The document outlines the technical specifications and requirements for a 69/22.9kV power transformer, including details on its type, cooling, insulation levels, and overload capabilities. It specifies features such as winding materials, audible sound levels, short circuit capabilities, and monitoring systems for gas and temperature. Additionally, it includes requirements for bushings, tap changers, and auxiliary power supply.

Uploaded by

Ahmed Abozahrah
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
12 views

2-Power transformer69kv

The document outlines the technical specifications and requirements for a 69/22.9kV power transformer, including details on its type, cooling, insulation levels, and overload capabilities. It specifies features such as winding materials, audible sound levels, short circuit capabilities, and monitoring systems for gas and temperature. Additionally, it includes requirements for bushings, tap changers, and auxiliary power supply.

Uploaded by

Ahmed Abozahrah
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 16

E.1.

2: POWER TRANSFORMER
Technical Data Sheets E1-PTR-1/16

E.1.2: POWER TRANSFORMER 69/22.9kv

B.1 Technical Features and Requirements

B.1.1 Transformer Description

Employer’s Requirements

a. Type Two-winding
b. Number of phase 3-phase
c. Insulation Mineral oil
d. Application Substation Transformer
e. Class (Outdoor, indoor) Outdoor
f. Continuous rated output at 65°C temp. rise (80°C hot spot),
MVA 100
g. Self-cooled rating (ONAN), MVA 60
st
h. 1 stage cooling rating, MVA 80
nd
i. 2 stage cooling rating, MVA 100
j. Percent overload, % 10
k. Type of overload capability Short time
l. Required number of hours for overload with top oil
temperature not exceeding 110ºC at any time 4
m. Insulation level:
1. Nominal voltage level for equipment
a) H-winding, kV 69
b) X-winding, kV 22.9
2. Highest Voltage Level:
a) H-winding, kV 72.5
b) X-winding, kV 25.8
c) X-winding, neutral terminal, kV 25.8
3. Basic Lightning Impulse Insulation Level
(BIL) (kV Crest):
a) H-winding, kV 350
b) X-winding, kV 150
c) X-winding, neutral terminal, kV 150
n. Exciting current at rated voltage and frequency and based
on maximum MVA rating of high voltage winding, not
more than 1.5%

B.1.2 Angular displacement for three-phase transformers (specify ANSI


Std. or vector group symbol if IEC Std. is applied) ANSI Std.

Name of Bidder:

Name & Signature of Bidder's Representative:

Designation:
E.1.2: POWER TRANSFORMER
Technical Data Sheets E1-PTR-2/16

Employer’s Requirements

B.1.3 Winding material shall be:


“H” Copper
“X” Copper

B.1.4 Capacity Ratings


The maximum continuous loading in the respective windings
without exceeding the temperature rise limitations under each
cooling conditions at rated voltage and frequency shall be as
follows:
a. Winding H&X
b. MVA Rating
1. H-winding 100
2. X-winding 100
c. PF (lead/lag) 0.85
d. Type of cooling ONAN/ONAF1/ONAF2
e. Temperature Rise top oil °C/Average °C 65/65

B.1.5 Impedance
a. Impedance (Percent/MVA Base) at 85°C
i. H-X winding Not more than 12%
ii. H-Y winding By manufacturer
iii. X-Y winding -do-

B.1.6 Audible Sound


a. Average audio sound level not more than, dB < 80
when measured at the factory, in accordance with (specify ANSI/IEEE C.57.12.90 or IEC
applied Standard) 60076-10
and with excitation of 100% MVA capacity

B.1.7 Short Circuit Capability


a. H-Terminals
1. Base Voltage, kV 69
2. Short circuit power According to ANSI C57.12 -2000
3. Ratio of zero to positive sequence impedance According to ANSI C57.12 -2000
b. X-Terminals
1. Base Voltage, kV 22
2. Short circuit power According to ANSI C57.12 -2000
3. Ratio of zero to positive sequence impedance According to ANSI C57.12 -2000

Name of Bidder:

Name & Signature of Bidder's Representative:

