Ocr Description
Ocr Description
Not Applicable
Not Applicable
Not Applicable
BACKGROUND OF INVENTION
Definitions
INTRODUCTION
Size (HP)
Synchronous Speed (RPM)
Enclosure Type
Full Load Efficiency (%)
Size (HP)
Synchronous Speed (RPM)
Enclosure Type
Full Load Efficiency (%)
Voltage AB
Voltage BC
Voltage CA
Current A
Current B
Current C
Power Factor
Measured Speed
Power Draw
Voltage AB
Voltage BC
Voltage CA
Current A
Current B
Current C
Power Factor
Measured Speed
Power Draw
Field
Value
Motor Load
(NB)
Assumptions:
Estimation
Method
Else if Voltage (AB, BC, and CA), Current (A, B, and C) and Power Factor
measurements are entered in the System and the Motor
Size and Full Load Efficiency are filled in the System then:
[TABLE-US-00002]
Field
Value
Motor Load
(NB)
Assumptions:
0.746).
Load
“kW Ratio − Voltage based”
Estimation
Method
If the Full Load Efficiency of the motor is not entered the System will
use the Full Load Efficiency of the Minimal Nominal
Efficiency Table (Drawings: FIG. 3.0—Minimal Nominal Efficiency
Table). See below section; the System calculates the motor efficiency as follows.
[TABLE-US-00003]
Field
Value
Motor Load
(NB)
Assumptions:
Load Estimation
“Voltage Compensated Amps Ratio”
Method
Else if Average Voltage and Measured Speed measurements are entered in the
System and the motor Synchronous Speed and Full
Load Speed and Wired For Voltage are filled in the System then:
[TABLE-US-00004]
Field
Value
Motor Load
(NB)
Assumptions:
Load
“Voltage Compensated Slip”
Estimation
Method
[TABLE-US-00005]
Field
Value
Motor Efficiency
Blank
If data is found in the System the System will compare the calculated
Motor Load with the efficiency percentages and populate
two variables (Minimum and Maximum Efficiency) and set the Load base
variable as follows:
If data is found in the System the System will compare the calculated
Motor Load with the efficiency percentages and populate
two variables (Minimum and Maximum Efficiency) and set the Load base
variable as follows:
[TABLE-US-00006]
Load
Motor Load
Minimum Efficiency
Maximum Efficiency
Base
<=25%
0
Efficiency at 25%
0
Load
Load
Load
Load
Load
>75%
Efficiency at 75%
Full load efficiency
75
Load
If the Motor Load is above the 75% threshold the Maximum Efficiency
will be replaced with the System's header motor nameplate
Full Load Efficiency providing this value is entered in the System
and higher than Maximum Efficiency.
The System will determine the Slope. Slope is the linear slope
between the Minimum and Maximum Efficiency as follows:
If the Motor Load is greater than 25% then the System will calculate
the Motor Efficiency as follows:
If the Motor Load is above the 75% threshold the Maximum Efficiency
will be replaced with the System's header motor nameplate
Full Load Efficiency providing this value is entered in the System
and higher than Maximum Efficiency.
The System will determine the Slope. Slope is the linear slope
between the Minimum and Maximum Efficiency as follows:
If the Motor Load is greater than 25% then the System will calculate
the Motor Efficiency as follows:
[TABLE-US-00007]
Field
Value
Motor Efficiency
(Motor Load − Load Base) * Slope +
Minimum Efficiency
Otherwise if the Motor Load is less than or equal to 25% then the
System will calculate the Motor Efficiency (=load served/load
served plus the fixed losses at 25% of the load) as follows:
Otherwise if the Motor Load is less than or equal to 25% then the
System will calculate the Motor Efficiency (=load served/load
served plus the fixed losses at 25% of the load) as follows:
[TABLE-US-00008]
Field
Value
Loss at 25%
(NB)
Horse Power at Load
(NB)
Motor Efficiency
(NB)
If the Motor Load was calculated with one of the two kW Ratio
techniques the System will recalculate the Motor Load with the
calculated Motor Efficiency instead of the Full Load Efficiency and
will stay in this loop until either:
The difference between two consecutive Motor Loads is less than 0.05
or
The System has recalculated 50 times.
If Rewound is selected for the System header motor then the calculated
Motor Efficiency is corrected as follows:
If the Motor Load was calculated with one of the two kW Ratio
techniques the System will recalculate the Motor Load with the
calculated Motor Efficiency instead of the Full Load Efficiency and
will stay in this loop until either:
The difference between two consecutive Motor Loads is less than 0.05
or
The System has recalculated 50 times.
If Rewound is selected for the System header motor then the calculated
Motor Efficiency is corrected as follows:
[TABLE-US-00009]
Motor Size in HP
Rewound Correction
<=40
0.5%
>40
0.25%
[TABLE-US-00010]
Field
Value
Motor Efficiency
Motor Efficiency − Rewound Correction
Inlet Diameter
Outlet Diameter
Design Friction Losses
Length of Discharge Pipe
Static Suction Head
Static Discharge Head
Inlet Diameter
Outlet Diameter
Design Friction Losses
Length of Discharge Pipe
Static Suction Head
Static Discharge Head
Capture the following pump operation statistics and
enter in the System. The Pump Discharge Pressure can be attained from
a pressure gauge, and the flow Pump Discharge Flow Rate
data from a flow meter or estimate.
