LV Release Coordination Report 1739041093
LV Release Coordination Report 1739041093
What is Relay?
❖ The relay is a device which open or close the circuit breaker contact; when
the current transformer sensed the abnormal current flow in it hence it gives a
signal to the relay so the relay which opens the circuit breaker to isolate the
faulty portion with a proper coordination time and to protect the system from
the damage.
Notes:
1. Release
2. Relay
What is Release?
Why release are preferring for LV system but not for MV system?
1. Simplicity of LV Systems:
c. Operate without the need for external components, reducing cost and
space requirements.
Unit protection:
1. High Selectivity: Detects and isolates faults within the specific zone only.
❖ The Non-Unit Protection, which doesn’t include the unit protection elements
and also it doesn’t had any specific area or boundaries to be protected.
❖ It will be important while it acting as the Backup Protection for the Primary
Protections. Because it will act as protective zone for its own designated
areas as well as these protective zones can overlap the other area’s which
are already covered by the other Primary protective element.
❖ Mainly it will identify the fault only with the help of current transformers
and it will incorporate an inverse time characteristic into the protection
operation which will allow protection nearer to the fault to be operate first.
The Backup protection includes the main characteristics like Overload and
Short-Circuit Protective functions.
What are the protection devices available in LV system?
❖ Switch
❖ Fuse
❖ Disconnector
❖ MCB – Miniature circuit breaker
❖ MCCB – Moulded case circuit breaker (Release)
❖ ACB – Air circuit breaker (Release)
❖ Current limiting breakers.
FUSE:
❖ Rated Current: It means the current that can be carried safely for an indefinite
period without undue heating and melting the fuse wire.
❖ Fusing Current: It means the value of current at which the fusing wire
melts when current passes through it even for a fraction of second
Step 1: Click Fuse and go to rating page
Step 3: Choose Manufacturer, Model, Max kV, Size of fuse. The continuous rating
of the fuse should be more than the motor FLA.
Step 4: Click star view and plot the TCC curve for motor and fuse.
Step 5: The below picture of TCC Curve which represents the fuse curve has
intersects the motor starting curve that means motor is not able to start with fuse in
properly so have to choose other protection device.
TCC CURVE FOR FUSE
.
Aspect Fuse MCB
What is MCB?
❖ It operates using thermal (for overload) and/or magnetic (for short circuits)
mechanisms to trip the circuit.
❖ It is reusable device; can be reset manually after tripping.
MCB
Types of MCB based on tripping characteristics curve:
load current
load current
load current
load current
Types of MCB based on Tripping characteristics curve:
Type B MCB:
Type C MCB:
Type D MCB:
Type K MCB:
Type Z MCB:
❖ A Triple Pole with Neutral (TPN) MCB is a type of circuit breaker designed
for three-phase systems with a neutral connection. It provides protection for
all three phases (R, Y, and B) while also including a connection for the
neutral wire. This ensures that the circuit is fully isolated during fault
conditions, including the neutral.
Step 1: Click the star – protection & coordination on top of the home page.
Step 2: Click create star view in the right corner by holding the equipment
which need for protection in the SLD.
Step 3: Click the star view manager when any new equipment will add to
the previous star view.
Step 4: Plot the TCC curve and adjust the curve for the protection.
Step 5: Click Run/Update short circuit current in KA at buses to update the
short circuit current.
Step 6: Click fault insertion (PD Sequence – of – operation) for the sequence
of breaker/ release to operate.
Step 7: Click sequence viewer option for in which time the event occurs
What is MCCB?
❖ The thermal release mechanism typically uses a bimetallic strip made of two
different metals with different coefficients of expansion.
❖ When the current exceeds the rated value, it causes the bimetallic strip to
heat up.
❖ As the strip heats, it bends due to the different expansion rates of the metals.
❖ If the overload condition persists, the bending of the strip triggers a trip
mechanism that disconnects the circuit.
❖ The magnetic release provides protection against short circuit conditions, where
a large amount of current flows instantaneously through the circuit. The
magnetic release operates very quickly to disconnect the circuit and prevent
damage.
❖ Working – Electromagnet:
❖ A coil of wire is placed inside the circuit breaker and is connected to the
electrical circuit.
❖ In the event of a short circuit, the current increases drastically and generates a
strong magnetic field.
❖ The magnetic field activates a plunger or armature that quickly trips the breaker
and disconnects the circuit.
Electronic Release:
❖ Electronic release in a circuit breaker is a protection mechanism that uses
electronic components and microprocessor-based systems to detect and respond
to faults such as overload, short circuits, and ground faults. This type of release
offers more precise and customizable protection compared to thermal or
thermal-magnetic releases. It is typically used in MCCBs (Moulded Case
Circuit Breakers) and other advanced circuit protection devices.
❖ Time delays can be provided for Short Circuit Release better discrimination
and co-ordination using LCD display. System Diagnosis is possible as it stores
the Trip history within the internal memory.