Designation:
E.1.2: POWER TRANSFORMER
Technical Data Sheets E1-PTR-3/16

Employer’s Requirements

B.1.8 Bushings
The Contractor shall provide bushings as follows:
a. Bushing class and standard:
HV terminals (H):
1. Rated continuous current, A 1200
2. Rated Maximum Voltage,kV 72.5
3. BIL in kV 350
4. Creepage length, mm > 1812.5
LV terminals (X)
1. Rated continuous current, A 3000
2. Rated Maximum Voltage, kV 25.8
3. BIL in kV 150
4. Creepage length, mm > 645
LV neutral terminal, (Xo)
1. Rated current, A 3000
2. Rated Maximum Voltage, kV 25.8
3. BIL in kV 150
4. Creepage length, mm > 645
b. Color of bushing shall be brown
c. Provided with potential taps on the condenser bushings
H-terminal bushings No
X-terminal bushings No
d. Provided with test taps on the condenser bushings
H-terminal bushings Yes
X-terminal bushings Yes
e. Terminal connectors shall be provided as listed below. Each
terminal shall have a maximum RIV level of 10 microvolts
when energized at 125 percent of the rating of the associated
winding.
Terminal
(H) Manufacturer’s Data
(X) Manufacturer’s Data
(Ho/Xo) Manufacturer’s Data

B.1.9 Cooling
a. Cooling medium will be (air, water, oil) Air and oil
b. Temperature
1. Temperature of cooling air, not to exceed 40oC

Name of Bidder:

Name & Signature of Bidder's Representative:

Designation:
E.1.2: POWER TRANSFORMER
Technical Data Sheets E1-PTR-4/16

Employer’s Requirements

2. Average temperature of the cooling air for any 24 h


period, not to exceed 32oC
c. Conduit connections to the weatherproof control cabinets
shall be: From bottom
d. Cooler arrangement (separately mounted or transformer
mounted) Transformer mounted
e. Coolers (specify radiator, cooler tubes) Radiator fin type
f. Steps of forced cooling (one, two) Two
g. Fan motor supply voltage, V 230 V, 1-phase, 60Hz
h. Cooling fan control, including selection and display of “Auto-
Manual” mode, selection and display of “Fan Group”, control
and display “ON” fan groups of the transformers shall be
integrated in the Transformer Monitoring and Control
System: Yes

B.1.10 Surge Arrester Mounted on Transformer

a. Type Metal-Oxide Gapless


b. Discharge counter provided with
c. Leakage current monitor provided with
d. Mounting Provisions provided with
e. Surge arresters shall be supplied for terminals as follows and
they shall be solidly grounded to the transformer pad:
1. Terminals H1, H2 & H3
i. Surge arrester Class & Rating, kV Station/60
2. Terminals X1, X2 & X3
i. Surge arrester Type & Rating, kV N/A
f. Construction Either hollow or caged design
g. Material of insulator Composite (silicon rubber)

B.1.11 Continuous Gas Monitoring System


a. Supply of intelligent on-line continuous gas-in-oil incipient
fault detection system for seven (7) key gases, namely:
hydrogen, methane, carbon monoxide, carbon dioxide,
ethylene, ethane & acetylene, including all attachment,
transmitter with sensor, communication controller, alarm
indicators, continuous ppm display, software and calibrator
(Yes, No) Yes
b. Type By Contractor
1. Hardware Microprocessor, computer
based, watchdog and time-of-
day clock

Name of Bidder:

Name & Signature of Bidder's Representative:

Designation:
E.1.2: POWER TRANSFORMER
Technical Data Sheets E1-PTR-5/16

Employer’s Requirements

2. Software Real-time operating system and


menu driven interface
c. Having the following functions: (Yes, No)
1. Gas level Indication Yes
2. Gas trends (hourly and daily trends) Yes
3. Faulty annunciation alarm indicator and status
indicator 1 Yes
4. History logging Yes
5. Configuration and self test Yes
6. Remote software upgrading possible Yes
d. Display range 0-2000ppm
e. Continuous Gas gas-in-oil Monitoring System of the
transformers shall be integrated in the transformer
monitoring and control system: Yes
f. Degree of protection of panel enclosures IP 55

