Siddhivinayak RMC 3rd party material testing reports

The document contains test reports for physical properties of coarse aggregates (crushed 20mm and 10mm) and fine aggregates (crushed sand) conducted by Buildcon Material Testing and Services. Each report includes details such as test results for specific gravity, water absorption, bulk density, flakiness index, elongation index, and sieve analysis, along with compliance to relevant IS codes. The tests were performed for Shree Siddhivinayak RMC, with samples received on August 10, 2024, and reports issued between August 18-28, 2024.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
21 views3 pages

Siddhivinayak RMC 3rd party material testing reports

The document contains test reports for physical properties of coarse aggregates (crushed 20mm and 10mm) and fine aggregates (crushed sand) conducted by Buildcon Material Testing and Services. Each report includes details such as test results for specific gravity, water absorption, bulk density, flakiness index, elongation index, and sieve analysis, along with compliance to relevant IS codes. The tests were performed for Shree Siddhivinayak RMC, with samples received on August 10, 2024, and reports issued between August 18-28, 2024.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 3

BUILDCON

B MATERIAL TESTING AND SERVICES PRIVATE LIMITED


LABORATORY
AN ISO/IEC 17025: 2017 NABL ACCREDITED TC-12980

TEST REPORT- PHYSICAL PROPERTY OF COARSE AGGREGATE (CRUSHED 20MM)


Test Report No and Date
:BMTS/18082024/059380 Date: 28-08-2024
ULR No. :TC1298024000008990F
icateslt
TestlRe
Name & Address of customer: :Shree Siddhivinayak RMC, MOI
: At MOI, Tal- Khed, District- Pune
Customer's Reference :Test Requisition Date : 10-08-2024
Sample a) Description Date of Receipt 10-08-2024
:Coarse Aggregate (Crushed 20 mm)
b) Quantity :01 sample Date of Testing 11-08-2024 to 16-08-2024

c) Condition Date of Report 18-08-2024


:Sample Accepted for Test
d) Testing Facility :Permanent Facility Room Temperature 28°C
e) Sample Description 20 mm Coarse Aggregates Source: Vignahar Stone Crusher
A) TEST REPORT- PHYSICAL PROPERTY OF COARSE AGGREGATE (CRUSHED 20MM)
OBSERVATIONS & CALCULATED VALUES
SI No Characteristic Unit Test Results Tested as per IS Code
1 Specific Gravity 2.860 IS 2386(3):1963(RA2021)
2 |Water Absorption 1.11 IS 2386(3):1963(RA2021)
3 Dry loose bulk density kg/lit 1.53 IS 2386(3);1963(RA2021)
Rod dry bulk density kg/lit 1.58 IS 2386(3):1963(RA2021)
5 Flakiness Index 8.68 IS 2386(1):1963(RA2021)
6 Elongation Index 11.21 IS 2386(1):1963(RA2021)
7 |Impact Value 9.25 IS 2386(4):1963(RA2021)
B) TEST REPORT- SIEVEANALYSIS OF COARSE AGGREGATE (CRUSHED 20MM)
IS Sieve Size W.Retain Cumulative IS: 383:2016 Limits
SI No % Wt. Retain Cumulative %Passing Table No 07
(mm) (g) % W. Retain
1 40.00 0.00 0.00 0.00 100 100

2 20.00 611.00 12.48 12.48 88 85 -100

3 10.00 4208.00 85.97 98.45 2 0- 20 Report


4 4.75 66.00 L35 99.80 0 -5

10.00 0,20 100.00 0


5 Pan Test
Cumulative %Passing Series2 -Series3
100 GRADATION CURVE FOR 20 mm COARSE AGG
the
60
Authe
40

20

4.75 10.00 20.00 40.00


7ram
L.S.Sieves (mm)
Remarks: Information based on test requisition submitted
Note:
01) The Remarks Given On This Report Are Based On The Available Information On Test Requisition Form submitted
2) The lest report and result relate to the particular specimen/ sample (s) of the material as delivered /received and tested in the laboratory
03) This test report may not be reproduced in part, without the pernnission of this
04) Any correction invalidales this lest reports
laboratorv TESTTING
Discipline/ Group : Mechanical - Buildings Materials
PUNE HologramO
Page 0l of 0L
Reviewed By Authoriscd Signatory
D
Omkar Sawant Shubham Badgujar
Testing, Engineer Ltd Technical Manager
For BUILDCON MATERIAL TESTING AND SERVICES Pvt For BUILDCON MATERIAL TESTING AND SERVICES Pvt Ltd

