0% found this document useful (0 votes)
19 views6 pages

LS 2022-2023 Catalogue

The document indicates that the training data extends up to October 2023, suggesting that any information or developments occurring after this date are not included in the training set.

Uploaded by

ohmarwynn1973
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
19 views6 pages

LS 2022-2023 Catalogue

The document indicates that the training data extends up to October 2023, suggesting that any information or developments occurring after this date are not included in the training set.

Uploaded by

ohmarwynn1973
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 6

LS-Gaon Cable Myanmar

The best cable maker in Myanmar

1
L S - G a o n C a b l e M y a n m a r

12/22kV and 35kV Conductor Screened, XLPE


Insulated Power Cable (12/22kV ACSR/AW-OC, 35kV
ACSR/AW-OC)
• Construction Stranded Aluminum conductor, Aluminium-Clad steel reinforce (ACSR/AW)) and Semi-conducting screened, XLPE
insulation power cable
*Option : Water blocking material shall be filled the layer stranded of conductor

• Application Used for overhead power transmission line and power distribution line

Conductor (Steel)
Conductor (Al)
Water Blocking
Conductor Screen
Insulation

12/22kV ACSR/AW-OC(BS EN 50397-1)


Conductor Thickness Approx. Approx. Min. Max. D.C.
Cross Sectional No. and Diameter No. and Diameter Outside of Overall Overalal Breaking Conductor
Area of wires (Al) of wires (Steel) Diameter Insulation Diameter Weight Load Resistance(20oC)
mm2 mm mm mm mm mm kg/km kN Ω / km
50 6/3.20 1/3.20 9.60 3.5 17.0 330 17.112 0.5951
70 6/3.80 1/3.80 11.40 3.5 18.0 430 24.130 0.4218
95 6/4.75 1/3.5 12.0 3.5 19.0 535 23.10 0.302
120 26/2.40 7/1.85 15.15 3.5 22.0 660 41.521 0.2440
150 24/2.80 7/1.85 16.75 3.5 24.0 760 46.307 0.2046
150 26/2.70 7/2.10 17.10 3.5 24.0 810 52.279 0.2039
185 24/3.15 7/2.10 18.90 3.5 26.0 930 58.075 0.1540
185 26/2.98 7/2.30 18.82 3.5 26.0 960 62.055 0.1519
240 24/3.60 7/2.40 21.60 3.5 29.0 1180 75.050 0.1182
300 24/4.00 7/2.65 23.95 3.5 31.0 1410 90.574 0.0958
330 54/2.80 7/2.80 25.20 3.5 32.0 1550 103.784 0.0869
400 54/3.05 7/3.05 27.50 3.5 35.0 1810 120.481 0.0733

35kV ACSR-CX (BS EN 50397-1)


Conductor Thickness Approx. Approx. Min. Max. D.C.
Cross Sectional No. and Diameter No. and Diameter Outside of Overall Overalal Breaking Conductor o
Area of wires (Al) of wires (Steel) Diameter Insulation Diameter Weight Load Resistance(20 C)
mm2 mm mm mm mm mm kg/km kN Ω / km
50/8 6/3.20 1/3.20 9.60 3.9 19.0 400 17.112 0.5951
70/11 6/3.80 1/3.80 11.40 3.9 21.0 510 24.130 0.4218
95/16 6/4.50 1/4.50 13.50 3.9 23.0 650 33.369 0.3007
120/19 26/2.40 7/1.85 15.15 3.9 25.0 760 41.521 0.2440
150/19 24/2.80 7/1.85 16.75 3.9 26.0 860 46.307 0.2046
150/24 26/2.70 7/2.10 17.10 3.9 27.0 910 52.279 0.2039
185/24 24/3.15 7/2.10 18.90 3.9 29.0 1040 58.075 0.1540
185/29 26/2.98 7/2.30 18.82 3.9 29.0 1070 62.055 0.1519
240/32 24/3.60 7/2.40 21.60 3.9 31.0 1300 75.050 0.1182
300/39 24/4.00 7/2.65 23.95 3.9 34.0 1540 90.574 0.0958
330/43 54/2.80 7/2.80 25.20 3.9 35.0 1690 103.784 0.0869
400/51 54/3.05 7/3.05 27.50 3.9 37.0 1960 120.481 0.0733

22
Power Cable
Typical Construction of Cables
Conductor Construction and D.C. Conductor Resisance
0.6/1kV Cu/XLPE/PVC, Al/XLPE/PVC, Cu/XLPE/ LSZH(0.6/1kV CV, 0.6/1kV AL-CV, 0.6/1kV HF-CO)
0.6/1kV Cu/XLPE/PVC/SWA(AWA)/PVC, 0.6/1kV AL/XLPE/PVC/SWA(AWA)/PVC
0.6/1kV Cu/XLPE/LSZH/SWA(AWA)/LSZH (0.6/1kV CV(A)WAV, 0.6/1kV AL-CV(A)WAV, 0.6/1kV HF-CO(A)WAO)