Current limiting breaker (MCB/MCCB):
interrupt fault currents before they reach their peak value. It limits the let-
through energy (I²t) that passes through the breaker, reducing the potential
responds within a fraction of a cycle (often less than half a cycle of AC).
❖ It creates a high resistance in the circuit, limiting the peak current before it
❖ This rapid action helps reduce stress on electrical components and minimizes
can reduce the peak apparent fault current to a lesser value and isolate the
❖ Fuses are also current limiter and cheaper. Current limiting circuit breakers
❖ Air Circuit Breaker (ACB) is a type of circuit breaker that uses air as the arc
commercial buildings.
❖ An Air Circuit Breaker (ACB) is a robust and reliable protection device for
low to medium voltage power systems. It is widely used in industrial,
commercial, and renewable energy applications due to its high fault-handling
capacity and easy maintenance.
LV Breaker current terminologies:
❑ Icw(or )Ithr - Short time withstand current with Tkr – withstand Time(1Sec - LV
/ 3 sec -MV ).
❖ Icu is really the maximum perspective fault which a circuit breaker can clear
(with the fault current being expressed as rms for ac). but it may not be usable
❖ After clearing a fault the circuit breaker does not have to remain serviceable
❖ This point is particularly important in circuit breakers when the Ics is lower
❖ Test sequence III : O - t - CO ( open - 3mins- close open) as per IEC 60947.
❖ Ics is the maximum perspective fault current which the circuit breaker can clear
and still remain serviceable. The standard does allow some minor welding
of the contacts to take place, so after a large fault it would still be necessary
❑ Icu= Ics = Icw for 1 Sec in only with few Air Circuit Breaker .
❑ For MV breakers Icu= Ics = Icw for 1 Sec or 3 Sec , That’s the reason behind
❑ Icu= Ics = Icw for 1 Sec in most of the Air Circuit Breaker .
❑ When we are using ETAP for LV circuit breaker which is current limiting
type and operated in 2-3 msec will not given a correct co-ordination result.
msec.
Notes on Breaker Current Terminologies: MCCB
Releases:
RELEASES
THERMAL
ELECTRONIC
MAGNETIC
RELEASE
THERMAL ADJUST
MAGNETIC FIXED
How to calculate Motor FLA?
occurs at the short period of the time. The locked rotor current occurs due to not
turning of the rotor (locked); hence after a period thus the rotor will gain a speed
and to run so thus the motor accelerates and the current gradually decreases and
The above picture is that motor starting curve of motor terminal bus voltage (Vt)
The Locked rotor current is the starting current of the motor starting. The current
occurs at the short period of the time. The Locked rotor current occurs due to not
turning of the rotor (locked); hence after a period thus the rotor will gain a speed
and to run so thus the motor accelerates and the current gradually decreases and
The above picture shows that the asymmetrical locked rotor current of 494.1 A
The Asymmetrical factor is that the ratio of the peak value of the Asymmetrical
Symmetrical current).
For a Three phase Induction motor the Asymmetrical factor is 1.6 to 2 higher
The Asymmetrical factor is crucial for designing the protection devices like
circuit breaker and fuses, as they need to handle the high initial current without
tripping unnecessiarly.
The Asymmetrical factor in the LRC of a motor refers to the phenomenon where
the current is not symmetrically distributed among the motor phases when the
rotor initially locked and the motor is started. This is particularly significant in
the three phase Induction motor. The Asymmetrical factor accounts for the
transient behaviour of the motor during startup, where the current waveform can
TCC Curve
TM ID = 63 A
TM ID = 63 A
Magnetic
TM ID = 63 A TM ID = 63 A
In the above TCC curve shows that the protection curve which overlap with
the motor starting current so thus the motor will not able to start properly
because the protection device has trips unnecessarily of the starting current of
the motor and also the protection curve which touches the motor damage
In the above TCC curve shows that the protection curve which overlap with
the motor starting current so thus the motor will not able to start properly
because the protection device has trips unnecessarily of the starting current of
the motor and also the protection curve which touches the motor damage
TIMES)
In the above TCC curve shows that the protection curve which is overlap with
the motor starting current so thus the motor able to start properly because the
protection device has not trips unnecessarily of the starting current of the
motor and also the protection curve which doesn’t touches the motor damage
XT2) Model
Instantaneous
MODEL
Long time pickup
tolerance (min =-
10% & max = 10%)
Min = 180 A
Max = 220 A
Long time band
Min = 1934 A
Max = 2616 A
Ground pickup tolerance (Min = -
15 & Max = 15%)
Min = 42.5 A
Max = 57.5 A
Manufacturer: ABB
LONG
SHORT
GROUND
TCC Curve : LV Incomer & Highest Motor Feeder
The above TCC curve shows that the coordination is proper because the LV
incomer curve is not overlap with the highest motor protection curve.
any fault occurs so the protective device will trip without any intentional time