The 38/40MAQ series ductless split systems offer a combination of outdoor condensing and indoor fan coil units, designed for efficient cooling and heating without the need for ductwork. They feature low sound levels, individual room comfort control, and easy installation, making them ideal for various applications including retrofits and historical renovations. The systems include advanced technology for reliability and energy savings, with options for remote controls and additional accessories.

Uploaded by

mmeixsell
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
20 views20 pages

38MAQ 2015

The 38/40MAQ series ductless split systems offer a combination of outdoor condensing and indoor fan coil units, designed for efficient cooling and heating without the need for ductwork. They feature low sound levels, individual room comfort control, and easy installation, making them ideal for various applications including retrofits and historical renovations. The systems include advanced technology for reliability and energy savings, with options for remote controls and additional accessories.

Uploaded by

mmeixsell
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 20

40MAQ / 38MAQ

High- Wall Ductless Split System


Sizes 09 to 30

Product Data
INDUSTRY LEADING
FEATURES / BENEFITS
A PERFECT BALANCE BETWEEN
BUDGET LIMITS, ENERGY SAVINGS AND
COMFORT.
The 38/40MAQ series ductless split systems are a matched
combination of an outdoor condensing unit and an indoor fan coil
unit connected only by refrigerant tubing and wires.
The fan coil is mounted on the wall, near the ceiling. This
selection of fan coils permits creative solutions to design problems
such as:

S Add- ons to current space (an office or family room


addition)
S Special space requirements
S When changes in the load cannot be handled by the
existing system.
S When adding air conditioning to spaces that are heated
by hydronic or electric heat and have no ductwork.
S Historical renovations or any application where
preserving the look of the original structure is essential.

The ideal compliment to your ducted system when it is


impractical or prohibitively expensive to use ductwork.
These compact indoor fan coil units take up very little space in the
room and do not obstruct windows. The fan coils are attractively
styled to blend with most room decors. Advanced system
components incorporate innovative technology to provide reliable
cooling performance at low sound levels.
LOW SOUND LEVELS BUILT- IN RELIABILITY
When noise is a concern, the ductless split systems are the answer. Ductless split system indoor and outdoor units are designed to
The indoor units are whisper quiet. There are no compressors provide years of trouble- free operation.
indoors, either in the conditioned space or directly over it, and The high wall indoor units include protection against freeze- up
there is none of the noise usually generated by air being forced and high evaporator temperatures on heat pumps.
through ductwork. The condensing units on heat pumps are protected by a three
When sound ordinances and proximity to neighbors demand quiet minute time delay before the compressor will start the over- current
operation, the 38MAQ unit is the right choice: The advanced, protection and the high temperature protection.
horizontal airflow design distributes air more evenly over the coil.
INDIVIDUAL ROOM COMFORT
SECURE OPERATION Maximum comfort is provided because each space can be
If security is an issue, outdoor and indoor units are connected only controlled individually based on usage pattern. The air sweep
by refrigerant piping and wiring to prevent intruders from feature provided permits optimal room air mixing to eliminate hot
crawling through ductwork. In addition, since 38MAQ units can and cold spots for occupant comfort. In addition, year- round
be installed close to an outside wall, coils are protected from comfort can be provided with heat pumps.
vandals and severe weather.
ECONOMICAL OPERATION
FAST INSTALLATION The ductless split system design allows individual room heating or
This compact ductless split system is simple to install. A cooling when required. There is no need to run large supply- air
mounting bracket is standard with the indoor units and only wire fans or chilled water pumps to handle a few spaces with unique
and piping need to be run between indoor and outdoor units. load patterns. In addition, because air is moved only in the space
These units are fast and easy to install ensuring minimal required, no energy is wasted moving air through ducts.
disruption to customers in the home or workplace. This makes the
38/40MAQ ductless split systems the equipment of choice,
especially in retrofit situations. EASY- TO- USE CONTROLS
The high- wall units have microprocessor- based controls to
SIMPLE SERVICING AND provide the ultimate in comfort and efficiency. The user friendly
wireless remote control provides the interface between user and
MAINTENANCE the unit.
Removing the top panel on outdoor units provides immediate
access to the control compartment, providing a service technician ACCESSORIES
access to check unit operation. In addition, the draw- thru design of
the outdoor section means that dirt accumulates on the outside Customizing these ductless split systems to your application is
surface of the coil. Coils can be cleaned quickly from the inside easily accomplished.
using a pressure hose and detergent. Adding a condensate pump accessory to the high wall fan coil
On all indoor units, service and maintenance expense is reduced provides installation flexibility.
due to easy- to- use cleanable filters. In addition, these high wall
systems have extensive self- diagnostics to assist in OPTIONAL WIRED CONTROLLER
troubleshooting.

AGENCY LISTINGS
All systems are listed with AHRI (Air Conditioning, Heating &
Refrigeration Institute), and ETL.

2
MODEL NUMBER NOMENCLATURE

INDOOR UNIT
40 MA Q B 09 B - - 3

40= FAN COIL UNIT

VOLTAGE
1 =115 - 1 - 60
MA = MODEL 3 = 208/230 - 1 - 60

SYSTEM TYPE
Q = HEAT PUMP

MAXIMUM NUMBER OF FAN COIL UNITS THAT


CAN BE CONNECTED TO THE OUTDOOR UNIT
B=1:1 NOT USED

NOMINAL CAPACITY
09 - 3/4 TON
12 - 1 TON
18 - 1 - 1/2 TONS INDOOR FAN COIL TYPE
24 - 2 TONS
30 - 2 - 1/2 TONS B= HIGH - WALL

OUTDOOR UNIT
38 MA Q B 09 - - - 3

38 = OUTDOOR UNIT

VOLTAGE
1 =115 - 1 - 60
3 = 208/230 - 1 - 60
MA = MODEL

SYSTEM TYPE
Q = HEAT PUMP

MAXIMUM NUMBER OF FAN COIL UNITS THAT


CAN BE CONNECTED TO THE OUTDOOR UNIT
B=1:1 NOT USED

NOMINAL CAPACITY
09 - 3/4 TON
12 - 1 TON
18 - 1 - 1/2 TONS UNIT TYPE
24 - 2 TONS
30 - 2 - 1/2 TONS - = OUTDOOR UNIT

Use of the AHRI Certified


TM Mark indicates a
manufacturer’s
participation in the
program For verification
of certification for individual
products, go to
www.ahridirectory.org.

3
STANDARD FEATURES AND ACCESSORIES
Ease Of Installation INDOOR UNITS
Mounting Brackets S
Low Voltage Controls S
Comfort Features
Microprocessor Controls S
Wired Remote Control A
Wireless Remote Control S
Automatic Horizontal Air Sweep S
Air Direction Control S
Auto Restart Function S
Cold Blow Protection On Heat Pumps S
Freeze Protection Mode On Heat Pumps S
Turbo Mode S
Silence Mode S
Auto Changeover On Heat Pumps S Fig. 1 – Condensate Pump Accessory
Follow Me S On high wall fan coils, the condensate pump has a lift capability
Energy Saving Features of 12 ft (3.6 m) on the discharge side with the pump mounted in
Sleep Mode S the fan coil or 6 ft (1.8 m) on the suction side if the pump is
Stop/Start Timer S remote mounted. The pump is recommended when adequate drain
46° F Heating Mode (Heating Setback) S line pitch cannot be provided, or when the condensate must move
Safety And Reliability up to exit.
3 Minute Time Delay For Compressor S NOTE: An external 115v power source will be required to run the
Over Current Protection For Compressor S pump on unit sizes 9k and 12k.
Indoor Coil Freeze Protection S
Indoor Coil High Temp Protection in Heating Mode S
Condenser High Temp Protection in Cooling Mode S OUTDOOR UNITS
Ease Of Service And Maintenance Crankcase Heater
Cleanable Filters S
Standard on all unit sizes. Heater clamps around compressor oil
Diagnostics S
stump.
Liquid Line Pressure Taps S
Application Flexibility
Condensate Pumps A
Crankcase Heater S
Legend
S Standard
A Accessory

4
DIMENSIONS - INDOOR

Fig. 2 – Indoor unit


Unit Size W in (mm) D in (mm) H in (mm) Operating Weight lb (kg)
9K/12K 32.9 (835) 7.8 (198) 11.0 (280) 19.2 (8.7)
18K 39.0 (990) 8.6 (218) 12.4 (315) 26.5 (12.0)
24K/30K 46.7 (1186) 10.2 (258) 13.4 (343) 40.8 (18.5)

DIMENSIONS - OUTDOOR

Fig. 3 – Outdoor unit


Operating
Model W in (mm) D in (mm) H in (mm) L1 in (mm) L2 in (mm)
Weight lb (kg)
9K/12K 32.0 (810) 12.2 (310) 22.0 (558) 20.9 (530) 11.4 (290) 82.5 (37.4)
18K 32.3 (845) 12.6 (320) 27.6 (700) 22.1 (560) 13.2 (335) 102.5 (46.5)
24K 37.2 (945) 15.6 (395) 31.9 (810) 25.1 (640) 15.9 (405) 137.6 (62.4)
30K 37.2 (945) 15.6 (395) 31.9 (810) 25.1 (640) 15.9 (405) 157.6 (71.5)

5
CLEARANCES - INDOOR
CEILING
6" (0.15m) min.

5" 5"
(0.13m) (0.13m)
min. min.