30
P o w r C a b l e

Typical Construction of Cables (AS)

0.6/1kV Unarmoured Cable

Conductor
Insulation
Filler
Binder
Oversheath

0.6/1kV Armoured Cable

Conductor
Insulation
Filler
Binder
Inner covering
Oversheath

Description
Conductors : The conductors shall be class 2 of plain annealed Copper or Aluminum in accordance with IEC 60228.
Insulation : Insulation shall be crosslinked Polyethylene or PVC complying with test requirements of IEC 60502 & IEC 60811.
Laying Up : In case of multi core cables, the multi cores are laid up together with e.g polypropylene yarn filler at the interstices between the cores.
A binder e.g. polypropylene tape is wrapped round the assembly to form a compact circular cable during this process.
Inner Covering : Inner covering shall be extruded PVC as per IEC 60502. PE, LSZH (Low Smoke Zero Halogen) are available on request.
Armour : Armour shall be as per IEC 60502 of the following type :
a) Round Wire Armour
Armour material shall be galvanized steel for multi core cables and aluminum for single core cables. This is as per IEC 60502 recommendation.
Oversheath : Oversheath shall be extruded PVC/ST1 or ST2 as per IEC 60502, special type of sheathing such as Flame retardant(FR-), Antitermite(/AT),
Anti-rodent( /AR) and Anti-vermin( /AV), etc. are avaiible on request. PE or LSZH(HF- : Halogen free Flame retardant) are available on request.

31
L S - G a o n C a b l e M y a n m a r

Conductor Construction and


D.C. Conductor Resisance

Conductor
Maximum Resistance of Conductor
o
Nominal Minimum Number Approx. D.C at 20 C
Cross-Sectional Area of Wires in the Conductor (No.) Diameter (Ω / km)
mm2 Copper Aluminum mm Copper Aluminum
1.5 7 -- 1.59 12.1 --
2.5 7 -- 2.01 7.41 --
4 7 7 2.55 4.61 7.41
6 7 7 3.12 3.08 4.61
10 7 7 4.05 1.83 3.08
16 6 6 4.7 1.15 1.91
25 6 6 5.9 0.727 1.20
35 6 6 6.9 0.524 0.868
50 6 6 8.1 0.387 0.641
70 12 12 9.8 0.268 0.443
95 15 15 11.4 0.193 0.320
120 18 15 12.9 0.153 0.253
150 18 15 14.4 0.124 0.206
185 30 30 15.9 0.0991 0.164
240 34 30 18.3 0.0754 0.125
300 34 30 20.5 0.0601 0.100
400 53 53 23.2 0.0470 0.0778
500 53 53 26.4 0.0366 0.0605
630 53 53 30.2 0.0283 0.0469
* ( ) : Weight of cable for Aluminum conductor
* Weight can be different depending on item

32
P o w r C a b l e

0.6/1kV Cu/XLPE/PVC, Al/XLPE/PVC, Cu/XLPE/LSZH


(0.6/1kV CV, 0.6/1kV AL-CV, 0.6/1kV HF-CO)

Conductor

Insulation

Oversheath

Nominal Thickness of Thickness of Oversheath Approx. Overall Diameter Approx.


Cross-Sectional
Area of Conductor Insulation (mm) (mm) Weight (kg/km)
mm2 mm 1C 2C 1C 2C 1C 2C
1.5 0.7 1.4 1.8 6.3 11 53 (- -) 127 (- -)
2.5 0.7 1.4 1.8 6.7 12 65 (- -) 153 (- -)
4 0.7 1.4 1.8 7.2 13 81 (60) 197 (160)
6 0.7 1.4 1.8 7.8 14 108 (70) 252 (210)
10 0.7 1.4 1.8 9.4 17 155 (90) 357 (250)
16 0.7 1.4 1.8 10 18.5 210 (120) 487 (300)
25 0.9 1.4 1.8 12 22 315 (160) 720 (420)
35 0.9 1.4 1.8 13 24 414 (200) 943 (530)
50 1.0 1.4 1.8 14.5 27 542 (250) 1229 (660)
70 1.1 1.4 1.8 14.6 31 710 (330) 1702 (870)
95 1.1 1.5 1.9 16.5 35 970 (430) 2285 (1,140)
120 1.2 1.5 2.0 18.4 38 1,195 (520) 2890 (1,400)
150 1.4 1.6 2.2 20.2 43 1,475 (640) 3475 (1,710)
185 1.6 1.6 2.3 24 47 1,872 (780) 4282 (2,110)
240 1.7 1.7 2.5 27 53 2,391 (1,000) 5469 (2,740)
300 1.8 1.8 2.6 30 58 3,023 (1,230) 6876 (3,360)
400 2.0 1.9 -- 34 -- 3,975 (1,550) -- --
500 2.2 2.0 -- 37 -- 4,894 (1,950) -- --
630 2.4 2.2 -- 42 -- 6,283 (2,580) -- --

* ( ) : Weight of cable for Aluminum conductor


* Weight can be different depending on item

33