0% found this document useful (0 votes)
6 views

NDM3-800 product specification

The document provides specifications for the Molded Case Circuit Breaker (MCCB) model NDM3-800, including its electrical characteristics, installation modes, and operational parameters. It details the product's rated current, insulation voltage, and environmental conditions for operation and storage. Additionally, it outlines the necessary precautions and accessories for installation and use.

Uploaded by

zaeem aslam
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
6 views

NDM3-800 product specification

The document provides specifications for the Molded Case Circuit Breaker (MCCB) model NDM3-800, including its electrical characteristics, installation modes, and operational parameters. It details the product's rated current, insulation voltage, and environmental conditions for operation and storage. Additionally, it outlines the necessary precautions and accessories for installation and use.

Uploaded by

zaeem aslam
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 9

www.sh-liangxin.

com

Product Specifications

Product name: Molded Case Circuit Breaker (MCCB)

Product model: NDM3-800

Date: 20150430

Prepared by Reviewed by Approved by

Peng Haoran Hu Qi CaiYuchang

Address: No. 668, Hengan Road, Pudong New District, Shanghai Zip Code: 200137 Tel.: (021) 68586699 Fax:
(021) 23025796
LX7.201R-14B
Document Implementat
NDT500264 Version 1 20160630
No. ion date

Revision History

Revision
Version Revision Content Revised By
Date

0 New addition 20111106 Xu Saijin

1 Update version 20150430 Peng Haoran

2 Update version 20160601 Peng Haoran

Page 2 of 8
Document Implementat
NDT500264 Version 1 20160630
No. ion date
1. Applicable Scope and Purpose
NDM3 series of molded case products apply to infrequent switching of circuits with the
AC 50Hz (or 60Hz), the rated working voltage of 400V and rated working current of 800A as well
as infrequent motor starting. With the overload, short circuit and undervoltage protection
functions, the circuit breaker can protect lines and power equipment from damage.

2. Picture of the Product

3. Model Instructions
ND M 3 -800 □ □ / □ □ □□ □ □ □ (□ □)
Product type (Note 8)
Remark on detailed accessory specifications (Note 7)
Remark on detailed accessory specifications (Note 6)

Rated current 630/700/800A


Neutral pole-N-pole type of the 4P product (Note 5)

Application code (Note 4)


Accessory code (see Table 1)
Release code(Note 3)
Number of poles: 3P, 4P
Operation mode (Note 2)
Rated limit short-circuit breaking capacity of 3P products (Note 1)

Design SN
Molded case circuit breaker (MCCB)
Nader brand low-voltage apparatus
Page 3 of 8
Document Implementat
NDT500264 Version 1 20160630
No. ion date
Note 1: Rated limit short-circuit breaking capacity of 3P products:
C: Basic type L: Standard type, M: Relatively high breaking type, H: High breaking type;
Note 2: Operation mode:
No code is available for the direct handle-operated mode
P: Motor-operated
Z: Rotation handle;
Note 3: Release code:
0: Tripper (none)
2: Instantaneous tripper only
3: Complex tripper;
Note 4: Application code
No code is available for the circuit breaker for distribution
2: Protection motor type;
Note 5: The neutral pole-N-pole type of the 4P product is divided into three types:
Type A: The N-pole isn't installed with an overcurrent tripper, but always connected;
Type B: The N-pole isn't installed with an overcurrent tripper, but on-off with the other
three poles;
Type C: The N-pole is installed with an overcurrent tripper, and on-off with the other
three poles.
Note 6: Remark on detailed accessory specifications
1. Detailed description of connection-type or rotation handle:
① Normal products are uncoded;
② P: Extended connection busbar;
③ H: Rear-plate connection
④ Z1: Plug-in rear-plate connection
⑤ Z2: Plug-in front-plate connection
For example: NDM3-400M/3300 400A (plug-in rear-plate connection),
NDM3-400LZ/3321 400A(CS1-A),
NDM3-400M/33002 400A(connection busbar), etc.
Note 7: Indicate the accessory voltage; the voltage of the electric operating mechanism,
undervoltage tripper and shunt tripper shall be indicated temporarily:
① The voltage of the electric operating mechanism is represented as CD2 space+voltage:
For example NDM3-400LP/3020 400A (CD2 DC24V),
② If only the voltage exists in the (), the voltage of the shunt tripper or undervoltage
tripper from the accessories is indicated in default,
For example: NDM3-400L/3341 400A (AC220V) (Dedicated for electric power)
③ If the shunt tripper or undervoltage tripper exists simultaneously with the different
voltage, it shall be clearly marked in front of the voltage,
For example: NDM3-400M/3350 400A(MX AC220V+Q AC380V) (Dedicated for electric power),
MX and Q represent the shunt tripper and undervoltage tripper
respectively.
Note 8: Product type
Normal products are uncoded
DL: Dedicated power products
Page 4 of 8
Document Implementat
NDT500264 Version 1 20160630
No. ion date

