DX Coil circuiting-Model

The document provides detailed pipe connection specifications for a Fresh Air Handling Unit (FAHU), including sizes for suction and liquid lines for different models. It emphasizes the importance of proper installation techniques for expansion valves and remote bulbs, as well as guidelines for connecting equalizer lines. Recommended pipe sizes are given for specific interconnection distances and configurations.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
21 views

DX Coil circuiting-Model

The document provides detailed pipe connection specifications for a Fresh Air Handling Unit (FAHU), including sizes for suction and liquid lines for different models. It emphasizes the importance of proper installation techniques for expansion valves and remote bulbs, as well as guidelines for connecting equalizer lines. Recommended pipe sizes are given for specific interconnection distances and configurations.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

PIPE CONNECTION DETAILS FOR FAHU

t
Gas ou on
ti
connec Liquid line connection

SV

D3 TXV SG DRIER
6

FPC 30ZE
Liquid line connection

SV

D4 TXV SG DRIER

Liquid line connection

SV
FAHU-01

D5 TXV SG DRIER

FPC 30ZE
Liquid line connection

SV

D6 TXV SG DRIER

Liquid line connection

SV

D7 TXV SG DRIER

FPC 25ZE
Liquid line connection

SV

D8 TXV SG DRIER

CU - CONDENSING UNIT
TXV - EXPANSION VALVE
NOTE:- Important to install Expansion Valve
D - DISTRIBUTOR
01) Always direct torch flame away from valve body when brazing and wrap expansion valve body with wet rag
02) Valves may be installed in any position, but should be located as close as possible to the distributor or evaporator inlet SG - SIGHT GLASS
SV
03) Attach the remote bulb to the suction line as close to the evaporator outlet as possible on a horizontal run. Position the bulb - Solenoid Valve
at the 3 or 4 o’clock position.
Clean surface of suction line where the remote bulb is to be attached, and then securely fasten the bulb with straps provided. - Ball Valve
04) Connect one end of the external equalizer line to the valve. Connect the other end to the suction line
slightly downstream from the remote bulb location and positioned so that it cannot siphon oil from the Ball Valve for suction line & solenoid valve for
suction line liquid line by MEP contractor

Suction line SIze : 1 5/8" x 4 Nos (FPC 30ZE) ; 1 3/8" x 2 No (FPC25ZE).


Liquid LIne Size : 7/8" x 4 Nos (FPC 30ZE); 5/8" x 2 No (FPC25ZE).
Above pipe size are recommneded for 20 mtrs. of maximum interconnection
distance between IDU & ODU and considering 6 elbows in the line.