B.1.12 Temperature Indicator


a. Supply of dial-type winding temperature indicators mounted
on the transformer for top oil and hot spot temperatures
mounted side by side with each other approximately 1500
mm above ground level Yes
b. Monitoring Equipment for Remote Temperature Indication
shall be provided Yes
1. Type Microprocessor based
2. Resistance Coil Hot Spot Temperature Indicator 1/phase
3. Transfer Switch (with, without) with
4. Instrument for Panel Mounting (size) 19” rack
5. Required points for remote digital temperature
recorder 3
c. Equipment for Data Logging to be provided Yes
1. Number or Number Per Phase 3 or 1/phase
2. Type: (Resistance Coil, Thermocouple, RTD, etc.) RTD
d. Integrated in the Transformer Monitoring and Control
System Yes

B.1.13 Sudden Pressure Relay


a. Sudden pressure relay, required (Yes, No) Yes
b. Type Manufacturer’s Data

1
Contractor to provide brief description

Name of Bidder:

Name & Signature of Bidder's Representative:

Designation:
E.1.2: POWER TRANSFORMER
Technical Data Sheets E1-PTR-6/16

Employer’s Requirements

c. Sudden Pressure Relay alarm/trip of the transformers should


be integrated in the Transformer Monitoring and Control
System
Yes

B.1.14 Annunciator
a. Local outdoor annunciator panel to be provided located at
the transformer outdoor cubicle Yes

B.1.15 Transformer Taps


a. The taps specified in Paragraph B.1.16 shall be full
capacity taps and shall be connected as described therein.
1. The taps, upon which all ratings shall be based, shall
be for the:
High Voltage Winding, kV 69 + 10% at 0.625 steps
2. The transformer shall be shipped with a: (specify on-
load, no-load) tap changers set at these taps On-load

B.1.16 Tap Changer


a. No-Load Tap Changer
1. A no-load tap changer shall be furnished and provided
for the transformer: N/A
2. Tap changer rated current, A N/A
3. Power supply for motor, V N/A
4. Power requirement, motor, kW N/A
b. On-Load Tap Changer No
1. A load tap changing mechanism shall be furnished
and provided for the transformer: Yes
2. Taps above rating shall be (percent steps/number) 0.625%/16
3. Taps below rating shall be (percent steps/number) 0.625%/16
4. Operation and Control (auto., remote, manual) Auto, remote & manual
5. Full kVA rating is required on all taps except: (tap
no/s.) N/A
6. Tap changer rated current, A 120% of the rated current of the
transformer
7. Power supply for motor, V 230 Vac, 1-phase, 60 Hz
8. Power requirement, motor, kW Manufacturer’s Data
9. Provision in the design of the LTC control circuit for
future-present operation with another transformer (Yes,
No) Yes
10. A complete indoor transformer control system panel
shall be provided Yes

Name of Bidder:

Name & Signature of Bidder's Representative:

Designation:
E.1.2: POWER TRANSFORMER
Technical Data Sheets E1-PTR-7/16

Employer’s Requirements

a) Paralleling device to be provided ( Yes, No) No


b) Degree of protection of transformer control
system panel IP50
11. A protective relay (oil-flow operated and a sudden-
pressure operated protection relay with trip contact
shall be provided for the conservator of the LTC Yes
12. All tap-changer functions, including tap changer
position sensing, selection and display of “Auto-
Manual” mode, oil-flow and sudden pressure operated
relays(analog output = 4-20 mA) shall be integrated
in the Transformer Monitoring and Control System. Yes