4.Main Technical Parameters


(1).Electrical characteristics
▲ Rated insulation voltage Ui: 1000V
▲ Rated working voltage Ue: AC 380/400/415V 660/690V
▲ Rated current of housing Inm: 800A
▲ Rated limit short-circuit breaking current Icu:
Type M: 70KA
Type H: 100KA
▲ Rated operating short-circuit breaking current Ics:
Page 5 of 8
Document Implementat
NDT500264 Version 1 20160630
No. ion date
Type M: 70KA
Type H: 75KA
▲ Rated working current of the auxiliary contact: 0.3A
▲ The conventional thermal current of the auxiliary contact: 3A
(2). Operating performance
▲ With electricity: 8,000 times
▲ Without electricity: 20,000 times

(3). Connection capacity:


Cable section Copper bar size
2
Rated current A Qty Section mm Qty Dimensions
2
mm
630 2 185 2 40×5
700 2 240 2 50×5
800 2 240 2 50×5
(4) Tightening torque value of terminal/mounting screw

Thread
SN Rated current of frame Torque value
diameter

M12 28
1 NDM3-800
M6 6

(5)Derating factor table of the circuit breaker

Note: 1). When the operating ambient temperature is below ﹢40℃, the product can be used
normally without derating capacity

(4) High-altitude derating factor


Altitude (km) Rated operating Maximum Rated power frequency
current operating voltage withstand voltage
2 In Ue U
2.5 In Ue U
3 0.980In 0.87Ue 0.909U
3.5 0.972In 0.846Ue 0.858U

Page 6 of 8
Document Implementat
NDT500264 Version 1 20160630
No. ion date

4 0.963In 0.813Ue 0.820U


4.5 0.951In 0.781Ue 0.784U
5 0.938In 0.743Ue 0.752U

5. Normal Working Environment


▲ Altitude: ≤2000m.
▲ Ambient temperature: -35℃~+70℃. (Reduced capacity is not considered with the
temperature below +40℃)
▲ The relative humidity at an ambient temperature of +40℃ should not exceed 50%. A
higher relative humidity is allowed at a lower temperature.
▲ Pollution level: 3.
▲ The product can withstand the effects of wet air, salt mist, oil mist and mould.
▲ The product should be installed free from snow and rain.
▲ The product can be disposed in places that are free from explosive media, media
corrosive to metal, insulation damaging gas, and conductive dust.
▲ In case of stricter user conditions than the above description, negotiate with the
manufacturer.
Derating Parameter Table of Temperature for the Circuit Breaker

High-altitude derating factor

6. Tripping Characteristics

Page 7 of 8
Document Implementat
NDT500264 Version 1 20160630
No. ion date
7. Outline and Installation Dimensions

Note: The limit deviation not indicated with the tolerance dimensions is as per GB/T 1804-m.

8. Installation Mode
Installation mode: To be installed horizontally or vertically

9. Packaging and Storage


Minimum packaging quantity: 1 piece/box. The packaged products should be stored in a warehouse
with the ambient temperature of -40℃~75℃ and the corresponding relative humidity below 80%
without acidic, alkali or other corrosive gas in the surrounding air. Under the conditions
above, the storage period shall be no more than 36 months since the manufacturing date.

10. List of Accessories and Installation


SN Name Specification Quantity/Set
Cross small pan-head
1 M6X95 4
screws
2. Plain washer 6 4
3 Spring washer 6 4
4 Hexagon nut(s) M6 4
5 Phase partition —— 4
6 NDM3-630 plug (black) —— 6

Page 8 of 8
Document Implementat
NDT500264 Version 1 20160630
No. ion date
11. Precautions
▲ Various characteristics and accessories of the circuit breaker are set in the factory,
which shall not be adjusted randomly;
▲ The circuit breaker handle can be located in three positions, indicating three states:
on, off and free tripping. When the handle is in the free tripping position, pull the
handle in the off direction when the circuit breaker is connected and on.

Page 9 of 8

You might also like