Field
Value
(NB)
(NB)
(NB)
Velocity Head
Velocity Head Outlet − Velocity Head Inlet
(m of head)
Total Head
Static Suction Head + Pump Discharge Pressure +
Velocity Head
(m of head)
(m of head)
Temp Flow Density
(NB)
(kW)
Output (kW)
Velocity Head Power
Pump Hydraulic
Pump Hydraulic Power Output / Motor Power * 100
Efficiency (%)
(NB)
Efficiency / 10000
(NB)
Note: the System calculates data conversion if necessary as follows:
[TABLE-US-00012]
Field
Value
Fluid Density
See below in Table 4; Convert Density.
TABLE 2
Convert Length
Conversion factor to Meters
From Meters
1
From Centimeters
100
From Feet
3.28084
From Inches
39.37008
[TABLE-US-00014]
TABLE 3
Convert Flow Rate
Conversion factor to Cubic Meters/Hour
From US Gallons/Hour
264.172
From US Gallons/Minute
From US Gallons/Hour/60
[TABLE-US-00015]
TABLE 4
Convert Pressure
Conversion factor to Meters of Head
From Meters of Head
1
From Bar
0.098068059
From PSI
1.421969428
[TABLE-US-00016]
TABLE 5
Convert Density
Conversion factor to Kilogram/Cubic Meter
Kilogram/Cubic Meter
1
US Pound/Cubic Feet
16.01846337
[TABLE-US-00017]
Cost per
Hourly
Base
Produc-
Pump
Hourly
Load
Pump
Rate
tion
Capac-
Running
De-
De-
System
Code
Hour
UOM
ity
Cost
liver
livery
Pump x
Off peak
00
.0123
80
0.984
Pump x
Off peak
01
.0123
80
0.984
. . .
Pump x
Off peak
08
.0123
80
0.984
Pump x
Off peak
20
.0123
80
0.984
Pump x
Off peak
21
.0123
80
0.984
. . .
Pump x
Off peak
23
.0123
80
0.984
Pump y
Off peak
00
.09
120
10.8
Pump y
Off peak
01
.09
120
10.8
. . .
Pump y
Off peak
08
.09
120
10.8
Pump y
Off peak
20
.09
120
10.8
Pump y
Off peak
21
.09
120
10.8
. . .
Pump y
Off peak
23
.09
120
10.8
Pump x
Peak
09
.134
80
10.72
Pump x
Peak
10
.134
80
10.72
. . .
Pump x
Peak
19
.134
80
10.72
Pump y
Peak
09
.19
120
22.8
Pump y
Peak
10
.19
120
22.8
. . .
Pump y
Peak
19
.19
120
22.8
2.6 the System Adds the Next Lowest Cost Pump-Hour to Schedule
With Daily Demand specified, Base Load and Hourly Demand
not specified the System will;
The System will then loop through the hours of the day
again as if no Base Load Demand was specified. The System behaves as
described above under; Daily Demand specified, Base
Load and Hourly Demand Not Specified and with Hourly Demand Specified.
The System will then loop through the hours of the day
again as if no Base Load Demand was specified. The System behaves as
described above under; Daily Demand specified, Base
Load and Hourly Demand Not Specified and with Hourly Demand Specified.
[TABLE-US-00018]
Pump
Cost per
Capacity
System
Rate Code
Hour
Production UOM
Per Hour
Deliver
Pump x
Off peak
00
.0123
80
80
Pump x
Off peak
01 . . .
.0123
80
80
Pump x
Off peak
08
.0123
80
80
Pump x
Off peak
20
.0123
80
80
Pump x
Off peak
21 . . .
.0123
80
80
Pump x
Off peak
23
.0123
80
80
Pump y
Off peak
00
.09
120
120
Pump y
Off peak
01
.09
120
120
Pump y
Off peak
02
.09
120
30
Pump y
Off peak
03 . . .
.09
120
Pump y
Off peak
8
.09
120
Pump y
Off peak
20
.09
120
Pump y
Off peak
21 . . .
.09
120
Pump y
Off peak
23
.09
120
Pump x
Peak
09
.134
80
Pump x
Peak
10 . . .
.134
80
Pump x
Peak
19
.134
80
Pump y
Peak
09
.19
120
Pump y
Peak
10 . . .
.19
120
Pump y
Peak
19
.19
120
2.7 Determine the Cost for Each Entry Delivered in the Delivery Matrix
[TABLE-US-00019]
Pump x
. . .
00
.0123
80
0.984
Pump x
. . .
01 . . .
.0123
80
0.984
. . .
For the Day to Optimize the System will find the last
Pump System that was added to the Delivery Matrix. The last Pump System
is also the most expensive pump (Cost per Production
UOM) of all that are included in the Delivery Matrix and therefore it
makes sense for the System to first try and remove
that from the Delivery Matrix.
The System will repeat with the now new last Pump
System until there is no capacity left.
For the Day to Optimize the System will find the last
Pump System that was added to the Delivery Matrix. The last Pump System
is also the most expensive pump (Cost per Production
UOM) of all that are included in the Delivery Matrix and therefore it
makes sense for the System to first try and remove
that from the Delivery Matrix.
The System will repeat with the now new last Pump
System until there is no capacity left.
Pump
0
1
2
3
4
5
6
7
8
9 thru 19
20
21
22
23
Px
80
80
80
80
80
80
80
80
80
80
80
80
80
Py
120
120
30
And after:
[TABLE-US-00021]
13 thru
Pump
0
1
2
3
4
5
6
7
8
9
10
11
12
19
20
21
22
23
Px
80
80
80
80
80
80
80
80
80
80
80
80
30
80
80
80
80
Py
2.9 Peak Shaving