0% found this document useful (0 votes)
48 views7 pages

Schneider Electric_PowerLogic-P3-Protection-Relays_REL52022

The document provides a comprehensive datasheet for the PowerLogic P3U universal protection relay, detailing its specifications, features, and functionalities. It includes information on power supply, digital and analog inputs/outputs, communication protocols, protection functions, and environmental data. Additionally, it outlines packaging details, warranty information, and sustainability efforts by Schneider Electric.

Uploaded by

energyarian2025
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
48 views7 pages

Schneider Electric_PowerLogic-P3-Protection-Relays_REL52022

The document provides a comprehensive datasheet for the PowerLogic P3U universal protection relay, detailing its specifications, features, and functionalities. It includes information on power supply, digital and analog inputs/outputs, communication protocols, protection functions, and environmental data. Additionally, it outlines packaging details, warranty information, and sustainability efforts by Schneider Electric.

Uploaded by

energyarian2025
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 7

Product datasheet

Specifications

universal protection relay,


PowerLogic P3U 3CT 1Io ringlug
4VT 16DI 8DO 48-230V DI24V
2RJ45
REL52022

Main
Range of product PowerLogic P3

Product or component type Protection relay

Relay application Universal

Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
product reference P3U30-6AAA1BCAA

Mounting case size 30TE

power supply 48...230 V AC/DC

measuring inputs : 1/5 A CT phase current 3


: 1/5 A CT residual current 1
: 100 V/110 V VT voltage 4

number of Digital Inputs (DI) 16

number of analogue inputs 0

number of Digital Outputs (DO) 1 watchdog


8

number of analogue outputs 0

communication ports USB port 1 front


RJ45 2 rear

communication protocols IEC 61850 ed. 1


IEC 61850 ed. 2
IEC 60870-5-101
DNP3 TCP
Modbus TCP
EtherNet/IP

Redundancy communication port RSTP


protocol PRP

Cybersecurity Password protection


Port hardening

Price is “List Price” and may be subject to a trade discount – check with your local distributor or retailer for actual price.

Feb 15, 2025 1


protection functions Phase overcurrent 50/51
Directional phase overcurrent 67
Earth fault overcurrent 50N/51N
Directional earth fault 67N
Transient earth fault 67NI
Capacitor bank unbalance 51C
Broken conductor 46 I2/I1
Cold load pick-up
Switch ON to fault (SOTF)
Breaker failure 50BF
Directional active underpower 37P
Fault locator 21FL
Recloser 79
Phase undercurrent 37
Excessive starting time, locked rotor 48/51LR
Motor restart inhibition 66
Capacitor overvoltage 59C
Negative sequence overcurrent 46
Overvoltage 59
Undervoltage 27
Positive sequence undervoltage 27P
Earth fault overvoltage 59N
Underfrequency 81/81N
Rate of change of frequency 81R
Synchro-check 25
Lockout relay 86
CT supervision 60
VT supervision 60
H2 detection 68H2
H5 detection 68H5
Negative sequence overcurrent 47
Programmable stages 99
Programmable curve

Arc flash protection No

measurement functions Current 3-phase


Current zero sequence
Current positive sequence
Current negative sequence
Current ratio of negative and positive
Voltage phase to earth
Voltage phase to phase
Voltage zero sequence
Voltage positive sequence
Voltage negative sequence
Voltage ratio of negative and positive
Short circuit fault reactance
Fault location current
Earth fault reactance
Frequency
Active power
RMS active power
Reactive power
RMS reactive power
Apparent power
RMS apparent power
Active energy
Reactive energy
Cos φ
Tan φ
Power angle
Power factor
Voltage phasor diagram view
Current phasor diagram view
Current 2nd, 15th harmonics with THD
Voltage 2nd, 15th harmonics with THD
Voltage interruption
Condition monitoring CB wear

control functions Switchgear control and monitoring


Programmable switchgear interlocking
Local control on single-line diagram
Local control with I/O keys
Local/remote control
2 function keys
Mobile application with Easergy SmartApp
Web-server
Programmable logic

2 Feb 15, 2025


controllable switchgear devices 4 controlled + 8 displayed

number of setting groups 4

monitoring functions Trip circuit supervision 74


Circuit breaker monitoring
Relay self-monitoring

logs and records Event recording


Disturbance recording
Tripping context

Switchgear diagnosis type CT/VT supervision ANSI code: 60


CT supervision
Trip circuit supervision ANSI code: TCS

Connections - terminals Screw removable (digital input/output)