B.1.17 Bushing Current Transformer


a) Bushing Current Transformer
1. Bushing current transformers of multi-ratio shall be
supplied at the following terminals: H,X. and neutral
2. Rated primary current, A:
a. H-bushing 1200
b. X-bushing 3000
c. Neutral 3000
3. Rated secondary current, A:
a. H-bushing 5A
b. X-bushing 5A
c. Neutral 5A
4. No. of Cores:
a. H-bushing 2
b. X-bushing 2
c. Neutral 2
5. Core Assignment:
a. H-bushing:
Core 1 Metering
Core 2 Relaying
b. X-bushing:
Core 1 Metering
Core 2 Relaying
c. Neutral bushing:
Core 1 Relaying
Core 2 Relaying
6. Accuracy class/Rated Burden
a. Metering Core 0.6/ B-0.2
b. Relaying cores C100/ B-1

Name of Bidder:

Name & Signature of Bidder's Representative:

Designation:
E.1.2: POWER TRANSFORMER
Technical Data Sheets E1-PTR-8/16

Employer’s Requirements

B.1.18 Auxiliary Power Supply


a. 230 VAC
1. No. of phase 1-phase
2. No. of wire 2-wire
3. Frequency, Hz 60
4. System (Specify ungrounded, grounded) Ungrounded
5. No. of set 2-independent power supply
6. Automatic power supply transfer switch4
(Specify provided, not provided) Provided
b. DC supply voltage
1. Voltage 48
2. No. of set 2-independent power supply
3. System (Specify ungrounded, grounded) Ungrounded

B.1.19 Oil Preservation system


a. The conservator type of oil preservation system of the
transformer shall be of the:(specify diaphragm, nitrogen gas sealed,
etc.) Diaphragm of the air -bag type
b. A single-float Buchholz relay shall be provided for each main
conservator connected to the highest point of the conservator
as leakage detector for the diaphragm of the air-bag type: (Yes,
No) Yes
c. A non-return valve with trip contact and automatic closing
action for each main conservator, isolating the conservator
when back-flow to the transformer corresponding to the
breathing action is exceeded shall be provided. (Yes, No) Yes

B.1.20 Insulating Oil


a. Insulating oil shall be mineral oil in accordance with ASTM Per Manufacturer’s
D3487 (Type I, Type II) recommendation
b. Additional Properties:
1. Min. Flash Point, oC (ASTM D92) 145
o
2. Pour Point, max. C (not higher than) -40
3. Kinematic, Viscosity at 40 C, mm²/s Max. 12
4. Elect. Breakdown limit, kV Min 50
c. Shipment Samples Required

4
The transfer switch shall be mounted in a separate control cabinet, or within the main control compartment but equipped with a fire
barrier between power and control wiring. Cables to the transfer switch shall be physically separated and not terminated on adjacent
terminal points. Contractor shall submit wiring diagrams for Employer's review and acceptance.

Name of Bidder:

Name & Signature of Bidder's Representative:

Designation:
E.1.2: POWER TRANSFORMER
Technical Data Sheets E1-PTR-9/16

Employer’s Requirements

B.1.21 The following shall be provided to facilitate handling the transformer:


a. Standard Skid Base of Heavy Steel (with or without wheels) Without wheels
b. Wheels shall be removable type (specify uni-directional, bi-
directional) N/A
c. Rail gage N/A
d. Transformer rails to be provided N/A

B.1.22 Bushing Location

B.1.22.1 The location of the bushings of the transformer shall be as shown below:

Left Hand Right Hand


High Voltage Side Terminal

Low Voltage Terminal *

Note: * - Location of the Low Voltage Terminal is tentative. Final arrangement shall depend on the final
layout of the substation.

B.1.23 Contractor’s coordination with other equipment

B.1.23.1 On transformers where flanges are supplied for bus ducts, the bushings are to be located to provide
ground clearance, as stated below, between bus enclosure and live parts of bushings to which bus duct is
connected and to other bushings not connected to the bus duct. Contractor shall cooperate with the
suppliers of the following equipment for the coordination of the power transformer terminals:

B.1.23.2 Isolated phase bus duct requires line to bus duct enclosure (ground) clearance from H, X, and Y terminals
N/A, N/A, by Contractor, mm., respectively.

B.1.23.3 Non-segregated phase bus duct requires line to bus duct enclosure (ground) clearance from H, X, and Y
terminals, _______, _______, _______mm, respectively.