6' (1.8m)

FLOOR
Fig. 4 – Indoor Unit Clearance

CLEARANCES - OUTDOOR

A
Air-inlet

D B C

Air-outlet

Fig. 5 – Clearances Outdoor

Minimum Value
UNIT
in. (mm)
A 24 (609)
B 24 (609)
C 24 (609)
D 4 (101)
E 4 (101)

6
SPECIFICATIONS - HEAT PUMP UNITS (MAQ SERIES)
Size 9 12 9 12 18 24 30
Outdoor Model 38MAQB09---1 38MAQB12---1 38MAQB09---3 38MAQB12---3 38MAQB18---3 38MAQB24---3 38MAQB30---3
System
Indoor Model 40MAQB09B--1 40MAQB12B--1 40MAQB09B--3 40MAQB12B--3 40MAQB18B--3 40MAQB24B--3 40MAQB30B--3
Energy Star YES YES YES YES YES YES NO
Cooling Rated Capacity Btu/h 9,000 12,000 9,000 12,000 17,500 23,000 30,000
Cooling Cap. Range Min - Max Btu/h 3500~11000 4000~13000 3500~11000 4000~13000 4500~18000 5500~23500 8000~30500
SEER 23.5 21.5 23.5 21.5 19.5 20.0 16.5
Perfor- EER 14.5 13 14.5 13 12.5 12.5 9.5
mance Heating Rated Capacity Btu/h 10,000 12,000 10,000 12,000 18,000 25,000 32,000
Heating Cap. Range Min - Max Btu/h 4,500~11,500 5,000~13,500 4,500~11,500 5,000~13,500 5,500~19,000 6,000~26,000 9,000~34,000
HSPF 10.0 10.0 10.0 10.0 9.6 10.0 9.6
COP W/W 3.36 3.22 3.66 3.36 3.36 3.22 2.92
Wireless Remote Controller (°F/°C Convertible) Standard
Controls
Wired Remote Controller (°F/°C Convertible) Optional
Cooling Outdoor DB Min - Max °F 4~122 4~122 4~122 4~122 4~122 4~122 4~122
Operating Heating Outdoor DB Min - Max °F 4~86 4~86 4~86 4~86 4~86 4~86 4~86
Range Cooling Indoor DB Min -Max °F 63~90 63~90 63~90 63~90 63~90 63~90 63~90
Heating Indoor DB Min -Max °F 32~86 32~86 32~86 32~86 32~86 32~86 32~86
Total Piping Length Ft. 82 82 82 82 98 98 164
Piping Lift* Ft. 32 32 32 32 65 65 82
Piping
Pipe Connection Size - Liquid In. 1/4 1/4 1/4 1/4 1/4 3/8 3/8
Pipe Connection Size - Suction In. 3/8 1/2 3/8 1/2 1/2 5/8 5/8
Type R410A
Refrigerant Design Pressure PSIG 550 550 550 550 550 550 550
Metering Device Electronic Expansion Valve Capillary Tube
Refrigerant Charge Lb. 2.76 2.76 2.76 2.76 4.19 5.18 6.62
Face Area Sq. Ft. 9.2 9.2 9.2 9.2 16.0 21.1 17.2
Outdoor No. Rows 2 2 2 2 2 3 3
Coil Fins per inch 21 21 21 21 18 18 17
Circuits 4 4 4 4 6 8 6
Face Area (sq. ft.) Sq. Ft. 2.2 2.2 2.2 2.2 2.6 3.7 3.7
No. Rows 2 2 2 2 2 3 3
Indoor Coil
Fins per inch 20 20 20 20 20 18 18
Circuits 3 3 3 3 4 7 7
Type Hermetic Rotary DC Inverter Compressor
Model ASM98D1UFZA ASM108D1UFZA ASM98D1UFZA ASM108D1UFZA ASM135D23UFZ DA250S2C-30MT TNB306FPGMC-L
Compres-
Oil Type VG74 VG74 VG74 VG74 VG74 VG74 FV50S
sor
Oil Charge Fl. Oz. 12.5 12.5 12.5 12.5 15.2 27.7 36.2
Rated Current RLA 5.3 5.7 5.3 5.7 7.3 8.8 13.5
Voltage, Phase, Cycle V/Ph/Hz 115-1-60 115-1-60 208/230-1-60 208/230-1-60 208/230-1-60 208/230-1-60 208/230-1-60
Power Supply Indoor unit powered from outdoor unit
Electrical
MCA A. 15 15 15 15 13 15 20
MOCP - Fuse Rating A. 20 20 15 15 20 25 30
Unit Width In. 31.9 31.9 .9 31.9 33.3 37.2 37.2
Unit Height In. 22.0 22.0 .0 22.0 .6 31.9 31.9
Unit Depth In. 12.2 12.2 .2 12.2 .6 15.6 15.6
Outdoor
Net Weight Lbs. 82.5 82.5 82.5 82.5 102.5 137.6 157.6
Airflow CFM 1200 1200 1200 1200 1390 2130 2130
Sound Pressure dB(A) 56 56 56 56 59 60 63
Unit Width In. 32.9 32.9 32.9 32.9 39.0 46.7 46.7
Unit Height In. 11.0 11.0 11.0 11.0 12.4 13.4 13.4
Unit Depth In. 7.8 7.8 7.8 7.8 8.6 10.2 10.2
Net Weight Lbs. 19.2 19.2 19.2 19.2 26.5 40.1 40.1
Indoor
Number of Fan Speeds 4 4 4 4 4 4 4
Airflow (lowest to highest) CFM 210/290/360/380 210/300/360/380 210/290/360/380 210/300/360/380 310/450/650/680 520/620/780/870 520/620/780/870
Sound Pressure (lowest to highest) dB(A) 27/34/42 27/34/42 27/34/42 27/34/42 33/40/46 39/45/50 39/45/50
Air throw Data Ft. 23 23 23 23 30 36 36