Call us : Pickup / Repc: 7767012930, Technical :8956071334, Accounts: 8482823250, Ouot: 9607993238 and Reports :9607993236
Office Address : CIN No: U74999PN2017PTC169178
No.22/5/2/1, Web : www.buildconservices.com
Suraj Plaza, Survey Near Sancheti
Swami Samarth Colony, Email : [email protected]
411033.
School, Thergaon, Pune - [email protected]
BUILDCON
MMATERIAL TESTING AND SERVICES PRIVATE LIMITED
AN ISO/IEC 17025: 2017 NABL ACCREDITED LABORATORY TC-12900

TEST REPORT- PHYSICAL PROPERTY OF COARSE AGGREGATE (CRUSHED 10 MM)


Test Report No and Date
:BMTS/8082024/O59379 Date: 18-08-2024
ULR No.
:TC1298024000008989F
Name & Address of customer:
:Shree Siddhivinayak RMC, MOI
Report
:At MOL Tal- Khed, District- Pune
Customer's Reference :Test Requisition Date : 10-08-2024 Test method followed As Mentioned
Test
Sample a) Description :Coarse Aggregate (Crushed 10 mm) Date of Receipt 10-08-2024
b) Quantity :01 sample Date of Testing 11-08-2024 to 16-08-2024 the
c) Condition : Sample Accepted for Test Date of Report 18-08-2024
Aten
d) Testing Facility : Permanent Facility Room Temperature 28°C
e) Sample Description 10 mm Coarse Aggregates Source: Vignahar Stone Crusher
A) TEST REPORT- PHYSICAL PROPERTY OF COARSE AGGREGATE (CRUSHED 10MM)
OBSERVATIONS & CALCULATED VALUES Holog
SINo Characteristic Unit Test Results Tested as per IS Code
|Specific Gravity 2.840 IS 2386(3):1963(RA2021)

Water Absorption 1.42 IS 2386(3):1963(RA2021)


sBuildc
3 |Dry loose bulk density kg/it 1.55 IS 2386(3):1963(RA2021)

4 Rod dry bulk density kg/lit 1.59 IS 2386(3):1963(RA2021)


Flakiness Index % 9.44 IS 2386(1):1963(RA2021)

Elongation Index % 10.56 IS 2386(1):1963(RA2021)


|Impact Value 10.91 IS 2386(4):1963(RA2021)
B) TEST REPORT -SIEVE ANALYSIS OF COARSE AGGREGATE (CRUSHED 10OMM)
SI No
IS Sieve Size Wt.Retaín % We Retain Cumulative % Passing(
1S: 383:2016 Limits
(mm) %W. Retain Table No 07
1 12.50 0.00 0.00 0 00 100 100

2 10.00 388.00 13.91 13.91 86 85-100


Repor
3 4.75 2389.00 85.66 99.57 0 - 20
4 2.36 0.00 0.00 99.57 0-5 Test
5 Pan 12,00 0.43 100.00

- Passing
the
GRADATION CURVE FOR 10 mm COARSE AGG -Series2 Series3
10
Authe
80

60

40

Holog
236 4.75 10.00 12.50
LS.Sieves (mm)
Remarks : Information based on test requisition submitted
Note:
o1) The Remarks Given On This Report Are Based On The Available Information On Test Requisition Form submitted
Buildc
02) The test report and result relate to the particular specimen/ sample (s) of the malerial as delivered /received and tested in the laboralory
03) This test report may not be reproduced in part, without the permission of this laboratory
04) Any correction invalidates this test reports

Discipline/ Group : Mechanical - Buildings Materials


PUNE Hologram
Reviewed By Authorised Signatory Page O1 of 01

Omkar Sawant Shubhanm Badgujar


Testing Engineer Technical Manager
Eor BUILDON MATERIAL TESTING AND SERVICES Pvt Ltd
For BUILDCON MATERIAL TESTING AND
SERVICES Pvt Lid