B.1.23.4 Transformer tank design shall be such that no additional heating will result from induction or conduction
from the bus ducts connected to it at rated load within its normal service condition.

B.1.23.5 Contractor shall inform the Employer of his coordination activities with vendors of connected or
associated equipment by forwarding copies of correspondence.

Name of Bidder:

Name & Signature of Bidder's Representative:

Designation:
E.1.2: POWER TRANSFORMER
Technical Data Sheets E1-PTR-10/16

Employer’s Requirements

B.1.24 Oil Filter Units


a. Oil Filter Units to be provided for each OLTC Tank Yes
b. Type Outdoor stationary mounted on
transformer tank
c. Flow rate capacity To be coordinated with the
requirement of OLTC
d. Filter accuracy 10 mm or better
e. Residual water content in oil after filter Less than 10 ppm

B.1.25 Environmental Measures


a. Fire walls to be provided Yes
b. Oil collection pit to be provided Yes
c. Oil-water separation pit to be provided Yes (see Note)
NOTE: This shall include all works and associated equipment and materials necessary for the function
of oil-water separation system

B.2 Test and Test Report(s) Requirements

B.2.1 Normal Test


a. Is transformer design new or of previous design with the same
rating and voltage level? By Contractor
1. If new, design (type) tests and reports are required Yes
2. If previous design of same rating and voltage level,
certified type test reports of duplicate production type are
acceptable. Yes
b. Routine Tests to be performed on all the transformers whether
new or of previous design. Yes
c. Certified Routine test reports to be submitted (Yes, No) Yes
e. Test reports of licenser instead of his own (Supplier) is
(acceptable, not acceptable) not acceptable
f. Test frequency requirement (Power) 60 Hz
g. Factory Acceptance Tests (Routine) to be witnessed by
Employer’s Representative (s) (Yes, No) Yes
h. Required no. of personnel to witness Factory Acceptance
Tests Three (3)

B.3 Auxiliary Power Supply

B.3.1 The items listed below shall be designed to receive the following auxiliary voltage source.
a. Space heaters for the transformer control cubicle, Vac 230 Vac, 1- , 60 Hz
b. Internal lights and convenience outlets 230 Vac, 1- , 60 Hz

Name of Bidder:

Name & Signature of Bidder's Representative:

Designation:
E.1.2: POWER TRANSFORMER
Technical Data Sheets E1-PTR-11/16

Employer’s Requirements

c. Motors 230 Vac, 1- , 60 Hz


d. Annunciator source 48 Vdc, +10% -15%
e. Indicating lights for position indicator of operating mechanism 48 Vdc, +10% -15%

B.4 Spares and Spare Parts


B.4.1 The following spares and spare parts aside from those Contractor’s recommended spare parts shall be
furnished for the transformer:
a. Bushings for the high voltage terminals complete w/ gaskets
and oil, if oil-filled:
“H” terminals 1 unit
“X” terminals 1 unit
b. Bushing Current Transformer used for the following high
voltage terminals:
“H” terminals 1 each
“X” terminals 1 each
c. Set(s) of gauges and thermometers of each type used 1 each
d. Fan motor set(s) 2
e. Set(s) of gaskets for cover, manhole, hand-holes and piping
connections for each transformer 1
f. A complete set of spare parts for the tap changing equipment,
consisting of, but not limited to the following:
1. set(s) of diverter switch assembly 1
2. set(s) of stationary contacts for one phase 1
3. set(s) of moving arcing contacts for one phase 1
4. kits for repairing seal between motor drive and tap-
changer compartment 1
g. Set(s) of control switch breaker and miniature circuit breaker
of each type used 2
h. Buccholz relay 1
i. Sudden pressure relay 1
j. Winding temperature relay 1
k. Amount of silica gel in container (25 kg) enough to refill the
dehydrating breaker 2 cans
l. Set of silica gel container 1
m. Insulating oil in sealed non-returnable drums (this is in
addition to the 5% excess mentioned in Paragraph 1.2.2.2.12.6
of the technical specification). 500 liters
n. 200% of actual use of filter materials for OLTC 1 lot
o. annunciator windows for annunciator panel 4 each
p. thermostat controlled heater of each type 1 each
q. Paper filter insert for the Oil Filter Unit 12 sets
r. Temperature switch for the Oil Filter Unit 3 pcs.