Condensing unit above or below indoor unit

7
COOLING PERFORMANCE DATA - 38/40MAQ (HEAT PUMP)
Cooling Outdoor conditions (DB)
Model
Indoor Conditions DB Indoor Conditions WB 77F(25C) 86F(30C) 95F(35C) 104F(40C) 113F(45C) 122F(50C)
TC 7.43 7.83 9.74 8.38 6.11 5.11
69.8F(21C) 59F(15C) SC 6.68 6.69 8.18 7.37 4.36 3.74
Input 0.35 0.54 0.81 0.8 0.75 0.75
TC 7.78 9.14 9.89 8.65 6.92 5.83
75.2F(24C) 62.6F(17C) SC 3.58 8.11 6.27 5.52 4.85 4.29
09 Input 0.35 0.54 0.81 0.8 0.75 0.75
(115V) TC 8.21 9.22 10.41 9.27 7.32 6
80.6F(27C) 66.2F(19C) SC 7.39 5.88 8.22 7.79 5.11 4.37
Input 0.35 0.75 0.82 0.81 0.75 0.75
TC 8.41 9.72 11.59 10.22 8.82 7.51
89.6F(32C) 73.4F(23C) SC 3.68 5.76 6.9 6.2 5.55 5
Input 0.36 0.56 0.83 0.82 0.76 0.77
TC 8.21 11.75 11.42 9 7.85 6.68
69.8F(21C) 59F(15C) SC 7.06 9.05 8.68 7.38 6.42 5.58
Input 0.38 0.8 1.04 0.87 0.82 0.81
TC 8.42 11.84 12.01 9.35 8.32 7.34
75.2F(24C) 62.6F(17C) SC 7.28 8.69 8.66 7.62 6.53 5.81
12 Input 0.57 0.94 1.25 1.27 0.98 0.94
(115V) TC 8.81 11.95 12.23 9.69 8.87 7.95
80.6F(27C) 66.2F(19C) SC 7.49 8.32 8.63 7.85 6.64 6.04
Input 0.39 0.75 1.06 0.89 0.85 0.82
TC 9.01 12.15 12.43 9.89 9.07 8.15
89.6F(32C) 73.4F(23C) SC 7.7 8.53 8.84 8.06 6.85 6.25
Input 0.4 0.97 1.3 1.34 0.92 0.85
TC 7.41 7.82 9.73 8.34 6.12 5.1
69.8F(21C) 59F(15C) SC 6.64 6.69 8.18 7.37 4.36 3.74
Input 0.35 0.54 0.81 0.8 0.75 0.75
TC 7.76 9.16 9.89 8.62 6.92 5.83
75.2F(24C) 62.6F(17C) SC 3.58 8.11 6.27 5.52 4.85 4.29
09 Input 0.35 0.54 0.81 0.8 0.75 0.75
(208-230V) TC 8.21 9.22 10.41 9.27 7.32 6
80.6F(27C) 66.2F(19C) SC 7.39 5.88 8.22 7.79 5.11 4.37
Input 0.35 0.75 0.82 0.81 0.75 0.75
TC 8.41 9.72 11.59 10.22 8.82 7.51
89.6F(32C) 73.4F(23C) SC 3.68 5.76 6.9 6.2 5.55 5
Input 0.36 0.56 0.83 0.82 0.76 0.77
TC 8.21 11.75 11.42 9 7.85 6.68
69.8F(21C) 59F(15C) SC 7.06 9.05 8.68 7.38 6.42 5.58
Input 0.38 0.8 1.04 0.87 0.82 0.81
TC 8.42 11.84 12.01 9.35 8.32 7.34
75.2F(24C) 62.6F(17C) SC 7.28 8.69 8.66 7.62 6.53 5.81
12 Input 0.57 0.94 1.25 1.27 0.98 0.94
(208-230V) TC 8.81 11.95 12.23 9.69 8.87 7.95
80.6F(27C) 66.2F(19C) SC 7.49 8.32 8.63 7.85 6.64 6.04
Input 0.39 0.75 1.06 0.89 0.85 0.82
TC 9.01 12.15 12.43 9.89 9.07 8.15
89.6F(32C) 73.4F(23C) SC 7.7 8.53 8.84 8.06 6.85 6.25
Input 0.4 0.97 1.3 1.34 0.92 0.85
TC 12.58 15.24 16.25 11.04 8.32 6.78
69.8F(21C) 59F(15C) SC 8.34 10.3 10.6 7.93 6.18 5.16
Input 0.58 0.93 1.53 1.2 1.42 1.32
TC 13.48 16.41 16.66 12.3 9.43 7.74
75.2F(24C) 62.6F(17C) SC 8.85 10.94 11.35 8.62 6.87 5.91
18 Input 0.57 0.93 1.56 1.22 1.45 1.35
(208-230V) TC 14.43 18.04 18.37 13.35 9.97 7.96
80.6F(27C) 66.2F(19C) SC 9.59 11.95 12.37 9.28 7.23 6.02
Input 0.57 0.94 1.59 1.24 1.48 1.38
TC 14.7 19.03 20.18 15.36 12.02 9.97
89.6F(32C) 73.4F(23C) SC 9.08 11.72 12.5 9.69 7.85 6.89
Input 0.6 0.97 1.62 1.27 1.51 1.41
TC 19.5 20.69 21.43 18.05 14.27 13.32
69.8F(21C) 59F(15C) SC 15.15 15.61 15.49 14.23 10.03 8.78
Input 1.2 1.88 2.29 2.14 1.9 1.86
TC 20.01 21.21 22.31 18.51 15.08 13.3
75.2F(24C) 62.6F(17C) SC 15.25 15.71 15.59 14.33 10.13 8.88
24 Input 1.2 1.87 2.3 2.21 2.14 1.92
(208-230V) TC 20.54 21.75 23.21 18.98 15.91 13.3
80.6F(27C) 66.2F(19C) SC 15.35 15.81 15.69 14.43 10.23 8.98
Input 1.21 1.86 2.31 2.26 2.16 1.93
TC 20.61 22.94 24.4 21.84 19.17 16.66
89.6F(32C) 73.4F(23C) SC 15.58 16.04 15.92 14.66 10.46 9.21
Input 1.22 1.87 2.34 2.33 2.32 1.96
TC 27.33 27.43 27.51 22.77 18.29 17.32
69.8F(21C) 59F(15C) SC 19.4 19.48 19.56 17.21 16.32 15.28
Input 2.28 3.29 3.63 3.11 2.35 2.25
TC 29.41 30.01 29.82 24.53 20.71 18.24
75.2F(24C) 62.6F(17C) SC 19.95 20.47 20.07 17.73 17.24 16.29
30 Input 2.31 3.32 3.68 3.17 2.41 2.31
(208-230V) TC 31.57 32.68 32.21 26.37 23.2 19.21
80.6F(27C) 66.2F(19C) SC 20.55 21.52 20.65 18.3 18.21 17.35
Input 2.35 3.35 3.74 3.23 2.47 2.38
TC 32.6 33.71 33.24 27.4 24.23 20.24
89.6F(32C) 73.4F(23C) SC 20.9 21.87 21 18.65 18.56 17.7
Input 2.42 3.42 3.81 3.3 2.54 2.45

LEGEND
DB - Dry Bulb
WB - Wet Bulb
TC - Total Net Cooling Capacity (1000 Btu/hour)
SC - Sensible Capacity (1000 Btu/hour)
Input - Total Power (kW)

8
HEATING PERFORMANCE DATA - - 38/40MAQ (HEAT PUMP)
Model Heating Outdoor conditions (DB)
38-40MAQ Indoor Conditions DB 53.6F(12C) 44.6F(7C) 39.2F(4C) 32F(0C) 24.8F(-4C) 19.4F(-7C) 17F(-8C) 5F(-15C)
TH 11.2 11.1 10.89 10.65 9.87 9.11 8.27 6.71
59F(15C)
Input 0.73 0.79 1.04 1.01 0.96 0.9 0.84 0.8
TH 11.1 10.8 10.65 10.54 9.63 8.84 8.01 5.46
64.4F(18C)
Input 0.78 0.8 1.08 1.03 0.98 0.94 0.9 0.82
09(115V)
TH 10.8 10.6 10.48 10.32 9.43 8.55 7.95 4.29
69F(20.5C)
Input 0.8 0.81 1.11 1.05 1 0.98 0.96 0.84
TH 10.6 10.3 10.21 10.11 9.23 8.41 7.89 4.11
71.6F(22C)
Input 0.82 0.83 1.15 1.07 1.02 1.02 0.92 0.86
TH 11.8 12.7 12.42 11.32 10.4 9.54 8.9 5.75
59F(15C)
Input 0.79 1.01 1.05 1.1 1.02 1 0.98 0.83
TH 12.1 12.7 12.32 11.34 10.32 9.32 8.81 6.14
64.4F(18C)
Input 0.83 1.37 1.4 1.26 1.22 1.27 1.01 0.91
12(115V)
TH 12.3 12.6 12.12 11.32 10.21 9.12 8.43 6.49
69F(20.5C)
Input 0.83 1.1 1.12 1.19 1.19 1.25 1.03 0.98
TH 11.1 12.4 12.01 11.21 10.01 9.02 8.21 6.01
71.6F(22C)
Input 0.85 1.15 1.16 1.21 1.23 1.31 1.05 1
59F(15C) TH 11.2 11.1 10.89 10.65 9.87 9.11 8.27 6.71
Input 0.73 0.79 1.04 1.01 0.96 0.9 0.84 0.8
TH 11.1 10.8 10.65 10.54 9.63 8.84 8.01 5.46
64.4F(18C)
09 Input 0.78 0.8 1.08 1.03 0.98 0.94 0.9 0.82
(208-230V) TH 10.8 10.6 10.48 10.32 9.43 8.55 7.95 4.29
69F(20.5C)
Input 0.8 0.81 1.11 1.05 1 0.98 0.96 0.84
TH 10.6 10.3 10.21 10.11 9.23 8.41 7.89 4.11
71.6F(22C)
Input 0.82 0.83 1.15 1.07 1.02 1.02 0.92 0.86
59F(15C) TH 11.8 12.7 12.42 11.32 10.4 9.54 8.9 5.75
Input 0.79 1.01 1.05 1.1 1.02 1 0.98 0.83
64.4F(18C) TH 12.1 12.7 12.32 11.34 10.32 9.32 8.81 6.14

