ATEX8_KJ3211X1-BA1_SeqofEvents

The ATEX Instruction Sheet provides essential safety and operational guidelines for the KJ3211X1-BA1 Sequence of Events Card, specifically in hazardous atmospheres. It outlines power specifications, environmental conditions, and maintenance instructions, emphasizing the importance of de-energizing circuits during installation and removal. The document also references additional installation instructions and safety approvals relevant to the product's use in hazardous areas.

Uploaded by

weird fish
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
8 views

ATEX8_KJ3211X1-BA1_SeqofEvents

The ATEX Instruction Sheet provides essential safety and operational guidelines for the KJ3211X1-BA1 Sequence of Events Card, specifically in hazardous atmospheres. It outlines power specifications, environmental conditions, and maintenance instructions, emphasizing the importance of de-energizing circuits during installation and removal. The document also references additional installation instructions and safety approvals relevant to the product's use in hazardous areas.

Uploaded by

weird fish
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

ATEX Instruction Sheet

Part Number: ATEX8


Publication date: May 2018 Sequence of Events Card

KJ3211X1-BA1 Sequence of Events Card


Hazardous Atmosphere Removal and Insertion
Do not remove or insert this unit with system power
energized unless the area is known to be non-
II 3G Ex nA IIC Gc hazardous. Remove or insert only one unit at a time.
FM12ATEX0090U
IECEx FMG 12.0035U Non-sparking field circuits must be de-energized
before removal and insertion.

Power Specifications A rotary keying system ensures compatibility


between I/O cards and terminal blocks after
Local Bus Power 12 VDC at 100 mA installation is complete. The terminal block must
have the keys set for the I/O card with which it is
Bussed Field Power 24 VDC at 75 mA
used.
Field Circuit 24 VDC at 5 mA/Channel

Maintenance and Adjustment


Environmental Specifications This unit contains no user-serviceable parts and
should not be disassembled for any reason.
Ambient -40 °C to +70 °C
Temperature
Calibration is not required.

Shock 10 g half-sine wave for 11 ms

Vibration 1 mm peak to peak from 2 to 13.2 Hz;


Other Safety Approvals
0.7 g from 13.2 to 150 Hz

Airborne ISA-S71.04 –1985 Airborne


Contaminants Contaminants Class G3

Relative Humidity 5 to 95% non-condensing IP 20 rating


Terminal Block C5
Key Position

Note: Refer to the product label for serial number


and location and date of manufacture.

Warning: This product has specific instructions for


installation, removal, and operation in hazardous
areas. Refer to document 12P2046, DeltaV™
Scalable Process System Zone 2 Installation
Instructions. Other installation instructions are
available in the DeltaV™ M-Series Hardware
Installation and Reference manual.