inspection.
Recommendations
Ventilation: Source
Soffit Inlet Vents, Ridge Exhaust
Venting
Insulation: Material
Blown-in Cellulose
Ventilation: OK
There were no signs of adverse conditions resulting from inadequate ventilation observed within the attic
space on the day of inspection.
Vent Piping: OK
No deficiencies were observed in the condition of the visible portions of the vent piping throughout the attic
space.
6: INTERIOR
Information
Door Bell: OK
The doorbell operated normally
when tested.
Floor Surfaces: OK
At the time of the inspection, no deficiencies were observed in the condition of floors in the home. Cosmetic
defects are not noted except where a functional concern exists.
Doors: Mostly OK
At the time of the inspection, few deficiencies were observed in the condition or operation of the interior doors.
Notable exceptions will be listed in this report.
Limitations
Limitations
INTERIOR
Assessing the quality and condition of interior finishes is highly subjective. Issues such as cleanliness,
cosmetic flaws, quality of materials, architectural appeal and color are outside the scope of this inspection.
Comments will be general, except where functional concerns exist. Furniture, area rugs, storage,
appliances and/or wall hangings are not moved to permit inspection and may block defects. Carpeting,
window treatments, central vacuum systems, household appliances, screening, recreational facilities, paint,
wallpaper, and other finish treatments are not inspected unless otherwise noted in this report.
Recommend thorough review of interior areas during final walk-through inspection prior to closing.
Recommendations
7: BATHROOMS
Information
Tub(s): OK
At the time of the inspection, no deficiencies were observed in the condition of bathtub components. Inspection
of the tub includes testing for functional flow, functional drainage and operational shut-off valves, faucet, and
diverter valve.
Shower(s): OK
All shower components appeared to be in serviceable condition at the time of the inspection. Inspection of the
shower typically includes evaluation of functional flow, functional drainage, proper operation of shut-off, diverter
valves and faucet; and moisture intrusion of walls and pan.
Toilet(s): OK
All toilet components operated in a manner consistent with their intended use, on the day of inspection.
Ventilation: OK
All bathrooms had an operable source of ventilation at the time of the inspection.
Recommendations
8: APPLIANCES
Information
Dishwasher: OK
The dishwasher was operated through one cycle and appeared to be in working order at time of inspection.
Kitchen Ventilation: OK
The over the range fan and lights functioned and operated normally when tested.
Microwave: OK
No deficiencies were observed in the condition or operation of the built-in microwave oven. The unit was tested
and appeared to be serviceable at time of inspection. Built-in microwave ovens are tested using normal operating
controls. Microwave leak and/or efficiency testing is beyond the scope of this inspection. If concerned, you should
seek further evaluation by qualified appliance technician.
Refrigerator: OK
The refrigerator was operational, at time of inspection. The efficiency of the appliance was not tested.
Central Vac: OK
The central vac blower operated when powered. Hoses, accessories and ports are not inspected as part of a
general home inspection. Ensure all accessories are present and functional at your final walk-through, if included
as part of your purchasing agreement.
Limitations
Dryer Vent
NOT VISIBLE
The transition ducting behind the dryer was not visible to inspect. It
should be verified that it meets UL2158A standard and the pipe to its
termination be properly cleaned.
Limitations
APPLIANCES
Appliances are checked for general functionality by turning them on for a short period of time using basic
operating modes. Thermostats, timers, clocks, self-cleaning features and other specialized functions are
not tested during this inspection. Appliances are not inspected for cosmetic flaws, performance or the
ability/accuracy of heating, cooling, etc. They are not inspected to ascertain whether the proper racks
and/or accessories are present or in working order. Laundry appliances (and other portable appliances)
are not moved and are outside the scope of this inspection; any comments are included for information
purposes only. Water supply valves are not operated for liability reasons. It is further recommended that
appliances be operated once again during the final walk through inspection prior to closing. Finally,
product recalls and consumer product safety alerts occur almost daily. To best address your specific
concerns, visit www.cpsc.gov or www.recalls.gov. Items, brand names, and model numbers will be required
for proper identification.
Recommendations
9: HVAC
Information
Heating System: Primary Heating System: Rated Output Heating System: Year of
Heating Source Capacity Manufacture
Electric Boiler, Electric Baseboard 68000 BTU 2011
Heaters
Air Exchanger: OK
The air exchanger operated
using normal controls at the time
of inspection.
Gas Fireplace(s): OK
Master Bedroom
At the time of the inspection, no deficiencies were observed in the condition of the propane-fueled fireplace.