12 Input 0.83 1.37 1.4 1.26 1.22 1.27 1.01 0.91


(208-230V) 69F(20.5C) TH 12.3 12.6 12.12 11.32 10.21 9.12 8.43 6.49
Input 0.83 1.1 1.12 1.19 1.19 1.25 1.03 0.98
71.6F(22C) TH 11.1 12.4 12.01 11.21 10.01 9.02 8.21 6.01
Input 0.85 1.15 1.16 1.21 1.23 1.31 1.05 1
59F(15C) TH 23.2 20.5 19.42 17.56 16.52 14.28 12.08 9.39
Input 1.58 1.49 1.48 1.58 1.46 1.4 1.35 1.21
64.4F(18C) TH 22.4 20.1 18.66 16.89 16.05 13.94 12.06 9.16

18 Input 1.62 1.55 1.55 1.61 1.52 1.45 1.4 1.29


(208-230V) 69F(20.5C) TH 21.7 19.7 17.93 16.26 15.62 13.62 12.07 8.95
Input 1.67 1.62 1.63 1.65 1.58 1.5 1.45 1.38
71.6F(22C) TH 21 19 17.23 15.56 14.92 12.92 11.37 8.25
Input 1.72 1.67 1.68 1.7 1.63 1.55 1.5 1.43
59F(15C) TH 28.6 27.8 25.85 23.56 23.42 23.22 23.16 18.93
Input 2 2.25 2.24 2.21 2.2 2.23 2.24 2.17
TH 27.6 27.6 24.52 23.54 23.4 22.52 20.45 17.45
64.4F(18C)
24 Input 2.24 2.45 2.35 2.35 2.32 2.23 2.21 2.16
(208-230V) TH 29.1 29.3 26.75 24.63 22.98 21.85 19.61 16.38
69F(20.5C)
Input 2.39 2.74 2.64 2.58 2.42 2.25 2.2 2.18
TH 26.9 27.5 24.21 23.41 22.54 21.67 19.54 16.24
71.6F(22C)
Input 2 2.25 2.24 2.21 2.2 2.23 2.24 2.17
TH 43 41.2 37.52 34.65 32.32 30.65 28.84 20.51
59F(15C)
Input 3.79 3.99 3.69 3.43 3.2 2.96 2.82 2.61
TH 39.6 39.9 36.55 33.84 30.95 28.58 26.47 19.96
64.4F(18C)
30 Input 3.35 4.23 3.85 3.65 3.24 3.11 3.04 2.76
(208-230V) TH 36.3 38.6 35.62 33.07 29.62 26.54 24.13 19.43
69F(20.5C)
Input 3.45 4.46 4.01 3.9 3.31 3.2 3.16 2.89
TH 32.9 35.2 32.22 29.67 26.22 23.14 20.73 16.03
71.6F(22C)
Input 3.68 4.69 4.24 4.13 3.54 3.43 3.39 3.12

LEGEND
DB - Dry Bulb
WB - Wet Bulb
TH - Total Net Heating Capacity (1000 Btu/hour)
Input - Total Power (kW)

9
APPLICATION DATA
UNIT SELECTION METERING DEVICES
Select equipment to either match or be slightly less than anticipated The outdoor unit (Sizes 09 - 18) has an electronic expansion valve
peak load. This provides better humidity control, fewer unit cycles, to manage the refrigerant flow of the fan coil connected.
and less part- load operation. Sizes 24 and 30 have capillary tube metering devices in the
For units used in spaces with high sensible loads, base equipment outdoor unit.
selection on unit sensible load, not on total anticipated load. Adjust for DRAIN CONNECTIONS
anticipated room wet bulb temperature to avoid undersizing
equipment. Install drains to meet local sanitation codes. If adequate gravity
drainage cannot be provided, unit should be equipped with
UNIT MOUNTING (INDOOR) accessory condensate pump. High wall fan coil unit condensate
Refer to unit Installation Instructions for further details. pumps have a maximum lift of 10’ (3.05 m) for 9k and 12k units
Unit leveling - For reliable operation, units should be level in all and 25’ (7.62 m) for 18k and 30k units.
planes. See physical dimension tables for drain sizes.
Clearance - Provide adequate clearance for airflow (see Fig. 2.) NOTE: High wall fan coil units have internal condensate traps.
Unit location - Select a location which will provide the best air A trap is not required.
circulation for the room. These units should be positioned as high Drain connections may be routed through alternate locations on
as possible on the wall for best air circulation. The unit return and most fan coils (see Fig. 4).
discharge should not be obstructed by furniture, curtains, or
anything which may cause unit short cycling or air recirculation. Pipe holder
Pipe cover
Place the unit in the middle of the selected wall (if possible). Use
an outside wall, if available, to make piping easier, and place the 4 Left piping
unit so it faces the normal location of room occupants. Pipe cover 3 Left back piping
UNIT MOUNTING (OUTDOOR)
Refer to unit Installation Instructions for further details. 1 2 Right back piping
Unit leveling - For reliable operation, units should be level in all Right piping
planes. Fig. 6 – Piping Locations
Clearance - Minimum clearance (see Fig. 5) must be provided
for airflow. The condensing units are designed for free- flow REFRIGERANT LINES
application. Air inlets and outlets should not be restricted. General refrigerant line sizing:
Unit location - A location which is convenient to installation and 1. The 38MAQ units are shipped with a full charge of R410A
not exposed to strong wind. A location that can bear the weight of refrigerant. All charges, line sizing, and capacities are based on
outdoor unit and where the outdoor unit can be mounted in a level runs of 25 ft (7.6 m). For runs over 25 ft (7.6 m), consult
position. long- line section on this page for proper charge adjustments.
Do not install the indoor or outdoor units in a location with special 2. Refrigerant lines should not be buried in the ground. If it is
environmental conditions. For those applications, contact your necessary to bury the lines, not more than 36- in (914 mm)
Carrier representative.
should be buried. Provide a minimum 6- in (152 mm) vertical
MOUNTING TEMPLATE rise to the service valves to prevent refrigerant migration.
Refer to unit Installation Instructions for further details. 3. Both lines must be insulated. Use a minimum of 1/2- in.
The fan coil units are furnished with mounting to mark the location (12.7 mm) thick insulation. Closed- cell insulation is
of the wiring, and refrigeration line hole locations. recommended in all long- line applications.
SUPPORT 4. Special consideration should be given to isolating
interconnecting tubing from the building structure. Isolate the
Adequate support must be provided to support the weight of all fan tubing so vibration or noise is not transmitted into the
coils. Refer to the Physical Data section for fan coil weights, and the structure.
base unit dimensional drawings for the location of mounting brackets.
Long Line Applications, 38MAQ Units:
SYSTEM OPERATING CONDITIONS 1. No change in line sizing is required.
Operating Range
Min / Max °F (°C)
2. Add refrigerant per table below.
Cooling Heating ADDITIONAL CHARGE TABLE
Outdoor DB 4 / 122 (-20 / 50) 4 / 86 (-20 / 30) Total Line Additional Charge, oz/ft.
Unit Length ft ft (m)
Indoor DB 63 / 90 (17 / 32) 32 / 86 (0 / 30) Size 10 - 25 >25 - 82 >82 - 164
Min Max
Indoor WB 59 / 84 (15 / 29) (3 - 8) (8 - 25) (25 - 50)
9
82
Non-Operating Temperature Range 12 0.16
Min / Max °F (°C) 18 10 None
98
24
Indoor/Outdoor DB 32 / 86 (0 / 30) 0.32 0.32
30 164
NOTE: Reference the Product Installation Instructions for more
information.