Ring lugs removable (current transformer)
Pin removable (voltage transformer)

Complementary
Operating threshold 24...230 V AC/DC

Time synchronisation protocol SNTP

Software name EcoStruxure Power Device


ESetup Easergy Pro

Web server Embedded HTTP server

Display type LCD 128 x 64 pixels with single line diagram

Number of key 2 customizable

Local signalling 4 LEDs


8 LEDs programmable

Standards IEC

Height 169.5 mm

Width 170 mm

Depth 205 mm

Net weight 2.5 kg maximum

Environment
climatic withstand Exposure to dry heat Bb tests conforming to EN/IEC 60068-2-2
Exposure to cold Ad tests conforming to EN/IEC 60068-2-1
Exposure to damp heat in service Db tests conforming to EN/IEC 60068-2-30
Exposure to damp heat in service Cab tests conforming to EN/IEC 60068-2-78

Mechanical robustness Vibrations (level: class II) conforming to IEC 60255-21-1


Vibrations: Fc conforming to IEC 60068-2-6
Shocks (level: class II) conforming to IEC 60255-21-2
Shocks: Ea conforming to IEC 60068-2-27
Seismic tests method A (level: class II) conforming to IEC 60255-21-3
Bumps (level: class II) conforming to IEC 60255-21-2
Bumps: Ea conforming to IEC 60068-2-27

Feb 15, 2025 3


Electromagnetic compatibility Emission tests conforming to IEC/EN 60255-26 ed. 3
Emission tests class A conforming to CISPR 11
Emission tests class A conforming to CISPR 22
EMC immunity conforming to IEC/EN 60255-26 ed. 3
EMC immunity conforming to EN/IEC 61000-4-18
EMC immunity level 4 conforming to EN/IEC 61000-4-2
EMC immunity level 3 conforming to EN/IEC 61000-4-3
EMC immunity level 4 conforming to EN/IEC 61000-4-4
EMC immunity level 3 conforming to EN/IEC 61000-4-5
EMC immunity level 3 conforming to EN/IEC 61000-4-6
EMC immunity conforming to EN/IEC 61000-4-8
EMC immunity level 5 conforming to EN/IEC 61000-4-9
EMC immunity conforming to EN/IEC 61000-4-29
EMC immunity conforming to EN/IEC 61000-4-11
EMC immunity conforming to EN/IEC 61000-4-17

Ambient air temperature for -40…65 °C


operation
IP degree of protection IP54 conforming to IEC 60529

maximum operating altitude 2000 m

Protective treatment Conformal coating

Relative humidity 0…95 %, without condensation

Packing Units
Unit Type of Package 1 PCE

Number of Units in Package 1 1

Package 1 Height 30 cm

Package 1 Width 29.9 cm

Package 1 Length 39.8 cm

Package 1 Weight 3.835 kg

Unit Type of Package 2 P06

Number of Units in Package 2 8

Package 2 Height 105 cm

Package 2 Width 60 cm

Package 2 Length 80 cm

Package 2 Weight 43.46 kg

Contractual warranty
Warranty Up to 10 years extended warranty (Standard warranty 2 years. Please check with
your local SE representative for extended warranty availability and conditions)

4 Feb 15, 2025


Environmental Data

Schneider Electric aims to achieve Net Zero status by 2050 through supply chain partnerships, lower impact materials, and circularity
via our ongoing “Use Better, Use Longer, Use Again” campaign to extend product lifetimes and recyclability.

Environmental Data explained

How we assess product sustainability

Environmental footprint

Environmental Disclosure Product Environmental Profile

Use Better

Materials and Substances

Packaging made with recycled cardboard Yes

Packaging without single use plastic No

China RoHS Regulation China RoHS declaration

Use Again

Repack and remanufacture

Circularity Profile End of Life Information

The product must be disposed on European Union


WEEE markets following specific waste collection and never end
up in rubbish bins

Take-back No

Feb 15, 2025 5


Product datasheet REL52022

Connections and Schema

Functional View

6 Feb 15, 2025


Product datasheet REL52022

Dimensions Drawings

Base Unit Dimensions

A B

With screw connector 214 mm/8.43” 192 mm/7.6”

With ring-lug connector 226 mm/8.90” 204 mm/8.0”

Feb 15, 2025 7

You might also like