Name of Bidder:

Name & Signature of Bidder's Representative:

Designation:
E.1.2: POWER TRANSFORMER
Technical Data Sheets E1-PTR-12/16

B.4.2 All spare parts subject to damage or deterioration by moisture shall be packed in moisture-proof material.
All spare parts shall be interchangeable with and identical in all respect to the original parts.

B.4.3 All transformers of one size and type and all transformer components of the same rating shall be fully
interchangeable.

B.5 Tools and Appliances

B.5.1 No particular tools will be required for the transformer.

B.6 Other Technical Requirements for the Transformer

B.6.1 Transformer Losses

1. Transformer Guaranteed Losses at rated MVA, frequency, voltage and temperature

a. No-Load Losses, kW (NL-L)


b. Load Losses, kW (LL)
c. Aux. Loss for Stage 1 Cooling, kW (AuxL1)
d. Aux. Loss for Stage 2 Cooling , kW (AuxL2)
e Total Losses, kW ( a + b + c + d )

Note: The Bidders shall provide the information on the Transformer Guaranteed Losses by filling
up the above requirements.

2. Total Allowable Transformer Losses:

The Total Transformer Losses based on the rated MVA shall not exceed 260kW. Bidder (s) whose
bid(s) is/are offering transformer(s) exceeding the given value for the transformer losses shall be
rejected outright.

3. Cost of Transformer Losses

During Factory Acceptance Test, if the transformer losses, as determined by test at rated voltage,
frequency and 100% rated kVA (on principal tapping) exceeded the guaranteed total losses, the excess
in losses shall be computed at the following rates and using the formula stipulated at Section
E.1.2.4.5.1.1 of the technical specification. The resulting amount shall be deducted from the contract
price of the transformer.

1. No-load loss at 100% of rated voltage on mid-tap, (NL-L) $ 4,500 /kW


2. Load loss related to 85°C, (LL) $ 3,200 /kW
3. Auxiliary Loss for Stage 1 Cooling, (AuxL1) $ 1,750 /kW
4. Auxiliary Loss for Stage 2 Cooling, (AuxL2) $ 1,300 /kW

B.6.2 Maintenance Free Dehydrating (silica gel) Breathers for the Transformers

In lieu of the conventional type of dehydrating breathers with silica gel or similar drying agents which
always require periodic sight checks and frequent replacement of used-up granulate of silica gel, a newly
develop maintenance free dehydrating breathers similar to MR type MTraB shall be used for the
transformers.

Name of Bidder:

Name & Signature of Bidder's Representative:

Designation:
E.1.2: POWER TRANSFORMER
Technical Data Sheets E1-PTR-13/16

B.6.3 Neutral Earthing Resistor

An earthing resistor shall be furnished in the neutral of the 22kV winding. This shall be mounted
preferably on the transformer. The determination of the value of the earthing resistor shall be calculated
by the bidder to limit the L.V single phase to ground fault current, with the HV and LV grounded, to
10,000 amperes. The neutral earthing resistor equipment shall be provided with current transformers
with the same technical data as the neutral bushing CT.

B.6.4 Impact Recorder for Transformer

A three dimensional shock recorder with a period recording chart for three months shall be provided by
the Contractor for each of the transformer to be supplied. The Contractor shall state the allowable safety
limit of the readings for the impact.

In the event that the reading of the impact recorder exceeded the safety limit during and after loading,
transport and unloading of the transformer, the Contractor should promptly report this matter to the
Employer and conduct a thorough examination of the transformer to assess the possible damage which
might occur in the transformer. If the result of the reading would render the transformer unserviceable,
then the Contractor should immediately take remedial measures to make sure that the transformer would
be safely and properly operational. If the defect however, would necessitate a complete replacement of
the transformer, then the Contractor should do so at his own expense. It is understood that the
replacement and/or the remedial measures undertaken on the transformer would not entail time extension
on the contractual date in the implementation of the Project.