10
WIRING
Recommended Connection Method for Power and ! CAUTION
Communication Wiring (To minimize communication wiring
EQUIPMENT DAMAGE HAZARD
interference)
Power Wiring: Failure to follow this caution may result in equipment
damage or improper operation.
The main power is supplied to the outdoor unit. The field supplied
S Be sure to comply with local codes while running wire
connecting cable from the outdoor unit to indoor unit consists of
from indoor unit to outdoor unit.
three (3) wires and provides the power for the indoor unit. Two
wires are high voltage AC power and one is a ground wire. S Every wire must be connected firmly. Loose wiring
may cause terminal to overheat or result in unit
Consult your local building codes and the NEC (National
malfunction. A fire hazard may also exist. Therefore,
Electrical Code) or CEC (Canadian Electrical Code) for special
be sure all wiring is tightly connected.
requirements.
S No wire should be allowed to touch refrigerant tubing,
All wires must be sized per NEC or CEC and local codes. Use compressor or any moving parts.
Electrical Data table MCA (minimum circuit amps) and MOCP
S Disconnecting means must be provided and shall be
(maximum over current protection) to correctly size the wires and
located within sight and readily accessible from the air
then disconnect fuse or breakers respectively.
conditioner.
Per caution note, only copper conductors with a minimum 300 volt S Connecting cable with conduit shall be routed through
rating and 2/64- inch thick insulation must be used. hole in the conduit panel.
Communication Wiring:
The main power is supplied to the outdoor unit. The field supplied
A separate shielded copper conductor only, with a minimum 300 connecting cable from the outdoor unit to indoor unit consists of
volt rating and 2/64- inch thick insulation, must be used as the four wires and provides the power for the indoor unit as well as the
communication wire from the outdoor unit to the indoor unit. communication signal between the outdoor unit and indoor unit.
To minimize voltage drop, the factory recommended wire size is Two wires are high voltage AC power (L1 and L2), one is a
14/3 stranded with a ground. In special cases where there is high ground wire, and one is a DC communication wire.
electrical interference, please use a separate shielded 16GA
stranded control wire.
CONTROL SYSTEM
Alternate Connection Method for Power and Communication The 619P unit is equipped with a microprocessor control to
Wiring (May not prevent communication wiring interference) perform two functions:
The main power is supplied to the outdoor unit. The field 1. Provide safety for the system
supplied connecting cable from the outdoor unit to indoor unit 2. Control the system and provide optimum levels of comfort
consists of four (4) wires and provides the power and and efficiency
communication signals for the indoor unit. Two conductors are for The main microprocessor is located on the control board of the
power wiring (L1/L2, or L/N), one is a ground wire, and one is a fan coil unit (outdoor units have a microprocessor too) with
DC communication wire. thermistors located in the fan coil air inlet and on the indoor coil.
Consult your local building codes and the NEC (National Heat pump units have a thermistor on the outdoor coil. These
Electrical Code) or CEC (Canadian Electrical Code) for special thermistors monitor the system operation to maintain the unit
requirements. All power wires must be sized per NEC or CEC and within acceptable parameters and control the operating mode.
local codes. Use Electrical Data table MCA (minimum circuit WIRELESS REMOTE CONTROL
amps) and MOCP (maximum over current protection) to correctly
size the wires and the disconnect fuse or breakers respectively.
Per caution note, only copper conductors with a minimum 300 volt
rating and 2/64- inch thick insulation must be used.

! CAUTION
EQUIPMENT DAMAGE HAZARD
Fig. 7 – Wireless remote control
Failure to follow this caution may result in equipment
1. A wireless remote control is supplied for system operation
damage or improper operation.
for system operation of all high- wall units.
S Wires should be sized based on NEC and local codes. 2. Each battery operated wireless (infrared) remote control
S Use copper conductors only with a minimum 300 volt may be used to control more than one unit.
rating and 2/64 inch thick insulation.
WIRED REMOTE CONTROL (OPTIONAL)
P/N KSACN0101AAA
1. Optional wired remote controller used
for system operation of all high- wall
units.
2. Kit includes a wired remote controller
and a connecting cable.
3. Connect with wire terminal between
remote controller and indoor unit.
4. Display in _F or _C and temperature
increments every 1_F or every 1_C.
Fig. 8 – Wired Remote Control

11
AIR FLOW DATA
SYSTEM SIZE 9K 12K 9K 12K 18K 24K 30K
(115V) (115V) (208-230V) (208-230V) (208-230V) (208-230V) (208-230V)
Turbo 380 380 380 380 680 870 870
High 360 360 360 360 650 780 780
Indoor (CFM)
Medium 290 300 290 300 450 620 620
Low 210 210 210 210 310 520 520
Outdoor
1200 1200 1200 1200 1390 2130 2130
(CFM)

AIR THROW DATA


Unit Capacity Max Approximate Air Throw ft. (m) Approximate Air Throw ft. (m) range
9K, 12K 23 (7) 11 (3.5) - 23 (7)
18K 30 (9) 13 (4) - 30 (9)
24K 36 (11) 16 (5) - 36 (11)
30K 36 (11) 16 (5) - 36 (11)

SOUND PRESSURE
9K 12K 9K 12K 18K 24K 30K
System Size
(115V) (115V) (208-230V) (208-230V) (208-230V) (208-230V) (208-230V)
Indoor Sound Pressure cooling mode (at
dBa 42/34/27 42/34/27 42/34/27 42/34/27 46.5/40/33 50/45/39 50/45/39
different speeds)
Indoor Sound Pressure heating mode (at
dBa 40/33/26 41/34/27 40/33/26 41/34/27 45/39/32 47/44/38 47/44/38
different speeds)
Outdoor sound pressure level dBa 55.5 56 55.5 56 59 60 63

ELECTRICAL DATA
UNIT OPER. VOLTAGE COMPRESSOR OUTDOOR FAN INDOOR FAN MAX FUSE
MCA
SIZE MAX / MIN* V/PH/HZ RLA V/PH/HZ FLA HP W V/PH/HZ FLA HP W CB AMP
9K 5.3
127 / 104 115/1/60 115/1/60 0.14 0.053 40 115/1/60 0.17 0.027 20 15 20
12K 5.7
9K 5.3 0.42 0.053 40 0.07 0.027 20 15
15
12K 5.70 0.42 0.053 40 0.07 0.027 20 15
18K 253 / 187 208-230/1/60 7.3 208-230/1/60 0.95 0.067 50 208-230/1/60 0.17 0.077 58 15 20
24K 8.8 0.47 0.16 120 0.23 0.080 60 15 25
30K 13.5 1.21 0.16 120 0.23 0.080 60 20 30
*Permissible limits of the voltage range at which the unit will operate satisfactorily.
LEGEND
FLA - Full Load Amps
MCA - Minimum Circuit Amps
RLA - Rated Load Amps

12
FAN AND MOTOR SPECIFICATIONS
9K 12K 9K 12K 18K 24K 30K
System size
(115V) (115V) (208-230V) (208-230V) (208-230V) (208-230V) (208-230V)
material AS AS AS AS AS AS AS
Indoor fan
Type GL-98*655-N GL-98*655-N GL-98*655-N GL-98*655-N GL-107.5*760-IN GL-118*895-IN GL-118*895-IN
Diameter inch 3.8 3.8 3.8 3.8 4.2 4.6 4.6
Indoor fan
Height inch 25.8 25.8 25.8 25.8 30 35.2 35.2
material AS AS AS AS AS AS AS

Outdoor Type ZL-421*117*8-3K ZL-421*117*8-3K ZL-421*117*8-3K ZL-421*117*8-3K ZL-460*180*10-3N ZL-560*139*12-3KN ZL-560*139*12-3KN


fan Diameter inch 16.5 16.5 16.5 16.5 18.1 22 22
Height inch 4.6 4.6 4.6 4.6 7 5.5 5.5
Model WZDK20-38M WZDK20-38M WZDK20-38G WZDK20-38G WZDK58-38G WZDK60-38G WZDK60-38G
Type DC DC DC DC DC DC DC
Phase 3 3 3 3 3 3 3
FLA 0.17 0.17 0.07 0.07 0.17 0.23 0.23
Insulation class E E E E E E E
Safe class IPX0 IPX0 IPX0 IPX0 IPX0 IPX0 IPX0
Input W 25 25 22 22 52 72 72