Limitations
Limitations
HEATING
Adequacy, efficiency, or the balanced distribution of air throughout the home are not performed as part of
a home inspection. These calculations are typically performed by designers to determine the required size
of HVAC systems.
Recommendations
There was no "visible" bonding of the propane supply line. Any metal components which may become
energized are required to be bonded to the grounding system. Recommend correction by a licensed
electrician.
Recommendation
Contact a qualified electrical contractor.
10: ELECTRICAL
Information
Sub Panel: Rating Sub Panel: Over Current Branch Wiring: Wire Sheathing
100 Amps Protection Nylon Jacket PVC Insulated Non-
Breakers Metallic Sheathed Cable "Romex"
Service Drop: OK
At the time of the inspection, the Inspector observed no deficiencies in the condition of the service drop.
Components inspected included the service conductors, splice, drip loop, and point of attachment to the home.
Service Equipment: OK
No deficiencies were observed at the electrical service panel at the time of the inspection. Inspection of the main
service panel typically includes examination of the panel interior and exterior condition, panel amperage rating,
main disconnect amperage rating and condition, main conductor amperage ratings, branch conductor types,
amperage rating and condition, visible wiring materials types, condition and connections, circuit breaker types,
amperage ratings and condition, label information, service and equipment grounding and bonding of service
equipment.
Sub Panel: OK
No deficiencies were observed at the electrical service panel at the time of the inspection. Inspection of the main
service panel typically includes examination of the panel interior and exterior condition, panel amperage rating,
main disconnect amperage rating and condition, main conductor amperage ratings, branch conductor types,
amperage rating and condition, visible wiring materials types, condition and connections, circuit breaker types,
amperage ratings and condition, label information, service and equipment grounding and bonding of service
equipment.
Smoke Detectors: OK
Smoke detector placement appeared to be adequate. Smoke detectors are not tested as part of a general home
inspection. Recommend all detectors be checked upon occupancy to confirm batteries and alarm are
operational.
Limitations
Limitations
ELECTRICAL
Load calculation are not performed to determine service capacity adequacy. The inspection does not
involve any electrical stress tests on the system to determine if a breaker trips properly. Labeling of electric
circuit locations on electrical panel are not checked for accuracy. Electrical components concealed behind
finished surfaces are not visible to be inspected. Determination of the type of branch circuit wiring used in
this home was made by inspection of the electric panels only. Inspection of the wiring in or at the
receptacles, switches, fixtures, junction boxes, walls, ceiling, floors, etc., is beyond the scope of a home
inspection and were not inspected. The inspection does not include remote control devices, alarm systems
and components, low voltage wiring, systems, and components, ancillary wiring, systems, and other
components which are not part of the primary electrical power distribution system.
Limitations
SECURITY SYSTEM
Due to the specialized nature of home security alarm systems, recommend you review this system with the
seller. Security systems are beyond the scope of a home inspection.
Recommendations
11: PLUMBING
Information
Water Supply: Water Source Water Supply: Service Piping Water Supply: Shut-Off Location
Private Water Supply Material Basement
Acrylonitrile-Butadiene-Styrene
(ABS)
Distribution Piping: Material Drain, Waste & Vent Piping: Sewage Disposal: System
Cross-Linked Polyethylene (PEX) Material Private Onsite Wastewater
Acrylonitrile-Butadiene-Styrene Handling
(ABS)
Water Heater: Description Water Heater: Date of Water Heater: Water heaters
Electric, 60 Gal Manufacture have a typical life expectancy of
2001 11
15 years.
Water Supply: OK
At the time of the inspection, no deficiencies were observed in the condition of the visible portion of main water
supply line or shut-off valve. The valve was not operated due to the potential for leakage but was visually
inspected.
Distribution Piping: OK
On the day of inspection, no deficiencies were observed in the condition of the visible water distribution pipes.
Fixtures: OK
The sinks were visually inspected and faucet valves operated with no deficiencies observed at the time of
inspection.
Limitations
Sewage Disposal
SEPTIC SYSTEM
This inspection did not access the septic tank. Evaluation of the septic sewage system is beyond the scope
of a home inspection. Septic tanks should be pumped a minimum of every five (5) years. Recommend tank
be pumped, by a licensed septic company, if it has not been done within the last year.
Limitations
Water quantity and water quality are not tested unless explicitly contracted for and discussed in this or a
separate report. The sections of the plumbing system concealed by finishes and/or storage (below sinks,
etc.), below the structure, or beneath the ground surface are not inspected. Overflow backup is not tested
due to the possibility of damage from water leakage. This is necessary due to the fact that that aged
gaskets may fail and leak.
Recommendations