Call us: Pickup/ Repc: 7767012930, 1lechnical : 8956071334, Accounts; 8482823250, Ouot 96079g3238 and Reports : 9607993236
Ofice Address: CIN No: U74999PN2017PTC169178
Web : www.buildconservices.com
Suraj Plaza, Survey No.22/5/2/1,
Swami Samarth Colony, Near Sancheti Email : [email protected]
School, Thergaon, Pune - 411033. [email protected]
BUILDCON
PRIVATE LIMITED
MATERIAL TESTING AND SERVICES
ACCREDITED LABORATORY
AN ISO/IEC 17025: 2017 NABL TC-12980

CRrSHED SAND)
TEST REPORT- PHYSICAL PROPERTY OF FINE AGGREGATE (
Test Report No and Date :BMTS/18082024/059381 Date: 18-08-2024

ULR No. :TC1298024000008991F


Name & Address of customer: :Shree Siddhivinayak RMC, MOI
Report
:At MOL, Tal- Khed, District- Pune
Customer's Reference :Test Requisition Date :10-08-2024
Test method followed As Mentioned Test
Sample
a) Description : Fine Aggregate (Crushed Sand) Date of Receipt 10-08-2024 the
b)Quantity :01 sample
Date of Testing 11-08-2024 to 18-08-2024 Authen
18-08-2024
c) Condition :Sample Accepted for Test Date of Report
Room Temperature 28 °C
d) Testing Facility :Permanent Facility
e) Sample Description :FineAggregates( C. sand) Source: Vignahar Stone Crusher

A)TEST REPORT- PHYSICA PROPERTY OF FINE AGGREGATE ( CRUSHEDSAND)


OBSERVATION & CALCULATED VALUES
Hologr
Test Results Tested as per IS Code
SINo Characteristic Unit
2,700 IS 2386(3):1963(RA2021)
Specific Gravity
IS 2386(3):1963(RA2021)
2 Water Absorption % 3.20 Buildco
1.65 IS 2386(3):1963(RA2021)
Dry loose bulk density kg/ lit
1.70 IS 2386(3):1963(RA2021)
4 Rod dry bulk density kg/lit
15.40 IS 2386(1):1963(RA2021)
5 Material finer than 75 micron IS Sieve
B)TEST REPORT -SIEVE ANALYSIS OF FINE AGGREGATE (CRUSHED SAND) IS 2386(1):1963(RA2021) IS: 383 Limits
IS Sieve Size WARetain Cumulative
SI No % Wt. Retain Cumulative % Passing (ZONE -I)
6Wt. Retain
(mm) ()
1 100 100.00
10.00 0.00 0.00 0.00
99 90 -100
2 4.75 10.00 1.00 1.00 o
19.58 20.58 79 60-95
3 2.36 196.00
47 30-70
4 1.18 321.00 32.07 52.65
15-34
Report
0.600 174.00 o 17.38 70.03 30
11.99 82.02 18 5-20
6 0.300 120.00
7 0.150 40.00 4.00 86.01 14 0 -20
Test
8 Pan 140.00 13.99 100.00
Cumulative % Passing -A(Max.) -C(Min.) the
GRADATION CURVE FOR CRUSHIED SAND
100
Authen
80

60

40

20 Buildc
0
0.30 0.60 236 4.75 10.00
0.15 LS.Sieves (mm
Remarks: Information based on test requisition submitted
Note:
01) The Remarks Given On This Report Are Based On The Available Information On Test Requisition Form submitted
02 The lest report and result relale to the particular specimen/ sample (s) of the material as delivered /received and tested in the laboratory
03) This test report may not be reproduced in part, without the permission of this laboratory.
04) Any correction invalidales this test reports STINGA
Discipline/ Group : Mechanical- Buildings Materials
Hologram
Reviewed By Authorised Signatory PUNE Page 01l of 01

Omkar Sawant
Shubham Badgujar
Testing Engineer Technical Manager
For BUILDCON MATERIAL TESTING AND SERVICES Pvt Ltd
For BUILDCON MATERIAL TESTING AND SERVICES Pvt Ltd

Call us: Pickup/Repc: 7767012930,Technical : 8956071334, Accounts: 8482823250. Ouot:9607993238 and Reports :9607993236
Office Address : CIN No: U74999PN2017PTC169178
Web :www.buildconservices.com
Suraj Plaza, Survey No.22/5/2/ 1,
Swami Samarth Colony, Near Sancheti Email : [email protected]
School, Thergaon, Pune - 411033. [email protected]

You might also like