Indoor fan Output W 20 20 20 20 58 60 60


motor Range of
Amps 0.17±10% 0.17±10% 0.07±10% 0.07±10% 0.17±10% 0.23±10% 0.23±10%
current
Rated current Amps 0.17 0.17 0.07 0.07 0.17 0.23 0.23
Rated HP HP 0.027 0.027 0.027 0.027 0.077 0.08 0.08
rev/mi
Speed 1300/1170/900/700 1300/1170/900/700 1300/1170/900/700 1300/1170/900/700 1300/1170/900/700 1250/1200/1100/900 250/1200/1100/900
n
rev/mi
Rated RPM 1350 1350 1350 1350 1350 1350 1350
n
Max. input W 25 25 22 22 52 72 72
Model WZDK40-38G-1 WZDK40-38G-1 WZDK40-38G-W-1 WZDK40-38G-W-1 ZKFN-50-8-2 WZDK120-38G-1 WZDK120-38G-W
Phase 3 3 3 3 3 3 3
FLA 0.14 0.14 0.42 0.42 0.95 0.47 1.21
Type DC DC DC DC DC DC DC
Insulation class E E E E E E E
Safe class IPX0 IPX0 IPX0 IPX0 IPX0 IPX0 IPX0
Input W 42 42 46 46 116 145 150

Outdoor Output W 40 40 40 40 50 120 120


fan motor Range of
Amps 0.14±10% 0.14±10% 0.42±10% 0.42±10% 0.95±10% 0.47±10% 1.21±10%
current
Rated current Amps 0.14 0.14 0.42 0.42 0.95 0.47 1.21
Rated HP HP 0.053 0.053 0.053 0.053 0.067 0.16 0.16
rev/mi
Speed 800/700/600 800/700/600 800/700/600 800/700/600 800/700/600 850/750/700 850/800/750
n
rev/mi
Rated RPM 900 900 900 900 900 1050 1050
n
Max. input W 42 42 46 46 116 145 150

13
WIRING DIAGRAMS
INDOOR UNIT
+($7(;&+$1*(56(1625
%/$&.
EXPANSIVE VALVE $0%,(176(1625
:+,7(

6(5)
,1)$1 M
CN16 CN15 CN31 BLACK
CN1 HEATER, CRANKCASE
',6&+$5*(6(1625 CN32 RED M

 

6:,1*02725
CN33 BLACK
HEATER, CRANKCASE 5
U CN34 RED
BLUE U
V RED
W V Dashed frame CN4 P_1 CN5
BLACK W 287'225 CN28 parts only for heat 52207(03(5$785(6(1625
:$<
CN26 pump model. &1
0$,1
3&% RY3 3,3(7(03(5$785(6(1625
RED &1
L2 CN2
&2035(6625 CN7 YELLOW BLUE(BLACK)
CS L-IN
CN5 BLUE YELLOW CN11
4 %/8( Y/G N
Y/G CN4 BROWN
5('
&1$
BLUE CN6 6
N-A &1

/ 1 6 / 1 CN16 OPTIONAL
L N S JX1
INDOOR UNIT Wi-Fi
Y/G Contoller
N-B CN10(CN19) Y/G ',63/$<%2$5'
8(7)
N OUTDOOR UNIT &1 
&1
L-A(CN37) L-B(CN36) CN8 CN9 L INDOOR WIRING DIAGRAM  OPTIONAL
Wire Contoller
Power Input

BLACK BLACK RED RED


Y/G
5
L N S GND

5($&725 287'225
&$3$&,725 )$1

287'225:,5,1*',$*5$0

14
Fig. 9 – Wiring Diagram Sizes 09- 12 (115V)
INDOOR UNIT CONTROL BOARD
INPUT or OUTPUT VALUE
L_IN Power Voltage :AC 115V
CN11 Power Voltage :AC115V
CN16 Relative to the N terminal voltage:DC 24V
CN15 Maximum voltage:DC5V
CN4 Indoor fan interface,Maximum voltage:DC310V
CN5 Stepper motor interface,Maximum voltage between the lines:DC12V
P_1 Ground
CN8 Room temperature sensor interface,maximum voltage:DC5V
CN9 Pipe temperature sensor interface,maximum voltage:DC5V
CN10A Display interface,maximum voltage between the lines:DC5V

OUTDOOR UNIT CONTROL BOARD


CODE PART NAME
CN1 Output:Pin5&6(12V) Pin1-Pin4:Pulse waveform,(0-12V)
CN15 Input:Pin1-Pin2(0-1.8V)
CN16 Input: Pin1,Pin3 ,Pin4,Pin5(0-1.8V)
CN19 Output:Pin1-Pin5(0-115V High voltage)
CN31,CN33 Output:115VAC High voltage
CN32,CN34 Output:115 VAC High voltage
CN26,CN28 Output:115 VAC for 4-way control
CN4 Input:115 VAC High voltage
CN5 Input:115 VAC High voltage
CN6 Connection to the earth
CN7 Output: Connection of the high voltage
CN8,CN9 Output: High voltage
CN36,CN37 Output: High voltage
N-B Output: High voltage
UV W Output: Pulse(0-320VDC)
COMPRESSOR
&21'(16(5 ,1)$1 M
7(03(5$785(6(1625

BLUE

BLACK
RED
DISCHARGE SENSOR
AMBIENT SENSOR
 
(/(&7521,&

6:,1*02725
(;3$16,9( HEATER, CRANKCASE
 9$/9( 5

CN33
CN28 CN29 CN30 CN22 CN21 CN31 HEATER, CRANKCASE CN4 P_1 CN5
52207(03(5$785(6(1625
&1

OPTIONAL:
CN26 :$<
RED
CN2

:$<
CN27
BLUE(BLACK) L-IN 3,3( 7(03(5$785( 6(1625
CN16 YELLOW YELLOW &1
%/8( CN11
CN1
BLUE Y/G N
CN9-1 CN32-1 BROWN
CN3 CN2 RED
CN7 &1$
6
 L1 L2 S L1 L2
&1

WHITE WHITE CN16 OPTIONAL
Y/G L1L2 S JX1
DC-FAN Y/G INDOOR UNIT Wi-Fi
L2 ',63/$<%2$5' Contoller
L1 8(7)
OUTDOOR UNIT &1 &1

REACTOR Power Input INDOOR WIRING DIAGRAM  OPTIONAL
Wire Contoller

Y/G
L1 L2 S GND

15
Fig. 10 – Wiring Diagram Sizes 09- 12 (208- 230V)
INDOOR UNIT CONTROL BOARD
INPUT or OUTPUT VALUE
L_IN Power Voltage :AC 230V
CN11 Power Voltage :AC230V
CN16 Relative to the N terminal voltage:DC 24V
CN15 Maximum voltage:DC5V
CN4 Indoor fan interface,Maximum voltage:DC310V
CN5 Stepper motor interface,Maximum voltage between the lines:DC12V
P_1 Ground
CN8 Room temperature sensor interface,maximum voltage:DC5V
CN9 Pipe temperature sensor interface,maximum voltage:DC5V
CN10A Display interface,maximum voltage between the lines:DC5V

OUTDOOR UNIT CONTROL BOARD


INPUT or OUTPUT VALUE
CN31 Output:Pin5&6(12V) Pin1-Pin4:Pulse waveform,(0-12V)
CN21 Input:Pin3-4 (3.3V) Pin2(0V),Pin1,Pin5(0-3.3V)
CN22 Input:Pin1 (3.3V) Pin2(0-3.3V)
CN37 Output: 230VAC High voltage
CN9-1,CN32-1 Output: Connection of the high voltage
CN1 Input:230VAC High voltage
CN2 Input:230 VAC High voltage
CN3 Connection to the earth
CN16 Output: Connection of the high voltage
CN26,CN27 Output: High voltage for 4-way control
CN7 Output: Pulse(0-320VDC) for DC FAN
U V W Output: Pulse(0-320VDC) for COMPRESSOR
OUT DOOR
FAN

HEATER 1 CN414

,1)$1 M
&1 +($7 CN15
HEATER 2 L-OUT M
BLUE
CN13

 

6:,1*02725
RY1 CN12 5
BLUE

CN3 5($&725
BLUE

4-WAY
CN4 BLUE 1 CN4 P_1
OUTDOOR U CN5
CN14 RED 52207(03(5$785(6(1625
RED V 2
RED CN8 MAIN BLACK &1
BLACK BLACK W 3
CN7 PCB
YELLOW CN2
RED
CN6 CN6-1 CN18 CN1 CN10 W V U CN2
BLUE(BLACK) L-IN 3,3( 7(03(5$785( 6(1625
COMPRESSOR YELLOW &1
CN11
6 WHITE BLACK
Y/G N
Y/G &1$
6
Y/G &1

RED &21'(16(5 Y/G CN16 OPTIONAL
OUTDOORAMBIENT 7(03(5$785(6(1625
',6&+$5*(6(1625 L1 L2 S JX1
BLUE ELECTRONIC Wi-Fi
EXPANSIVE TEMPERATURE SENSOR INDOOR UNIT
VALVE ',63/$<%2$5' Contoller
8(7)
/ / 6 / / OUTDOOR UNIT &1 &1