B.6.5 Transformer Bushings

Haefely Trench made bushing for the Power Transformer is not acceptable. The name of the bushing
manufacturer shall be specifically given in the Technical Data Sheets. Bidder(s) whose bid(s) is/are offering
Haefely Trench made bushing shall be rejected outright.

C. Other Technical Data to be Filled-in by Contractor

C.1 The Contractor furnished data and information are included in this Specification to indicate the
guaranteed performance data, predicted performance, interface requirements and construction features of
all Contractor furnished equipment. The accuracy of such information and the compatibility of such
information with overall performance requirements specified by Employer are the sole responsibility of
the Contractor.

C.2 Environmental Considerations

C.2.1 In accordance with Paragraph 1.1.8 of the General Technical Requirements and the Technical Data
Sheets of Section E.1.1, the operating environment for this installation _(will , will not ) affect the life
expectancy of the components used in this equipment. If there will be an effect, the following components
will be affected as follows:

Component Effect

Name of Bidder:

Name & Signature of Bidder's Representative:

Designation:
E.1.2: POWER TRANSFORMER
Technical Data Sheets E1-PTR-14/16

C.3 Other Technical Data for Power Transformer


Contractor’s Data
a Manufacturer
1. Transformer
Type and Designation
Country of Origin
2. Bushings
a) H-Terminal
Type and Designation
Country of Origin
b) X-Terminal
Type and Designation
Country of Origin
c) Y-Terminal
Type and Designation
Country of Origin
d) Neutral
Type and Designation
Country of Origin
3. Surge Arrester Mounted on Transformer
Type and Designation
Country of Origin
4. Continuous Gas Monitoring System
Type and Designation
Country of Origin
5. On-Load Tap Changer
Type and Designation
Country of Origin
6. Transformer Control System
Type and Designation
Country of Origin
b. Winding Construction
(layer, disc, etc.)
c. Core Construction
(core, shell)
d. Exciting Current
1. at rated voltage
2. at 110% voltage
e. Resistance per phase, ohm
1. H-winding
2. X-winding
3. Y-winding

Name of Bidder:

Name & Signature of Bidder's Representative:

Designation:
E.1.2: POWER TRANSFORMER
Technical Data Sheets E1-PTR-15/16

Contractor’s Data
f. Winding Distributed Capacitance per Phase
(microfarad)
1. Winding to Ground
H
X
Y
2. Between Winding
H-X
H-Y
X-Y
g. Bushing Capacitance (stud to tap/tap to flange), pf
H /
X /
Y /
Z /
h. CT Capacitance to Ground, pf
i. Estimated Natural Resonant Frequency of the
Transformer, Hz
j. Cooling Power Required
1. First step cooling, kW
2. Second step cooling, kW
k. Coolers
1. Quantity
2. Surface area, each (cm2)
l. Winding Temperature Setting, °C
1. High Temperature Alarm
2. High Temperature Trip
3. First Step Cooling
4. Second Step Cooling
m. Fans
1. Type
2. Quantity
3. Motor size, hp
4. Motor speed, rpm
5. Capacity, cfm
6. Locked rotor, A
7. Normal load, kW
n. Magnetic flux density at rated voltage and
frequency

Name of Bidder:

Name & Signature of Bidder's Representative:

Designation:
E.1.2: POWER TRANSFORMER
Technical Data Sheets E1-PTR-16/16

Contractor’s Data
o. Percent regulation at:
1. 0.8 pf
2. 0.9 pf
3. 1.0 pf
p Guaranteed sound level without forced-cooling
equipment, dB
q. Reduction of Transformer capacity, %
1. Outage of 1- radiator assembly
2. Outage of 2-radiator assembly
3. Outage of 3-radiator assembly
r. Maximum pressure that the transformer tank can
withstand:
1. Positive internal pressure
2. Vacuum (gauge pressure)
s. Thickness of tank wall, mm
t. Thickness of tank bottom, mm