INDOOR WIRING DIAGRAM  OPTIONAL
Wire Contoller
Y/G
/ /
72,1'22581,7 32:(56833/<

16
Fig. 11 – Wiring Diagram Size 18 (208- 230V)
INDOOR UNIT CONTROL BOARD
INPUT or OUTPUT VALUE
L_IN Power Voltage :AC 230V
CN11 Power Voltage :AC230V
CN16 Relative to the N terminal voltage:DC 24V
CN15 Maximum voltage:DC5V
CN4 Indoor fan interface,Maximum voltage:DC310V
CN5 Stepper motor interface,Maximum voltage between the lines:DC12V
P_1 Ground
CN8 Room temperature sensor interface,maximum voltage:DC5V
CN9 Pipe temperature sensor interface,maximum voltage:DC5V
CN10A Display interface,maximum voltage between the lines:DC5V

OUTDOOR UNIT CONTROL BOARD


INPUT or OUTPUT VALUE
CN7、 CN8 Input: 230V High voltage
CN2 Output: Connection of the high voltage
CN3、 CN4 Output: High voltage for 4-way control
CN11、 CN16 Output: 230V High voltage for HEATER
CN5 Output: Pulse(0-320V) for DC FAN
CN12、 CN13 Output: Connection of the high voltage
U V W Output: Pulse(0-320V) for compressor
CN10 Input:Pin1 (5V) Pin2(0-5V)
CN1 Input:Pin3-4 (5V) Pin2(0V),Pin1,Pin5(0-5V)
CN18 Output:Pin5&6(12V) Pin1-Pin4:Pulse waveform,(0-12V)
%/8(

5('

287'225$0%,(17
7 7(03(5$785(6(1625

&1
&7 7 &21'(16(5
1287 7(03(5$785(6(1625
L-OUT

&1
& 1 &1  ,30%2$5' ',6&+$5*(6(1625
21 
&20  ,1)$1 M
5< 0$,1%2$5' 
 '&)$1

&1
a a &1
M

&1
&1 &1
2  

6:,1*02725
&1  5

&1
5('
&1
%/8( %/8(
%/8( &1 CN4

&1
8 9 : P_1 CN5
52207(03(5$785(6(1625
*1' /,1 1,1 S &1
%/8( 5(' %/$&. 3 &1 &1 CN10
:$< +($7 +($7
&1 &1 &1 &1 &1 &1
RED
RED BLACK CN2
BLUE(BLACK) L-IN 3,3( 7(03(5$785( 6(1625
YELLOW CN11 &1
YELLOW
Y/G N
5($&725 Y/G
RED
&1$
6
96 :& BL ACK &1

85 CN16 OPTIONAL
L1L2 S JX1
Wi-Fi

:$<
INDOOR UNIT

+($7(5

+($7(5
/ / 6 / / ',63/$<%2$5' Contoller
&2035(6625 8(7)
OUTDOOR UNIT &1
&1 
INDOOR WIRING DIAGRAM  OPTIONAL
Wire Contoller
Y/G / / S / /
<* 72,1'22581,7 32:(56833/<

17
Fig. 12 – Wiring Diagram Size 24 (208- 230V)
INDOOR UNIT CONTROL BOARD
INPUT or OUTPUT VALUE
L_IN Power Voltage :AC 230V
CN11 Power Voltage :AC230V
CN16 Relative to the N terminal voltage:DC 24V
CN15 Maximum voltage:DC5V
CN4 Indoor fan interface,Maximum voltage:DC310V
CN5 Stepper motor interface,Maximum voltage between the lines:DC12V
P_1 Ground
CN8 Room temperature sensor interface,maximum voltage:DC5V
CN9 Pipe temperature sensor interface,maximum voltage:DC5V
CN10A Display interface,maximum voltage between the lines:DC5V
OUTDOOR UNIT CONTROL BOARD
INPUT or OUTPUT VALUE
L_IN Power Voltage :AC 230V
CN11 Power Voltage :AC230V
CN16 Relative to the N terminal voltage:DC 24V
CN15 Maximum voltage:DC5V
CN6 Maximum output voltage :AC230V
CN4 Indoor fan interface,Maximum voltage:DC310V
CN5 Stepper motor interface,Maximum voltage between the lines:DC12V
P_1 Ground
CN8 Room temperature sensor interface,maximum voltage:DC5V
CN9 Pipe temperature sensor interface,maximum voltage:DC5V
CN10A Display interface,maximum voltage between the lines:DC5V
CN14 Stepper motor interface (optional),maximum voltage between the lines:DC12V
,1)$1 M


BLACK M
W
RED

 

6:,1*02725
COMP V TP 5
BLUE Applicable to the units
U adopting DC motor only
Y/G

Y/G
CN4 P_1
FM1 CN5
52207(03(5$785(6(1625
&1

 

RED
CN2
7 CN33 CN12 CN11 BLUE(BLACK) L-IN 3,3( 7(03(5$785( 6(1625
&1

CN55
YELLOW

CN19
CN11
Y/G N
W &1$
BLACK CN3 6
SV 
&1
V CN16 OPTIONAL
YELLOW L1L2 S JX1

WAY1
RED
CN4 S Wi-Fi
U INDOOR UNIT
DRIVER BOARD BLUE BLACK ',63/$<%2$5' Contoller
HEAT1 CN2 8(7)
RED CN10 OUTDOOR UNIT &1 &1

CN54 OPTIONAL
INDOOR WIRING DIAGRAM 
The electric heating CN22 Wire Contoller
belt of compressor CN1
BLUE RED
CN51 CN40
CN44
BLACK
CN53 HEAT2 The electric heating
belt of chassis
BLUE
MAIN BOARD P-1
CN52 Y/G
T3

CN8
T4
H-PRO

CN9
BLACK
CN5
L-PRO
CN6

CN7
YELLOW YELLOW 7 RED

5('
%/$&.
<(//2:
CODE PART NAME
COMP COMPRESSOR %/$&.
5('
FM1 OUTDOOR DC FAN
-;, / L2 S L1 L2
HEAT CRANKCASE HEATING

H-PRO HIGH PRESSURE SWITCH


<* 72,1'22581,7 32:(56833/<
L PFC INDUCTOR
L-PRO LOW PRESSURE SWITCH
SV 4-WAY VALVE
TP EXHAUST
TEMPERATURE SENSOR

T3 CONDENSER
TEMPERATURE SENSOR

OUTDOOR AMBIENT
T4 TEMPERATURE SENSOR

18
Fig. 13 – Wiring Diagram Size 30 (208- 230V)
INDOOR UNIT CONTROL BOARD
INPUT or OUTPUT VALUE
L_IN Power Voltage :AC 230V
CN11 Power Voltage :AC230V
CN16 Relative to the N terminal voltage:DC 24V
CN15 Maximum voltage:DC5V
CN4 Indoor fan interface,Maximum voltage:DC310V
CN5 Stepper motor interface,Maximum voltage between the lines:DC12V
P_1 Ground
CN8 Room temperature sensor interface,maximum voltage:DC5V
CN9 Pipe temperature sensor interface,maximum voltage:DC5V
CN10A Display interface,maximum voltage between the lines:DC5V
OUTDOOR UNIT CONTROL BOARD
INPUT or OUTPUT VALUE
CN1、 CN2 Input: 230V High voltage
S Output: Connection of the high voltage
CN11、 CN12 Output: Pulse(0-320V) for DC FAN
CN33 Input:Pin1 (5V) Pin2(0-5V)
CN3、 CN22 Output: High voltage for 4-way control
CN4、 CN40 Output: 230V High voltage for HEATER1
CN10、 CN44 Output: 230V High voltage for HEATER2
CN8 Input:Pin3-4 (5V) Pin2(0V),Pin1,Pin5(0-5V)
CN9 Input:Pin1~3 (0V) Pin2~4(0-5V)
CN51 CN52 Output: Connection of the high voltage
U V W Output: Pulse(0-380V) for compressor
GUIDE SPECIFICATIONS
INDOOR WALL- MOUNTED DUCTLESS UNITS
Size Range: 3/4 to 2 1/2 Ton Nominal Cooling and Heating Capacity
Carrier Model Number: 40MAQ

PART 1 - GENERAL The unit shall have the following functions as a minimum:
1. An automatic restart after power failure at the same
1.01 System Description operating conditions as at failure.
Indoor, wall- mounted, direct- expansion fan coils are matched with 2. A timer function to provide a minimum 24- hour timer
the heat pump outdoor unit. cycle for system Auto Start/Stop.
1.02 Agency Listings 3. Temperature- sensing controls shall sense return air
Unit shall be rated per AHRI Standards 210/240 and listed in the temperature.
AHRI directory as a matched system. 4. Indoor coil freeze protection.
1.03 Delivery, Storage, And Handling 5. Wireless infrared remote control to enter set points and
Units shall be stored and handled per unit manufacturer’s operating conditions.
recommendations. 6. Automatic air sweep control to provide on or off activation
1.04 Warranty (For Inclusion By Specifying of air sweep louvers.
Engineer) 7. Dehumidification mode shall provide increased latent
removal capability by modulating system operation and set
point temperature.
PART 2 - PRODUCTS 8. Fan- only operation to provide room air circulation when no
2.01 Equipment cooling is required.
A. General: 9. Diagnostics shall provide continuous checks of unit
Indoor, direct- expansion, wall- mounted fan coil. Unit shall be operation and warn of possible malfunctions. Error
complete with cooling/heating coil, fan, fan motor, piping messages shall be displayed at the unit.
connectors, electrical controls, microprocessor control system, and 10. Fan speed control shall be user- selectable: turbo, high,
integral temperature sensing. Unit shall be furnished with integral medium, low, or microprocessor controlled automatic
wall mounting bracket and mounting hardware. operation during all operating modes.
B. Unit Cabinet: 11. Automatic heating- to- cooling changeover in heat pump
Cabinet discharge and inlet grilles shall be attractively styled, mode. Control shall include deadband to prevent rapid
high- impact polystyrene. Cabinet shall be fully insulated for mode cycling between heating and cooling.
improved thermal and acoustic performance. 12. Indoor coil high temperature protection shall be provided to
C. Fans: detect excessive indoor discharge temperature when unit is
1. Fan shall be tangential direct- drive blower type with air in heat pump mode.
intake at the top of the unit and discharge at the bottom G. Filters:
front. Automatic, motor- driven vertical air sweep shall be Unit shall have filter track with factory- supplied cleanable filters.
provided standard. H. Electrical Requirements:
2. Air sweep operation shall be user selectable. The vertical Indoor fan motor to operate on 115V on model sizes 09- 12 and on
sweep may be adjusted (using the remote control) and the 208- 230V on model sizes 09- 30, as specified. Power is supplied
horizontal air direction may be set manually. from the outdoor unit.
D. Coil: I. Operating Characteristics:
Coil shall be copper tube with aluminum fins and galvanized steel The 40MA system shall have a minimum SEER (Seasonal Energy
tube sheets. Fins shall be bonded to the tubes by mechanical Efficiency Ratio) and HSPF at AHRI conditions, as listed on the
expansion. A drip pan under the coil shall have a drain connection for specifications table.
hose attachment to remove condensate. Condensate pan shall have
J. Refrigerant Lines:
internal trap.
All units should have refrigerant lines that can be oriented to
E. Motors:
connect from the left, right or back of unit. Both refrigerant lines
Motors shall be open drip- proof, permanently lubricated ball need to be insulated.
bearing with inherent overload protection. Fan motors shall be
K. Special Features (Field Installed):
4- speed.
1. Condensate Pump:
F. Controls:
- The condensate pump shall remove condensate from the
Controls shall consist of a microprocessor- based control system drain pan when gravity drainage cannot be used. Pump
which shall control space temperature, determine optimum fan shall be designed for quiet operation. Pump shall consist of
speed, and run self diagnostics. The temperature control range two parts: an internal reservoir/sensor assembly, and a
shall be from 62_F to 86_F (17_C to 30_C) in increments of 1_F remote sound- shielded pump assembly. A liquid level
or 1_C, and have 46_F Heating Mode (Heating Setback). The sensor in the reservoir shall stop cooling operation if the
wireless remote controller shall have the ability to act as the
liquid level in the reservoir is unacceptable.
temperature sensing location for room comfort.

19
GUIDE SPECIFICATIONS
HORIZONTAL DISCHARGE OUTDOOR UNITS
Size Range: 3/4 to 2 1/2 Ton Nominal Cooling and Heating Capacity
Carrier Model Number:38MAQ
PART 1 - GENERAL 3. Shaft shall have inherent corrosion resistance.
4. Fan blades shall be non metallic and shall be statically and
1.01 System Description dynamically balanced.
A. Outdoor air- cooled split system compressor sections suitable
5. Outdoor fan openings shall be equipped with PVC
for on- the- ground, rooftop, wall hung or balcony mounting.
metal/mesh coated protection grille over fan.
Units shall consist of a rotary compressor, an air- cooled coil,
D. Compressor:
propeller- type draw- through outdoor fan, reversing valve
(HP), accumulator (HP units), metering device(s), and control 1. Compressor shall be fully hermetic rotary type.
box. Units shall discharge air horizontally as shown on the 2. Compressor shall be equipped with oil system, operating oil
contract drawings. Units shall function as the outdoor charge, and motor. Internal overloads shall protect the
component of an air- to- air heat pump system. compressor from over- temperature and over- current.
B. Units shall be used in a refrigeration circuit matched to ductless 3. Motor shall be NEMA rated class F, suitable for operation
heat pump fan coil units. in a refrigerant atmosphere.
1.02 Agency Listings 4. Compressor assembly shall be installed on rubber vibration
isolators.
A. Unit construction shall comply with ANSI/ASHRAE 15, latest
revision, and with the NEC. 5. Compressors shall be single phase.
B. Units shall be evaluated in accordance with UL standard 1995. E. Outdoor Coil:
C. Units shall be listed in the CEC directory. Coil shall be constructed of aluminum fins mechanically bonded to
seamless copper tubes, which are cleaned, dehydrated, and sealed.
D. Unit cabinet shall be capable of withstanding 500- hour salt
spray test per Federal Test Standard No. 141 (method 6061). F. Refrigeration Components:
E. Air- cooled condenser coils shall be leak tested at 550 psig. Refrigerant circuit components shall include brass external liquid
line service valve with service gage port connections, suction line
1.03 Delivery, Storage, And Handling service valve with service gage connection port, service gage port
Units shall be shipped in one piece and shall be stored and handled connections on compressor suction and discharge lines with
per unit manufacturer’s recommendations. Schrader type fittings with brass caps, accumulator, reversing
valve.
1.04 Warranty (For Inclusion By Specifying
G. Controls and Safeties:
Engineer)
Operating controls and safeties shall be factory selected, assembled,
and tested. The minimum control functions shall include the
PART 2 - PRODUCTS following:
2.01 Equipment 1. Controls:
A. General: a. A time delay control sequence is provided standard through
Factory assembled, single piece, air- cooled outdoor unit. the fan coil board.
Contained within the unit enclosure shall be all factory wiring, b. Automatic outdoor- fan motor protection.
piping, controls, and the compressor. 2. Safeties:
B. Unit Cabinet: a. System diagnostics.
1. Unit cabinet shall be constructed of galvanized steel, b. Compressor motor current and temperature overload
bonderized and coated with a baked- enamel finish on protection.
inside and outside. c. Outdoor fan failure protection.
2. Unit access panels shall be removable with minimal screws H. Electrical Requirements:
and shall provide full access to the compressor, fan, and
1. Unit shall operate on single- phase, 60 Hz power at 115 v
control components.
for unit sizes 09- 12 and 208- 230v for unit sizes 09, 12, 18,
3. Outdoor compartment shall be isolated and have an acoustic 24, and 30, as specified.
lining to assure quiet operation.
2. Unit electrical power shall be a single point connection.
C. Fans:
3. Unit Control voltage to the indoor fan coil shall be 0- 15V DC.
1. Outdoor fans shall be direct- drive propeller type, and shall
4. All power and control wiring must be installed per NEC
discharge air horizontally. Fans shall draw air through the
and all local electrical codes.
outdoor coil.
5. Unit shall have high- and low- voltage terminal block
2. Outdoor fan motors shall be totally- enclosed, single phase
connections.
motors with class B insulation and permanently- lubricated
ball bearings. Motor shall be protected by internal thermal
overload protection.

Carrier 2015 Corp D 7310 W. Morris St. D Indianapolis, IN 46231 Edition Date: 05/15 Catalog No: 38- 40MA- 02PD

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. Replaces: 38- 40MA- 01PD